{"data":{"standard":{"code":"au_as_1851_2012","name":"AS 1851-2012","country_code":"AU","enabled":true},"version":"full","categories":[{"id":"rec25D1cI73i8oNSb","name":"Fire Hose Reels","asset_types":[{"id":"recQqdPE7BQOJOrqt","name":"Fire Hose Reels","checklist":[{"id":"00d78f29-73e5-42cc-a2ea-9dd1e02b8b19","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.2 YEARLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"2.4","prompt":"CHECK that all hose fittings and connections are\n tight.","input":null,"possible_fault":"Fittings/connections loose","possible_fault_description":"AS1851 2012 TABLE 9.4.2 ITEM 2.4 - Hose fittings and connections not tight","severity_level":"non-critical","fault_id":"recQhJevfbuPkl1Q7","prompt_id":"recQhJevfbuPkl1Q7_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"1_year::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"08f16752-18c2-42d4-a229-6f113bb0c8d9","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.2 YEARLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"2.10","prompt":"CHECK that no alterations have been made to the\n building, which impede access to the hose reel or\n restrict the running out of the hose, and that the hose\n can reach the fire hazard/risk in accordance with\n AS 2441.","input":null,"possible_fault":"Access obstructed/reach restricted","possible_fault_description":"AS1851 2012 TABLE 9.4.2 ITEM 2.10 - Building alterations impede access/reach per AS2441","severity_level":"non-critical","fault_id":"recTCY29cGAyxpJXM","prompt_id":"recTCY29cGAyxpJXM_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"1_year::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"0ca23478-3c4d-4241-9ade-bbb38995c9ef","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.10*","prompt":"TEST water to ensure it is able to flow through the\n reel by opening and closing the nozzle.\n\n*After completing these actions, the nozzle shall be re-installed in the nozzle interlock and the hose depressurized (see Clause 9.2.6).","input":null,"possible_fault":"Water flow restricted/blocked","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.10 - Water unable to flow through reel/nozzle","severity_level":"critical","fault_id":"recIME3mWRXpT2eja","prompt_id":"recIME3mWRXpT2eja_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"1c963065-65db-4bce-a077-526f13457364","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.2 YEARLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"2.7","prompt":"CHECK hose for kinking, excessive damage or\n wear, or collapse.","input":null,"possible_fault":"Hose kinked/damaged/collapsed","possible_fault_description":"AS1851 2012 TABLE 9.4.2 ITEM 2.7 - Hose kinked, damaged, worn or collapsed","severity_level":"non-critical","fault_id":"recSeD2ZN0Vogv2Em","prompt_id":"recSeD2ZN0Vogv2Em_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"1_year::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"3f95fc21-f25e-4d1d-b9f3-8a5f5fff97f7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.9*","prompt":"With the nozzle closed, pressurize the reel by\n opening the stop valve. DETERMINE if there are\n any leaks from the reels waterway, including\n glands, nozzle, stop valve, hose or any fittings.\n NOTE: In order to check that there is no leakage\n of water from any part of the reel waterway, it is\n recommended that the hose be completely\n unwound off the reel, so that all parts of the\n waterway can be examined.\n\n*After completing these actions, the nozzle shall be re-installed in the nozzle interlock and the hose depressurized (see Clause 9.2.6).","input":null,"possible_fault":"Water leaks from waterway","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.9 - Leakage from waterway/glands/nozzle/fittings","severity_level":"non-critical","fault_id":"recSb6UGJUmxDm90V","prompt_id":"recSb6UGJUmxDm90V_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"4aa2c334-6ee3-4ebe-9a43-2ffca35ac11e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.2 YEARLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"2.3","prompt":"CHECK that any hose guide fixed to the hose reel\n supply pipe is not able to move upwards and cause\n the hose to jamb.","input":null,"possible_fault":"Hose guide moving/causing jam","possible_fault_description":"AS1851 2012 TABLE 9.4.2 ITEM 2.3 - Hose guide moves upward causing hose to jam","severity_level":"non-critical","fault_id":"recE13vZlEEjSAp0p","prompt_id":"recE13vZlEEjSAp0p_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"1_year::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"5fd4680a-3864-484a-a1aa-9338c8937905","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.8*","prompt":"With the nozzle closed and stop valve open, TEST\n that the hose reel can be unwound freely in its\n intended direction by unwinding at least 5 m of\n hose.\n\n*After completing these actions, the nozzle shall be re-installed in the nozzle interlock and the hose depressurized (see Clause 9.2.6).","input":null,"possible_fault":"Hose cannot unwind freely","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.8 - Hose reel cannot unwind freely minimum 5m","severity_level":"non-critical","fault_id":"recel5wjgTWdDTOBK","prompt_id":"recel5wjgTWdDTOBK_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"66660c45-784d-4fc8-a3d9-71e58a12e1ed","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.5","prompt":"CHECK that any hose reel cabinet is accessible,\n clear of extraneous materials, clearly and correctly\n marked and in good repair.","input":null,"possible_fault":"Cabinet inaccessible/damaged","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.5 - Cabinet not accessible or in poor repair","severity_level":"non-critical","fault_id":"recorxzMKbHfkkDcB","prompt_id":"recorxzMKbHfkkDcB_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"71f2f0df-29bc-446d-a057-9d41b4697e82","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.4","prompt":"CHECK for any damage or corrosion of\n components that could adversely affect the\n operation of the hose reel.","input":null,"possible_fault":"Component damage/corrosion","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.4 - Damage/corrosion affecting hose reel operation","severity_level":"non-critical","fault_id":"recn1uzS03YxhSGz3","prompt_id":"recn1uzS03YxhSGz3_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"830f2ae7-5e6e-4b6b-b05c-5ec3a6ef07d6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.2","prompt":"Where a location sign is required by AS 2441,\n CHECK that it is correctly located and visible.","input":null,"possible_fault":"Location sign missing/incorrect","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.2 - Location sign not visible or incorrectly located","severity_level":"non-conformance","fault_id":"recsx8TXRXLPm7c0j","prompt_id":"recsx8TXRXLPm7c0j_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"888bcccb-35c8-40f2-95b9-bfb697cb11ec","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.7*","prompt":"Where fitted, TEST the swing arm to ensure it\n operates correctly and allows the hose to be run off\n in its intended direction.\n\n*After completing these actions, the nozzle shall be re-installed in the nozzle interlock and the hose depressurized (see Clause 9.2.6).","input":null,"possible_fault":"Swing arm not operating correctly","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.7 - Swing arm not operating correctly","severity_level":"non-critical","fault_id":"rec9qgrANkQf9DNDM","prompt_id":"rec9qgrANkQf9DNDM_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"8a5d175c-b16d-4847-b038-2a735d0affb3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.2 YEARLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"2.9","prompt":"CHECK that the hose reel is appropriate protection\n for the fire hazard/risk.","input":null,"possible_fault":"Protection inappropriate for hazard","possible_fault_description":"AS1851 2012 TABLE 9.4.2 ITEM 2.9 - Hose reel inappropriate for fire hazard/risk","severity_level":"critical","fault_id":"recdqaXD0Yx6mhnjT","prompt_id":"recdqaXD0Yx6mhnjT_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"1_year::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"96a87e61-a935-4990-8237-de41e0dd08d4","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.3","prompt":"CHECK that the operating instructions are legible.","input":null,"possible_fault":"Instructions illegible/missing","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.3 - Operating instructions not legible","severity_level":"non-critical","fault_id":"recrVFoaMo9PbPRTg","prompt_id":"recrVFoaMo9PbPRTg_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"a57528af-400d-4912-afd7-f421a60072a5","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.6","prompt":"CHECK that the nozzle is retained in the nozzle\n interlock.","input":null,"possible_fault":"Nozzle not retained in interlock","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.6 - Nozzle not retained in nozzle interlock","severity_level":"critical","fault_id":"rec1DHrlHqOy48tDR","prompt_id":"rec1DHrlHqOy48tDR_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"be8f00b4-572d-471a-b2a7-462792e852a6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.11","prompt":"CHECK that the service tag or label is firmly\n attached to the hose reel.","input":null,"possible_fault":"Service tag missing/loose","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.11 - Service tag/label not firmly attached","severity_level":"non-conformance","fault_id":"recSRnq9Z4AdNyUQG","prompt_id":"recSRnq9Z4AdNyUQG_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"cfe6e8c3-9882-4b02-9952-ac130c2078b5","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.2 YEARLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"2.1","prompt":"COMPLETE all six-monthly service activities,\n as listed in Table 9.4.1.","input":null,"possible_fault":"Six-monthly service incomplete","possible_fault_description":"AS1851 2012 TABLE 9.4.2 ITEM 2.1 - Six-monthly service activities not completed","severity_level":"non-conformance","fault_id":"recE8IDEPfle73ZbK","prompt_id":"recE8IDEPfle73ZbK_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"1_year::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"d45d8b55-ce4e-4668-8e07-cfa4b7b36614","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.2 YEARLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"2.5","prompt":"CHECK that the hose reel bearings are not damaged\n or excessively worn.","input":null,"possible_fault":"Bearings damaged/worn","possible_fault_description":"AS1851 2012 TABLE 9.4.2 ITEM 2.5 - Hose reel bearings damaged or excessively worn","severity_level":"non-critical","fault_id":"recKQf2JzXvyLHdU4","prompt_id":"recKQf2JzXvyLHdU4_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"1_year::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"d57cd56d-25a4-4aec-a436-8f29734db3e7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.2 YEARLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"2.8","prompt":"CHECK that any foam branch pipe or other\n equipment is in good repair and maintained in\n accordance with the manufacturer’s instructions.","input":null,"possible_fault":"Equipment damaged/not maintained","possible_fault_description":"AS1851 2012 TABLE 9.4.2 ITEM 2.8 - Foam branch pipe/equipment not maintained per manufacturer","severity_level":"non-critical","fault_id":"recsf5tyRgsaGqw6F","prompt_id":"recsf5tyRgsaGqw6F_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"1_year::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"dd630c86-90dc-4ec4-9eda-f58943b2a6fc","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.2 YEARLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"2.2","prompt":"CHECK that the hose reel is securely mounted and\n that the anchor points are tight.","input":null,"possible_fault":"Anchor points loose/damaged","possible_fault_description":"AS1851 2012 TABLE 9.4.2 ITEM 2.2 - Hose reel not securely mounted/anchor points loose","severity_level":"non-critical","fault_id":"rec8Hf66h3NlNer32","prompt_id":"rec8Hf66h3NlNer32_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"1_year::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"e44c6e9f-55e8-462e-ae07-dbdd61fd46bf","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.2 YEARLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"2.6","prompt":"With the stop valve and nozzle fully opened,\n MEASURE the water flow rate from the most\n disadvantaged hose reel.\n Minimum acceptable flow rates:\n (a) 0.33 L/s for reels with 19 mm hose.\n (b) 0.41 L/s for reels with 25 mm hose.","input":null,"possible_fault":"Flow rate below 0.33 L/s\nFlow rate below 0.41 L/s","possible_fault_description":"AS1851 2012 TABLE 9.4.2 ITEM 2.6 - Flow rate below 0.33 L/s for 19mm hose\nAS1851 2012 TABLE 9.4.2 ITEM 2.6 - Flow rate below 0.41 L/s for 25mm hose","severity_level":"critical","fault_id":"rec0dPhuqAxMi4GRq","prompt_id":"rec0dPhuqAxMi4GRq_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"1_year::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"},{"id":"fe28f503-e928-400d-a99d-62816bf2dc81","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hose Reels","category_id":"rec25D1cI73i8oNSb","group_header":"TABLE 9.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE HOSE REELS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hose Reels","variant":null,"variant_id":"recQqdPE7BQOJOrqt","item_no":"1.1","prompt":"CHECK that the hose reel is readily accessible with\n no obstacles restricting its access. Where a hose\n reel is installed in a recess or cabinet, CHECK that\n the clearances around the hose reel comply with the\n requirements of AS 2441.","input":null,"possible_fault":"Access restricted/blocked","possible_fault_description":"AS1851 2012 TABLE 9.4.1 ITEM 1.1 - Hose reel access restricted by obstacles","severity_level":"critical","fault_id":"rec8wmgJWRpus1gQx","prompt_id":"rec8wmgJWRpus1gQx_prompt","inspection_id":"c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb","grouping_key":"6_month::c_recQqdPE7BQOJOrqt_rec25D1cI73i8oNSb"}]}],"other_checklist_items":[]},{"id":"rec3U01F6OlYh40uD","name":"Fire Detection and Alarm Systems","asset_types":[{"id":"rec25eomX5uBrivZP","name":"Emergency intercom systems","checklist":[{"id":"0969b7fa-2261-4172-91ad-babd1c52e4fa","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.17.B","prompt":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":"DATE","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recNTgToVN6am5SO7_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"10425a2d-374f-4184-ae97-fdc2b8a676a3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.19","prompt":"INSPECT the building to ensure that no changes to occupancy have affected the required audibility of the warden call signal at the WIP.","input":null,"possible_fault":"Occupancy changes affect WIP audibility","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.19 - Building use changes impact warden call audibility","severity_level":"informational","fault_id":"rec8xGZBuFKRX8kWE","prompt_id":"rec8xGZBuFKRX8kWE_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"155918f6-5137-4b8d-bc7f-4e16062db874","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.15.A","prompt":"MEASURE system quiescent and alarm currents. Calculate the required battery capacity and CHECK the installed battery’s nominal capacity is no less than the required capacity. See Appendix F for calculating the required battery capacity.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec6VReqJnuLyWLmr_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"176f0603-1d6f-499d-a8f6-9f9760f3c39f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.16","prompt":"CONDUCT a functional test with any interfaced systems (see Appendix D).","input":null,"possible_fault":"Interface with other systems fails","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.16 - Interfaced system functional test failure","severity_level":"critical","fault_id":"rec6gYBMIS9Y9gMs2","prompt_id":"rec6gYBMIS9Y9gMs2_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"1afc6c08-a5f5-4843-b834-abf3d6ed3d66","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.5","prompt":"TEST the operation of each required control (e.g. secondary emergency control panels).","input":null,"possible_fault":"Controls fail operational test","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.5 - Panel control operation malfunction","severity_level":"critical","fault_id":"recyeEBjx7yKzqOW1","prompt_id":"recyeEBjx7yKzqOW1_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"1dfec104-4f7c-4720-85f4-36bbb434d552","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.7","prompt":"TEST the operation of the reset function.","input":null,"possible_fault":"Reset function fails to operate","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.7 - System reset function malfunction","severity_level":"non-critical","fault_id":"recJSR3RHwevBRTlY","prompt_id":"recJSR3RHwevBRTlY_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"2ac86a0c-8ee6-40cc-8637-abdb2da5aa87","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.17.C","prompt":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":null,"possible_fault":"Battery fails discharge test","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.17 - Battery condition inadequate per discharge test","severity_level":"critical","fault_id":"recE6ktR0pYgw0K6K","prompt_id":"recE6ktR0pYgw0K6K_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"2d493441-3faa-4554-9c8e-afca9512d773","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.4","prompt":"TEST the operation of the aural indicators.","input":null,"possible_fault":"Aural indicators fail to operate","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.4 - Aural indicator operational failure","severity_level":"non-critical","fault_id":"recXyTAPdGAVk5Gga","prompt_id":"recXyTAPdGAVk5Gga_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"41df6068-2652-4374-aef5-37440f64a5c3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.15.B","prompt":"MEASURE system quiescent and alarm currents. Calculate the required battery capacity and CHECK the installed battery’s nominal capacity is no less than the required capacity. See Appendix F for calculating the required battery capacity.","input":null,"possible_fault":"Installed battery capacity insufficient","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.15 - Battery capacity less than calculated requirement","severity_level":"critical","fault_id":"rec1pUneLYeM9dHmm","prompt_id":"rec1pUneLYeM9dHmm_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"49dd4433-4938-4708-b6f6-b6435d7473b6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.17.A","prompt":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recE6U36WcN12aink_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"616b84aa-ac84-4d5b-86db-1324104379d5","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.9","prompt":"INSPECT all WIPs to ensure they are clearly visible and readily accessible. Where the WIP is obscured by a door, check that the door is correctly labelled.","input":null,"possible_fault":"WIPs not visible/accessible or incorrectly labelled","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.9 - WIP accessibility/labelling issues","severity_level":"non-conformance","fault_id":"recf2038gFE6NC7ud","prompt_id":"recf2038gFE6NC7ud_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"6f4f2fe6-175d-45bc-9cb8-d654e34a4be4","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.8","prompt":"CHECK the operation of each warden indicator and controls.","input":null,"possible_fault":"Warden indicators/controls fail to operate","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.8 - Warden indicator/control operational failure","severity_level":"critical","fault_id":"receKDJSndPyKI0lj","prompt_id":"receKDJSndPyKI0lj_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"7c916d25-234e-416c-bf5e-ead9aeab02e8","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.2","prompt":"INSPECT the intercom panel to ensure that it is clearly visible, readily accessible and free from dust and contaminants. Where the panel is obscured by a door, check that the door is correctly labelled.","input":null,"possible_fault":"Panel contaminated/obscured or incorrectly labelled","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.2 - Intercom panel accessibility/cleanliness issues","severity_level":"non-conformance","fault_id":"recygciEBpOaJV96N","prompt_id":"recygciEBpOaJV96N_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"7e7a3763-b80f-41f5-a70c-bf9eb93e6a57","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.10","prompt":"INSPECT all WIPs to ensure there is no mechanical damage.","input":null,"possible_fault":"WIPs show mechanical damage","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.10 - WIP mechanical damage affecting operation","severity_level":"non-critical","fault_id":"recwsPSKjw4YA7OGs","prompt_id":"recwsPSKjw4YA7OGs_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"7e8da9a0-7fce-4043-8110-63176af19f84","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.18","prompt":"INSPECT building to ensure that no structural changes have occurred to change zones.","input":null,"possible_fault":"Structural changes affect evacuation zones","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.18 - Building modifications impact zone requirements","severity_level":"critical","fault_id":"rec0cJEEMbgunf0aB","prompt_id":"rec0cJEEMbgunf0aB_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"80d9aa9a-cf6a-4d51-86fc-a1dd5d9b1cdd","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.3","prompt":"TEST the operation of visual indicators and alphanumeric displays.","input":null,"possible_fault":"Visual indicators/displays fail to operate","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.3 - Visual indicator/display operational failure","severity_level":"non-critical","fault_id":"recAVFW5xZicSUnCh","prompt_id":"recAVFW5xZicSUnCh_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"87ee1804-8766-4533-b199-ab99a58bb440","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.13","prompt":"INITIATE a call to each WIP and phone and confirm that each WIP is indicating correctly and that clear communication is possible with the intercom panel operator.","input":null,"possible_fault":"WIP incoming calls fail or unclear communication","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.13 - Panel to WIP communication failure","severity_level":"non-critical","fault_id":"recPMVy19mnGA8FoI","prompt_id":"recPMVy19mnGA8FoI_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"a6ec3d6b-4bcc-4a38-a149-cc13217d938e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.6","prompt":"SIMULATE a WIP circuit fault condition and confirm the fault condition is indicated at the intercom panel.","input":null,"possible_fault":"WIP circuit fault not indicated at panel","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.6 - WIP circuit fault indication failure","severity_level":"critical","fault_id":"recJ2Mzrhbu3P0GJp","prompt_id":"recJ2Mzrhbu3P0GJp_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"bf81da27-fedb-4b2f-afaf-d9d10c6f4b24","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.12","prompt":"INITIATE a call from each WIP and confirm that each WIP is indicating correctly and that clear communication is possible with the intercom panel operator.","input":null,"possible_fault":"WIP outgoing calls fail or unclear communication","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.12 - WIP to panel communication failure","severity_level":"non-critical","fault_id":"recWDlkHCbrL81ucF","prompt_id":"recWDlkHCbrL81ucF_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"dbe1640b-5e6a-42ff-8aea-2cb06573ff8c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.11","prompt":"Where vented batteries are used, INSPECT the battery enclosure for evidence of corrosion.","input":null,"possible_fault":"Battery enclosure corrosion evident","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.11 - Stand-alone system battery enclosure corrosion","severity_level":"non-critical","fault_id":"recqdwNiIix93TPxH","prompt_id":"recqdwNiIix93TPxH_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"e462ba9b-c49a-4307-af77-81762fa501be","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.14","prompt":"Select the all-call address function and CHECK that the visual indicator for all WIP phones activate. CHECK that the address is heard at all WIP phones. NOTE: This test may be carried out in conjunction with a practice evacuation or ECO training.","input":null,"possible_fault":"All-call function doesn't activate all WIPs","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.14 - All-call address function malfunction","severity_level":"non-critical","fault_id":"recfh9Io7FjRCYf1P","prompt_id":"recfh9Io7FjRCYf1P_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"},{"id":"fb1f3a6f-409f-4b57-b7fb-d3959a52d39e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.4.1 YEARLY SERVICE SCHEDULE EMERGENCY INTERCOM SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency intercom systems","variant":null,"variant_id":"rec25eomX5uBrivZP","item_no":"1.20","prompt":"INSPECT all evacuation zones to ensure at least one WIP is installed where required.","input":null,"possible_fault":"Required WIPs missing from evacuation zones","possible_fault_description":"AS1851 2012 TABLE 6.4.4.1 ITEM 1.20 - WIP coverage inadequate for evacuation zones","severity_level":"non-conformance","fault_id":"recniXlyx1Jizn3jw","prompt_id":"recniXlyx1Jizn3jw_prompt","inspection_id":"c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec25eomX5uBrivZP_rec3U01F6OlYh40uD"}]},{"id":"rec5PYzWjYMKYLkYI","name":"Smoke/Heat Alarm System","checklist":[]},{"id":"recAhOjivmmUeMZhW","name":"Fire detection and alarm systems","checklist":[{"id":"2cdd6840-06fa-4124-918b-da012cde31c6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.9","prompt":"Where the system is monitored, TEST that the loss of each of the monitoring links is indicated at the monitored site.","input":null,"possible_fault":"Monitoring link loss not indicated","possible_fault_description":"AS1851 2012 TABLE 6.4.1.5 ITEM 4.9 - Loss of monitoring links not indicated","severity_level":"non-critical","fault_id":"recyNkcTSdthXef0c","prompt_id":"recyNkcTSdthXef0c_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"},{"id":"38b57c5b-5a0b-43da-a3a4-e8e390bed693","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.2","prompt":"TEST each input and output supervised circuit for any condition that prevents the transmission of the required signal and ensure a fault is registered at the FIP.","input":null,"possible_fault":"Circuit fails to transmit signal/fault","possible_fault_description":"AS1851 2012 TABLE 6.4.1.5 ITEM 4.2 - Supervised circuit prevents signal transmission","severity_level":"critical","fault_id":"recpzjtSZjPpGm4m8","prompt_id":"recpzjtSZjPpGm4m8_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"},{"id":"6138cbe7-bf4e-4014-ac5c-ec197c89d68d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.10","prompt":"TEST one detector of each type per circuit withalarm verification facility enabled to check that it functions as required.","input":null,"possible_fault":"Alarm verification doesn't function","possible_fault_description":"AS1851 2012 TABLE 6.4.1.5 ITEM 4.10 - Alarm verification facility malfunction","severity_level":"critical","fault_id":"recnjMnT5M2Dlgv9o","prompt_id":"recnjMnT5M2Dlgv9o_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"},{"id":"6689faa8-d043-4c30-ab21-2ba7a7d7d181","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.5","prompt":"SIMULATE a circuit fault condition at the FIP and confirm that all required common or general visual and audible indications operate. Where such faults are monitored, ensure the fault has activated the alarm signalling equipment. Where the panel is an SIP confirm that the fault condition is indicated at the FIP.","input":null,"possible_fault":"Power fault indications fail","possible_fault_description":"AS1851 2012 TABLE 6.4.1.5 ITEM 4.5 - Power supply fault indications don't operate","severity_level":"non-critical","fault_id":"recMzJJRxJnDVcnHe","prompt_id":"recMzJJRxJnDVcnHe_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"},{"id":"6be375c4-7e70-49d7-8aac-e49db09fd863","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.1","prompt":"Complete all monthly, six-monthly and yearly service activities, as listed in Tables 6.4.1.2, 6.4.1.3 and 6.4.1.4.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 6.4.1.5 ITEM 4.1 - Monthly/six-monthly/yearly activities incomplete","severity_level":"non-conformance","fault_id":"recS6UroiTgVjiwJ6","prompt_id":"recS6UroiTgVjiwJ6_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"},{"id":"8023e8f4-578b-4ca7-a43f-2b067cdce971","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.8.B","prompt":"MEASURE and record the impedance of each loud speaker circuit and check that it has not changed by more than 15% from the last test nor exceeded the rated output as required for the amplifier.","input":null,"possible_fault":"Circuit impedance changed >15%","possible_fault_description":"AS1851 2012 TABLE 6.4.1.5 ITEM 4.8 - Speaker circuit impedance exceeds limits","severity_level":"non-critical","fault_id":"rectq7mGl4gdjYHlw","prompt_id":"rectq7mGl4gdjYHlw_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"},{"id":"9e312b67-6fd7-47b7-8ebb-7bc978444548","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.7","prompt":"CONDUCT a functional test with each system’s interface and VERIFY that each interfaced system responds to the signal as required (see Appendix D).","input":null,"possible_fault":"Interfaced systems don't respond","possible_fault_description":"AS1851 2012 TABLE 6.4.1.5 ITEM 4.7 - Interface systems don't respond to signals","severity_level":"critical","fault_id":"recXcUSODZ6kRVg0l","prompt_id":"recXcUSODZ6kRVg0l_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"},{"id":"b96a54de-880c-4f68-bc0c-fa1bbab5b30a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.6","prompt":"For each collective fire detection circuit, REMOVE the last detector or device on the circuit and confirm that a fault signal is registered at the CIE.","input":null,"possible_fault":"Fault signal not registered at CIE","possible_fault_description":"AS1851 2012 TABLE 6.4.1.5 ITEM 4.6 - Detection circuit fault not registered","severity_level":"critical","fault_id":"recYA41NhzaWGJAWo","prompt_id":"recYA41NhzaWGJAWo_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"},{"id":"ef0bb62a-9e6a-4ea6-ae6c-ab216630691a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.3","prompt":"SIMULATE a circuit fault condition at the FIP and\n confirm that all required common or general visual\n and audible indications operate. Where such faults\n are monitored, ensure the fault has activated the\n alarm signalling equipment. Where the panel is an\n SIP confirm that the fault condition is indicated at\n the FIP.","input":null,"possible_fault":"Fault indications don't operate","possible_fault_description":"AS1851 2012 TABLE 6.4.1.5 ITEM 4.3 - Circuit fault visual/audible indications fail","severity_level":"non-critical","fault_id":"recXox6RWi7jXFE7L","prompt_id":"recXox6RWi7jXFE7L_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"},{"id":"fb0a716c-c35c-46d8-8e4b-712e2b4bf9b0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.8.A","prompt":"MEASURE and record the impedance of each loud speaker circuit and check that it has not changed by more than 15% from the last test nor exceeded the rated output as required for the amplifier.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recsAUUQWvKoF2Zcu_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"},{"id":"ff8fd5b7-cc1c-44db-81be-e69262e559e5","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.5 FIVE-YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire detection and alarm systems","variant":null,"variant_id":"recAhOjivmmUeMZhW","item_no":"4.4","prompt":"Apply short circuits as required to verify that the\n short circuit isolation functions as required.","input":null,"possible_fault":"Short circuit isolation fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.5 ITEM 4.4 - Addressable short circuit isolation malfunction","severity_level":"critical","fault_id":"recgsWU02dRcPJGxn","prompt_id":"recgsWU02dRcPJGxn_prompt","inspection_id":"c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recAhOjivmmUeMZhW_rec3U01F6OlYh40uD"}]},{"id":"recqjdzxhag0yzqOi","name":"Smoke/Heat Alarm System (SOU)","checklist":[]},{"id":"rectLPJrpuPKS4gL6","name":"Smoke Hazard Management Systems","checklist":[{"id":"00a7637a-6525-4f28-8dbd-9dc344eae17f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke Hazard Management Systems","variant":null,"variant_id":"rectLPJrpuPKS4gL6","item_no":"3.25","prompt":"CHECK the operation of the fan-running indicator.","input":null,"possible_fault":"Fan-running indicator fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.25 - Fan-running indicator operation failure","severity_level":"non-critical","fault_id":"reciMnmxOF0635XA4","prompt_id":"reciMnmxOF0635XA4_prompt","inspection_id":"c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"40332623-6c9a-4137-b88c-80da6c3d203e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke Hazard Management Systems","variant":null,"variant_id":"rectLPJrpuPKS4gL6","item_no":"3.19","prompt":"CHECK that after initiation by a signal from \nthe FIP, the FFCP remains operating in the fire \nmode until reset by the reset switch on the \nFFCP.","input":null,"possible_fault":"FFCP fails to latch in fire mode","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.19 - FFCP does not remain in fire mode after FIP activation or fails to reset properly","severity_level":"critical","fault_id":"recx3hT2X5c3bt9qZ","prompt_id":"recx3hT2X5c3bt9qZ_prompt","inspection_id":"c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"49cd652c-b14c-44a5-9696-41bd0b4a919f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke Hazard Management Systems","variant":null,"variant_id":"rectLPJrpuPKS4gL6","item_no":"3.20","prompt":"CHECK that manual override ON-AUTO-OFF \ncontrol operates. \nNOTE: Manual override should","input":null,"possible_fault":"Manual override doesn't operate","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.20 - Manual override ON-AUTO-OFF control failure","severity_level":"critical","fault_id":"recxloYr4IONDMZbl","prompt_id":"recxloYr4IONDMZbl_prompt","inspection_id":"c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"546e459c-6d18-406a-8f25-bf93a77fb25a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke Hazard Management Systems","variant":null,"variant_id":"rectLPJrpuPKS4gL6","item_no":"3.21","prompt":"CHECK the operation of the airflow fault \nindicator","input":null,"possible_fault":"Airflow fault indicator fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.21 - Airflow fault indicator operation failure","severity_level":"non-critical","fault_id":"recykcJ3i19OJc5x1","prompt_id":"recykcJ3i19OJc5x1_prompt","inspection_id":"c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"570f86a2-ffa6-42a6-a92d-c261ef4a7720","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke Hazard Management Systems","variant":null,"variant_id":"rectLPJrpuPKS4gL6","item_no":"3.26","prompt":"CHECK the operation of the fan-stopped indicator.","input":null,"possible_fault":"Fan-stopped indicator fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.26 - Fan-stopped indicator operation failure","severity_level":"non-critical","fault_id":"recxZWj6kJJuVwAaA","prompt_id":"recxZWj6kJJuVwAaA_prompt","inspection_id":"c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"5f27ed80-5408-402b-8947-0fbf8514a1ee","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke Hazard Management Systems","variant":null,"variant_id":"rectLPJrpuPKS4gL6","item_no":"3.22","prompt":"CHECK the operation of the air-handling \nequipment interconnecting cable open-circuit \nfault indicator.","input":null,"possible_fault":"Open-circuit indicator fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.22 - Open-circuit fault indicator operation failure","severity_level":"critical","fault_id":"recDTpB4ubND6UU6X","prompt_id":"recDTpB4ubND6UU6X_prompt","inspection_id":"c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"76a54e01-2856-48d9-bee6-102605d8bfff","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke Hazard Management Systems","variant":null,"variant_id":"rectLPJrpuPKS4gL6","item_no":"3.27","prompt":"CHECK the operation of the fan-fault indicator.","input":null,"possible_fault":"Fan-fault indicator fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.27 - Fan-fault indicator operation failure","severity_level":"non-critical","fault_id":"recXU3Yc4k0DP0u7V","prompt_id":"recXU3Yc4k0DP0u7V_prompt","inspection_id":"c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"a4b4bd24-6d29-441c-9012-0d8cfe26279c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke Hazard Management Systems","variant":null,"variant_id":"rectLPJrpuPKS4gL6","item_no":"3.24","prompt":"CHECK the operation of the electricity phase-fail fault indicator.","input":null,"possible_fault":"Phase-fail indicator fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.24 - Electricity phase-fail fault indicator failure","severity_level":"non-critical","fault_id":"reciDUPJ7HVYLdAUN","prompt_id":"reciDUPJ7HVYLdAUN_prompt","inspection_id":"c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"fe66a983-021a-43ef-b5ca-274df79b79a1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke Hazard Management Systems","variant":null,"variant_id":"rectLPJrpuPKS4gL6","item_no":"3.23","prompt":"CHECK the operation of the air-handling equipment interconnecting cable closed-circuit fault indicator.","input":null,"possible_fault":"Closed-circuit indicator fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.23 - Closed-circuit fault indicator operation failure","severity_level":"non-critical","fault_id":"reckHgLQSoBrBsu40","prompt_id":"reckHgLQSoBrBsu40_prompt","inspection_id":"c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"}]},{"id":"recy1ku5NAMITWtry","name":"Emergency Warning System","checklist":[{"id":"029638a1-04f8-4427-aba7-f767e8be7002","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.12","prompt":"TEST the operation of each control.","input":null,"possible_fault":"Controls fail operational test","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.12 - Panel control operation malfunction","severity_level":"critical","fault_id":"recA0nYxzVAeVzkNp","prompt_id":"recA0nYxzVAeVzkNp_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"05142ff1-22b0-4884-b6a4-31761e0e1470","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.20.A","prompt":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"reck6pPCMGOXhj2aT_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"0a1c3a0b-8419-4e3c-8a65-82e8b2fc1af3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.13","prompt":"SIMULATE a fault between the fire system and the warning system and confirm the fault condition is indicated at the EWP and the FIP.","input":null,"possible_fault":"Interface fault not indicated at panels","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.13 - Fire/warning system interface fault not indicated","severity_level":"non-conformance","fault_id":"rechbBtJxsNOHISPh","prompt_id":"rechbBtJxsNOHISPh_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"0a7bb5f8-2b6a-4e66-b6ce-ac3b1a0d3f76","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.18","prompt":"CONFIRM that the alarm signal overrides non-emergency audible signals.","input":null,"possible_fault":"Alarm doesn't override non-emergency signals","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.18 - Alarm signal override function failure","severity_level":"non-critical","fault_id":"recvKlBjVNmRhWv7c","prompt_id":"recvKlBjVNmRhWv7c_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"0b4081ba-4e66-42ec-96da-4c4acee073b6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.3 FIVE YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"3.2","prompt":"UNDERTAKE tests to ensure intelligibility in all areas of the building where required.","input":null,"possible_fault":"Speech not intelligible in required areas","possible_fault_description":"AS1851 2012 TABLE 6.4.3.3 ITEM 3.2 - Speech intelligibility below required standards","severity_level":"critical","fault_id":"rec4FnT3qQsyPyeeA","prompt_id":"rec4FnT3qQsyPyeeA_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"2648d8e6-3773-450a-b982-440c001dd2d1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.9","prompt":"SIMULATE an alarm condition via the fire system with the warning system in automatic mode.","input":null,"possible_fault":"Automatic warning system doesn't activate","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.9 - Fire system doesn't initiate warning system in auto mode","severity_level":"critical","fault_id":"rec5HBlqHKDjebo1x","prompt_id":"rec5HBlqHKDjebo1x_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"31346879-7ba1-4efe-9faa-2b22ea28a7d3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.15.A","prompt":"MEASURE system quiescent and alarm currents. Calculate the required battery capacity and CHECK the installed battery’s nominal capacity is no less than the required capacity. See Appendix F for calculating the required battery capacity.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rectX5fYS1Iy69dVd_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"36669dc7-c072-4e72-8e26-ff58d76d11ad","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.3 FIVE YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"3.4.B","prompt":"MEASURE and record the impedance of each loud speaker circuit and check that it has not changed by more than 15% from the last test nor exceeded the rated output as required for the amplifier.","input":null,"possible_fault":"Circuit impedance changed >15% from last test","possible_fault_description":"AS1851 2012 TABLE 6.4.3.3 ITEM 3.4 - Speaker circuit impedance exceeds acceptable limits","severity_level":"non-critical","fault_id":"recjKCvtgD2YjDtkE","prompt_id":"recjKCvtgD2YjDtkE_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"490657c1-a137-4e7f-84b0-4c63c2554969","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.1 MONTHLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"1.4","prompt":"Where vented batteries are used, INSPECT the battery enclosure for evidence of corrosion.","input":null,"possible_fault":"Battery enclosure corrosion evident","possible_fault_description":"AS1851 2012 TABLE 6.4.3.1 ITEM 1.4 - Vented battery enclosure showing corrosion damage","severity_level":"non-critical","fault_id":"reccVRta9g1NHhMX9","prompt_id":"reccVRta9g1NHhMX9_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"5340a71d-c5c2-463a-bad4-92d4c89617b2","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.8","prompt":"INSPECT the as-installed drawings to ensure the plan is legible and current.","input":null,"possible_fault":"Drawings illegible or not current","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.8 - As-installed drawings outdated or unreadable","severity_level":"non-conformance","fault_id":"rec7fji3a9BXhkyg0","prompt_id":"rec7fji3a9BXhkyg0_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"58b28a72-b613-4743-b051-924eec3be972","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.11","prompt":"TEST or confirm the operation of the aural indicators as required.","input":null,"possible_fault":"Aural indicators fail to operate","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.11 - Aural indicator operational failure","severity_level":"non-critical","fault_id":"recR2LwFodHdfCQ3f","prompt_id":"recR2LwFodHdfCQ3f_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"5dbabcae-d64e-40d4-b627-7d6dad2900a7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.15.B","prompt":"MEASURE system quiescent and alarm currents. Calculate the required battery capacity and CHECK the installed battery’s nominal capacity is no less than the required capacity. See Appendix F for calculating the required battery capacity.","input":null,"possible_fault":"Installed battery capacity insufficient","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.15 - Battery capacity less than calculated requirement","severity_level":"critical","fault_id":"reck2d9ujMihhNfqK","prompt_id":"reck2d9ujMihhNfqK_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"60995c46-8327-4a9a-84bc-6642a6d2cffd","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.3 FIVE YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"3.4.A","prompt":"MEASURE and record the impedance of each loud speaker circuit and check that it has not changed by more than 15% from the last test nor exceeded the rated output as required for the amplifier.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recF4bvlvyGrt3PzJ_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"6249f1ab-cea7-4f80-8bd1-57311bfb0be1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.16","prompt":"TEST the operation of ancillary control functions and ensure that each controlled device can be correctly initiated.","input":null,"possible_fault":"Ancillary control functions fail","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.16 - Controlled devices don't respond to initiation","severity_level":"critical","fault_id":"recifmzkqfBn4GgzU","prompt_id":"recifmzkqfBn4GgzU_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"63234778-549f-4c16-8759-ce0e945ddd2b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.19","prompt":"CONDUCT a functional system test with other interfaced fire systems (see Appendix D) and CHECK the interface functions as required.","input":null,"possible_fault":"Interface with other fire systems fails","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.19 - Interfaced fire system functional test failure","severity_level":"critical","fault_id":"rec7a5N80MTHJye1F","prompt_id":"rec7a5N80MTHJye1F_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"6911268d-243c-49ec-8cd9-d6c29c6f851a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.17","prompt":"TEST the Emergency warning system and check the signals are distinctly audible in all areas of the building. NOTE: In order to reduce the disturbance to occupants an acceptable means of conducting this test is to provide an audio signal other than the warning signal at a reduced sound pressure level.","input":null,"possible_fault":"Warning signals not audible in all areas","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.17 - Emergency warning signals inadequately audible","severity_level":"non-critical","fault_id":"recR6iyUfqbY0vp2l","prompt_id":"recR6iyUfqbY0vp2l_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"6f753a02-369d-40ca-bd64-9266c450088e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.1 MONTHLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"1.3","prompt":"INSPECT the warning system panel, and—(a) ensure that it is clearly visible, readily accessible and free from dust and contaminants; (b) where a panel is obscured by a door, CHECK that the door is correctly labelled; and (c) where manual call points use replaceable frangible elements, ENSURE that at least one replacement element and a tool is available for replacing the element where required.","input":null,"possible_fault":"Panel contaminated/obscured or manual call point elements missing","possible_fault_description":"AS1851 2012 TABLE 6.4.3.1 ITEM 1.3 - Warning system panel accessibility/cleanliness issues","severity_level":"non-conformance","fault_id":"recEPkoxOtUOVJ2ph","prompt_id":"recEPkoxOtUOVJ2ph_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"704c699c-9d1c-42c4-be48-a8641b7fff92","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.21","prompt":"INSPECT all areas of the building to ensure that no structural changes are likely to affect evacuation zones.","input":null,"possible_fault":"Structural changes affect evacuation zones","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.21 - Building modifications impact evacuation requirements","severity_level":"critical","fault_id":"recCC7VMdeGpREC58","prompt_id":"recCC7VMdeGpREC58_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"7a129af8-313d-4ab2-9e70-684a8454dac7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.14","prompt":"TEST the operation of each visual indicator and alphanumeric displays.","input":null,"possible_fault":"Visual indicators/displays fail to operate","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.14 - Visual indicator/display operational failure","severity_level":"non-critical","fault_id":"rechbE1ePUv6sX5CO","prompt_id":"rechbE1ePUv6sX5CO_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"8fa76c6a-db7e-488e-a081-964e9925725b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.10","prompt":"SIMULATE a speaker circuit fault, emergency call point circuit fault and visual warning device circuit fault for each circuit and confirm the fault condition is indicated at the emergency warning panel (EWP), FIP and any corresponding SIP.","input":null,"possible_fault":"Fault conditions not indicated at panels","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.10 - Circuit fault indications don't appear at EWP/FIP/SIP","severity_level":"non-conformance","fault_id":"recompYx6JgQeWQyY","prompt_id":"recompYx6JgQeWQyY_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"9f8db537-812c-4076-95be-7b77bf36577e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.6","prompt":"Where other warning devices are used as alarm-indicating devices, INSPECT all devices to ensure that they are in place and ensure that they are clearly and correctly labelled where labelling is required.","input":null,"possible_fault":"Warning devices missing or incorrectly labelled","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.6 - Other warning devices not properly positioned/labelled","severity_level":"non-conformance","fault_id":"recuom7xokz7TFVx3","prompt_id":"recuom7xokz7TFVx3_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"a956f7ac-4b9f-4c2a-872a-169a89ae257a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.1 MONTHLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"1.2","prompt":"INSPECT zone block plans to ensure that they are\n securely mounted and legible and supplementary\n zone drawings, if provided, are available and legible.","input":null,"possible_fault":"Zone plans not securely mounted or illegible","possible_fault_description":"AS1851 2012 TABLE 6.4.3.1 ITEM 1.2 - Zone block plans not properly displayed or readable","severity_level":"non-conformance","fault_id":"recdBAtS2UcjiHwBx","prompt_id":"recdBAtS2UcjiHwBx_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"aa22aec4-f27a-418e-a616-9f71aaadbea6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.2","prompt":"INSPECT all emergency call points for any condition that is likely to adversely affect their operation.","input":null,"possible_fault":"Call points damaged or contaminated","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.2 - Emergency call point condition affects operation","severity_level":"non-critical","fault_id":"recEenVNJehF0Lqmz","prompt_id":"recEenVNJehF0Lqmz_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"b98f5d5c-90be-4e8c-831b-77257e3d6f9b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.5","prompt":"TEST the operation of each visual warning device.","input":null,"possible_fault":"VWDs fail operational test","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.5 - Visual warning device operation malfunction","severity_level":"non-critical","fault_id":"recLfBwGFj1V84YH7","prompt_id":"recLfBwGFj1V84YH7_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"bb8a3fae-c7d3-45d7-8e27-1055c2e20de7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.4","prompt":"Where visual warning devices (VWDs) are used as the alarm-indicating devices, INSPECT all devices for any condition or damage that is likely to adversely affect their operation and ensure that they are clearly and correctly labelled where labelling is required.","input":null,"possible_fault":"VWDs damaged or incorrectly labelled","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.4 - Visual warning device condition/labelling defects","severity_level":"non-critical","fault_id":"reciRlznLPteFXbBs","prompt_id":"reciRlznLPteFXbBs_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"c69e0226-a486-422e-b4cf-d9d0ffb6f937","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.3 FIVE YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"3.3","prompt":"MEASURE and record the sound pressure level from at least one reference point for each amplifier used and ensure at each recorded point the measured value is consistent with the reference sound pressure level.","input":"TEXT","possible_fault":"SPL inconsistent with reference levels","possible_fault_description":"AS1851 2012 TABLE 6.4.3.3 ITEM 3.3 - Sound pressure level deviates from reference","severity_level":"non-critical","fault_id":"recRmpDl6HAgntL9k","prompt_id":"recRmpDl6HAgntL9k_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"ca5bd16e-3ab4-4f5b-baed-7c3d5f2e9058","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.7","prompt":"TEST for correct operation.","input":null,"possible_fault":"Warning devices fail operational test","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.7 - Other warning device operation malfunction","severity_level":"critical","fault_id":"rece5eyG9BkJY9lKk","prompt_id":"rece5eyG9BkJY9lKk_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"d4fa4cb8-f846-4d7d-95cd-38d6aaf0c812","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.20.C","prompt":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":null,"possible_fault":"Battery fails discharge test","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.20 - Battery condition inadequate per discharge test","severity_level":"critical","fault_id":"recbYaIVQ3b7QIJA6","prompt_id":"recbYaIVQ3b7QIJA6_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"d87fb79f-0017-474c-88d0-4c85a00c5600","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.1 MONTHLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"1.5","prompt":"SIMULATE an alarm condition and confirm that the required warning signal(s) operate. NOTE: It is recommended that the warden intercom system is used by the floor wardens to confirm the operation of the warning signals.","input":null,"possible_fault":"Warning signals fail to operate correctly","possible_fault_description":"AS1851 2012 TABLE 6.4.3.1 ITEM 1.5 - Simulated alarm condition doesn't activate warning signals","severity_level":"critical","fault_id":"rec64CzNrSqdw1eUy","prompt_id":"rec64CzNrSqdw1eUy_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"d954a795-d69f-461f-a5a6-8ca341f04fe9","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.22","prompt":"INSPECT all areas of the building to ensure that\n changes to the occupancy are not likely to affect\n the required performance of the system.","input":null,"possible_fault":"Occupancy changes affect system performance","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.22 - Building use changes impact system requirements","severity_level":"critical","fault_id":"rec8IS9SyCkYtpCMH","prompt_id":"rec8IS9SyCkYtpCMH_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"edb58a77-4573-4c9b-8964-4cab7db5d8d6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.3 FIVE YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"3.1","prompt":"INSPECT all areas of the building to ensure that changes to the occupancy are not likely to affect the required performance of the system.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 6.4.3.3 ITEM 3.1 - Monthly/yearly service requirements not fulfilled","severity_level":"non-conformance","fault_id":"recJpDB8QlTJHUyOO","prompt_id":"recJpDB8QlTJHUyOO_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"5_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"f6ba1c21-6371-40f5-8cf1-8ff8de075e63","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.1","prompt":"COMPLETE all monthly service activities, as listed in Table 6.4.3.1.","input":null,"possible_fault":"Monthly service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.1 - Previous monthly service requirements not fulfilled","severity_level":"non-conformance","fault_id":"rec8xBDepbM1feKwH","prompt_id":"rec8xBDepbM1feKwH_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"f751c698-7567-473c-85d3-f76307aec592","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.20.B","prompt":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":"DATE","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec8qgtxiwO9pEzDk_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"},{"id":"f8a1fc26-4930-4a37-8985-4762f0a01547","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.3.2 YEARLY SERVICE SCHEDULE EMERGENCY WARNING SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Emergency Warning System","variant":null,"variant_id":"recy1ku5NAMITWtry","item_no":"2.3","prompt":"TEST the operation of each emergency call point.","input":null,"possible_fault":"Call points fail operational test","possible_fault_description":"AS1851 2012 TABLE 6.4.3.2 ITEM 2.3 - Emergency call point operation malfunction","severity_level":"critical","fault_id":"reci9U6qoUQQYg5iS","prompt_id":"reci9U6qoUQQYg5iS_prompt","inspection_id":"c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recy1ku5NAMITWtry_rec3U01F6OlYh40uD"}]}],"other_checklist_items":[{"id":"05045d34-13d7-4034-b0d3-8fd2d6b8e43c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.6","prompt":"(e) Isolation or fault in any part of the fire detection or control system that prevents the automatic or electrical manual discharge of the suppression system.","input":null,"possible_fault":"VWD fails on system isolation/fault","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.6 - VWD fails on detection/control system fault","severity_level":"critical","fault_id":"recpWZTs6goILn0YV","prompt_id":"recpWZTs6goILn0YV_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"054b66ce-6ce8-4422-8d4a-6fbf3cf21e9d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.3 YEARLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"2.2","prompt":"Where alarms are interconnected, TEST that the activation of each alarm operates the audible alarm indication in other alarms.","input":null,"possible_fault":"Interconnected alarms don't activate together","possible_fault_description":"AS1851 2012 TABLE 6.4.2.3 ITEM 2.2 - Interconnection circuit failure between alarms","severity_level":"critical","fault_id":"recrC3o8QNzh4pSjx","prompt_id":"recrC3o8QNzh4pSjx_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"09e0d499-5d3c-4937-9a7c-a68f2037d39e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.3","prompt":"TEST the operation of each manual call point.","input":null,"possible_fault":"Call points fail to operate correctly","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.3 - Manual call point operation failure","severity_level":"critical","fault_id":"recixxdY1uAMEwMET","prompt_id":"recixxdY1uAMEwMET_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"0be65b30-6db9-4516-97a2-06f09a05fd03","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.2 MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD MANAGEMENT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"1.2","prompt":"INSPECT the following as applicable: Fire indicator panel (FIP), sub-indicator panel (SIP), repeater panel, fire brigade panel (FBP), mimic panel, fire fan control panel (FFCP) and—(a) ensure that they are clearly visible, readily accessible and free from dust and contaminants; and (b) where a panel is obscured by a door, check that the door is correctly labelled. Where manual call points use replaceable frangible elements, ENSURE that at least one replacement element and tool are available for replacing the element where required.","input":null,"possible_fault":"CIE not visible/accessible/contaminated\nPanel door not correctly labelled\nReplacement elements/tools not available","possible_fault_description":"AS1851 2012 TABLE 6.4.1.2 ITEM 1.2 - CIE not visible/accessible/free from contaminants\nAS1851 2012 TABLE 6.4.1.2 ITEM 1.2 - Panel door not correctly labelled when obscured\nAS1851 2012 TABLE 6.4.1.2 ITEM 1.2 - Replacement frangible elements/tools not available","severity_level":"non-conformance","fault_id":"recV5sJciEytB8ldN","prompt_id":"recV5sJciEytB8ldN_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"0dd5d279-ac3f-4d95-9a5e-3365e9d15e97","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.2 MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD MANAGEMENT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"1.4","prompt":"SIMULATE an alarm condition and confirm that all required common or general visual and audible indications operate and the external alarm is activated. Where the system is monitored ensure the alarm has activated the alarm signalling equipment. Where CIE is a sub-indicator panel, confirm that the alarm condition is indicated at the FIP.","input":null,"possible_fault":"Required alarm indications not operating\nAlarm signalling equipment not activated\nAlarm condition not indicated at FIP","possible_fault_description":"AS1851 2012 TABLE 6.4.1.2 ITEM 1.4 - Visual/audible/external alarm indications not operating\nAS1851 2012 TABLE 6.4.1.2 ITEM 1.4 - Monitored system alarm signalling equipment not activated\nAS1851 2012 TABLE 6.4.1.2 ITEM 1.4 - SIP alarm condition not indicated at FIP","severity_level":"critical","fault_id":"reczGxrtx5WrC0ZMI","prompt_id":"reczGxrtx5WrC0ZMI_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"0e9bac48-1156-4cd5-8c20-cde8588398ae","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.2 MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD MANAGEMENT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"1.5","prompt":"SIMULATE an alarm and confirm the alarm initiates the occupant warning system including any visual warning devices (VWD).","input":null,"possible_fault":"Occupant warning system not initiating","possible_fault_description":"AS1851 2012 TABLE 6.4.1.2 ITEM 1.5 - Occupant warning system/VWD not initiating on alarm","severity_level":"critical","fault_id":"recHSa8WUOA7KuqQP","prompt_id":"recHSa8WUOA7KuqQP_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"1084c92d-fcc1-41bd-a98c-ff8e5dc9ef1d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.6","prompt":"(d) Operation of a manual inhibit switch (where fitted).","input":null,"possible_fault":"VWD fails on manual inhibit switch","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.6 - VWD doesn't operate on manual inhibit","severity_level":"critical","fault_id":"rectJEaYYoNtoiifU","prompt_id":"rectJEaYYoNtoiifU_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"11996759-3f17-4654-a180-3a263dc822cb","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.2","prompt":"(a) Ensure that they are clearly visible readily accessible and free from dust and contaminants.","input":null,"possible_fault":"LCS not visible or accessible","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.2 - Local control station not clearly visible/accessible","severity_level":"non-conformance","fault_id":"recNO9RmOnmftrRoM","prompt_id":"recNO9RmOnmftrRoM_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"14aa56d9-d3a9-4926-9c6c-b78313a19964","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.11","prompt":"TEST not less than 20% of installed alarm \nacknowledgement facilities in such a manner \nthat over a 5-year period, all facilities are \ntested. CHECK the alarm acknowledgement \nfacility functions as required.","input":null,"possible_fault":"Acknowledgement facilities fail","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.11 - Alarm acknowledgement facility malfunction","severity_level":"critical","fault_id":"recUTLwikEGTHjSsx","prompt_id":"recUTLwikEGTHjSsx_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"14c0b7eb-76eb-4299-ba65-dc46b6f75e24","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.1","prompt":"COMPLETE all monthly and six-monthly service activities, as listed in Table 6.4.1.2 and 6.4.1.3.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.1 - Monthly/six-monthly activities not completed","severity_level":"non-conformance","fault_id":"recheG4mNMKojiFVX","prompt_id":"recheG4mNMKojiFVX_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"19c61a6f-bcf1-4cc4-a328-6f45e0b80e21","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.7","prompt":"• equipment fire mode signal/output","input":null,"possible_fault":"Equipment fire mode signal fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.7 - Equipment fire mode signal/output failure","severity_level":"critical","fault_id":"recA0FaFUZHfRubgY","prompt_id":"recA0FaFUZHfRubgY_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"24cea7f8-7a26-4649-899a-4c8ee79ecbd1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.2 MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD MANAGEMENT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"1.8","prompt":"INSPECT zone block plans to ensure that they are securely mounted and legible and supplementary zone drawings, where required, are available and legible.","input":null,"possible_fault":"Zone block plans not secure/legible","possible_fault_description":"AS1851 2012 TABLE 6.4.1.2 ITEM 1.8 - Zone block plans not securely mounted or legible","severity_level":"non-conformance","fault_id":"rec7Ywo967fqENZsW","prompt_id":"rec7Ywo967fqENZsW_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"286488e2-3116-49b4-88d0-6c57281be530","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.7","prompt":"TEST the system logic (e.g. dual detector operation or dependency on more than one alarm) and confirm the operation of—","input":null,"possible_fault":"System logic fails to operate correctly","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.7 - System logic operation failure","severity_level":"critical","fault_id":"rec34amDEmUmKqPFL","prompt_id":"rec34amDEmUmKqPFL_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"2ae71ac2-d643-48f1-a012-7633aa3c8db1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.12","prompt":"TEST the alarm investigation facility if enabled and check it functions as required.","input":null,"possible_fault":"Investigation facility malfunction","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.12 - Alarm investigation facility doesn't function","severity_level":"critical","fault_id":"recXpIB23bqPeGPhA","prompt_id":"recXpIB23bqPeGPhA_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"32b46811-3d8f-4e3b-b357-de0fd7a81ece","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.7","prompt":"• ancillary controls","input":null,"possible_fault":"Ancillary controls fail to operate","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.7 - Ancillary controls operation failure","severity_level":"critical","fault_id":"recKHECuhegtCm3md","prompt_id":"recKHECuhegtCm3md_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"397e6e4a-3b76-4469-a309-73fe7111d75e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.7.A","prompt":"MEASURE system quiescent and maximum alarm currents in accordance with Appendix F. Calculate the required battery capacity and CHECK the nominal capacity of the installed batteries is not less than the calculated capacity. ‘Text deleted’","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec3sCMpU1oCj4LVQ_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"3ec85202-3410-49e6-8bd6-e0e619a2020c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.8","prompt":"TEST detectors as specified in Appendix G and confirm correct alarm zone indication. Where the detectors are used as part of special hazards systems 100% of the detectors shall be functionally tested yearly.","input":null,"possible_fault":"Detectors fail functional test","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.8 - Fire detector test failure/wrong zone","severity_level":"critical","fault_id":"recF4QYQ3BlTOemJG","prompt_id":"recF4QYQ3BlTOemJG_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"435b8fba-f090-4926-891b-5e1e1477e16b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.2 MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD MANAGEMENT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"1.3","prompt":"Where vented batteries are used, INSPECT the battery enclosure for evidence of corrosion.","input":null,"possible_fault":"Battery enclosure showing corrosion evidence","possible_fault_description":"AS1851 2012 TABLE 6.4.1.2 ITEM 1.3 - Vented battery enclosure showing corrosion evidence","severity_level":"non-critical","fault_id":"recp10Trcxt6tJY04","prompt_id":"recp10Trcxt6tJY04_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"46ea8bfe-307b-4260-8124-5ae032a5eb5b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.2 MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD MANAGEMENT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"1.6","prompt":"INITIATE an isolate/disable condition at the fire indicator panel and confirm that all required common or general visual and audible indications operate. Where the system is monitored, ensure the isolate is received by the monitoring service provider alarm signalling equipment. Where the panel is an SIP, confirm that the isolate/disable condition is indicated at the FIP as either a fault or isolate/disable.","input":null,"possible_fault":"Isolate/disable indications not operating\nIsolate not received by monitoring service\nIsolate/disable not indicated at FIP","possible_fault_description":"AS1851 2012 TABLE 6.4.1.2 ITEM 1.6 - Isolate/disable visual/audible indications not operating\nAS1851 2012 TABLE 6.4.1.2 ITEM 1.6 - Isolate not received by monitoring service provider\nAS1851 2012 TABLE 6.4.1.2 ITEM 1.6 - SIP isolate/disable condition not indicated at FIP","severity_level":"non-conformance","fault_id":"recGevnhyDSt6oLHK","prompt_id":"recGevnhyDSt6oLHK_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"49f08388-1d3f-4e0d-8dfa-9df10e39c45c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.7","prompt":"• system discharge actuator","input":null,"possible_fault":"System discharge actuator fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.7 - System discharge actuator operation failure","severity_level":"critical","fault_id":"recDWkfXbwZUPV49w","prompt_id":"recDWkfXbwZUPV49w_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"4c18973e-3262-4843-8d6a-cc6db4844db2","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.4","prompt":"Where other warning devices are used as the\n alarm-indicating devices, INSPECT all devices\n to ensure that they are in place.","input":null,"possible_fault":"Warning devices missing or displaced","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.4 - Other warning devices not in place","severity_level":"non-conformance","fault_id":"rech7eqZgeNUQ9yaL","prompt_id":"rech7eqZgeNUQ9yaL_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"4de8dff0-a2c8-4408-993f-96a0f4752bf0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.7","prompt":"• audible alarms","input":null,"possible_fault":"Audible alarms fail to operate","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.7 - Audible alarms don't operate with system logic","severity_level":"critical","fault_id":"recCQjkscorVvMakD","prompt_id":"recCQjkscorVvMakD_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"52f9c001-4803-4b67-9456-9c0a4942eb64","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.29","prompt":"SIMULATE the system operation and confirm that each electrical directional valve operates as required.","input":null,"possible_fault":"Directional valves don't operate","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.29 - Electrical directional valve operation failure","severity_level":"critical","fault_id":"recLdYBvFilsvpbzh","prompt_id":"recLdYBvFilsvpbzh_prompt","inspection_id":"c_recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"583817d4-aeb8-4ce5-bd51-57dd1010013d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.3","prompt":"• FIRE ALARM","input":null,"possible_fault":"Visual warning devices damaged/faulty","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.3 - Visual warning devices condition affects function","severity_level":"non-critical","fault_id":"recKpQ1vdg2CWie2s","prompt_id":"recKpQ1vdg2CWie2s_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"59714d8e-75f4-412b-9309-30da2d297b8a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.3 YEARLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"2.6","prompt":"CLEAN each alarm in accordance with the manufacturer’s instructions.","input":null,"possible_fault":"Alarms require cleaning/contamination present","possible_fault_description":"AS1851 2012 TABLE 6.4.2.3 ITEM 2.6 - Alarm contamination affecting performance","severity_level":"non-critical","fault_id":"recdlIVY9T2SDfisu","prompt_id":"recdlIVY9T2SDfisu_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"5b2e58f2-6b89-4d76-8159-a54c7567f4c6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.3","prompt":"• SYSTEM INOPERATIVE","input":null,"possible_fault":"Visual warning devices damaged/faulty","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.3 - Visual warning devices condition affects function","severity_level":"non-critical","fault_id":"recYGvcq51j7kEEyK","prompt_id":"recYGvcq51j7kEEyK_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"5e592355-0adf-46cc-8460-b973e38b04e1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.6","prompt":"TEST the operation of each visual indicator and alphanumeric displays.","input":null,"possible_fault":"Visual indicators/displays fail","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.6 - Visual indicator/alphanumeric display failure","severity_level":"critical","fault_id":"rec4D6rAirBbVQSZq","prompt_id":"rec4D6rAirBbVQSZq_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"5e772ead-6bf2-4361-9e24-e344b4fc9b8e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.2 SIX-MONTHLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"1.2","prompt":"INSPECT all alarms to ensure that any required ‘battery missing indicator’ has not operated.","input":null,"possible_fault":"Battery missing indicator has operated","possible_fault_description":"AS1851 2012 TABLE 6.4.2.2 ITEM 1.2 - Battery missing indicator shows battery fault","severity_level":"non-critical","fault_id":"recYAbktpt9ziHZ6e","prompt_id":"recYAbktpt9ziHZ6e_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"6_month::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"64cc6150-f26f-4a0d-b011-2f86e2995e1f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.3 YEARLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"2.8","prompt":"REPLACE smoke alarms and heat alarms where the service life date is exceeded.","input":null,"possible_fault":"Alarms exceed manufacturer's service life","possible_fault_description":"AS1851 2012 TABLE 6.4.2.3 ITEM 2.8 - Alarm service life date exceeded","severity_level":"recommendation","fault_id":"recJ6jDYi1954aqxI","prompt_id":"recJ6jDYi1954aqxI_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"65a0c5b4-76d5-43e2-a9bc-e99e4b7500cf","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.15","prompt":"Inspect detectors, equipment or other items having a defined service life and report where the service life is exceeded or will be exceeded before the next scheduled service.","input":null,"possible_fault":"Equipment exceeds service life","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.15 - Service life exceeded/will exceed before service","severity_level":"non-critical","fault_id":"recXGw4D6DGgdKXeL","prompt_id":"recXGw4D6DGgdKXeL_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"664c5af1-0117-497f-a53c-c2cb04b7d43b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.2 SIX-MONTHLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"1.3","prompt":"INSPECT that the mains power on indicator is illuminated.","input":null,"possible_fault":"Mains power indicator not illuminated","possible_fault_description":"AS1851 2012 TABLE 6.4.2.2 ITEM 1.3 - Loss of mains power to alarm system","severity_level":"non-critical","fault_id":"recZScrk0MU4sSXgW","prompt_id":"recZScrk0MU4sSXgW_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"6_month::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"666bec1f-b43f-4eab-904b-8b24a5e00ac2","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.3 YEARLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"2.9","prompt":"INSPECT each alarm to ensure spacing and location requirements are as required.","input":null,"possible_fault":"Alarm spacing/location non-compliant","possible_fault_description":"AS1851 2012 TABLE 6.4.2.3 ITEM 2.9 - Alarm positioning doesn't meet requirements","severity_level":"non-conformance","fault_id":"receTAnzO80hk5gif","prompt_id":"receTAnzO80hk5gif_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"6e2e6bc1-8822-4edb-91e1-23277a770180","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.3","prompt":"for any condition or damage that is likely to adversely affect their function.","input":null,"possible_fault":"Visual warning devices damaged/faulty","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.3 - Visual warning devices condition affects function","severity_level":"non-critical","fault_id":"recUuYGoVuATus4XM","prompt_id":"recUuYGoVuATus4XM_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"6e62edf7-4234-4592-af45-869564afef2d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.2 MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD MANAGEMENT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"1.1","prompt":"INSPECT the external alarm (bell or strobe light) to ensure it clearly indicates the designated building entry point. Inspect to ensure the external alarm label is legible with the word ‘FIRE’ in characters not less than 25 mm in height.","input":null,"possible_fault":"External alarm not clearly indicating/labelled","possible_fault_description":"AS1851 2012 TABLE 6.4.1.2 ITEM 1.1 - External alarm not indicating entry/label illegible","severity_level":"non-conformance","fault_id":"recIEBh2CEYkcsNQ2","prompt_id":"recIEBh2CEYkcsNQ2_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"6f7ebebe-d760-4f8c-9a4c-765bfd64e453","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.17","prompt":"(c) for any condition that may cause a nuisance alarm or the unintentional operation of a suppression system","input":null,"possible_fault":"Conditions causing nuisance alarms","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.17 - Conditions may cause nuisance/unintended operation","severity_level":"recommendation","fault_id":"recFvu37D3qJJFliC","prompt_id":"recFvu37D3qJJFliC_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"705c87ea-0b2b-432d-ba0c-b384be099600","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.4","prompt":"(b) Stops and resets the normal system discharge sequence.","input":null,"possible_fault":"Switch fails to stop/reset discharge","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.4 - Inhibit switch doesn't reset discharge sequence","severity_level":"critical","fault_id":"recCcTMg52bx0QE1v","prompt_id":"recCcTMg52bx0QE1v_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"751876b7-7588-4588-bce7-5375291a4897","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.17","prompt":"(d) all exposed cabling, conduits, junction boxes and the like for any condition that may impact on the performance of the system and are labelled correctly; and (e) all CIE to ensure all components are appropriately mounted and secure.","input":null,"possible_fault":"Cabling/components damaged/unlabelled","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.17 - Cabling/components affect performance/incorrectly labelled","severity_level":"non-conformance","fault_id":"recBObdoFPHoxijhF","prompt_id":"recBObdoFPHoxijhF_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"7e45d030-724f-448e-9ce6-db794e04b2a5","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.2 SIX-MONTHLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"1.5","prompt":"Where other sensory warning devices are used as alarm-indicating devices, INSPECT all devices to ensure that they are in place.","input":null,"possible_fault":"Warning devices missing or displaced","possible_fault_description":"AS1851 2012 TABLE 6.4.2.2 ITEM 1.5 - Sensory warning devices not in correct position","severity_level":"non-critical","fault_id":"recZvPDX6sXKW0yir","prompt_id":"recZvPDX6sXKW0yir_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"6_month::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"818d281c-bbf8-4cb1-870e-ece96874c9ac","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.7","prompt":"• VWDs","input":null,"possible_fault":"Visual warning devices fail to operate","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.7 - VWDs don't operate with system logic","severity_level":"non-critical","fault_id":"recmNdrPvbSUPFcvE","prompt_id":"recmNdrPvbSUPFcvE_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"830992a8-fe8b-4a4d-b46a-d93c12d9a8e3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.9","prompt":"TEST the occupant warning system and check the signals are distinctly audible in all areas of the building. NOTE: In order to reduce the disturbance to occupants an acceptable means of conducting this test is to provide an audio signal other than the warning signal at a reduced sound pressure level. Where the FIP is connected to a sound systems and intercom systems for emergency purposes (AS 1670.4) or EWIS (AS 2220.2) test in accordance with Table 6.4.3.2.","input":null,"possible_fault":"Warning signals not audible","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.9 - Warning signals not audible in all areas","severity_level":"critical","fault_id":"recLCN6FY0P5liFoB","prompt_id":"recLCN6FY0P5liFoB_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"86fab619-91eb-4b34-a1f5-c8c8cf5bac3e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.28","prompt":"TEST the each suppression system status monitored function (e.g. container level, \npressure switches, pump controllers, isolation valves) and CHECK each monitored function \nindicates at the suppression system control panel.","input":null,"possible_fault":"Status monitoring functions fail","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.28 - Suppression system status monitoring failure","severity_level":"critical","fault_id":"recFkEDHd3y7Xx4vB","prompt_id":"recFkEDHd3y7Xx4vB_prompt","inspection_id":"c_recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"88f24a2c-be45-4bb8-9b9a-7b24283b62d5","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.2","prompt":"CHECK all manual call points are free of conditions likely to adversely affect their function.","input":null,"possible_fault":"Call points damaged or obstructed","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.2 - Manual call points condition affects function","severity_level":"non-critical","fault_id":"rechkGwvI37uSnU51","prompt_id":"rechkGwvI37uSnU51_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"8b9a25fa-fac6-4549-bf05-c98015dea93c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.7","prompt":"• directional valve signal/output","input":null,"possible_fault":"Directional valve signal/output fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.7 - Directional valve signal/output failure","severity_level":"critical","fault_id":"recaEyK5qDy018Wex","prompt_id":"recaEyK5qDy018Wex_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"8d3f1dc0-7f70-4097-b7c3-54f450f40d27","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.4","prompt":"(c) Causes the illumination of a visual indicator at the LCS and the system FIP.","input":null,"possible_fault":"Visual indicator fails to illuminate","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.4 - Visual indicator at LCS/FIP doesn't illuminate","severity_level":"non-critical","fault_id":"rec9XiOmHTLkQVQmO","prompt_id":"rec9XiOmHTLkQVQmO_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"93b9b734-3da2-4f1c-8751-2638df447926","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.8","prompt":"TEST each supervised actuator circuit to ensure a fault is registered at the FIP.","input":null,"possible_fault":"Circuit fault not registered at FIP","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.8 - Actuator circuit fault not detected at FIP","severity_level":"critical","fault_id":"rec6c7OnoFizZOfxM","prompt_id":"rec6c7OnoFizZOfxM_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"99766bf7-486a-4023-a133-b24cd426cc9c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.4","prompt":"(d) Causes an audible indication.","input":null,"possible_fault":"Audible indication fails to activate","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.4 - Audible indication doesn't activate","severity_level":"non-critical","fault_id":"recyMRe3T9ddDwFm0","prompt_id":"recyMRe3T9ddDwFm0_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"a5160fcf-3339-48df-92c4-6b116d8a3c80","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.3","prompt":"• EVACUATE","input":null,"possible_fault":"Visual warning devices damaged/faulty","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.3 - Visual warning devices condition affects function","severity_level":"non-critical","fault_id":"recAY2cld8RfwjnOz","prompt_id":"recAY2cld8RfwjnOz_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"aa4afb3a-1343-418c-a0a4-e67816d09fcb","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.2 MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD MANAGEMENT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"1.7","prompt":"TEST the operation of each filament type visual indicators.","input":null,"possible_fault":"Filament visual indicators not operating","possible_fault_description":"AS1851 2012 TABLE 6.4.1.2 ITEM 1.7 - Filament type visual indicators not operating","severity_level":"non-critical","fault_id":"recTLz02wY9la0eRg","prompt_id":"recTLz02wY9la0eRg_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"b48052c0-ad6c-41e0-ac9d-3c6bdfe82984","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.3","prompt":"• DO NOT ENTER","input":null,"possible_fault":"Visual warning devices damaged/faulty","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.3 - Visual warning devices condition affects function","severity_level":"non-critical","fault_id":"recEZRYx1o5N9Jry6","prompt_id":"recEZRYx1o5N9Jry6_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"b63740f0-2578-4eac-aecf-c294da31e4ed","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.3 YEARLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"2.4","prompt":"TEST 100% of heat alarms in accordance with the manufacturer’s instructions.","input":null,"possible_fault":"Heat alarms fail manufacturer's test","possible_fault_description":"AS1851 2012 TABLE 6.4.2.3 ITEM 2.4 - Heat detection function malfunction","severity_level":"critical","fault_id":"recZH1JMEZAGReF6n","prompt_id":"recZH1JMEZAGReF6n_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"b7512c1a-3090-4e23-b100-c384f9ae6318","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.17","prompt":"(b) detection device and remote indicators are appropriate for the current use;","input":null,"possible_fault":"Devices inappropriate for current use","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.17 - Detection devices inappropriate for use","severity_level":"non-conformance","fault_id":"rec4zKshcwejCpmFx","prompt_id":"rec4zKshcwejCpmFx_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"ba251908-2af5-4699-8cd7-6ef96216148e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.5","prompt":"TEST the operation of the manual initiate switch and confirm normal system discharge sequence, including fire and evacuation alarms, time delays equipment shutdowns, and that it overrides the LCS discharge inhibit switch.","input":null,"possible_fault":"Manual initiate sequence fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.5 - Manual initiate doesn't trigger discharge sequence","severity_level":"critical","fault_id":"recNb1EmdPN5bW7w8","prompt_id":"recNb1EmdPN5bW7w8_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"bbc07c7b-71b2-4f64-86d8-6a8a01d1aae7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.9","prompt":"TEST the function of each actuator and ensure that each actuator operates correctly. Ensure that each actuator has been mechanically isolated or temporarily removed from the suppressant supply to prevent unintended discharge. For non-resettable actuators (e.g. pyrotechnic types) substitute the actuator with a load of equivalent value and CONFIRM the operating current is as required.","input":null,"possible_fault":"Actuator fails to operate correctly","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.9 - Actuator function test failure","severity_level":"critical","fault_id":"rec7nta9HsN8QHi0M","prompt_id":"rec7nta9HsN8QHi0M_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"bfb4a6ce-1a5d-4f46-831c-b301eaf0ef5a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.2 SIX-MONTHLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"1.4","prompt":"ACTIVATE the alarm test function and check correct activation of the audible indication.","input":null,"possible_fault":"Audible indication fails to activate","possible_fault_description":"AS1851 2012 TABLE 6.4.2.2 ITEM 1.4 - Alarm test function or audible alarm malfunction","severity_level":"critical","fault_id":"recTMdcJU9Z4PBTkw","prompt_id":"recTMdcJU9Z4PBTkw_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"6_month::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"c0208f01-bed2-4733-8b66-6aea05d9d2fa","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.31","prompt":"TEST the agent release detection device (e.g. pressure switch) and confirm the operation of the agent release is indicated at the FIP.","input":null,"possible_fault":"Agent release not indicated at FIP","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.31 - Agent release detection/indication failure at FIP","severity_level":"non-conformance","fault_id":"recL9eyI9t3oUmadU","prompt_id":"recL9eyI9t3oUmadU_prompt","inspection_id":"c_recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"c095a8d9-c1ab-486b-8a08-fee8413d0e96","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.17","prompt":"SURVEY all areas of the building from floor level and check— (a) that the fire detection and alarm system has not been altered, damaged or compromised;","input":null,"possible_fault":"System altered/damaged/compromised","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.17 - Fire detection system altered/damaged","severity_level":"non-critical","fault_id":"recCHDWXRGIY6u5D6","prompt_id":"recCHDWXRGIY6u5D6_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"c199481a-4375-4e5a-be59-7ac165612db8","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.30","prompt":"TEST and RECORD the system discharge sequence and confirm the time delay period is as required.","input":null,"possible_fault":"Time delay period incorrect","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.30 - System discharge time delay not as required","severity_level":"non-critical","fault_id":"recgFh7xZ0gmWMl4B","prompt_id":"recgFh7xZ0gmWMl4B_prompt","inspection_id":"c_recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"c3f908c0-2a1a-4429-ad24-ebe5d15a1be8","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.3 YEARLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"2.5","prompt":"Where other sensory warning devices are used as alarm-indicating devices, TEST all devices to ensure that they are functioning correctly.","input":null,"possible_fault":"Warning devices not functioning correctly","possible_fault_description":"AS1851 2012 TABLE 6.4.2.3 ITEM 2.5 - Sensory warning device operational failure","severity_level":"non-critical","fault_id":"recaxuKCt1mX2Bypm","prompt_id":"recaxuKCt1mX2Bypm_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"c6af8e42-2444-4dde-ab0c-809198d187ee","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.6","prompt":"(c) Operation of a lock-off valve (where fitted).","input":null,"possible_fault":"VWD fails on lock-off valve operation","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.6 - VWD doesn't operate on lock-off valve","severity_level":"critical","fault_id":"recVZTfinlxem0M10","prompt_id":"recVZTfinlxem0M10_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"c72b4b81-7c48-44e3-9472-2b58a79a949c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.6","prompt":"CONFIRM the system inoperative VWD operates\n for:\n (a) Operation of a service switch (discharge initiating circuit electrical isolation).","input":null,"possible_fault":"VWD fails on service switch operation","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.6 - System inoperative VWD fails on isolation","severity_level":"critical","fault_id":"recq6iNemooUH4PTT","prompt_id":"recq6iNemooUH4PTT_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"c81cb9c9-07b5-4b3e-9a43-e36bf07a01bf","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.4","prompt":"(e) Does not override the operation of the manual discharge switch.","input":null,"possible_fault":"Manual discharge not overriding inhibit","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.4 - Manual discharge doesn't override inhibit","severity_level":"critical","fault_id":"rec0dHK1X5GasTHpg","prompt_id":"rec0dHK1X5GasTHpg_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"cad9ff68-c7e7-4643-98df-4b362ccc9226","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.5","prompt":"TEST the operation of each control.","input":null,"possible_fault":"Control switches/keypads malfunction","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.5 - Panel control operation failure","severity_level":"non-critical","fault_id":"recVmGwlCDmlcfESm","prompt_id":"recVmGwlCDmlcfESm_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"d1d79c4d-4291-4f9d-b8d4-d05ac2fa7b02","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.3 YEARLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"2.3","prompt":"TEST 100% of smoke alarms in accordance with the manufacturer’s\n instructions.","input":null,"possible_fault":"Smoke alarms fail manufacturer's test","possible_fault_description":"AS1851 2012 TABLE 6.4.2.3 ITEM 2.3 - Smoke detection function malfunction","severity_level":"critical","fault_id":"recUJu3Sx9KZq4yta","prompt_id":"recUJu3Sx9KZq4yta_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"d4bb816c-734d-413b-a44c-e8074730ae7a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.13.A","prompt":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recfqno6toNncCNZf_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"d4fc5d1b-cdbf-4b05-b180-fe72641a3be4","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.17","prompt":"(e) all CIE to ensure all components are appropriately mounted and secure.","input":null,"possible_fault":"Loose parts risk damage, poor contact, or failure.","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.17 - Loose parts risk damage, poor contact, or failure.","severity_level":"critical","fault_id":"recgpxyc5TuSqwESN","prompt_id":"recgpxyc5TuSqwESN_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"d516dfcd-7f34-49e9-98fb-938598fa5756","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.3 YEARLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"2.7","prompt":"CHECK the manufacturer’s requirements for battery replacement and replace the battery if required.","input":null,"possible_fault":"Battery replacement required/overdue","possible_fault_description":"AS1851 2012 TABLE 6.4.2.3 ITEM 2.7 - Battery life exceeded manufacturer's specification","severity_level":"recommendation","fault_id":"recVTqfTeCMNZctZ1","prompt_id":"recVTqfTeCMNZctZ1_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"d7f17f4b-b4ba-4249-b454-1e3d6afa1cc9","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.7","prompt":"• door and damper release and","input":null,"possible_fault":"Door/damper release fails to operate","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.7 - Door and damper release operation failure","severity_level":"critical","fault_id":"reccenhdtxcrAP0K6","prompt_id":"reccenhdtxcrAP0K6_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"d94ab4f8-29d1-4aa7-8c48-04db4896b339","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.3 YEARLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"2.1","prompt":"COMPLETE all six-monthly service activities, as listed in Table 6.4.2.2.","input":null,"possible_fault":"Six-monthly service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 6.4.2.3 ITEM 2.1 - Previous service requirements not fulfilled","severity_level":"non-conformance","fault_id":"recpxlPt4WZEs7JTH","prompt_id":"recpxlPt4WZEs7JTH_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"1_year::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"db86d4e5-2f4a-48ab-bba8-fb5c0380e6cf","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.2.2 SIX-MONTHLY SERVICE SCHEDULE SMOKE ALARMS AND HEAT ALARMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Smoke/Heat Alarm System,Smoke/Heat Alarm System (SOU)","variant":null,"variant_id":"rec5PYzWjYMKYLkYI, recqjdzxhag0yzqOi","item_no":"1.1","prompt":"INSPECT all alarms for any condition that is likely to adversely affect their operation, such as excessive deposition of dust or coating of paint.","input":null,"possible_fault":"Excessive dust/paint coating affecting operation","possible_fault_description":"AS1851 2012 TABLE 6.4.2.2 ITEM 1.1 - Alarm contamination impairs detection capability","severity_level":"non-critical","fault_id":"recfOvvZWNirqh6gV","prompt_id":"recfOvvZWNirqh6gV_prompt","inspection_id":"c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD","grouping_key":"6_month::c_rec5PYzWjYMKYLkYI:recqjdzxhag0yzqOi_rec3U01F6OlYh40uD"},{"id":"de7175d1-10b6-427b-ab7d-ef0a9f45fac4","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.13.B","prompt":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":"DATE","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recxL2CiTELsad8IW_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"dff1f924-6a05-4f69-8d33-30590f3f1883","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.6","prompt":"(b) Fault in the discharge actuator circuit.","input":null,"possible_fault":"VWD fails on discharge actuator fault","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.6 - VWD doesn't operate on actuator circuit fault","severity_level":"critical","fault_id":"recgtlOSKiD6uFziZ","prompt_id":"recgtlOSKiD6uFziZ_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"e33b5071-40b9-46a2-95e5-8dfb934da819","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.10","prompt":"MEASURE and record the sound pressure level \nfrom at least one reference point for each \namplifier used and ensure at each reference \npoint the measured value is consistent with the \nrequired sound pressure level at each reference \npoint.","input":null,"possible_fault":"SPL below required level","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.10 - Sound pressure level inconsistent with requirement","severity_level":"non-conformance","fault_id":"reclqcBRgxWdtPXmm","prompt_id":"reclqcBRgxWdtPXmm_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"e4426fdc-3a0e-41a5-8dca-63c915bac54f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.2","prompt":"(b) Check that the door is correctly labelled.","input":null,"possible_fault":"Door labelling incorrect or missing","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.2 - LCS door not correctly labelled","severity_level":"non-conformance","fault_id":"recbvue5xetbSIvVg","prompt_id":"recbvue5xetbSIvVg_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"e48e8d98-f053-4bfb-918f-4500675f57f3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.4","prompt":"TEST the operation of each inhibit or auto/manual switch and confirm that: (a) It prevents the automatic discharge of suppression system.","input":null,"possible_fault":"Inhibit switch fails to prevent discharge","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.4 - Inhibit switch doesn't prevent automatic discharge","severity_level":"critical","fault_id":"rec2RerCfBiTJxeM1","prompt_id":"rec2RerCfBiTJxeM1_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"e7cd9529-1f68-46e7-91f8-f4351d47a618","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.3","prompt":"INSPECT all visual warning devices, including:","input":null,"possible_fault":"Visual warning devices damaged/faulty","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.3 - Visual warning devices condition affects function","severity_level":"non-critical","fault_id":"recdEF5terM9NA9Hx","prompt_id":"recdEF5terM9NA9Hx_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"e9bd4a9a-56d5-49fa-9933-0604c51fa371","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.18","prompt":"Simulate alarm(s) to verify that each interface transmission path initiates the corresponding interfaced system(s) as required.","input":null,"possible_fault":"Interface transmission fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.18 - Interface doesn't initiate corresponding systems","severity_level":"critical","fault_id":"receAmgylPZA9x3IU","prompt_id":"receAmgylPZA9x3IU_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"ed5418ee-4fe4-4e6c-bb37-f85bac52816f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.14","prompt":"Refer to Clause 6.4.2.","input":null,"possible_fault":"Conditions causing nuisance alarms","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.17 - Conditions may cause nuisance/unintended operation","severity_level":"informational","fault_id":"rec8SQsFAgtWS0Ht4","prompt_id":"rec8SQsFAgtWS0Ht4_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"eec1e17b-cca9-4dcb-a7b8-8b7f42877191","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.7","prompt":"• HVAC fire mode signal/output","input":null,"possible_fault":"HVAC fire mode signal fails","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.7 - HVAC fire mode signal/output failure","severity_level":"critical","fault_id":"recXAMgSwt1rRpvfY","prompt_id":"recXAMgSwt1rRpvfY_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"f0810dd6-0eaa-48fd-926e-1504d0314b1f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE DETECTION, ALARMS AND CONTROLS FOR SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire detection and alarm systems,Special Hazards Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB","item_no":"2.1","prompt":"Complete all monthly service activities, as listed in Table 6.4.1.2.","input":null,"possible_fault":"Monthly service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 6.4.1.3 ITEM 2.1 - Monthly service activities not completed","severity_level":"non-conformance","fault_id":"recKJMY6Eo5EZQb3Y","prompt_id":"recKJMY6Eo5EZQb3Y_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD","grouping_key":"6_month::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB_rec3U01F6OlYh40uD"},{"id":"f864d1fd-5598-4504-b5dd-72ec612cd812","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.13.C","prompt":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":null,"possible_fault":"Battery fails discharge test","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.13 - Battery condition inadequate per discharge test","severity_level":"non-conformance","fault_id":"recTt0Qz1WWsP8Erc","prompt_id":"recTt0Qz1WWsP8Erc_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"},{"id":"fa1d59cf-aa12-4481-b28b-cea97214e08d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Detection and Alarm Systems","category_id":"rec3U01F6OlYh40uD","group_header":"TABLE 6.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE DETECTION AND ALARM SYSTEM, SPECIAL HAZARD SYSTEMS AND SMOKE HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire detection and alarm systems,Special Hazards Systems,Smoke Hazard Management Systems","variant":null,"variant_id":"recAhOjivmmUeMZhW, recoMHFXU1KocjaUB, rectLPJrpuPKS4gL6","item_no":"3.7.B","prompt":"MEASURE system quiescent and maximum alarm currents in accordance with Appendix F. Calculate the required battery capacity and CHECK the nominal capacity of the installed batteries is not less than the calculated capacity. ‘Text deleted’","input":null,"possible_fault":"Battery capacity insufficient","possible_fault_description":"AS1851 2012 TABLE 6.4.1.4 ITEM 3.7 - Battery capacity below calculated requirement","severity_level":"critical","fault_id":"recvcQbOw7ZKQAmde","prompt_id":"recvcQbOw7ZKQAmde_prompt","inspection_id":"c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD","grouping_key":"1_year::c_recAhOjivmmUeMZhW:recoMHFXU1KocjaUB:rectLPJrpuPKS4gL6_rec3U01F6OlYh40uD"}]},{"id":"recA6pWmW422Ltih1","name":"Water Storage Tanks for Fire Protection Systems","asset_types":[{"id":"recAn91z5MfnsPweZ","name":"Water Storage Tank : Rectangular panel tanks","checklist":[]},{"id":"recbbAItgqFl4yvnc","name":"Water Storage Tank : Pressure tanks","checklist":[{"id":"0f6478c3-7f07-41f7-9286-ba6032bf84f5","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Pressure tanks","variant":null,"variant_id":"recbbAItgqFl4yvnc","item_no":"3.36","prompt":"(a) INSPECT externally for structural integrity,\nfreedom from corrosion, and acceptable\ncondition in accordance with AS/NZS 3788.","input":null,"possible_fault":"Structural corrosion","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.36 - External pressure tank corroded or deformed","severity_level":"non-critical","fault_id":"recGffPPvm4cBC5MT","prompt_id":"recGffPPvm4cBC5MT_prompt","inspection_id":"c_recbbAItgqFl4yvnc_recA6pWmW422Ltih1","grouping_key":"1_year::c_recbbAItgqFl4yvnc_recA6pWmW422Ltih1"},{"id":"b43e43b7-9d2c-4593-82ef-9aa1b924fbda","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.4 TEN-YEARLY AND OTHER SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Water Storage Tank : Pressure tanks","variant":null,"variant_id":"recbbAItgqFl4yvnc","item_no":"4.4","prompt":"Conduct a six-yearly inspection by a qualified pressure vessel inspector.","input":null,"possible_fault":"No pressure inspection","possible_fault_description":"AS1851 2012 TABLE 5.4.4 ITEM 4.4 - No formal 6-year pressure vessel check done","severity_level":"non-conformance","fault_id":"recKfnTh9ln6RS3G6","prompt_id":"recKfnTh9ln6RS3G6_prompt","inspection_id":"c_recbbAItgqFl4yvnc_recA6pWmW422Ltih1","grouping_key":"10_year::c_recbbAItgqFl4yvnc_recA6pWmW422Ltih1"},{"id":"b705c6e8-aeec-4781-8a59-591866d884a6","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Pressure tanks","variant":null,"variant_id":"recbbAItgqFl4yvnc","item_no":"3.36","prompt":"(b) VERIFY low water level alarm switch\noperates at predetermined level","input":null,"possible_fault":"Alarm fails to activate","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.36 - Low water alarm not triggering when required","severity_level":"critical","fault_id":"recwavdiZIgtWtrzj","prompt_id":"recwavdiZIgtWtrzj_prompt","inspection_id":"c_recbbAItgqFl4yvnc_recA6pWmW422Ltih1","grouping_key":"1_year::c_recbbAItgqFl4yvnc_recA6pWmW422Ltih1"}]},{"id":"receJzXoQISUPKcqA","name":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","checklist":[{"id":"2b7b4d74-aa90-4093-aeb3-6188714581be","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"receJzXoQISUPKcqA","item_no":"3.31","prompt":"CHECK for signs of leaks, cuts and tears of the\nliner.","input":null,"possible_fault":"Liner leaks or torn","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.31 - Submerged liner shows tears or perforation","severity_level":"critical","fault_id":"recqe35thoKBAZrBb","prompt_id":"recqe35thoKBAZrBb_prompt","inspection_id":"c_receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"1_year::c_receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"399a62af-a3be-46d1-828b-f5737deedc7f","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"receJzXoQISUPKcqA","item_no":"3.32","prompt":"(c) refill the tank as soon as practicable.\nNOTES:\n1 For water conservation measures when tanks\nneed to be drained, see AS 2304.\n2 Ensure the liner is in the correct position\nprior to refilling; this includes the\npositioning of the neoprene mat (where\nfitted) under the vortex inhibitor bottom\nsupport and strainer.\n3 A diver or other underwater inspection and\ncleaning technique may be used in lieu of\ndraining the tank in consultation with the\ntank manufacturer to satisfy warranty\nrequirements.","input":null,"possible_fault":"Tank not refilled correctly","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.32 - Liner or mat not aligned before refilling","severity_level":"non-critical","fault_id":"recEvB4NhJzoUrvUW","prompt_id":"recEvB4NhJzoUrvUW_prompt","inspection_id":"c_receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"1_year::c_receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"436f8091-fdc9-4459-8f91-c23bbbefd478","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"receJzXoQISUPKcqA","item_no":"3.33","prompt":"Complete a sludge depth measurement to\ndetermine the next period for draining and\ncleaning the tank.","input":null,"possible_fault":"Sludge depth excessive","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.33 - Depth exceeds threshold for cleaning","severity_level":"non-critical","fault_id":"recqnA0SXLM4VIBBR","prompt_id":"recqnA0SXLM4VIBBR_prompt","inspection_id":"c_receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"1_year::c_receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"5d156b8f-479b-4bec-b57e-0aa37ecb2153","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"receJzXoQISUPKcqA","item_no":"3.28","prompt":"CHECK to determine the extent of any\ndiscolouration to the tank liner.","input":null,"possible_fault":"Liner discoloured","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.28 - Visible colour change to submerged liner surface","severity_level":"non-critical","fault_id":"recd6tZMVNkFgW9ZL","prompt_id":"recd6tZMVNkFgW9ZL_prompt","inspection_id":"c_receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"1_year::c_receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"722af157-f039-4baa-a74b-ad8b604afc5e","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"receJzXoQISUPKcqA","item_no":"3.29","prompt":"CHECK for signs of elongation of the liner.","input":null,"possible_fault":"Liner is stretched","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.29 - Liner elongated beyond standard tolerance","severity_level":"non-critical","fault_id":"rec7S3OhMZDXfFMbe","prompt_id":"rec7S3OhMZDXfFMbe_prompt","inspection_id":"c_receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"1_year::c_receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"78dd7613-5fce-4ee9-832e-f9d5b5de829d","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"receJzXoQISUPKcqA","item_no":"3.34","prompt":"Undertake a study of the tank base and liner for\nweak spots due to undermining, noting that\nfounding material needs to be felt solid at all\nareas. Minor hollow areas are to be underpinned\nand major hollowing requires a geotechnical\ninvestigation and reassessment of the sealing\nsystem.","input":null,"possible_fault":"Base not stable","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.34 - Hollow or soft spots detected under liner","severity_level":"non-critical","fault_id":"recMbdNyvvzVE71kg","prompt_id":"recMbdNyvvzVE71kg_prompt","inspection_id":"c_receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"1_year::c_receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"bab6fe34-ddb6-45b6-83c7-aba8eabf37f4","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"receJzXoQISUPKcqA","item_no":"3.27","prompt":"CHECK for signs of loss of flexibility.","input":null,"possible_fault":"Loss of flexibility","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.27 - Liner material no longer pliable as required","severity_level":"non-critical","fault_id":"recs4jfmkkf0quVWC","prompt_id":"recs4jfmkkf0quVWC_prompt","inspection_id":"c_receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"1_year::c_receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"dbbb5d4a-1f94-4d14-abd1-efc35d00359e","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"receJzXoQISUPKcqA","item_no":"3.32","prompt":"DRAIN and CLEAN the tank leaving a minimum\nof 50 mm of water to prevent liner movement,\nand—\n(a) remove all sludge and debris without using\nsharp tools or shovels to prevent tearing and\npuncturing of the liner;\n\nNOTES:\n1 For water conservation measures when tanks \nneed to be drained, see AS 2304. \n2 Ensure the liner is in the correct position \nprior to refilling; this includes the \npositioning of the neoprene mat (where \nfitted) under the vortex inhibitor bottom \nsupport and strainer. \n3 A diver or other underwater inspection and \ncleaning technique may be used in lieu of \ndraining the tank in consultation with the \ntank manufacturer to satisfy warranty \nrequirements.","input":null,"possible_fault":"Debris not cleared","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.32 - Sludge or debris left; liner may be at risk","severity_level":"non-critical","fault_id":"recJ1tV3Mrc8lEfkF","prompt_id":"recJ1tV3Mrc8lEfkF_prompt","inspection_id":"c_receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"1_year::c_receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"f96c0f89-b41e-41e3-b529-8f9d0fd306d1","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"receJzXoQISUPKcqA","item_no":"3.30","prompt":"CHECK for signs of the liner bulging out from\nunder the base girder (external).","input":null,"possible_fault":"Liner bulging externally","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.30 - Liner pushes out from under tank base ring","severity_level":"non-critical","fault_id":"recckhfohfnab6oI4","prompt_id":"recckhfohfnab6oI4_prompt","inspection_id":"c_receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"1_year::c_receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"fd1f6ce8-eec8-4adf-97dc-1d5ac1ab1299","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"receJzXoQISUPKcqA","item_no":"3.32","prompt":"(b) clean all internal surfaces, excluding the\nroof, with low pressure water spray using\nappropriate footwear to avoid damage to the\ntank liner; and\n\nNOTES:\n1 For water conservation measures when tanks \nneed to be drained, see AS 2304. \n2 Ensure the liner is in the correct position \nprior to refilling; this includes the \npositioning of the neoprene mat (where \nfitted) under the vortex inhibitor bottom \nsupport and strainer. \n3 A diver or other underwater inspection and \ncleaning technique may be used in lieu of \ndraining the tank in consultation with the \ntank manufacturer to satisfy warranty \nrequirements.","input":null,"possible_fault":"Liner not cleaned safely","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.32 - Surfaces not cleaned properly; liner damaged","severity_level":"non-critical","fault_id":"rect2h0v0V1nLSZZ1","prompt_id":"rect2h0v0V1nLSZZ1_prompt","inspection_id":"c_receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"1_year::c_receJzXoQISUPKcqA_recA6pWmW422Ltih1"}]},{"id":"recPVmEAYvGKqZVfK","name":"Water Storage Tank : Water Tank with Liners - (a) above the waterline","checklist":[{"id":"47011576-c0cf-4da6-915c-a9adec083148","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (a) above the waterline","variant":null,"variant_id":"recPVmEAYvGKqZVfK","item_no":"3.23","prompt":"CHECK for signs of shrinkage and increased\nliner tension.","input":null,"possible_fault":"Liner shrinkage evident","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.23 - Liner appears taut or pulled due to shrinkage","severity_level":"non-critical","fault_id":"recS6ha4lH9H5hD71","prompt_id":"recS6ha4lH9H5hD71_prompt","inspection_id":"c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1","grouping_key":"1_year::c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1"},{"id":"794e5c61-b626-4cf7-b7c7-4e394f636060","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (a) above the waterline","variant":null,"variant_id":"recPVmEAYvGKqZVfK","item_no":"3.24","prompt":"CHECK for signs of liner brittleness.","input":null,"possible_fault":"Liner is brittle","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.24 - Material loses flexibility and shows brittleness","severity_level":"non-critical","fault_id":"recj7frEaI7SovMOG","prompt_id":"recj7frEaI7SovMOG_prompt","inspection_id":"c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1","grouping_key":"1_year::c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1"},{"id":"9abbbb85-5890-4aa0-9f1f-351dc9329952","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (a) above the waterline","variant":null,"variant_id":"recPVmEAYvGKqZVfK","item_no":"3.25","prompt":"CHECK for signs of cuts and tear.","input":null,"possible_fault":"Cuts or tears present","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.25 - Visible liner damage such as tears or cuts","severity_level":"non-critical","fault_id":"recvPGJnBb5BRVs7q","prompt_id":"recvPGJnBb5BRVs7q_prompt","inspection_id":"c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1","grouping_key":"1_year::c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1"},{"id":"a4354509-41f9-480d-aa61-23dd582a7b64","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (a) above the waterline","variant":null,"variant_id":"recPVmEAYvGKqZVfK","item_no":"3.26","prompt":"CHECK for signs of surface deterioration or\nchalking.","input":null,"possible_fault":"Surface worn or faded","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.26 - Liner shows signs of aging or surface breakdown","severity_level":"non-critical","fault_id":"recYMGFeaxpHJ6vmZ","prompt_id":"recYMGFeaxpHJ6vmZ_prompt","inspection_id":"c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1","grouping_key":"1_year::c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1"},{"id":"c0eb5ee7-8a18-42fb-a602-e3ea4e1bd27c","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (a) above the waterline","variant":null,"variant_id":"recPVmEAYvGKqZVfK","item_no":"3.21","prompt":"CHECK eyelets, attachment connectors and other\nmechanical fixings for wear, detachment or\ncorrosion.","input":null,"possible_fault":"Fixings worn or loose","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.21 - Liner eyelets or fixings worn, corroded or detached","severity_level":"non-critical","fault_id":"rechUtT8AAnxT1hLz","prompt_id":"rechUtT8AAnxT1hLz_prompt","inspection_id":"c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1","grouping_key":"1_year::c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1"},{"id":"e6b9f931-0e4d-43fa-a3e7-57f3c40f8606","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank : Water Tank with Liners - (a) above the waterline","variant":null,"variant_id":"recPVmEAYvGKqZVfK","item_no":"3.22","prompt":"CHECK to determine the extent of any\ndiscolouration to the tank liner and, if significant,\ncontact the liner manufacturer.","input":null,"possible_fault":"Liner discoloured","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.22 - Liner shows notable discoloration; review required","severity_level":"non-critical","fault_id":"recV6dRvX2qg3S7Y3","prompt_id":"recV6dRvX2qg3S7Y3_prompt","inspection_id":"c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1","grouping_key":"1_year::c_recPVmEAYvGKqZVfK_recA6pWmW422Ltih1"}]},{"id":"recYcid2mLApcEh2Z","name":"Water Storage Tank","checklist":[{"id":"0553d2a9-6838-464e-9217-ff0f741fac58","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.2 SIX-MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"2.3","prompt":"VERIFY all water level indicators (mechanical\nand electronic) are operating properly by\nexercising the indicator or mechanism.","input":null,"possible_fault":"Level indicator not working","possible_fault_description":"AS1851 2012 TABLE 5.4.2 ITEM 2.3 - Indicator not functioning during test","severity_level":"non-critical","fault_id":"recZBMkFTo3nnN6y1","prompt_id":"recZBMkFTo3nnN6y1_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"6_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"0c4db533-3ef1-4b5b-98cb-f6b9f307d0b7","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.4 TEN-YEARLY AND OTHER SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"4.2","prompt":"(b) CLEAN all internal surfaces, excluding the\nroof, with low pressure water spray.\n\nNOTES:\n1 A diver or other underwater inspection and \ncleaning technique may be used in lieu of \ndraining the tank. \n2 For water conservation measures when \ntanks need to be drained see AS 2304","input":null,"possible_fault":"Surfaces not cleaned","possible_fault_description":"AS1851 2012 TABLE 5.4.4 ITEM 4.2 - Tank surfaces not cleaned as required","severity_level":"recommendation","fault_id":"recYSicKDO2NQEA7j","prompt_id":"recYSicKDO2NQEA7j_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"10_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"11088787-9408-415b-87c9-dbd231ec6094","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.4","prompt":"CHECK for any physical damage caused by\nimpact, including scratches and dents.","input":null,"possible_fault":"Impact damage","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.4 - Physical damage such as dents or scratches","severity_level":"non-critical","fault_id":"recBqCOvHfexAUHAo","prompt_id":"recBqCOvHfexAUHAo_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"117f124c-7baf-46bc-ad6a-1deba64ec66a","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.3.B","prompt":"(c) Air pressure switch operates at specified\ncompressor cut-in and cut-out pressures.","input":null,"possible_fault":"Switch not operating correctly","possible_fault_description":"AS1851 2012 TABLE 5.4.1 ITEM 1.3 - Cut-in/cut-out pressure incorrect","severity_level":"critical","fault_id":"recDoaba4lJZSuoH6","prompt_id":"recDoaba4lJZSuoH6_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"236a9dd8-92fb-4737-a8b3-8efb119e7193","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.20","prompt":"(b) Cleaning all internal surfaces, excluding the\nroof, with low pressure water spray.\n\nNOTES:\n1 A diver or other underwater inspection and \ncleaning technique may be used in lieu of \ndraining the tank in consultation with the \ntank manufacturer to satisfy warranty \nrequirements. \n2 For water conservation measures when \ntanks need to be drained, see AS 2304","input":null,"possible_fault":"Surfaces not clean","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.20 - Tank surfaces not cleaned per standard","severity_level":"non-critical","fault_id":"recmscP0cYM8GNuIg","prompt_id":"recmscP0cYM8GNuIg_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"29509eeb-29df-4b10-9738-45a7a733726a","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.2","prompt":"CHECK for water leakage from all joints, flanges\nand fittings.","input":null,"possible_fault":"Leak from joints or flanges","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.2 - Visible leak at joints or fittings","severity_level":"non-critical","fault_id":"recs8awyMb0JOdIKN","prompt_id":"recs8awyMb0JOdIKN_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"336eb40e-ecb0-4d2a-a390-4365d7cef4d7","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.20","prompt":"DRAIN and CLEAN the tank completely\nincluding:\n(a) Removing all sludge and debris.\n\nNOTES:\n1 A diver or other underwater inspection and \ncleaning technique may be used in lieu of \ndraining the tank in consultation with the \ntank manufacturer to satisfy warranty \nrequirements. \n2 For water conservation measures when \ntanks need to be drained, see AS 2304","input":null,"possible_fault":"Sludge/debris remains","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.20 - Debris not removed from tank base","severity_level":"non-critical","fault_id":"recZS9fWE66H7LjtR","prompt_id":"recZS9fWE66H7LjtR_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"3807667c-f574-4532-afe7-975e52de13bf","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.3.A","prompt":"(c) Air pressure switch operates at specified\ncompressor cut-in and cut-out pressures.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec0VOi50U8XSCR26_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"391fe33b-e793-48b3-a5bf-037e0da289bf","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.2 SIX-MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"2.2","prompt":"VERIFY the operation of the float valve by\nexercising the valve.","input":null,"possible_fault":"Float valve not operating","possible_fault_description":"AS1851 2012 TABLE 5.4.2 ITEM 2.2 - Float valve fails when exercised","severity_level":"critical","fault_id":"rec9epf2SMN39Jrn5","prompt_id":"rec9epf2SMN39Jrn5_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"6_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"3a148cd0-5077-41e1-9d92-1c842b8f2ac7","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.14","prompt":"CHECK for adequate means to access the tank.","input":null,"possible_fault":"Access inadequate","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.14 - No safe or proper access available","severity_level":"non-critical","fault_id":"recDxRZPnj0twi8Ss","prompt_id":"recDxRZPnj0twi8Ss_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"4048e5ae-fec7-4375-b616-1ade0cf671c7","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.3.B","prompt":"(c) Air pressure switch operates at specified\ncompressor cut-in and cut-out pressures.","input":null,"possible_fault":"Switch not operating correctly","possible_fault_description":"AS1851 2012 TABLE 5.4.1 ITEM 1.3 - Cut-in/cut-out pressure incorrect","severity_level":"critical","fault_id":"recXney2PgFE1jrnJ","prompt_id":"recXney2PgFE1jrnJ_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"47d24ef3-9e98-4a9a-861b-2b8606222a6c","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.8","prompt":"CHECK the ladder system is secure and free from\ncorrosion.","input":null,"possible_fault":"Loose or corroded ladder","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.8 - Ladder insecure or shows rust","severity_level":"non-critical","fault_id":"rec2TaONNV9auw17s","prompt_id":"rec2TaONNV9auw17s_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"4cd689f2-019c-4762-9ba3-38c9b0be0280","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.7","prompt":"CHECK to ensure the access hatch is secure and\nin satisfactory condition.","input":null,"possible_fault":"Access hatch faulty","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.7 - Hatch not secure or damaged","severity_level":"non-critical","fault_id":"recM2E2UnTqKzJ2WH","prompt_id":"recM2E2UnTqKzJ2WH_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"519a7c90-541e-4779-b91f-d53ff05d1ace","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.10","prompt":"CHECK the condition of vermin proofing and\nadequacy of the positioning.","input":null,"possible_fault":"Vermin proofing failed","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.10 - Proofing damaged or not effective","severity_level":"non-critical","fault_id":"recF4SDa9zGsNUEbt","prompt_id":"recF4SDa9zGsNUEbt_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"59d2b566-9494-430d-bb93-6ad713fdf965","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.3","prompt":"CHECK for loose bolts, anchors and fittings\nthroughout the tank.","input":null,"possible_fault":"Loose tank components","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.3 - Loose bolts or anchors found","severity_level":"non-critical","fault_id":"rec5v2kUUQFj97PIc","prompt_id":"rec5v2kUUQFj97PIc_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"5d5830ba-bb2d-4b86-a10a-700d2da95fbd","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.16","prompt":"CHECK the condition of all gaskets and sealants.","input":null,"possible_fault":"Gaskets/seals degraded","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.16 - Gaskets or sealants worn or cracked","severity_level":"non-critical","fault_id":"reczKRMTZw6DBPavo","prompt_id":"reczKRMTZw6DBPavo_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"607beb79-39bd-4ddf-8c7e-a36996d966b8","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.3.A","prompt":"(c) Air pressure switch operates at specified\ncompressor cut-in and cut-out pressures.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recT3KZEVttJLO6Jt_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"67ba0bf7-a8e8-4880-874c-a3eb7870c1e7","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.12","prompt":"CHECK for internal accumulation of algae.","input":null,"possible_fault":"Algae inside tank","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.12 - Algae growth seen during inspection","severity_level":"non-critical","fault_id":"recHjgy2tGk28b21c","prompt_id":"recHjgy2tGk28b21c_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"6950b68d-f9a2-4d22-8eab-2c30fdf3485f","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.6","prompt":"CHECK for corrosion of all external components\nand surfaces, and internal components as far as is\nsafe to do so from the top inspection/access\nhatch.","input":null,"possible_fault":"Corrosion found","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.6 - Visible corrosion on surfaces or fittings","severity_level":"non-critical","fault_id":"rec7KfFyhyiEbclO8","prompt_id":"rec7KfFyhyiEbclO8_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"6b2213eb-7af2-47a1-b6f7-444c6679d262","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.3.A","prompt":"(d) Low tank pressure alarm operates at\nspecified pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recDMqlZ8WXRF1oDp_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"7d3f318e-5053-4bd2-9ce5-51f17ec03638","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.9","prompt":"(b) Adequacy of sealing of penetrations.","input":null,"possible_fault":"Poor roof sealing","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.9 - Roof sealants inadequate or failing","severity_level":"non-critical","fault_id":"rec5DdlJs3yQrmkGH","prompt_id":"rec5DdlJs3yQrmkGH_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"815157f5-d6eb-43ca-a526-20b8c869949b","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.3","prompt":"VERIFY:\n(a) Gauge glass indicates the correct water level.","input":null,"possible_fault":"Incorrect gauge reading","possible_fault_description":"AS1851 2012 TABLE 5.4.1 ITEM 1.3 - Gauge glass not indicating actual level","severity_level":"non-critical","fault_id":"recZawhcAKAhSXxQV","prompt_id":"recZawhcAKAhSXxQV_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"8419980e-1137-47cf-87e9-76f166712428","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.2","prompt":"CHECK for correct operation and reading of\nwater level indicator.","input":null,"possible_fault":"Faulty indicator","possible_fault_description":"AS1851 2012 TABLE 5.4.1 ITEM 1.2 - Indicator not showing correct water level","severity_level":"non-critical","fault_id":"rec80RiPKhLOeW9R3","prompt_id":"rec80RiPKhLOeW9R3_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"888f3713-56ad-48d2-b75e-3b3aa8d1b41f","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.4 TEN-YEARLY AND OTHER SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"4.2","prompt":"DRAIN and CLEAN the tank completely\nincluding—","input":null,"possible_fault":"Tank not drained","possible_fault_description":"AS1851 2012 TABLE 5.4.4 ITEM 4.2 - Full tank drainage not performed","severity_level":"non-critical","fault_id":"recxGRAxLnjpgSXL7","prompt_id":"recxGRAxLnjpgSXL7_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"10_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"9702f46d-5ec5-40e7-9533-7342d8d61d37","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.3.A","prompt":"(b) Tank pressure gauge reads within the range\nnominated.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec6gQA4zo0Cc0nY2_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"975bfbca-4a9b-4a0f-bb46-6dd787b00dac","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.9","prompt":"CHECK the roof structure for:\n(a) Stability and security roof sheets are\nsecured.","input":null,"possible_fault":"Roof not stable or secured","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.9 - Roof sheets loose or unstable","severity_level":"critical","fault_id":"recNd2U9WKLty65lZ","prompt_id":"recNd2U9WKLty65lZ_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"9a51b46a-307e-406c-b8cf-248e6fce4943","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.4 TEN-YEARLY AND OTHER SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"4..1","prompt":"VERIFY completion of all monthly, six-monthly\nand yearly activities as listed in Tables 5.4.1,\n5.4.2 and 5.4.3.","input":null,"possible_fault":"Routine checks missed","possible_fault_description":"AS1851 2012 TABLE 5.4.4 ITEM 4.1 - Activities from Tables 5.4.1–5.4.3 not completed","severity_level":"non-conformance","fault_id":"recdH0XuE0RHSTilD","prompt_id":"recdH0XuE0RHSTilD_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"10_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"a95e5cb5-5b0e-4e3f-a287-121e7de0653b","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.4 TEN-YEARLY AND OTHER SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"4.2","prompt":"(c) REFILL the tank as soon as practicable.\nNOTES:\n1 A diver or other underwater inspection and\ncleaning technique may be used in lieu of\ndraining the tank.\n2 For water conservation measures when\ntanks need to be drained see AS 2304.","input":null,"possible_fault":"Tank not refilled","possible_fault_description":"AS1851 2012 TABLE 5.4.4 ITEM 4.2 - Refill delayed; liner at risk of movement","severity_level":"critical","fault_id":"recSXOPWFDQL1NuJu","prompt_id":"recSXOPWFDQL1NuJu_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"10_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"ab6340a2-0d1d-4c31-9b8b-50182e2ad3c6","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.1","prompt":"COMPLETE all monthly and six-monthly service\nactivities, as listed in Tables 5.4.1 and 5.4.2.","input":null,"possible_fault":"Service not completed","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.1 - Routine service activities not completed","severity_level":"non-conformance","fault_id":"recMVHATDobSnosTz","prompt_id":"recMVHATDobSnosTz_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"b3f166d6-3a59-4b01-b29d-6598bf81848e","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.11","prompt":"CHECK for internal foreign objects visually\nthrough the top inspection/access hatch.","input":null,"possible_fault":"Foreign objects inside tank","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.11 - Debris or foreign matter observed","severity_level":"non-critical","fault_id":"recxe4P82jOZBKOwY","prompt_id":"recxe4P82jOZBKOwY_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"c0b1e78b-6950-45b7-961e-36af6e64f6f5","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.3","prompt":"(e) Air compressor or gas cylinder supply is\noperational.","input":null,"possible_fault":"Compressor not working","possible_fault_description":"AS1851 2012 TABLE 5.4.1 ITEM 1.3 - Air/gas supply not functioning","severity_level":"critical","fault_id":"recD9cEaKDoAlRZPt","prompt_id":"recD9cEaKDoAlRZPt_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"c863198e-5c7b-4944-9be9-2c2fc69b8a40","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.18","prompt":"LUBRICATE water level indicator, pulleys and\ncables.","input":null,"possible_fault":"Indicator mechanism dry","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.18 - Indicator/pulley system not lubricated","severity_level":"non-critical","fault_id":"recxYSoOy7env7sof","prompt_id":"recxYSoOy7env7sof_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"c8c14aa2-9077-4cc0-b767-e13bf34e7bee","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.3.B","prompt":"(b) Tank pressure gauge reads within the range\nnominated.","input":null,"possible_fault":"Pressure out of range","possible_fault_description":"AS1851 2012 TABLE 5.4.1 ITEM 1.3 - Tank pressure outside acceptable range","severity_level":"non-critical","fault_id":"recYPwTju148DfSYv","prompt_id":"recYPwTju148DfSYv_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"cf219fbe-72a6-4269-a282-a245f4bf34da","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.19","prompt":"CHECK fittings are compatible with the local fire\nauthority’s hard suction fittings.","input":null,"possible_fault":"Fittings incompatible","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.19 - Fittings not match fire authority standards","severity_level":"non-conformance","fault_id":"recE8DT4iCP5fwFYa","prompt_id":"recE8DT4iCP5fwFYa_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"d14a6375-e1cc-452f-a95f-5d79e3727519","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.20","prompt":"(c) Refilling the tank as soon as practicable.\nNOTES:\n1 A diver or other underwater inspection and\ncleaning technique may be used in lieu of\ndraining the tank in consultation with the\ntank manufacturer to satisfy warranty\nrequirements.\n2 For water conservation measures when\ntanks need to be drained, see AS 2304.","input":null,"possible_fault":"Tank not refilled","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.20 - Tank not refilled or liner displaced","severity_level":"critical","fault_id":"recXO2sBXKTZ7QLeH","prompt_id":"recXO2sBXKTZ7QLeH_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"d459e7ea-189e-4be4-ba37-e6e1cdff0b92","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.1","prompt":"CHECK that the tank is full.","input":null,"possible_fault":"Tank not full","possible_fault_description":"AS1851 2012 TABLE 5.4.1 ITEM 1.1 - Tank water level below full mark","severity_level":"critical","fault_id":"rec6FTE6AAOp1aTgU","prompt_id":"rec6FTE6AAOp1aTgU_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"d5e20614-e75d-4f92-bf66-320f1cbecf81","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.17","prompt":"CHECK the condition of the vortex inhibitor\nvisually from the access hatch if practicable.","input":null,"possible_fault":"Vortex inhibitor damaged","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.17 - Visible damage or corrosion to vortex inhibitor","severity_level":"non-critical","fault_id":"rectmTOJwykkt9p2y","prompt_id":"rectmTOJwykkt9p2y_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"da8dd5f2-e999-42bd-914a-a7eb208c860a","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.15","prompt":"CHECK for satisfactory condition of all signs.","input":null,"possible_fault":"Signs damaged or missing","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.15 - Required signage not legible or missing","severity_level":"non-critical","fault_id":"recgUqfSgILu47b9r","prompt_id":"recgUqfSgILu47b9r_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"e60116f4-a10a-4b07-8bbc-e510fdc87cc2","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.2 SIX-MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"2.1","prompt":"COMPLETE all monthly service activities, as\nlisted in Table 5.4.1.","input":null,"possible_fault":"Monthly service not done","possible_fault_description":"AS1851 2012 TABLE 5.4.2 ITEM 2.1 - Monthly checks from Table 5.4.1 not completed","severity_level":"non-conformance","fault_id":"recZeuK8iIGLMJi9C","prompt_id":"recZeuK8iIGLMJi9C_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"6_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"e7916cf3-0428-4c27-8d89-11030a5f47ed","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.4 TEN-YEARLY AND OTHER SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"4.2","prompt":"(a) REMOVE all sludge and debris.\n\nNOTES:\n1 A diver or other underwater inspection and \ncleaning technique may be used in lieu of \ndraining the tank. \n2 For water conservation measures when \ntanks need to be drained see AS 2304","input":null,"possible_fault":"Sludge or debris present","possible_fault_description":"AS1851 2012 TABLE 5.4.4 ITEM 4.2 - Sludge/debris not fully removed","severity_level":"non-critical","fault_id":"recwuaz0YNl7h4y8d","prompt_id":"recwuaz0YNl7h4y8d_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"10_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"eecf8cd5-7386-4938-83d8-77123263590e","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.13","prompt":"CHECK the condition and satisfactory operation\nof vents and rotary spinners.","input":null,"possible_fault":"Vents/spinners faulty","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.13 - Vents or spinners blocked or not working","severity_level":"non-critical","fault_id":"recJZG3c0FaPldLn8","prompt_id":"recJZG3c0FaPldLn8_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"f26850e6-0ebf-4629-b39d-37f5dc078586","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"3.5","prompt":"CHECK for earth subsidence and foundation\ncracks.","input":null,"possible_fault":"Subsidence or cracks","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.5 - Cracked foundation or soil movement","severity_level":"non-critical","fault_id":"recPCbOCJGBEPk6Ck","prompt_id":"recPCbOCJGBEPk6Ck_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_year::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"},{"id":"fde669b0-9400-409e-990f-1fba3a214f89","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.1 MONTHLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Water Storage Tank","variant":null,"variant_id":"recYcid2mLApcEh2Z","item_no":"1.3.B","prompt":"(d) Low tank pressure alarm operates at\nspecified pressure.","input":null,"possible_fault":"Alarm not triggering","possible_fault_description":"AS1851 2012 TABLE 5.4.1 ITEM 1.3 - Alarm fails at low tank pressure","severity_level":"critical","fault_id":"recIQlKw82X0DWv0X","prompt_id":"recIQlKw82X0DWv0X_prompt","inspection_id":"c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1","grouping_key":"1_month::c_recYcid2mLApcEh2Z_recA6pWmW422Ltih1"}]}],"other_checklist_items":[{"id":"0ef9fd44-ee63-4e86-9a01-db94521b7665","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.4 TEN-YEARLY AND OTHER SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Water Storage Tank : Water Tank with Liners - (a) above the waterline,Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"recPVmEAYvGKqZVfK, receJzXoQISUPKcqA","item_no":"4.3","prompt":"(b) CLEAN all internal surfaces, excluding the\nroof, with low pressure spray using\nappropriate footwear to avoid damage to the\ntank liner.","input":null,"possible_fault":"Unsafe cleaning practice","possible_fault_description":"AS1851 2012 TABLE 5.4.4 ITEM 4.3 - Improper footwear or method used","severity_level":"non-conformance","fault_id":"recutYD6PXeANiQDL","prompt_id":"recutYD6PXeANiQDL_prompt","inspection_id":"c_recPVmEAYvGKqZVfK:receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"10_year::c_recPVmEAYvGKqZVfK:receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"145dec4c-2eb1-4718-aec5-caab490033e6","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.4 TEN-YEARLY AND OTHER SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Water Storage Tank : Water Tank with Liners - (a) above the waterline,Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"recPVmEAYvGKqZVfK, receJzXoQISUPKcqA","item_no":"4.3","prompt":"(c) REFILL the tank as soon as practicable.\nNOTES:\n1 For water conservation measures when\ntanks need to be drained, see AS 2304.\n2 Ensure the liner is in the correct position\nprior to refilling; this includes the\npositioning of the neoprene mat (where\nfitted) under the vortex inhibitor bottom\nsupport and strainer.\n3 A diver or other underwater inspection\ntechnique may be used in lieu of draining\nthe tank in consultation with the tank\nmanufacturer (to satisfy warranty\nrequirements).","input":null,"possible_fault":"Liner not aligned","possible_fault_description":"AS1851 2012 TABLE 5.4.4 ITEM 4.3 - Liner or mat not positioned before refill","severity_level":"non-critical","fault_id":"recxwuZjR2e897YJa","prompt_id":"recxwuZjR2e897YJa_prompt","inspection_id":"c_recPVmEAYvGKqZVfK:receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"10_year::c_recPVmEAYvGKqZVfK:receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"3c075a58-4e3a-45b5-bd2b-9100b149a51c","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.4 TEN-YEARLY AND OTHER SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Water Storage Tank : Water Tank with Liners - (a) above the waterline,Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"recPVmEAYvGKqZVfK, receJzXoQISUPKcqA","item_no":"4.3","prompt":"(a) REMOVE all sludge and debris without\nusing sharp tools or shovels to prevent\ntearing and puncturing of the liner.","input":null,"possible_fault":"Liner damaged","possible_fault_description":"AS1851 2012 TABLE 5.4.4 ITEM 4.3 - Sharp tools used; liner at risk of tear","severity_level":"non-critical","fault_id":"recaFiN4BESYJc42t","prompt_id":"recaFiN4BESYJc42t_prompt","inspection_id":"c_recPVmEAYvGKqZVfK:receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"10_year::c_recPVmEAYvGKqZVfK:receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"47db4d5b-fe84-43e5-94b1-939d313d9804","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.4 TEN-YEARLY AND OTHER SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Water Storage Tank : Water Tank with Liners - (a) above the waterline,Water Storage Tank : Water Tank with Liners - (b) below the waterline","variant":null,"variant_id":"recPVmEAYvGKqZVfK, receJzXoQISUPKcqA","item_no":"4.3","prompt":"DRAIN and CLEAN the tank leaving a minimum\nof 50 mm of water to prevent liner movement,\nand:","input":null,"possible_fault":"Tank not drained correctly","possible_fault_description":"AS1851 2012 TABLE 5.4.4 ITEM 4.3 - Water not retained to protect liner","severity_level":"non-critical","fault_id":"recRzTpbHv4bNwKNs","prompt_id":"recRzTpbHv4bNwKNs_prompt","inspection_id":"c_recPVmEAYvGKqZVfK:receJzXoQISUPKcqA_recA6pWmW422Ltih1","grouping_key":"10_year::c_recPVmEAYvGKqZVfK:receJzXoQISUPKcqA_recA6pWmW422Ltih1"},{"id":"7cb2fc26-6aca-4c6b-8b3b-98ec017bea96","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Water Storage Tank : Rectangular panel tanks \n\"","variant":null,"variant_id":"recAn91z5MfnsPweZ","item_no":"3.35","prompt":"Complete a visual inspection of the internal stay\nsupport system comprising stay bars, bolts and\nbrackets for the following:","input":null,"possible_fault":"Stay system defects","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.35 - Internal stay structure is loose or corroded","severity_level":"recommendation","fault_id":"rec0TM6fhozyCgHCg","prompt_id":"rec0TM6fhozyCgHCg_prompt","inspection_id":"c_recAn91z5MfnsPweZ_recA6pWmW422Ltih1","grouping_key":"1_year::c_recAn91z5MfnsPweZ_recA6pWmW422Ltih1"},{"id":"872fc846-9b5d-4930-be58-14a7b770cb28","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Water Storage Tank : Rectangular panel tanks \n\"","variant":null,"variant_id":"recAn91z5MfnsPweZ","item_no":"3.35","prompt":"(b) Tightness of bolts.","input":null,"possible_fault":"Loose bolts","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.35 - Internal support bolts not tightened","severity_level":"non-critical","fault_id":"recrhVpi6DmlOcf2d","prompt_id":"recrhVpi6DmlOcf2d_prompt","inspection_id":"c_recAn91z5MfnsPweZ_recA6pWmW422Ltih1","grouping_key":"1_year::c_recAn91z5MfnsPweZ_recA6pWmW422Ltih1"},{"id":"c4d56b6d-f13e-4840-98b5-3cdb4d6a2b6e","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Water Storage Tank : Rectangular panel tanks \n\"","variant":null,"variant_id":"recAn91z5MfnsPweZ","item_no":"3.35","prompt":"(d) Distortion of panels and connection points.","input":null,"possible_fault":"Panels distorted","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.35 - Visible warping of panels or stay junctions","severity_level":"non-critical","fault_id":"recwCwQOWOZ3tPLDe","prompt_id":"recwCwQOWOZ3tPLDe_prompt","inspection_id":"c_recAn91z5MfnsPweZ_recA6pWmW422Ltih1","grouping_key":"1_year::c_recAn91z5MfnsPweZ_recA6pWmW422Ltih1"},{"id":"c5127ed0-212e-455a-9c3c-b950a20ffc1d","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Water Storage Tank : Rectangular panel tanks \n\"","variant":null,"variant_id":"recAn91z5MfnsPweZ","item_no":"3.35","prompt":"(c) Elongation of bolt holes.","input":null,"possible_fault":"Holes are stretched","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.35 - Stay bar bolt holes elongated or worn","severity_level":"non-critical","fault_id":"recbrJM4vzuDb3g7x","prompt_id":"recbrJM4vzuDb3g7x_prompt","inspection_id":"c_recAn91z5MfnsPweZ_recA6pWmW422Ltih1","grouping_key":"1_year::c_recAn91z5MfnsPweZ_recA6pWmW422Ltih1"},{"id":"c6f79cab-fcbf-487d-8bac-ebe8b253eb13","standard_code":"au_as_1851_2012","version":"full","category":"Water Storage Tanks for Fire Protection Systems","category_id":"recA6pWmW422Ltih1","group_header":"TABLE 5.4.3 YEARLY SERVICE SCHEDULE WATER STORAGE TANKS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Water Storage Tank : Rectangular panel tanks \n\"","variant":null,"variant_id":"recAn91z5MfnsPweZ","item_no":"3.35","prompt":"(a) Corrosion at connection points.","input":null,"possible_fault":"Corrosion at joints","possible_fault_description":"AS1851 2012 TABLE 5.4.3 ITEM 3.35 - Rust found on stay bar or connection ends","severity_level":"non-critical","fault_id":"recOjmNIKXq7ZWjvW","prompt_id":"recOjmNIKXq7ZWjvW_prompt","inspection_id":"c_recAn91z5MfnsPweZ_recA6pWmW422Ltih1","grouping_key":"1_year::c_recAn91z5MfnsPweZ_recA6pWmW422Ltih1"}]},{"id":"recBjw7jZ33SWs7B1","name":"Portable And Wheeled Fire Extinguishers","asset_types":[{"id":"recAtQLGgbEbGMXi8","name":"Portable Extinguisher","checklist":[{"id":"03927f61-ad1e-4141-898c-ec779785afbd","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":"Water (gas container),Water (stored pressure),Wet chemical,Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recAtQLGgbEbGMXi8","item_no":"2.2","prompt":"CHECK that the threads on operating head\n or cap are not damaged, vent(s) is (are) not\n blocked, and any strainer or expansion\n device is unobstructed. For heads with no\n screw thread, determine that security locking\n device is undamaged and operational.\n Water (gas container), foam (gas container),\n water with additive (stored pressure), foam\n (stored pressure), powder (gas container)","input":null,"possible_fault":"Operating head/cap threads damaged/vents blocked/strainer obstructed/security locking device damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.2 - Threads on operating head or cap damaged, vent(s) blocked, strainer or expansion device obstructed, or security locking device damaged/non-operational","severity_level":"non-critical","fault_id":"recc2KGwtTh8RO296","prompt_id":"recc2KGwtTh8RO296_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"0596955d-6253-4125-8baa-98204f26b533","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.2","prompt":"CHECK that the anti-tamper device is intact.\n All extinguishers types","input":null,"possible_fault":"Anti-tamper device damaged/missing/broken","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.2 - Anti-tamper device not intact or damaged","severity_level":"non-critical","fault_id":"recWrnpwZcwB2J6fg","prompt_id":"recWrnpwZcwB2J6fg_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"0d3a8685-4601-41d5-a211-277c3e4b3ff5","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":"Water (gas container),Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recAtQLGgbEbGMXi8","item_no":"2.4","prompt":"CHECK that the actuating device is free of\n corrosion, moves freely, and is undamaged;\n any cutting edge is sharp; and all sealing\n gaskets are in good condition.\n Water (gas container), foam (gas container),\n foam (stored pressure) powder (gas\n container)","input":null,"possible_fault":"Actuating device corroded/seized/damaged/cutting edge dull/sealing gaskets deteriorated","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.4 - Actuating device corroded, doesn't move freely, damaged, cutting edge not sharp, or sealing gaskets in poor condition","severity_level":"non-critical","fault_id":"recAgShM4fQ7R9dQd","prompt_id":"recAgShM4fQ7R9dQd_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"0f159b11-5ead-4db5-a133-49f79a3d9111","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.10","prompt":"CHECK that the location sign is visible.\n All extinguishers types","input":null,"possible_fault":"Location sign not visible/missing/damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.10 - Location sign not visible","severity_level":"non-conformance","fault_id":"rec8nMMV7BHRCrJUi","prompt_id":"rec8nMMV7BHRCrJUi_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"1546c3b8-031d-4b3a-b3e2-02413cc281fa","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.6","prompt":"CHECK that the exterior of the extinguisher is\n not pitted or otherwise damaged by corrosion\n (see Clause 10.2.5 and AS 2337.1).\n All extinguishers types","input":null,"possible_fault":"Exterior pitting/corrosion damage","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.6 - Exterior pitted or damaged by corrosion (see Clause 10.2.5 and AS 2337.1)","severity_level":"non-critical","fault_id":"rec3N4Z9afqCFd26G","prompt_id":"rec3N4Z9afqCFd26G_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"17585804-4462-419a-9dc3-c556ff20076e","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.3","prompt":"CHECK that the extinguisher is clean and the\n operating instructions are legible.\n All extinguishers types","input":null,"possible_fault":"Extinguisher dirty/operating instructions illegible","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.3 - Extinguisher not clean or operating instructions not legible","severity_level":"non-critical","fault_id":"recC5v5TBAT0nH7vw","prompt_id":"recC5v5TBAT0nH7vw_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"177b6d6a-1f07-49b8-9ab6-cd2666b41378","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"3.11","prompt":"RENEW all seals and gaskets fitted to the\n actuating device, operating head, or cap.\n All extinguisher types","input":null,"possible_fault":"Seals and gaskets deteriorated/damaged/wrong specification/installation failure","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.11 - Renew all seals and gaskets fitted to actuating device, operating head, or cap for all extinguisher types","severity_level":"non-critical","fault_id":"recqnPMgw5YUuYvV1","prompt_id":"recqnPMgw5YUuYvV1_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"1e4f0cf2-dd6e-4c24-a6c3-c2f4005a4134","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":"Water (stored pressure),Wet chemical,Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recAtQLGgbEbGMXi8","item_no":"3.7","prompt":"CHECK that the operating head or cap seal is in\n good condition.\n Water (stored pressure), wet chemical, powder\n (stored pressure), carbon dioxide, vaporizing\n liquid","input":null,"possible_fault":"Operating head or cap seal deteriorated/damaged/missing/compromised integrity","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.7 - Operating head or cap seal not in good condition","severity_level":"critical","fault_id":"recxo7c4XD27NQO3T","prompt_id":"recxo7c4XD27NQO3T_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"2465b81d-2ed6-452f-8ac0-d7bd12d22e7d","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":"Water (gas container),Water (stored pressure),Wet chemical,Foam (gas container),Powder (gas container),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recAtQLGgbEbGMXi8","item_no":"3.2","prompt":"CHECK that the extinguisher functions in\n accordance with the operating instructions and\n that the discharge is satisfactory. Recharge in\n accordance with Item 3.9.\n Water (gas container), water (stored pressure),\n wet chemical, foam (gas container), powder\n (gas container), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Extinguisher doesn't function per instructions/discharge unsatisfactory/performance degraded","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.2 - Check that extinguisher functions in accordance with operating instructions and discharge is satisfactory. Recharge in accordance with Item 3.9","severity_level":"critical","fault_id":"recaHZhdVtJcB4kxz","prompt_id":"recaHZhdVtJcB4kxz_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"257e3463-18db-4274-aec9-c6f1cb4d1364","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.8","prompt":"Where fitted, CHECK that the pressure\n indicator is legible, and registering within the\n operable range.\n All extinguishers types","input":null,"possible_fault":"Pressure indicator illegible/outside operable range","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.8 - Pressure indicator not legible or not registering within operable range","severity_level":"non-critical","fault_id":"rec9g1OWFftjeRr1y","prompt_id":"rec9g1OWFftjeRr1y_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"31828f68-ae22-47d1-9053-b084f9bfc7ce","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":"Water (gas container),Foam (gas container)","variant_id":"recAtQLGgbEbGMXi8","item_no":"1.18","prompt":"DETERMINE that the internal discharge tube\n and strainer (where fitted) provide clear\n passage and are securely attached.\n Water (gas container), foam (gas container)","input":null,"possible_fault":"Internal discharge tube blocked/strainer obstructed/loose attachment","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.18 - Internal discharge tube or strainer not providing clear passage or not securely attached","severity_level":"critical","fault_id":"recZaMXhDKwyvnESw","prompt_id":"recZaMXhDKwyvnESw_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"36cbcf84-fa02-409d-a778-be5a15af4bb4","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"3.5","prompt":"For carbon dioxide extinguishers, this\n examination shall be in accordance with\n AS 2030.5, and shall be performed at a gas\n cylinder test station certified by a registered\n certifying body (see AS 2337.1).","input":null,"possible_fault":"Internal examination fails AS 2030.5 requirements/cylinder test station findings","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.5 - For CO2 extinguishers, examination in accordance with AS 2030.5 at certified gas cylinder test station","severity_level":"critical","fault_id":"recepevt3hxft21cU","prompt_id":"recepevt3hxft21cU_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"3c13f474-6c7d-444d-91af-99853941b00e","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":"Water (stored pressure),Wet chemical,Foam (gas container),Foam (stored pressure),Powder (gas container),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recAtQLGgbEbGMXi8","item_no":"1.17","prompt":"DETERMINE, where possible and without\n discharging any contents, that the actuating\n device is free of corrosion, moves freely and is\n undamaged.\n Water (stored pressure), wet chemical, foam\n (stored pressure), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Device corroded/seized/damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.17 - Actuating device corroded, doesn't move freely, or damaged","severity_level":"non-critical","fault_id":"recIVeb5CHZMF3aUS","prompt_id":"recIVeb5CHZMF3aUS_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"3ef49c8d-8150-4cbf-a526-bed76952eaef","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":"Foam (gas container),Water (gas container),Powder (gas container)","variant_id":"recAtQLGgbEbGMXi8","item_no":"1.16","prompt":"DETERMINE that the compressed gas\n container is the correct size and type, in good\n condition, fully charged, and subjected to\n service as per AS 2030.5.\n All gas container extinguishers","input":null,"possible_fault":"Wrong size/type/poor condition/not fully charged/service overdue","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.16 - Gas container incorrect size/type, poor condition, not fully charged, or not serviced per AS 2030.5","severity_level":"non-critical","fault_id":"recQ9ejlf3qNgnal3","prompt_id":"recQ9ejlf3qNgnal3_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"40c96fcf-1eb8-4fff-ae55-5d3eacdf9b81","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":"Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recAtQLGgbEbGMXi8","item_no":"3.4","prompt":"(b) CHECK that the internal discharge tube\n provides clear passage, is securely\n attached, and there is no evidence of\n moisture or foreign matter in the cylinder.\n Powder (stored pressure), carbon dioxide,\n vaporizing liquid","input":null,"possible_fault":"Internal discharge tube blocked/moisture ingress/foreign matter contamination/loose attachment","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.4(b) - Internal discharge tube doesn't provide clear passage, not securely attached, or evidence of moisture or foreign matter in cylinder","severity_level":"critical","fault_id":"recoHPitO2DJs2emI","prompt_id":"recoHPitO2DJs2emI_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"4ac08190-1ae5-498f-b33b-4291c9043a37","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":"Powder (gas container)","variant_id":"recAtQLGgbEbGMXi8","item_no":"2.5","prompt":"(b) CHECK that the internal discharge\n tube, or the gas inlet tube or ports,\n provide clear passage and are correctly\n installed, and that the powder is free\n flowing.\n Powder (gas container)","input":null,"possible_fault":"Internal discharge tube blocked/gas inlet tube blocked/incorrect installation/powder not free flowing","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.5(b) - Internal discharge tube or gas inlet tube/ports don't provide clear passage, incorrectly installed, or powder not free flowing","severity_level":"critical","fault_id":"rec5J9LLmGLYrHrDr","prompt_id":"rec5J9LLmGLYrHrDr_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"4b8615ab-e6bb-4d9d-8885-45b28a84ebf6","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":"Water (gas container),Water (stored pressure),Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recAtQLGgbEbGMXi8","item_no":"2.6","prompt":"CHECK that the interior of cylinder is clean,\n is not pitted by corrosion (see AS 2337.1),\n and any internal lining is in good condition.\n Water (gas container), water with additive\n (stored pressure), foam (gas container),\n foam (stored pressure), powder (gas\n container)","input":null,"possible_fault":"Cylinder interior dirty/pitted by corrosion/internal lining deteriorated","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.6 - Interior of cylinder not clean, pitted by corrosion (see AS 2337.1), or internal lining in poor condition","severity_level":"non-critical","fault_id":"rec4PjqEFXA89s0ef","prompt_id":"rec4PjqEFXA89s0ef_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"4ea0236c-1ce0-425b-a72b-b37423d33b6f","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"3.10","prompt":"Upon the completion of recharging stored\n pressure type extinguishers, perform a leak test\n as per Item 3.12.","input":null,"possible_fault":"Leaks detected after recharging stored pressure extinguishers/seal integrity compromised","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.10 - Upon completion of recharging stored pressure type extinguishers, perform leak test as per Item 3.12","severity_level":"non-critical","fault_id":"recHhRAxXWgD8ExOg","prompt_id":"recHhRAxXWgD8ExOg_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"57473321-5356-4274-9a66-844571c62339","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":"Carbon dioxide","variant_id":"recAtQLGgbEbGMXi8","item_no":"3.8","prompt":"(b) SUBJECT the extinguisher body to a\n hydrostatic pressure test, in accordance\n with the requirements of AS 2030.5, at a\n Gas Cylinder Test Station certified by a\n Registered Certifying body (see\n AS 2337.1).\n Carbon dioxide","input":null,"possible_fault":"Cylinder fails AS 2030.5 pressure test requirements/test station rejection","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.8(b) - Subject CO2 extinguisher body to hydrostatic pressure test in accordance with AS 2030.5 at certified Gas Cylinder Test Station","severity_level":"critical","fault_id":"rec6BtvAJXcUwRz4x","prompt_id":"rec6BtvAJXcUwRz4x_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"5aebca8a-c1ae-450a-9f4c-47f9485e3a7f","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":"Water (stored pressure),Foam (stored pressure)","variant_id":"recAtQLGgbEbGMXi8","item_no":"2.3","prompt":"CHECK that the extinguisher functions in\n accordance with the operating instructions\n and that the discharge is satisfactory.\n Recharge in accordance with Item 2.8.\n (a) Water with additive (stored pressure),\n foam (stored pressure)\n (b) Water with corrosion inhibitors or\n freezing point depressants (stored\n pressure)*\n * To be discharged on a three-yearly\n frequency.","input":null,"possible_fault":"Extinguisher doesn't function per instructions/discharge unsatisfactory","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.3 - Extinguisher doesn't function in accordance with operating instructions or discharge is unsatisfactory","severity_level":"critical","fault_id":"recRQGlvXhnRNXi9X","prompt_id":"recRQGlvXhnRNXi9X_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"6467595f-53e1-4f6b-9bc8-e3a593cc8e3c","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"3.1","prompt":"COMPLETE all six-monthly and yearly service\n activities, as listed in Table 10.4.1 and 10.4.2.","input":null,"possible_fault":"Any fault identified in six-monthly and yearly service items","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.1 - Complete all six-monthly and yearly service activities, as listed in Table 10.4.1 and 10.4.2","severity_level":"non-conformance","fault_id":"reccnNx6JBbKrAnm3","prompt_id":"reccnNx6JBbKrAnm3_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"67b43554-cc4e-42fc-8479-38ee2fd435eb","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":"Water (stored pressure),Wet chemical","variant_id":"recAtQLGgbEbGMXi8","item_no":"3.4","prompt":"(a) CHECK that the internal discharge tube,\n strainer and anti-overfill tube (where\n fitted) provide clear passage and are\n securely attached, and that the anti overfill\n device is undamaged.\n Water (stored pressure), wet chemical","input":null,"possible_fault":"Internal discharge tube blocked/strainer obstructed/anti-overfill tube blocked/loose attachment/anti-overfill device damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.4(a) - Internal discharge tube, strainer, or anti-overfill tube don't provide clear passage or not securely attached, or anti-overfill device damaged","severity_level":"critical","fault_id":"recOnWIOTkOsg7fXF","prompt_id":"recOnWIOTkOsg7fXF_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"683f1f21-312e-4b21-ab0a-85f692ed3980","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"2.11","prompt":"CHECK that the fire hazard/risk to be\n protected has not changed.\n All extinguisher types","input":null,"possible_fault":"Fire hazard/risk has changed from original assessment","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.11 - Fire hazard/risk to be protected has changed","severity_level":"non-conformance","fault_id":"recvmCzqT6WWxAU2P","prompt_id":"recvmCzqT6WWxAU2P_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"6e48b73c-4b17-4150-93d2-a3fe1d1bf6a2","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.9","prompt":"WEIGH the extinguisher to determine that it is\n fully charged.\n All extinguisher types","input":null,"possible_fault":"Extinguisher underweight/not fully charged","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.9 - Weight indicates extinguisher is not fully charged","severity_level":"critical","fault_id":"recE37ALPMOMtS8ic","prompt_id":"recE37ALPMOMtS8ic_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"75a7418c-e634-489b-a86c-3fca954d9df2","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.11","prompt":"CHECK that the appropriate support bracket is\n securely attached to wall or other suitable\n feature.\n All extinguishers types","input":null,"possible_fault":"Support bracket loose/damaged/inadequate","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.11 - Support bracket not securely attached to wall or suitable feature","severity_level":"non-critical","fault_id":"receRuYN73MvpsfK4","prompt_id":"receRuYN73MvpsfK4_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"78dc85dc-3925-40b4-8288-a26c7f41e64d","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.7","prompt":"CHECK that the hose is securely fitted, the\n nozzle is securely attached, the assembly is\n free from obstruction, and the hose shows no\n cracking or other signs of damage or\n deterioration.\n All extinguishers types","input":null,"possible_fault":"Hose loose/nozzle loose/obstruction/damage/deterioration","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.7 - Hose not securely fitted, nozzle not securely attached, assembly obstructed, or hose showing cracking/damage/deterioration","severity_level":"non-critical","fault_id":"recNYVEkV9sOkrNwr","prompt_id":"recNYVEkV9sOkrNwr_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"794e0556-eb5c-46dd-b06c-0126ba6b3b6a","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":"Water (stored pressure),Wet chemical,Powder (stored pressure),Vaporizing liquid","variant_id":"recAtQLGgbEbGMXi8","item_no":"3.5","prompt":"CHECK that the interior of the cylinder is clean,\n is not pitted by corrosion (see AS 2337.1), and\n any internal lining is in good condition.\n Where the lining cannot be removed to inspect\n the interior of the cylinder, the cylinder shall be\n accepted or rejected as per AS 2337.1.\n Water (stored pressure), wet chemical, powder\n (stored pressure), vaporizing liquid.","input":null,"possible_fault":"Cylinder interior dirty/pitted by corrosion/internal lining deteriorated/contamination present","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.5 - Interior of cylinder not clean, pitted by corrosion (see AS 2337.1), or internal lining in poor condition. Where lining cannot be removed, cylinder shall be accepted or rejected as per AS 2337.1","severity_level":"non-critical","fault_id":"recEHR66Y86WBH2qk","prompt_id":"recEHR66Y86WBH2qk_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"7c331a6a-d1dd-409a-97ae-978059da00ab","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":"Water (stored pressure),Wet chemical,Foam (stored pressure),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recAtQLGgbEbGMXi8","item_no":"3.12","prompt":"CHECK if there are any leaks at the joints and\n seals that were renewed or disturbed during\n recharging.\n Water (stored pressure), wet chemical, foam\n (stored pressure), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Leaks present at joints/seals renewed or disturbed during servicing/pressure loss detected","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.12 - Check if there are leaks at joints and seals that were renewed or disturbed during recharging","severity_level":"non-critical","fault_id":"reco2CHxagT67PFdK","prompt_id":"reco2CHxagT67PFdK_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"7e4eff44-1e1a-48f3-8445-addc6414d287","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"2.12","prompt":"CHECK that the extinguisher is the correct\n type, class, size and/or rating for the hazard\n to be protected.\n All extinguisher types","input":null,"possible_fault":"Extinguisher incorrect type/class/size/rating for current hazard","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.12 - Extinguisher not correct type, class, size and/or rating for hazard to be protected","severity_level":"non-conformance","fault_id":"recxZP0LSplKjTF3v","prompt_id":"recxZP0LSplKjTF3v_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"80a9e5be-fabd-4708-8adf-f5695b7eeb84","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.5","prompt":"CHECK that the extinguisher, including any\n attachments, is not damaged (see AS 2337.1).\n All extinguishers types","input":null,"possible_fault":"Physical damage to extinguisher/attachments","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.5 - Extinguisher or attachments damaged (see AS 2337.1)","severity_level":"non-critical","fault_id":"recqWEx0DmN2cAxoR","prompt_id":"recqWEx0DmN2cAxoR_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"89ff02ab-9d8c-49e6-b323-fd89c1425516","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":"Water (stored pressure),Foam (stored pressure)","variant_id":"recAtQLGgbEbGMXi8","item_no":"2.10","prompt":"CHECK if there are any leaks at the joints\n and seals that were renewed or disturbed\n during recharging.\n Water with additive (stored pressure), foam\n (stored pressure)","input":null,"possible_fault":"Leaks detected at joints/seals after recharging","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.10 - Leaks present at joints and seals that were renewed or disturbed during recharging","severity_level":"non-critical","fault_id":"recUUxniXmtXkQXUC","prompt_id":"recUUxniXmtXkQXUC_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"8ce46860-bf8a-4e70-bb0e-d91203b36900","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"2.1","prompt":"COMPLETE all six-monthly service\n activities, as listed in Table 10.4.1.","input":null,"possible_fault":"Any fault identified in six-monthly service items","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.1 - Complete all six-monthly service activities, as listed in Table 10.4.1","severity_level":"non-conformance","fault_id":"recy1vdEhyMXwEXoJ","prompt_id":"recy1vdEhyMXwEXoJ_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"a99aedc0-b5e6-4ba8-97a3-d7044843e2ba","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":"Water (gas container),Water (stored pressure),Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recAtQLGgbEbGMXi8","item_no":"2.9","prompt":"CHECK that the operating head or cap seal\n is in good condition.\n Water (gas container), water with additive\n (stored pressure), foam (gas container),\n foam (stored pressure), powder (gas\n container)","input":null,"possible_fault":"Operating head or cap seal deteriorated/damaged/missing","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.9 - Operating head or cap seal not in good condition","severity_level":"non-critical","fault_id":"recF7DZaJtGOGeLRx","prompt_id":"recF7DZaJtGOGeLRx_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"b4087ba3-a525-4597-8b12-670e462e89a4","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":"Water (stored pressure),Wet chemical,Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recAtQLGgbEbGMXi8","item_no":"3.3","prompt":"CHECK that the actuating device is free of\n corrosion, moves freely, and is undamaged; any\n cutting edge is sharp; and all sealing gaskets are\n in good condition.\n Water (stored pressure), wet chemical, powder\n (stored pressure), carbon dioxide, vaporizing\n liquid","input":null,"possible_fault":"Actuating device corroded/seized/damaged/cutting edge dull/sealing gaskets deteriorated","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.3 - Actuating device corroded, doesn't move freely, damaged, cutting edge not sharp, or sealing gaskets in poor condition","severity_level":"non-critical","fault_id":"recCTvvrSnUyW6T8o","prompt_id":"recCTvvrSnUyW6T8o_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"d30f045c-dca8-4fc4-b7f4-4e9057ebb847","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.4","prompt":"CHECK that the service tag or label is firmly\n attached to the extinguisher.\n All extinguishers types","input":null,"possible_fault":"Service tag/label missing/loose/damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.4 - Service tag or label not firmly attached to extinguisher","severity_level":"non-conformance","fault_id":"recUooHO2FTWFCem4","prompt_id":"recUooHO2FTWFCem4_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"d3f17a75-957e-4828-84d1-11783df82755","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":"Water (stored pressure),Foam (stored pressure)","variant_id":"recAtQLGgbEbGMXi8","item_no":"2.5","prompt":"(a) CHECK that the internal discharge\n tube, strainer and anti-overfill tube\n (where fitted) provide clear passage\n and are securely attached, and that the\n anti-overfill device is undamaged.\n Water with additive (stored pressure),\n foam (stored pressure)","input":null,"possible_fault":"Internal discharge tube blocked/strainer obstructed/anti-overfill tube blocked/loose attachment/anti-overfill device damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.5(a) - Internal discharge tube, strainer, or anti-overfill tube don't provide clear passage or not securely attached, or anti-overfill device damaged","severity_level":"critical","fault_id":"recMNlg1WPiJvulT8","prompt_id":"recMNlg1WPiJvulT8_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"d47fe812-8c44-4e5f-8a84-619b011e16a4","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.12","prompt":"CHECK that the appropriate discharge nozzle\n is fitted and is not blocked or damaged.\n All extinguishers types","input":null,"possible_fault":"Discharge nozzle blocked/damaged/incorrect type","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.12 - Inappropriate discharge nozzle fitted, blocked, or damaged","severity_level":"critical","fault_id":"recdvKc7X9ygnhajI","prompt_id":"recdvKc7X9ygnhajI_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"d8a6a07e-ab9e-4871-b6d8-9522ac369237","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"1.1","prompt":"CHECK the extinguisher is conspicuous,\n readily accessible and in its assigned location.\n All extinguishers types","input":null,"possible_fault":"Extinguisher not accessible/visible/in wrong location","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.1 - Extinguisher not conspicuous, not readily accessible, or not in assigned location","severity_level":"non-conformance","fault_id":"recxUhIL71tnYjODG","prompt_id":"recxUhIL71tnYjODG_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"dfb15581-c6fc-4bb1-abb9-185d150797d3","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":"Water (stored pressure),Foam (gas container),Foam (stored pressure)","variant_id":"recAtQLGgbEbGMXi8","item_no":"2.8","prompt":"RECHARGE the extinguisher with fresh\n extinguishing agent in accordance with the\n manufacturer’s instructions.\n Water with additive (stored pressure), foam\n (gas container), foam (stored pressure)\nUpon the completion of recharging stored\n pressure type extinguishers, perform a leak\n test as per Item 2.10.","input":null,"possible_fault":"Extinguishing agent contaminated/expired/incorrect type/recharge failed","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.8 - Recharge extinguisher with fresh extinguishing agent in accordance with manufacturer's instructions","severity_level":"critical","fault_id":"recIls4pBNiaBsV1Y","prompt_id":"recIls4pBNiaBsV1Y_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"e1ebcc62-50b8-4f5b-abb0-ea53726a607f","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":"Wet chemical,Powder (gas container),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recAtQLGgbEbGMXi8","item_no":"3.10","prompt":"At the frequency specified by the extinguishing\n manufacturer, RECHARGE the extinguisher\n with fresh extinguishing agent, as specified on\n the extinguisher label, in accordance with the\n manufacturer’s instructions.\n Wet chemical, foam (gas container with\n sealed foam liquid container), powder (gas\n container), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Extinguishing agent contaminated/expired/degraded/incorrect specification/recharge failure","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.10 - Recharge extinguisher with fresh extinguishing agent as specified on label, in accordance with manufacturer's instructions at frequency specified by manufacturer","severity_level":"critical","fault_id":"recKQAZ8DVt5V9PVi","prompt_id":"recKQAZ8DVt5V9PVi_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"e572fff1-154f-4964-bab2-ab9cfb45ca4c","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher","variant":null,"variant_id":"recAtQLGgbEbGMXi8","item_no":"2.13","prompt":"(a) CHECK that no alterations have been\n made to the building that may impede\n access to the extinguisher or increase\n the travel distances to more than those\n required.\n All portable extinguishers","input":null,"possible_fault":"Building alterations impede access/increase travel distances beyond requirements","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.13(a) - Alterations made to building that impede access to extinguisher or increase travel distances beyond required limits","severity_level":"critical","fault_id":"recO0aFNlQASedaP2","prompt_id":"recO0aFNlQASedaP2_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"f05abf10-f2b5-444c-80fb-b4976326a0da","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher","variant":"Water (gas container),Water (stored pressure),Wet chemical,Foam (gas container),Foam (stored pressure),Powder (gas container),Powder (stored pressure),Vaporizing liquid","variant_id":"recAtQLGgbEbGMXi8","item_no":"3.8","prompt":"(a) SUBJECT the extinguisher body to a\n hydrostatic pressure test of 1.5 times the\n working pressure, the marked periodic test\n pressure, or 2 MPa, whichever is the\n greatest.\n Water (gas container), water (stored\n pressure), wet chemical, foam (gas\n container), foam (stored pressure), powder\n (gas container), powder (stored pressure),\n vaporizing liquid","input":null,"possible_fault":"Cylinder fails hydrostatic pressure test/structural integrity compromised/leakage under test pressure","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.8(a) - Subject extinguisher body to hydrostatic pressure test of 1.5 times working pressure, marked periodic test pressure, or 2 MPa, whichever is greatest","severity_level":"critical","fault_id":"recG6voDTfTcNj6pe","prompt_id":"recG6voDTfTcNj6pe_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"},{"id":"fad5fb14-a9db-43f0-83f2-5f77a2207d97","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher","variant":"Powder (gas container),Powder (stored pressure)","variant_id":"recAtQLGgbEbGMXi8","item_no":"1.15","prompt":"INVERT the extinguisher and ensure that the\n powder remains free flowing.\n Powder (stored pressure), powder (gas\n container)","input":null,"possible_fault":"Powder consolidated/not free flowing","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.15 - Powder not remaining free flowing when extinguisher inverted","severity_level":"non-critical","fault_id":"recZILKw5VsYCrJKB","prompt_id":"recZILKw5VsYCrJKB_prompt","inspection_id":"c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recAtQLGgbEbGMXi8_recBjw7jZ33SWs7B1"}]},{"id":"recCtPsSMx1T8wKw9","name":"Portable Extinguisher Wheeled","checklist":[{"id":"004d49d5-d61a-4293-9f65-6780a3bffbcb","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"2.11","prompt":"CHECK that the fire hazard/risk to be\n protected has not changed.\n All extinguisher types","input":null,"possible_fault":"Fire hazard/risk has changed from original assessment","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.11 - Fire hazard/risk to be protected has changed","severity_level":"informational","fault_id":"recIwBuJv4khGsNVy","prompt_id":"recIwBuJv4khGsNVy_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"05dd821a-7a51-4549-9ba3-aaf64f37d73b","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.1","prompt":"CHECK the extinguisher is conspicuous,\n readily accessible and in its assigned location.\n All extinguishers types","input":null,"possible_fault":"Extinguisher not accessible/visible/in wrong location","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.1 - Extinguisher not conspicuous, not readily accessible, or not in assigned location","severity_level":"non-conformance","fault_id":"recSQDrwBRsaClD71","prompt_id":"recSQDrwBRsaClD71_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"0a671015-2556-4c73-bb17-4ce59e7a587d","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"3.13","prompt":"(b) SUBJECT the hose assembly to a\n hydrostatic pressure test of 1.5 times the\n extinguisher working pressure, or 2 MPa,\n whichever is the greater.\n All wheeled extinguishers (other than CO2)","input":null,"possible_fault":"Hose assembly fails pressure test of 1.5 times working pressure or 2 MPa/structural failure/leakage","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.13(b) - Subject hose assembly to hydrostatic pressure test of 1.5 times extinguisher working pressure, or 2 MPa, whichever is greater for all wheeled extinguishers (other than CO2)","severity_level":"critical","fault_id":"recKKKg07bUrnhxLb","prompt_id":"recKKKg07bUrnhxLb_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"12c48733-5627-408b-b558-4e65884da654","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (stored pressure),Foam (stored pressure)","variant_id":"recCtPsSMx1T8wKw9","item_no":"2.3","prompt":"CHECK that the extinguisher functions in\n accordance with the operating instructions\n and that the discharge is satisfactory.\n Recharge in accordance with Item 2.8.\n (a) Water with additive (stored pressure),\n foam (stored pressure)\n (b) Water with corrosion inhibitors or\n freezing point depressants (stored\n pressure)*\n * To be discharged on a three-yearly\n frequency.","input":null,"possible_fault":"Extinguisher doesn't function per instructions/discharge unsatisfactory","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.3 - Extinguisher doesn't function in accordance with operating instructions or discharge is unsatisfactory","severity_level":"critical","fault_id":"recX4dvuA0Fo1y85q","prompt_id":"recX4dvuA0Fo1y85q_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"18b15027-0298-4040-8dad-cc734be7a213","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (gas container),Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recCtPsSMx1T8wKw9","item_no":"2.4","prompt":"CHECK that the actuating device is free of\n corrosion, moves freely, and is undamaged;\n any cutting edge is sharp; and all sealing\n gaskets are in good condition.\n Water (gas container), foam (gas container),\n foam (stored pressure) powder (gas\n container)","input":null,"possible_fault":"Actuating device corroded/seized/damaged/cutting edge dull/sealing gaskets deteriorated","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.4 - Actuating device corroded, doesn't move freely, damaged, cutting edge not sharp, or sealing gaskets in poor condition","severity_level":"non-critical","fault_id":"recxPbZBAEVCPw8H1","prompt_id":"recxPbZBAEVCPw8H1_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"1f4084e8-0473-4714-8e0f-e3ffbb619a55","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (stored pressure),Wet chemical,Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.7","prompt":"CHECK that the operating head or cap seal is in\n good condition.\n Water (stored pressure), wet chemical, powder\n (stored pressure), carbon dioxide, vaporizing\n liquid","input":null,"possible_fault":"Operating head or cap seal deteriorated/damaged/missing/compromised integrity","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.7 - Operating head or cap seal not in good condition","severity_level":"critical","fault_id":"recyZNwnX8DN6WlsS","prompt_id":"recyZNwnX8DN6WlsS_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"20cf1b9e-4bbc-416b-ac8c-f4d02bfdf2b2","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (stored pressure),Foam (gas container),Foam (stored pressure)","variant_id":"recCtPsSMx1T8wKw9","item_no":"2.8","prompt":"RECHARGE the extinguisher with fresh\n extinguishing agent in accordance with the\n manufacturer’s instructions.\n Water with additive (stored pressure), foam\n (gas container), foam (stored pressure)","input":null,"possible_fault":"Extinguishing agent contaminated/expired/incorrect type/recharge failed","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.8 - Recharge extinguisher with fresh extinguishing agent in accordance with manufacturer's instructions","severity_level":"critical","fault_id":"recQF17DF9EoejmkJ","prompt_id":"recQF17DF9EoejmkJ_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"258095ee-315f-417a-97eb-28be7c379b40","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (stored pressure),Wet chemical,Foam (stored pressure),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.12","prompt":"CHECK if there are any leaks at the joints and\n seals that were renewed or disturbed during\n recharging.\n Water (stored pressure), wet chemical, foam\n (stored pressure), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Leaks present at joints/seals renewed or disturbed during servicing/pressure loss detected","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.12 - Check if there are leaks at joints and seals that were renewed or disturbed during recharging","severity_level":"non-critical","fault_id":"recW9tNI7gnaxv27Y","prompt_id":"recW9tNI7gnaxv27Y_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"2e7cac48-20b9-4a62-8048-144ffa1fb8c7","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.3","prompt":"CHECK that the extinguisher is clean and the\n operating instructions are legible.\n All extinguishers types","input":null,"possible_fault":"Extinguisher dirty/operating instructions illegible","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.3 - Extinguisher not clean or operating instructions not legible","severity_level":"non-critical","fault_id":"rec6MMv58x9YXfoUG","prompt_id":"rec6MMv58x9YXfoUG_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"308b7f44-1980-4f0f-90d2-aa48c8271d19","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (stored pressure),Wet chemical,Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.3","prompt":"CHECK that the actuating device is free of\n corrosion, moves freely, and is undamaged; any\n cutting edge is sharp; and all sealing gaskets are\n in good condition.\n Water (stored pressure), wet chemical, powder\n (stored pressure), carbon dioxide, vaporizing\n liquid","input":null,"possible_fault":"Actuating device corroded/seized/damaged/cutting edge dull/sealing gaskets deteriorated","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.3 - Actuating device corroded, doesn't move freely, damaged, cutting edge not sharp, or sealing gaskets in poor condition","severity_level":"non-critical","fault_id":"recLi183C7YjPFKF3","prompt_id":"recLi183C7YjPFKF3_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"41e95c48-9548-4c07-b158-4e61051c3ec8","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (stored pressure),Foam (stored pressure)","variant_id":"recCtPsSMx1T8wKw9","item_no":"2.10","prompt":"CHECK if there are any leaks at the joints\n and seals that were renewed or disturbed\n during recharging.\n Water with additive (stored pressure), foam\n (stored pressure)","input":null,"possible_fault":"Leaks detected at joints/seals after recharging","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.10 - Leaks present at joints and seals that were renewed or disturbed during recharging","severity_level":"non-critical","fault_id":"recUDd6AO0k4mYBdO","prompt_id":"recUDd6AO0k4mYBdO_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"4699c251-265f-4641-85af-b8378874c852","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (stored pressure),Wet chemical,Powder (stored pressure),Vaporizing liquid","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.5","prompt":"CHECK that the interior of the cylinder is clean,\n is not pitted by corrosion (see AS 2337.1), and\n any internal lining is in good condition.\n Where the lining cannot be removed to inspect\n the interior of the cylinder, the cylinder shall be\n accepted or rejected as per AS 2337.1.\n Water (stored pressure), wet chemical, powder\n (stored pressure), vaporizing liquid.","input":null,"possible_fault":"Cylinder interior dirty/pitted by corrosion/internal lining deteriorated/contamination present","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.5 - Interior of cylinder not clean, pitted by corrosion (see AS 2337.1), or internal lining in poor condition. Where lining cannot be removed, cylinder shall be accepted or rejected as per AS 2337.1","severity_level":"non-critical","fault_id":"recz78TOKQTuwaCoi","prompt_id":"recz78TOKQTuwaCoi_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"4f2d2453-9ad8-4a15-a5f9-1ec7896fba55","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (gas container),Water (stored pressure),Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recCtPsSMx1T8wKw9","item_no":"2.6","prompt":"CHECK that the interior of cylinder is clean,\n is not pitted by corrosion (see AS 2337.1),\n and any internal lining is in good condition.\n Water (gas container), water with additive\n (stored pressure), foam (gas container),\n foam (stored pressure), powder (gas\n container)","input":null,"possible_fault":"Cylinder interior dirty/pitted by corrosion/internal lining deteriorated","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.6 - Interior of cylinder not clean, pitted by corrosion (see AS 2337.1), or internal lining in poor condition","severity_level":"non-critical","fault_id":"recWAGFh9zBWgUY7r","prompt_id":"recWAGFh9zBWgUY7r_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"515da453-ae93-497c-8f6c-8fa00ff4aa5e","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.2","prompt":"CHECK that the anti-tamper device is intact.\n All extinguishers types","input":null,"possible_fault":"Anti-tamper device damaged/missing/broken","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.2 - Anti-tamper device not intact or damaged","severity_level":"non-critical","fault_id":"recooBCUpqyJMaxTu","prompt_id":"recooBCUpqyJMaxTu_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"575e6441-8d31-40c6-94e4-5c5c7d7e9196","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"3.5","prompt":"For carbon dioxide extinguishers, this\n examination shall be in accordance with\n AS 2030.5, and shall be performed at a gas\n cylinder test station certified by a registered\n certifying body (see AS 2337.1).","input":null,"possible_fault":"Internal examination fails AS 2030.5 requirements/cylinder test station findings","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.5 - For CO2 extinguishers, examination in accordance with AS 2030.5 at certified gas cylinder test station","severity_level":"critical","fault_id":"rec76e2LF6VqlR2sT","prompt_id":"rec76e2LF6VqlR2sT_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"5b6f775f-019f-4e73-a154-7e343468ab27","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.14","prompt":"CHECK that the carriage assembly is\n functional and free from corrosion.\n All wheeled extinguishers","input":null,"possible_fault":"Carriage assembly damaged/corroded/non-functional","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.14 - Carriage assembly not functional or showing corrosion","severity_level":"non-critical","fault_id":"recEfJamu6eXYsCyN","prompt_id":"recEfJamu6eXYsCyN_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"5e5f573c-59cb-4af5-8709-dd8a00e43d51","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":"Powder (gas container)","variant_id":"recCtPsSMx1T8wKw9","item_no":"2.5","prompt":"(b) CHECK that the internal discharge\n tube, or the gas inlet tube or ports,\n provide clear passage and are correctly\n installed, and that the powder is free\n flowing.\n Powder (gas container)","input":null,"possible_fault":"Internal discharge tube blocked/gas inlet tube blocked/incorrect installation/powder not free flowing","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.5(b) - Internal discharge tube or gas inlet tube/ports don't provide clear passage, incorrectly installed, or powder not free flowing","severity_level":"critical","fault_id":"recWhYYp5yGOyTUis","prompt_id":"recWhYYp5yGOyTUis_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"5fd5e7c3-74ef-4cba-b4c0-081447c78f3f","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"3.1","prompt":"COMPLETE all six-monthly and yearly service\n activities, as listed in Table 10.4.1 and 10.4.2.","input":null,"possible_fault":"Any fault identified in six-monthly and yearly service items","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.1 - Complete all six-monthly and yearly service activities, as listed in Table 10.4.1 and 10.4.2","severity_level":"non-conformance","fault_id":"recCACKUEJoj74WWW","prompt_id":"recCACKUEJoj74WWW_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"6143ed0d-b6f2-48d7-9f65-9ef4eede7193","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Carbon dioxide","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.13","prompt":"(a) SUBJECT the hose assembly to a\n hydrostatic pressure test of 10 MPa.\n All CO2 type wheeled extinguishers","input":null,"possible_fault":"Hose assembly fails 10 MPa hydrostatic pressure test/structural failure/leakage","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.13(a) - Subject hose assembly to hydrostatic pressure test of 10 MPa for all CO2 type wheeled extinguishers","severity_level":"critical","fault_id":"rece9rcS2dwzu6P6U","prompt_id":"rece9rcS2dwzu6P6U_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"620b65f9-1deb-4d2d-8032-5700345990d1","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Carbon dioxide","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.8","prompt":"(b) SUBJECT the extinguisher body to a\n hydrostatic pressure test, in accordance\n with the requirements of AS 2030.5, at a\n Gas Cylinder Test Station certified by a\n Registered Certifying body (see\n AS 2337.1).\n Carbon dioxide","input":null,"possible_fault":"Cylinder fails AS 2030.5 pressure test requirements/test station rejection","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.8(b) - Subject CO2 extinguisher body to hydrostatic pressure test in accordance with AS 2030.5 at certified Gas Cylinder Test Station","severity_level":"critical","fault_id":"recfIDdPi1vJ0VkuK","prompt_id":"recfIDdPi1vJ0VkuK_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"636d9ba3-240a-44cb-9750-d9cd7ada192e","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"3.9","prompt":"SUBJECT the extinguisher body to a\n hydrostatic pressure test, in accordance with the\n requirements of AS 2030.5, at a Gas Cylinder\n Test Station certified by a Registered Certifying\n Body (see AS 2337.1).\n All wheeled extinguishers","input":null,"possible_fault":"Cylinder fails AS 2030.5 pressure test requirements/test station rejection","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.90 - Subject wheeled extinguisher body to hydrostatic pressure test in accordance with AS 2030.5 at certified Gas Cylinder Test Station for all wheeled extinguishers","severity_level":"critical","fault_id":"recXKUGgPOPELLZqO","prompt_id":"recXKUGgPOPELLZqO_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"6563e35e-3b57-4064-a95f-27f75c4c0f32","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.9","prompt":"WEIGH the extinguisher to determine that it is\n fully charged.\n All extinguisher types","input":null,"possible_fault":"Extinguisher underweight/not fully charged","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.9 - Weight indicates extinguisher is not fully charged","severity_level":"non-critical","fault_id":"recZqCmQIeFsZpknI","prompt_id":"recZqCmQIeFsZpknI_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"684a692e-6b47-4621-a8bd-90385fda65c4","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":"Powder (gas container),Powder (stored pressure)","variant_id":"recCtPsSMx1T8wKw9","item_no":"1.15","prompt":"INVERT the extinguisher and ensure that the\n powder remains free flowing.\n Powder (stored pressure), powder (gas\n container)","input":null,"possible_fault":"Powder consolidated/not free flowing","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.15 - Powder not remaining free flowing when extinguisher inverted","severity_level":"non-critical","fault_id":"recpTHbDNTlhMh1OB","prompt_id":"recpTHbDNTlhMh1OB_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"6c9534b4-f8cb-4f55-9e4c-8523e495bf7d","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"3.6","prompt":"CHECK the interior of the cylinder in\n accordance with the internal examination\n requirements of AS 2030.5 at a Gas Cylinder\n Test Station certified by a Registered Certifying\n Body (see AS 2337.1).\n All wheeled extinguishers","input":null,"possible_fault":"Cylinder interior fails AS 2030.5 internal examination requirements/test station rejection","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.6 - Check interior of cylinder in accordance with internal examination requirements of AS 2030.5 at certified Gas Cylinder Test Station for all wheeled extinguishers","severity_level":"critical","fault_id":"recWZFSEShnNb8QWl","prompt_id":"recWZFSEShnNb8QWl_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"7d91da45-1490-44f9-8c16-f177ad32e6d4","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (gas container),Water (stored pressure),Wet chemical,Foam (gas container),Foam (stored pressure),Powder (gas container),Powder (stored pressure),Vaporizing liquid","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.8","prompt":"(a) SUBJECT the extinguisher body to a\n hydrostatic pressure test of 1.5 times the\n working pressure, the marked periodic test\n pressure, or 2 MPa, whichever is the\n greatest.\n Water (gas container), water (stored\n pressure), wet chemical, foam (gas\n container), foam (stored pressure), powder\n (gas container), powder (stored pressure),\n vaporizing liquid","input":null,"possible_fault":"Cylinder fails hydrostatic pressure test/structural integrity compromised/leakage under test pressure","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.8(a) - Subject extinguisher body to hydrostatic pressure test of 1.5 times working pressure, marked periodic test pressure, or 2 MPa, whichever is greatest","severity_level":"critical","fault_id":"recGVQPKaneqJkEI0","prompt_id":"recGVQPKaneqJkEI0_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"81ff8bc0-796a-4162-b18d-8a0e5c48cfbd","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"2.12","prompt":"CHECK that the extinguisher is the correct\n type, class, size and/or rating for the hazard\n to be protected.\n All extinguisher types","input":null,"possible_fault":"Extinguisher incorrect type/class/size/rating for current hazard","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.12 - Extinguisher not correct type, class, size and/or rating for hazard to be protected","severity_level":"non-conformance","fault_id":"recVTWt6U3Mik2Mwi","prompt_id":"recVTWt6U3Mik2Mwi_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"8230835e-940e-4b06-9c71-49345e1c43d3","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"2.13","prompt":"(b) CHECK that no alterations have been\n made to the building that may impede\n access to, or restrict the movement of,\n the extinguisher.\n All wheeled extinguishers","input":null,"possible_fault":"Building alterations impede access/restrict movement of wheeled extinguisher","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.13(b) - Alterations made to building that impede access to or restrict movement of wheeled extinguisher","severity_level":"non-critical","fault_id":"recXjatd3twRKD9li","prompt_id":"recXjatd3twRKD9li_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"8d5035fe-e5c3-4eca-a1de-4e36b38ac2a1","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.11","prompt":"CHECK that the appropriate support bracket is\n securely attached to wall or other suitable\n feature.\n All extinguishers types","input":null,"possible_fault":"Support bracket loose/damaged/inadequate","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.11 - Support bracket not securely attached to wall or suitable feature","severity_level":"non-critical","fault_id":"recNBlIA1wZCWAann","prompt_id":"recNBlIA1wZCWAann_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"8db256b7-d01c-498e-aece-97e09973d088","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"3.11","prompt":"RENEW all seals and gaskets fitted to the\n actuating device, operating head, or cap.\n All extinguisher types","input":null,"possible_fault":"Seals and gaskets deteriorated/damaged/wrong specification/installation failure","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.11 - Renew all seals and gaskets fitted to actuating device, operating head, or cap for all extinguisher types","severity_level":"non-critical","fault_id":"recmvJfvA1N9gdrAK","prompt_id":"recmvJfvA1N9gdrAK_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"952f5af9-b4e0-42ad-ae32-f004e0bb898b","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (gas container),Water (stored pressure),Wet chemical,Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recCtPsSMx1T8wKw9","item_no":"2.2","prompt":"CHECK that the threads on operating head\n or cap are not damaged, vent(s) is (are) not\n blocked, and any strainer or expansion\n device is unobstructed. For heads with no\n screw thread, determine that security locking\n device is undamaged and operational.\n Water (gas container), foam (gas container),\n water with additive (stored pressure), foam\n (stored pressure), powder (gas container)","input":null,"possible_fault":"Operating head/cap threads damaged/vents blocked/strainer obstructed/security locking device damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.2 - Threads on operating head or cap damaged, vent(s) blocked, strainer or expansion device obstructed, or security locking device damaged/non-operational","severity_level":"non-critical","fault_id":"reccIVb9vLbr54Wsd","prompt_id":"reccIVb9vLbr54Wsd_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"95ab5add-b1ff-4338-bf0d-0461ba5dfeb5","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Wet chemical,Powder (gas container),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.10","prompt":"At the frequency specified by the extinguishing\n manufacturer, RECHARGE the extinguisher\n with fresh extinguishing agent, as specified on\n the extinguisher label, in accordance with the\n manufacturer’s instructions.\n Wet chemical, foam (gas container with\n sealed foam liquid container), powder (gas\n container), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Extinguishing agent contaminated/expired/degraded/incorrect specification/recharge failure","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.10 - Recharge extinguisher with fresh extinguishing agent as specified on label, in accordance with manufacturer's instructions at frequency specified by manufacturer","severity_level":"critical","fault_id":"rechONahaDbWMw63n","prompt_id":"rechONahaDbWMw63n_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"9bd8840f-a440-4857-bb4c-325c1d5dbbc4","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (stored pressure),Foam (stored pressure)","variant_id":"recCtPsSMx1T8wKw9","item_no":"2.5","prompt":"(a) CHECK that the internal discharge\n tube, strainer and anti-overfill tube\n (where fitted) provide clear passage\n and are securely attached, and that the\n anti-overfill device is undamaged.\n Water with additive (stored pressure),\n foam (stored pressure)","input":null,"possible_fault":"Internal discharge tube blocked/strainer obstructed/anti-overfill tube blocked/loose attachment/anti-overfill device damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.5(a) - Internal discharge tube, strainer, or anti-overfill tube don't provide clear passage or not securely attached, or anti-overfill device damaged","severity_level":"critical","fault_id":"recuVD5MfRXPMbC6k","prompt_id":"recuVD5MfRXPMbC6k_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"9da545d8-e1dd-4a5b-a0fe-cc28ba7f6d39","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":"Foam (gas container),Water (gas container),Powder (gas container)","variant_id":"recCtPsSMx1T8wKw9","item_no":"1.16","prompt":"DETERMINE that the compressed gas\n container is the correct size and type, in good\n condition, fully charged, and subjected to\n service as per AS 2030.5.\n All gas container extinguishers","input":null,"possible_fault":"Wrong size/type/poor condition/not fully charged/service overdue","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.16 - Gas container incorrect size/type, poor condition, not fully charged, or not serviced per AS 2030.5","severity_level":"non-critical","fault_id":"rec7fr193T4LpkwYc","prompt_id":"rec7fr193T4LpkwYc_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"9e5a6893-d03b-4b98-b139-22b641439b73","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (gas container),Foam (gas container),Foam (stored pressure)","variant_id":"recCtPsSMx1T8wKw9","item_no":"2.7","prompt":"CHECK that the interior of cylinder is clean.\n Water (gas container), foam (gas container),\n foam (stored pressure)","input":null,"possible_fault":"Cylinder interior dirty/contaminated","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.7 - Interior of cylinder not clean","severity_level":"non-critical","fault_id":"reciLXBFn65XgmAlI","prompt_id":"reciLXBFn65XgmAlI_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"a53385d8-ca0e-4caf-9bfd-517b1b59e318","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.13","prompt":"CHECK that the discharge nozzle is not\n blocked and that the control valve is\n functional.\n All wheeled extinguishers","input":null,"possible_fault":"Discharge nozzle blocked/control valve non-functional","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.13 - Discharge nozzle blocked or control valve not functional","severity_level":"critical","fault_id":"recdFwRAxmV0drKhk","prompt_id":"recdFwRAxmV0drKhk_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"a9a2888c-72aa-4320-92b9-897badc9e028","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"2.13","prompt":"(a) CHECK that no alterations have been\n made to the building that may impede\n access to the extinguisher or increase\n the travel distances to more than those\n required.\n All portable extinguishers","input":null,"possible_fault":"Building alterations impede access/increase travel distances beyond requirements","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.13(a) - Alterations made to building that impede access to extinguisher or increase travel distances beyond required limits","severity_level":"critical","fault_id":"rec1I5K3A4jQKCZGa","prompt_id":"rec1I5K3A4jQKCZGa_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"acac3488-cfc3-4f08-b9dc-8880b46d6af8","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (gas container),Water (stored pressure),Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recCtPsSMx1T8wKw9","item_no":"2.9","prompt":"CHECK that the operating head or cap seal\n is in good condition.\n Water (gas container), water with additive\n (stored pressure), foam (gas container),\n foam (stored pressure), powder (gas\n container)","input":null,"possible_fault":"Operating head or cap seal deteriorated/damaged/missing","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.9 - Operating head or cap seal not in good condition","severity_level":"non-critical","fault_id":"recKn0tOemFxc2S0K","prompt_id":"recKn0tOemFxc2S0K_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"aefb08c0-bf92-46bb-a019-3f33bb71081e","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (stored pressure),Wet chemical,Foam (gas container),Foam (stored pressure),Powder (gas container),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recCtPsSMx1T8wKw9","item_no":"1.17","prompt":"DETERMINE, where possible and without\n discharging any contents, that the actuating\n device is free of corrosion, moves freely and is\n undamaged.\n Water (stored pressure), wet chemical, foam\n (stored pressure), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Device corroded/seized/damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.17 - Actuating device corroded, doesn't move freely, or damaged","severity_level":"non-critical","fault_id":"rec1MNwt9QVBj2Zf4","prompt_id":"rec1MNwt9QVBj2Zf4_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"afe61f72-5386-4a19-9953-b0d52bc311b4","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (gas container),Foam (gas container)","variant_id":"recCtPsSMx1T8wKw9","item_no":"1.18","prompt":"DETERMINE that the internal discharge tube\n and strainer (where fitted) provide clear\n passage and are securely attached.\n Water (gas container), foam (gas container)","input":null,"possible_fault":"Internal discharge tube blocked/strainer obstructed/loose attachment","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.18 - Internal discharge tube or strainer not providing clear passage or not securely attached","severity_level":"critical","fault_id":"rec1ECgXHoBQAIRgc","prompt_id":"rec1ECgXHoBQAIRgc_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"b716cb0a-99eb-4dee-9c81-7bb5eeeac7ea","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.8","prompt":"Where fitted, CHECK that the pressure\n indicator is legible, and registering within the\n operable range.\n All extinguishers types","input":null,"possible_fault":"Pressure indicator illegible/outside operable range","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.8 - Pressure indicator not legible or not registering within operable range","severity_level":"non-critical","fault_id":"recovDcg1rD55C3AD","prompt_id":"recovDcg1rD55C3AD_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"b8e6641c-a85a-4b9d-a883-b34341d7ff6e","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.6","prompt":"CHECK that the exterior of the extinguisher is\n not pitted or otherwise damaged by corrosion\n (see Clause 10.2.5 and AS 2337.1).\n All extinguishers types","input":null,"possible_fault":"Exterior pitting/corrosion damage","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.6 - Exterior pitted or damaged by corrosion (see Clause 10.2.5 and AS 2337.1)","severity_level":"non-critical","fault_id":"recvp1xl8MQ3HNwQ2","prompt_id":"recvp1xl8MQ3HNwQ2_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"c209d5f9-9b81-4b44-98cf-f7a3433a8a4c","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.4","prompt":"CHECK that the service tag or label is firmly\n attached to the extinguisher.\n All extinguishers types","input":null,"possible_fault":"Service tag/label missing/loose/damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.4 - Service tag or label not firmly attached to extinguisher","severity_level":"non-conformance","fault_id":"recfSUETbSrv73ZQc","prompt_id":"recfSUETbSrv73ZQc_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"c3ebab70-dcde-4207-b03c-f660d2439745","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.10","prompt":"CHECK that the location sign is visible.\n All extinguishers types","input":null,"possible_fault":"Location sign not visible/missing/damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.10 - Location sign not visible","severity_level":"non-critical","fault_id":"rececYFXSjwKpaQzR","prompt_id":"rececYFXSjwKpaQzR_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"cb24b7b1-58f0-4b30-a5fc-09f8bb35539b","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"2.1","prompt":"COMPLETE all six-monthly service\n activities, as listed in Table 10.4.1.","input":null,"possible_fault":"Any fault identified in six-monthly service items","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.1 - Complete all six-monthly service activities, as listed in Table 10.4.1","severity_level":"non-conformance","fault_id":"recOb1cWhwMpA9z4Z","prompt_id":"recOb1cWhwMpA9z4Z_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"cdea1cf4-25c9-44f6-962a-a4d92eb3f508","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (gas container),Water (stored pressure),Wet chemical,Foam (gas container),Powder (gas container),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.2","prompt":"CHECK that the extinguisher functions in\n accordance with the operating instructions and\n that the discharge is satisfactory. Recharge in\n accordance with Item 3.9.\n Water (gas container), water (stored pressure),\n wet chemical, foam (gas container), powder\n (gas container), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Extinguisher doesn't function per instructions/discharge unsatisfactory/performance degraded","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.2 - Check that extinguisher functions in accordance with operating instructions and discharge is satisfactory. Recharge in accordance with Item 3.9","severity_level":"critical","fault_id":"recYmeAIuQLOrRC3W","prompt_id":"recYmeAIuQLOrRC3W_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"d06402b4-be57-40fd-8fea-74b87afe9ef3","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.12","prompt":"CHECK that the appropriate discharge nozzle\n is fitted and is not blocked or damaged.\n All extinguishers types","input":null,"possible_fault":"Discharge nozzle blocked/damaged/incorrect type","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.12 - Inappropriate discharge nozzle fitted, blocked, or damaged","severity_level":"critical","fault_id":"rec2ryT02rUXXXLZm","prompt_id":"rec2ryT02rUXXXLZm_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"d0bcb2fa-daa5-44e1-ba5e-323135d8b0cf","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.5","prompt":"CHECK that the extinguisher, including any\n attachments, is not damaged (see AS 2337.1).\n All extinguishers types","input":null,"possible_fault":"Physical damage to extinguisher/attachments","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.5 - Extinguisher or attachments damaged (see AS 2337.1)","severity_level":"non-critical","fault_id":"recAVbfoeC6ih6lZi","prompt_id":"recAVbfoeC6ih6lZi_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"dbc249ba-6a48-4cd7-a84d-844a92dda300","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.4","prompt":"(b) CHECK that the internal discharge tube\n provides clear passage, is securely\n attached, and there is no evidence of\n moisture or foreign matter in the cylinder.\n Powder (stored pressure), carbon dioxide,\n vaporizing liquid","input":null,"possible_fault":"Internal discharge tube blocked/moisture ingress/foreign matter contamination/loose attachment","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.4(b) - Internal discharge tube doesn't provide clear passage, not securely attached, or evidence of moisture or foreign matter in cylinder","severity_level":"critical","fault_id":"rec8UnX7Ggj9M03nT","prompt_id":"rec8UnX7Ggj9M03nT_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"e84be6b7-3b68-446a-9dcf-15cdf677c86e","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.19","prompt":"DETERMINE that pneumatic tyres, where\n fitted, are pressurized to the recommended\n pressure.\n All wheeled extinguishers","input":null,"possible_fault":"Pneumatic tyres not pressurized to recommended pressure","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.19 - Pneumatic tyres not pressurized to recommended pressure","severity_level":"non-critical","fault_id":"recf9uahI3sorkc5M","prompt_id":"recf9uahI3sorkc5M_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"e9d2848b-4e6c-49a5-b490-4dc0abaaf07e","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.20","prompt":"LUBRICATE wheel bearings (where\n applicable).\n All wheeled extinguishers","input":null,"possible_fault":"Wheel bearings require lubrication","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.20 - Wheel bearings not lubricated","severity_level":"recommendation","fault_id":"recLg71JPr0YWAAcB","prompt_id":"recLg71JPr0YWAAcB_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"ead67718-0495-4f8c-a09c-41eb257627c3","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"3.10","prompt":"Upon the completion of recharging stored\n pressure type extinguishers, perform a leak test\n as per Item 3.12.","input":null,"possible_fault":"Leaks detected after recharging stored pressure extinguishers/seal integrity compromised","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.10 - Upon completion of recharging stored pressure type extinguishers, perform leak test as per Item 3.12","severity_level":"non-critical","fault_id":"reclinfYvXsLePpLE","prompt_id":"reclinfYvXsLePpLE_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"ec1863f7-46d3-4ede-bb7e-757d92662064","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.21","prompt":"CHECK that the extinguisher moves readily on\n its wheels by rolling it for a distance of at least\n 5 m.\n All wheeled extinguishers","input":null,"possible_fault":"Extinguisher doesn't move readily on wheels","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.21 - Extinguisher doesn't roll readily for at least 5m distance","severity_level":"non-critical","fault_id":"recnqJh0gA30jyGdb","prompt_id":"recnqJh0gA30jyGdb_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"f342dad8-a657-4c0f-a0c9-f2d062016300","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Wheeled","variant":"Water (stored pressure),Wet chemical","variant_id":"recCtPsSMx1T8wKw9","item_no":"3.4","prompt":"(a) CHECK that the internal discharge tube,\n strainer and anti-overfill tube (where\n fitted) provide clear passage and are\n securely attached, and that the anti overfill\n device is undamaged.\n Water (stored pressure), wet chemical","input":null,"possible_fault":"Internal discharge tube blocked/strainer obstructed/anti-overfill tube blocked/loose attachment/anti-overfill device damaged","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.4(a) - Internal discharge tube, strainer, or anti-overfill tube don't provide clear passage or not securely attached, or anti-overfill device damaged","severity_level":"critical","fault_id":"recvLbovM7eq8Jznz","prompt_id":"recvLbovM7eq8Jznz_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"},{"id":"f4d1aec6-e0a6-4397-b1e5-7b7c6e746eaf","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Wheeled","variant":null,"variant_id":"recCtPsSMx1T8wKw9","item_no":"1.7","prompt":"CHECK that the hose is securely fitted, the\n nozzle is securely attached, the assembly is\n free from obstruction, and the hose shows no\n cracking or other signs of damage or\n deterioration.\n All extinguishers types","input":null,"possible_fault":"Hose loose/nozzle loose/obstruction/damage/deterioration","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.7 - Hose not securely fitted, nozzle not securely attached, assembly obstructed, or hose showing cracking/damage/deterioration","severity_level":"non-critical","fault_id":"rec9LMkbOx72oMAGv","prompt_id":"rec9LMkbOx72oMAGv_prompt","inspection_id":"c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recCtPsSMx1T8wKw9_recBjw7jZ33SWs7B1"}]},{"id":"recNDWLONf131V1bp","name":"Portable Extinguisher Adverse Environment","checklist":[{"id":"042252ff-f8a1-4e43-b9eb-cd964d060e43","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.2","prompt":"CHECK that the anti-tamper device is intact.\n All extinguishers types","input":null,"possible_fault":"Anti-tamper device damaged by weather/corrosion/vibration/temperature extremes","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.2 - Anti-tamper device not intact or damaged (Consider salt spray corrosion, temperature cycling effects, vibration damage)","severity_level":"non-critical","fault_id":"recS7z6FaZOE8yh4l","prompt_id":"recS7z6FaZOE8yh4l_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"0b85aef8-921f-460c-b2ef-cd8390a11921","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"2.13","prompt":"(a) CHECK that no alterations have been\n made to the building that may impede\n access to the extinguisher or increase\n the travel distances to more than those\n required.\n All portable extinguishers","input":null,"possible_fault":"Environmental factors creating new obstructions/access impediments/equipment additions blocking access","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.13(a) - Access obstructed by environmental equipment, new installations, weather protection measures, process modifications affecting travel distances","severity_level":"non-critical","fault_id":"recmP72chiCbcmrmp","prompt_id":"recmP72chiCbcmrmp_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"0eb032ff-1774-466a-913b-400cc99f5ca8","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Powder (gas container)","variant_id":"recNDWLONf131V1bp","item_no":"2.5","prompt":"(b) CHECK that the internal discharge\n tube, or the gas inlet tube or ports,\n provide clear passage and are correctly\n installed, and that the powder is free\n flowing.\n Powder (gas container)","input":null,"possible_fault":"Components corroded/powder contaminated by moisture/caked by humidity/gas system compromised","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.5(b) - Gas system corroded, powder contaminated by moisture ingress, components damaged by environmental stress, powder caked by humidity","severity_level":"critical","fault_id":"reca7W0u3pIrj3f1Z","prompt_id":"reca7W0u3pIrj3f1Z_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"1b4aeb70-a951-4326-9a8d-460b6aed9365","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.8","prompt":"Where fitted, CHECK that the pressure\n indicator is legible, and registering within the\n operable range.\n All extinguishers types","input":null,"possible_fault":"Pressure indicator obscured by dirt/moisture/damaged by temperature/illegible/inaccurate readings","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.8 - Pressure indicator not legible or not registering within operable range (Consider condensation, dust accumulation, temperature effects on gauge accuracy)","severity_level":"non-critical","fault_id":"recZYIcVX2VkWWZjd","prompt_id":"recZYIcVX2VkWWZjd_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"1d70cb03-1b60-4136-8a08-02991c286e46","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (gas container),Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recNDWLONf131V1bp","item_no":"2.4","prompt":"CHECK that the actuating device is free of\n corrosion, moves freely, and is undamaged;\n any cutting edge is sharp; and all sealing\n gaskets are in good condition.\n Water (gas container), foam (gas container),\n foam (stored pressure) powder (gas\n container)","input":null,"possible_fault":"Device seized by salt corrosion/dirt accumulation/damaged by vibration/thermal cycling/gaskets degraded by environment","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.4 - Device corroded by salt spray/chemicals, seized by debris, damaged by vibration/thermal stress, gaskets degraded by UV/ozone/temperature","severity_level":"non-critical","fault_id":"recyIjEPdB0kxXyIG","prompt_id":"recyIjEPdB0kxXyIG_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"22b3ee79-516e-45b9-9d99-80b2e425b569","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.11","prompt":"CHECK that the appropriate support bracket is\n securely attached to wall or other suitable\n feature.\n All extinguishers types","input":null,"possible_fault":"Support bracket corroded/loosened by vibration/damaged by environmental factors","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.11 - Support bracket not securely attached to wall or suitable feature (Consider corrosion of fasteners, vibration loosening, thermal expansion effects)","severity_level":"non-critical","fault_id":"recvhZu92z98ggzpN","prompt_id":"recvhZu92z98ggzpN_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"2774adcb-a4f1-4f2f-a162-da37a4002066","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"3.1","prompt":"COMPLETE all six-monthly and yearly service\n activities, as listed in Table 10.4.1 and 10.4.2.","input":null,"possible_fault":"Any fault identified in six-monthly and yearly service items (accelerated by environmental conditions)","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.1 - Complete all six-monthly and yearly service activities, considering accelerated deterioration from environmental exposure","severity_level":"non-conformance","fault_id":"recfdCovrlN4S4tn3","prompt_id":"recfdCovrlN4S4tn3_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"2f5485e2-049e-4dc3-a3be-a984fedf0bc3","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"3.10","prompt":"Upon the completion of recharging stored\n pressure type extinguishers, perform a leak test\n as per Item 3.12.","input":null,"possible_fault":"Severe leakage from environmental damage to seals/joints/accelerated seal failure/pressure loss from environmental stress","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.10 - Leaks from environmental stress on seals/joints, accelerated degradation, thermal cycling damage, corrosion of fittings","severity_level":"critical","fault_id":"reczsGqBQJB3LKdac","prompt_id":"reczsGqBQJB3LKdac_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"2f828dbe-c95e-43ce-a77f-345a6e5870f2","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"2.12","prompt":"CHECK that the extinguisher is the correct\n type, class, size and/or rating for the hazard\n to be protected.\n All extinguisher types","input":null,"possible_fault":"Extinguisher suitability affected by environmental changes/process modifications/new hazard classification","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.12 - Suitability compromised by environmental changes, new processes, modified hazard classification, changed operating conditions","severity_level":"informational","fault_id":"recLYH9QZ5iG7Acg4","prompt_id":"recLYH9QZ5iG7Acg4_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"2f88669f-9ec7-464a-bba2-0b3830914504","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (stored pressure),Wet chemical,Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recNDWLONf131V1bp","item_no":"3.3","prompt":"CHECK that the actuating device is free of\n corrosion, moves freely, and is undamaged; any\n cutting edge is sharp; and all sealing gaskets are\n in good condition.\n Water (stored pressure), wet chemical, powder\n (stored pressure), carbon dioxide, vaporizing\n liquid","input":null,"possible_fault":"Device seized by salt corrosion/chemical attack/debris accumulation/severely damaged by environmental stress/gaskets degraded by UV/temperature/chemical exposure","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.3 - Device corroded by salt spray/chemicals, seized by environmental debris, damaged by vibration/thermal cycling, gaskets severely degraded by environmental exposure","severity_level":"critical","fault_id":"recK9TZNGCT5PrtxK","prompt_id":"recK9TZNGCT5PrtxK_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"324b60aa-abeb-4d68-8ef7-4d9d13808323","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (stored pressure),Foam (stored pressure)","variant_id":"recNDWLONf131V1bp","item_no":"2.3","prompt":"CHECK that the extinguisher functions in\n accordance with the operating instructions\n and that the discharge is satisfactory.\n Recharge in accordance with Item 2.8.\n (a) Water with additive (stored pressure),\n foam (stored pressure)\n (b) Water with corrosion inhibitors or\n freezing point depressants (stored\n pressure)*\n * To be discharged on a three-yearly\n frequency.","input":null,"possible_fault":"Extinguisher function compromised by environmental contamination/seal degradation/internal corrosion","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.3 - Function impaired by environmental ingress, seal degradation from temperature cycling, internal contamination affecting discharge","severity_level":"critical","fault_id":"rec2M0dG4kbJOjzuA","prompt_id":"rec2M0dG4kbJOjzuA_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"3d637c39-04d7-4a6c-aedb-e9ea902db202","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (stored pressure),Wet chemical","variant_id":"recNDWLONf131V1bp","item_no":"3.4","prompt":"(a) CHECK that the internal discharge tube,\n strainer and anti-overfill tube (where\n fitted) provide clear passage and are\n securely attached, and that the anti overfill\n device is undamaged.\n Water (stored pressure), wet chemical","input":null,"possible_fault":"Components severely corroded/blocked by environmental contamination/damaged by thermal cycling/seals completely degraded","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.4(a) - Internal components severely corroded by environmental ingress, blocked by contamination buildup, damaged by repeated thermal expansion/contraction, anti-overfill systems compromised","severity_level":"critical","fault_id":"recvkgl6GV3VM327V","prompt_id":"recvkgl6GV3VM327V_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"3e5ab686-b4ee-461e-9f22-00b9a8efcf61","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (stored pressure),Wet chemical,Foam (stored pressure),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recNDWLONf131V1bp","item_no":"3.12","prompt":"CHECK if there are any leaks at the joints and\n seals that were renewed or disturbed during\n recharging.\n Water (stored pressure), wet chemical, foam\n (stored pressure), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Extensive leakage from environmental damage/accelerated joint failure/widespread seal compromise/pressure loss","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.12 - Extensive leaks from environmental stress, accelerated joint deterioration, widespread seal failure, multiple pressure loss points from environmental damage","severity_level":"critical","fault_id":"reczGenlkMifQ1YfI","prompt_id":"reczGenlkMifQ1YfI_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"40c307f9-d468-4eff-8785-3aca7e616cd3","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"3.5","prompt":"For carbon dioxide extinguishers, this\n examination shall be in accordance with\n AS 2030.5, and shall be performed at a gas\n cylinder test station certified by a registered\n certifying body (see AS 2337.1).","input":null,"possible_fault":"Cylinder fails AS 2030.5 examination due to environmental corrosion/contamination/stress corrosion cracking","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.5 - CO2 cylinder examination failure due to environmental stress corrosion, contamination from external sources, accelerated deterioration from adverse conditions","severity_level":"critical","fault_id":"recRgLMYMFrxdmjRK","prompt_id":"recRgLMYMFrxdmjRK_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"43a34f64-a1ac-48ef-b767-e29cde732416","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.6","prompt":"CHECK that the exterior of the extinguisher is\n not pitted or otherwise damaged by corrosion\n (see Clause 10.2.5 and AS 2337.1).\n All extinguishers types","input":null,"possible_fault":"Accelerated corrosion from salt spray/chemicals/moisture/temperature cycling","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.6 - Exterior pitted or damaged by corrosion (Consider salt spray corrosion, chemical attack, galvanic corrosion, condensation effects)","severity_level":"recommendation","fault_id":"rec1sNSroHRCR3sjX","prompt_id":"rec1sNSroHRCR3sjX_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"58f0d818-b289-484e-9442-49c2063a3982","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (gas container),Water (stored pressure),Wet chemical,Foam (gas container),Foam (stored pressure),Powder (gas container),Powder (stored pressure),Vaporizing liquid","variant_id":"recNDWLONf131V1bp","item_no":"3.8","prompt":"(b) SUBJECT the extinguisher body to a\n hydrostatic pressure test, in accordance\n with the requirements of AS 2030.5, at a\n Gas Cylinder Test Station certified by a\n Registered Certifying body (see\n AS 2337.1).\n Carbon dioxide","input":null,"possible_fault":"Cylinder fails AS 2030.5 pressure test due to environmental damage/corrosion/structural compromise","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.8(b) - CO2 pressure test failure due to environmental stress corrosion, structural damage from adverse conditions, accelerated cylinder deterioration","severity_level":"critical","fault_id":"recYMT4fC9Px0ojSp","prompt_id":"recYMT4fC9Px0ojSp_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"643c88b3-abd2-4804-9f47-5443d5cb0e64","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.10","prompt":"CHECK that the location sign is visible.\n All extinguishers types","input":null,"possible_fault":"Location sign obscured/faded/damaged by weather/UV/chemicals/vibration","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.10 - Location sign not visible (Consider UV fading, weather damage, chemical attack, dust/debris accumulation)","severity_level":"non-critical","fault_id":"receIZMohPtqy4Jhr","prompt_id":"receIZMohPtqy4Jhr_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"661982a9-a0af-475c-8084-c88f13445e01","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"3.8","prompt":"(a) SUBJECT the extinguisher body to a\n hydrostatic pressure test of 1.5 times the\n working pressure, the marked periodic test\n pressure, or 2 MPa, whichever is the\n greatest.\n Water (gas container), water (stored\n pressure), wet chemical, foam (gas\n container), foam (stored pressure), powder\n (gas container), powder (stored pressure),\n vaporizing liquid","input":null,"possible_fault":"Cylinder structural integrity compromised by environmental corrosion/stress corrosion cracking/wall thinning/test failure","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.8(a) - Hydrostatic pressure test failure due to environmental corrosion, stress corrosion cracking, wall thinning from chemical exposure, structural compromise","severity_level":"critical","fault_id":"recUTnoCO8R6rTjqt","prompt_id":"recUTnoCO8R6rTjqt_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"689ae501-6e25-4696-b723-579c9854f924","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (gas container),Water (stored pressure),Wet chemical,Foam (gas container),Powder (gas container),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recNDWLONf131V1bp","item_no":"3.2","prompt":"CHECK that the extinguisher functions in\n accordance with the operating instructions and\n that the discharge is satisfactory. Recharge in\n accordance with Item 3.9.\n Water (gas container), water (stored pressure),\n wet chemical, foam (gas container), powder\n (gas container), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Function compromised by environmental contamination/corrosion/seal degradation/performance severely degraded","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.2 - Function impaired by environmental ingress, internal corrosion, contamination affecting discharge mechanism, seal degradation from environmental exposure","severity_level":"critical","fault_id":"recZ3xMfzqr7pfFld","prompt_id":"recZ3xMfzqr7pfFld_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"6f8f3602-f5cd-4fc7-9f4b-5ffc8894a458","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Foam (gas container),Water (gas container),Powder (gas container)","variant_id":"recNDWLONf131V1bp","item_no":"1.16","prompt":"DETERMINE that the compressed gas\n container is the correct size and type, in good\n condition, fully charged, and subjected to\n service as per AS 2030.5.\n All gas container extinguishers","input":null,"possible_fault":"Gas container corroded/damaged by environment/pressure affected by temperature","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.16 - Gas container incorrect size/type, poor condition, not fully charged, or not serviced per AS 2030.5 (Consider corrosion, temperature effects on pressure, seal degradation)","severity_level":"non-critical","fault_id":"recXpQU7Hs4CmbAdw","prompt_id":"recXpQU7Hs4CmbAdw_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"6f9117ea-716d-4652-8934-dcfeeda8f00d","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.4","prompt":"CHECK that the service tag or label is firmly\n attached to the extinguisher.\n All extinguishers types","input":null,"possible_fault":"Service tag/label missing/loose/damaged by weather/UV/chemicals/vibration","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.4 - Service tag or label not firmly attached to extinguisher (Consider UV degradation, chemical attack, adhesive failure due to temperature extremes)","severity_level":"non-critical","fault_id":"recprpK0EydaLJE3K","prompt_id":"recprpK0EydaLJE3K_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"6fe08b00-5248-4483-9234-90e4f50b8a9c","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.5","prompt":"CHECK that the extinguisher, including any\n attachments, is not damaged (see AS 2337.1).\n All extinguishers types","input":null,"possible_fault":"Physical damage from environmental factors/impact/thermal cycling/vibration","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.5 - Extinguisher or attachments damaged (Consider impact damage from equipment, thermal expansion/contraction, vibration fatigue)","severity_level":"non-critical","fault_id":"recaG5q0xv7DMW7bm","prompt_id":"recaG5q0xv7DMW7bm_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"70dbe55b-7533-493e-af20-0179b8a38d01","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"2.11","prompt":"CHECK that the fire hazard/risk to be\n protected has not changed.\n All extinguisher types","input":null,"possible_fault":"Environmental changes affecting fire risk/new hazards introduced/existing hazards modified","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.11 - Fire hazard changed by environmental factors, process changes, new equipment installation, modified operating conditions","severity_level":"informational","fault_id":"recEwMYdK5l4kP2vN","prompt_id":"recEwMYdK5l4kP2vN_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"753ea5eb-280d-4486-9e31-adb9ccccaf67","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.7","prompt":"CHECK that the hose is securely fitted, the\n nozzle is securely attached, the assembly is\n free from obstruction, and the hose shows no\n cracking or other signs of damage or\n deterioration.\n All extinguishers types","input":null,"possible_fault":"Hose degraded by UV/ozone/chemicals/temperature/vibration/blockage from dust/debris","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.7 - Hose not securely fitted, nozzle not securely attached, assembly obstructed, or hose showing cracking/damage/deterioration (Consider UV/ozone cracking, chemical degradation, dust/debris blockage)","severity_level":"non-critical","fault_id":"recKWFtsfXqVgBI2w","prompt_id":"recKWFtsfXqVgBI2w_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"774bb2e8-4d60-4cae-943c-69420f438793","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Powder (gas container),Powder (stored pressure)","variant_id":"recNDWLONf131V1bp","item_no":"1.15","prompt":"INVERT the extinguisher and ensure that the\n powder remains free flowing.\n Powder (stored pressure), powder (gas\n container)","input":null,"possible_fault":"Powder consolidated due to moisture/vibration/temperature cycling","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.15 - Powder not remaining free flowing when extinguisher inverted (Consider moisture absorption, vibration compaction, temperature effects on powder)","severity_level":"non-critical","fault_id":"recFaDD1svrNh7o2p","prompt_id":"recFaDD1svrNh7o2p_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"7acd1185-a4b0-4cc9-942c-1f99f8ba22ab","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"2.1","prompt":"COMPLETE all six-monthly service\n activities, as listed in Table 10.4.1.","input":null,"possible_fault":"Any fault identified in six-monthly service items (environmental factors accelerate deterioration)","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.1 - Complete all six-monthly service activities, as listed in Table 10.4.1 (Consider accelerated wear from environmental conditions)","severity_level":"critical","fault_id":"recE1WuB1GNA5aX0B","prompt_id":"recE1WuB1GNA5aX0B_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"83741320-c8a0-41a6-9587-dffb581db717","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (gas container),Foam (gas container)","variant_id":"recNDWLONf131V1bp","item_no":"1.18","prompt":"DETERMINE that the internal discharge tube\n and strainer (where fitted) provide clear\n passage and are securely attached.\n Water (gas container), foam (gas container)","input":null,"possible_fault":"Internal components blocked/corroded/damaged by environmental ingress","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.18 - Internal discharge tube or strainer not providing clear passage or not securely attached (Consider dust ingress, moisture effects, corrosion, vibration damage)","severity_level":"critical","fault_id":"rec085vtTpviVsnUW","prompt_id":"rec085vtTpviVsnUW_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"846406db-18c1-4b1b-9f5d-b76c068dce97","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (gas container),Water (stored pressure),Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recNDWLONf131V1bp","item_no":"2.9","prompt":"CHECK that the operating head or cap seal\n is in good condition.\n Water (gas container), water with additive\n (stored pressure), foam (gas container),\n foam (stored pressure), powder (gas\n container)","input":null,"possible_fault":"Seals degraded by UV/ozone/temperature cycling/chemical exposure/salt spray","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.9 - Seals degraded by environmental exposure, UV/ozone cracking, temperature cycling effects, chemical attack, salt spray corrosion","severity_level":"non-critical","fault_id":"recdX5Rpw1gh0wTUN","prompt_id":"recdX5Rpw1gh0wTUN_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"89375d7b-a1db-447a-8511-3a526a825546","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (gas container),Water (stored pressure),Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recNDWLONf131V1bp","item_no":"2.6","prompt":"CHECK that the interior of cylinder is clean,\n is not pitted by corrosion (see AS 2337.1),\n and any internal lining is in good condition.\n Water (gas container), water with additive\n (stored pressure), foam (gas container),\n foam (stored pressure), powder (gas\n container)","input":null,"possible_fault":"Accelerated internal corrosion from environmental ingress/contamination/moisture/chemical exposure","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.6 - Internal corrosion accelerated by environmental conditions, contamination from external sources, moisture ingress, chemical exposure","severity_level":"critical","fault_id":"rec0nhgnjPleQnYxm","prompt_id":"rec0nhgnjPleQnYxm_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"903ef6a2-937b-4b23-855a-397e89207342","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recNDWLONf131V1bp","item_no":"3.4","prompt":"(b) CHECK that the internal discharge tube\n provides clear passage, is securely\n attached, and there is no evidence of\n moisture or foreign matter in the cylinder.\n Powder (stored pressure), carbon dioxide,\n vaporizing liquid","input":null,"possible_fault":"Components severely corroded/powder heavily contaminated/caked by environmental moisture/gas system compromised by corrosion","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.4(b) - Internal components severely corroded, powder contaminated by moisture/salt ingress, foreign matter from environmental exposure, gas systems compromised","severity_level":"critical","fault_id":"recsnTruGf79zth5V","prompt_id":"recsnTruGf79zth5V_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"9298783e-2221-4ee8-b184-6a8f7a24e18a","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.1","prompt":"CHECK the extinguisher is conspicuous,\n readily accessible and in its assigned location.\n All extinguishers types","input":null,"possible_fault":"Extinguisher not accessible/blocked by environmental factors/in wrong location","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.1 - Extinguisher not conspicuous, not readily accessible, or not in assigned location (Consider weather exposure, dust accumulation, temperature extremes affecting access)","severity_level":"critical","fault_id":"recEE84Brlnf3bzvk","prompt_id":"recEE84Brlnf3bzvk_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"9e20a265-718c-450c-be9e-579f813752a5","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (gas container),Water (stored pressure),Wet chemical,Foam (gas container),Foam (stored pressure),Powder (gas container)","variant_id":"recNDWLONf131V1bp","item_no":"2.2","prompt":"CHECK that the threads on operating head\n or cap are not damaged, vent(s) is (are) not\n blocked, and any strainer or expansion\n device is unobstructed. For heads with no\n screw thread, determine that security locking\n device is undamaged and operational.\n Water (gas container), foam (gas container),\n water with additive (stored pressure), foam\n (stored pressure), powder (gas container)","input":null,"possible_fault":"Operating head/cap threads damaged by corrosion/salt spray/temperature cycling/vents blocked by debris/environmental deposits","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.2 - Threads damaged by environmental corrosion, vents blocked by dust/salt deposits, expansion devices obstructed by debris, security devices damaged by weather/vibration","severity_level":"non-critical","fault_id":"rec9Dh7leu1v4mgP7","prompt_id":"rec9Dh7leu1v4mgP7_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"a319d719-fbfe-45f7-81f1-981e12edb63c","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (stored pressure),Wet chemical,Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recNDWLONf131V1bp","item_no":"3.7","prompt":"CHECK that the operating head or cap seal is in\n good condition.\n Water (stored pressure), wet chemical, powder\n (stored pressure), carbon dioxide, vaporizing\n liquid","input":null,"possible_fault":"Seals severely degraded by environmental exposure/complete failure from UV/ozone/chemical attack/temperature cycling damage","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.7 - Seals severely degraded by environmental exposure, UV/ozone cracking, chemical attack, salt spray corrosion, extreme temperature cycling effects","severity_level":"critical","fault_id":"recQ5zLTD26NAbbi5","prompt_id":"recQ5zLTD26NAbbi5_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"a6446298-4d04-4bbb-a314-b5a35c832fb0","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.9","prompt":"WEIGH the extinguisher to determine that it is\n fully charged.\n All extinguisher types","input":null,"possible_fault":"Extinguisher underweight due to seal degradation/temperature effects/pressure loss","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.9 - Weight indicates extinguisher is not fully charged (Consider seal degradation from temperature cycling, pressure loss from thermal effects)","severity_level":"non-critical","fault_id":"recMu0EHxckkTCYAx","prompt_id":"recMu0EHxckkTCYAx_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"c974e358-ad7d-40be-8940-7f8612e16dd4","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (stored pressure),Foam (stored pressure)","variant_id":"recNDWLONf131V1bp","item_no":"2.10","prompt":"CHECK if there are any leaks at the joints\n and seals that were renewed or disturbed\n during recharging.\n Water with additive (stored pressure), foam\n (stored pressure)","input":null,"possible_fault":"Accelerated seal degradation/joint failure from environmental stress/thermal cycling","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.10 - Leaks from environmental stress on seals/joints, thermal cycling effects, corrosion of fittings, pressure variations from temperature","severity_level":"non-critical","fault_id":"recRH2TyDns7ML8UJ","prompt_id":"recRH2TyDns7ML8UJ_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"d921bc28-74d2-477c-910d-a9e81cdb31c3","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.12","prompt":"CHECK that the appropriate discharge nozzle\n is fitted and is not blocked or damaged.\n All extinguishers types","input":null,"possible_fault":"Discharge nozzle blocked by dust/debris/corrosion/damaged by environmental factors","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.12 - Inappropriate discharge nozzle fitted, blocked, or damaged (Consider dust/debris blockage, corrosion buildup, impact damage)","severity_level":"critical","fault_id":"recsZx9byaUmwMY6V","prompt_id":"recsZx9byaUmwMY6V_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"dfcef886-67f3-4477-99a2-2d30a47ee43b","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"1.3","prompt":"CHECK that the extinguisher is clean and the\n operating instructions are legible.\n All extinguishers types","input":null,"possible_fault":"Extinguisher dirty from dust/salt spray/weather/instructions faded/illegible due to UV/moisture","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.3 - Extinguisher not clean or operating instructions not legible (Consider dust accumulation, salt spray deposits, UV fading, moisture damage)","severity_level":"non-critical","fault_id":"rec5gipuUyK2GfZCW","prompt_id":"rec5gipuUyK2GfZCW_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"f0e50b6e-ec0f-4773-808f-6a1bd1d553d8","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (stored pressure),Foam (gas container),Foam (stored pressure)","variant_id":"recNDWLONf131V1bp","item_no":"2.8","prompt":"RECHARGE the extinguisher with fresh\n extinguishing agent in accordance with the\n manufacturer’s instructions.\n Water with additive (stored pressure), foam\n (gas container), foam (stored pressure)\nUpon the completion of recharging stored\n pressure type extinguishers, perform a leak\n test as per Item 2.10.","input":null,"possible_fault":"Agent contaminated by environmental ingress/degraded by temperature extremes/chemical exposure","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.8 - Agent contaminated by environmental ingress, degraded by temperature extremes/UV exposure, compromised by chemical contamination","severity_level":"critical","fault_id":"rechQOmEpIhKVtop8","prompt_id":"rechQOmEpIhKVtop8_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"fb3ea00f-d148-474c-bba2-6724bfb0b86f","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Wet chemical,Powder (gas container),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recNDWLONf131V1bp","item_no":"3.10","prompt":"At the frequency specified by the extinguishing\n manufacturer, RECHARGE the extinguisher\n with fresh extinguishing agent, as specified on\n the extinguisher label, in accordance with the\n manufacturer’s instructions.\n Wet chemical, foam (gas container with\n sealed foam liquid container), powder (gas\n container), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Agent severely contaminated by environmental ingress/degraded by extreme temperatures/chemical contamination/complete breakdown","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.10 - Agent contaminated by environmental ingress, degraded by temperature extremes/UV exposure, chemically contaminated, performance severely compromised","severity_level":"critical","fault_id":"rec3uT84j4kmfdeMI","prompt_id":"rec3uT84j4kmfdeMI_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"fd8667e3-cf54-4921-a19b-f5c7f40645d4","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (stored pressure),Wet chemical,Powder (stored pressure),Vaporizing liquid","variant_id":"recNDWLONf131V1bp","item_no":"3.5","prompt":"CHECK that the interior of the cylinder is clean,\n is not pitted by corrosion (see AS 2337.1), and\n any internal lining is in good condition.\n Where the lining cannot be removed to inspect\n the interior of the cylinder, the cylinder shall be\n accepted or rejected as per AS 2337.1.\n Water (stored pressure), wet chemical, powder\n (stored pressure), vaporizing liquid.","input":null,"possible_fault":"Severe internal corrosion from environmental ingress/extensive pitting/lining failure/contamination throughout cylinder","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.5 - Internal corrosion accelerated by environmental conditions, extensive pitting from salt/chemical exposure, lining degradation from temperature cycling, contamination from external sources","severity_level":"critical","fault_id":"recVzy6GV1oalZsiF","prompt_id":"recVzy6GV1oalZsiF_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"fd9d248e-093e-4803-b6e1-09e7c09103e2","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.2 YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (stored pressure),Foam (stored pressure)","variant_id":"recNDWLONf131V1bp","item_no":"2.5","prompt":"(a) CHECK that the internal discharge\n tube, strainer and anti-overfill tube\n (where fitted) provide clear passage\n and are securely attached, and that the\n anti-overfill device is undamaged.\n Water with additive (stored pressure),\n foam (stored pressure)","input":null,"possible_fault":"Components corroded/blocked by environmental contamination/damaged by thermal cycling/seals degraded","possible_fault_description":"AS1851 2012 TABLE 10.4.2 ITEM 2.5(a) - Internal components corroded by moisture ingress, blocked by contamination, damaged by thermal expansion/contraction, seals degraded by environmental exposure","severity_level":"non-critical","fault_id":"reczlcqfRefisCcFu","prompt_id":"reczlcqfRefisCcFu_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"1_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"ffb43d2c-0a96-44a0-a6f7-bf82e83a0832","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.3 FIVE-YEARLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Portable Extinguisher Adverse Environment","variant":null,"variant_id":"recNDWLONf131V1bp","item_no":"3.11","prompt":"RENEW all seals and gaskets fitted to the\n actuating device, operating head, or cap.\n All extinguisher types","input":null,"possible_fault":"Seals and gaskets require environmental-resistant specification/frequent replacement due to accelerated degradation","possible_fault_description":"AS1851 2012 TABLE 10.4.3 ITEM 3.11 - Seals and gaskets require upgrade to environmental-resistant materials, more frequent replacement due to accelerated degradation from adverse conditions","severity_level":"recommendation","fault_id":"recVpQTXKYy6Xl92m","prompt_id":"recVpQTXKYy6Xl92m_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"5_year::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"},{"id":"ffd3ea1b-bf71-48bc-9f2d-4f100c98bb0e","standard_code":"au_as_1851_2012","version":"full","category":"Portable And Wheeled Fire Extinguishers","category_id":"recBjw7jZ33SWs7B1","group_header":"TABLE 10.4.1 SIX-MONTHLY SERVICE SCHEDULE FIRE EXTINGUISHERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Portable Extinguisher Adverse Environment","variant":"Water (stored pressure),Wet chemical,Foam (gas container),Foam (stored pressure),Powder (gas container),Powder (stored pressure),Carbon dioxide,Vaporizing liquid","variant_id":"recNDWLONf131V1bp","item_no":"1.17","prompt":"DETERMINE, where possible and without\n discharging any contents, that the actuating\n device is free of corrosion, moves freely and is\n undamaged.\n Water (stored pressure), wet chemical, foam\n (stored pressure), powder (stored pressure),\n carbon dioxide, vaporizing liquid","input":null,"possible_fault":"Device seized by corrosion/dirt/damaged by vibration/temperature cycling","possible_fault_description":"AS1851 2012 TABLE 10.4.1 ITEM 1.17 - Actuating device corroded, doesn't move freely, or damaged (Consider salt spray corrosion, dirt accumulation, vibration damage, thermal cycling effects)","severity_level":"non-critical","fault_id":"recajgavmVpiZzhaX","prompt_id":"recajgavmVpiZzhaX_prompt","inspection_id":"c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1","grouping_key":"6_month::c_recNDWLONf131V1bp_recBjw7jZ33SWs7B1"}]}],"other_checklist_items":[]},{"id":"recgdjZcA59rW2yfM","name":"Fire Hydrant Systems","asset_types":[{"id":"recKv879KGEvHpA2l","name":"Fire Hydrant","checklist":[{"id":"002b5208-f509-4714-bfe6-2572998b3f60","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.4","prompt":"(c) Check cover plate for ease of opening.","input":null,"possible_fault":"Cover plate difficult to open","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.4 - Below ground hydrant cover plate not opening easily","severity_level":"non-critical","fault_id":"recHzlr6AOmxQ3XbK","prompt_id":"recHzlr6AOmxQ3XbK_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"038ab87a-88d5-40e0-8821-7f9b452404fd","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.1","prompt":"COMPLETE all monthly service activities, as\nlisted in Table 4.4.1.","input":null,"possible_fault":"Monthly service activities not completed","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.1 - Monthly service activities not completed","severity_level":"non-conformance","fault_id":"recWrwAKgmc1zpuu2","prompt_id":"recWrwAKgmc1zpuu2_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"03b6ce00-dede-4191-950f-eb2ba06a422e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.7","prompt":"FIT new seatings to all hydrant valves and\nlubricate spindles. (Perishable items only.)\nNOTE: This activity should be completed prior\nto conducting the hydrostatic pressure test.","input":null,"possible_fault":"Valve seating worn","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.7 - Hydrant valve seatings not renewed/lubed","severity_level":"non-critical","fault_id":"reczEobU5zbpPVOVF","prompt_id":"reczEobU5zbpPVOVF_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"05035090-909f-4a41-b890-45dfae0d64ab","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.5","prompt":"(e) For legible labelling indicating maximum\nsystem working pressure.","input":null,"possible_fault":"Maximum pressure labelling not legible","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.5 - Booster maximum pressure labelling not legible","severity_level":"non-critical","fault_id":"recEvUZ90Rb9W70R6","prompt_id":"recEvUZ90Rb9W70R6_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"08345b25-7922-4715-8888-012eccce1efb","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.4","prompt":"(b) Blanking caps, where fitted, are in good\ncondition.","input":null,"possible_fault":"Blanking caps in poor condition","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.4 - Below ground hydrant blanking caps poor condition","severity_level":"non-critical","fault_id":"reclIde4G8QRKj9I9","prompt_id":"reclIde4G8QRKj9I9_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"0a814d40-34ba-4c74-8946-e7bb66d2b118","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.3","prompt":"CHECK all hydrant valves:\n(a) Are accessible.","input":null,"possible_fault":"Hydrant valves not accessible","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.3 - Above ground hydrant valves not accessible","severity_level":"critical","fault_id":"recqDavJnQ4sTaYWi","prompt_id":"recqDavJnQ4sTaYWi_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"0b3f1cba-06fe-4ce1-8fa2-1d8bdf6c625b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.3","prompt":"(c) TEST each valve monitor (where fitted) by\nclosing and re-opening the valve. Verify\ncorrect indication at the CIE.","input":null,"possible_fault":"Monitor not indicating properly","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.3 - Valve monitor fails to indicate at CIE","severity_level":"critical","fault_id":"rec3bOJYlcYdDMWgI","prompt_id":"rec3bOJYlcYdDMWgI_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"2030df6f-66a3-4c44-8e70-4273c98f904b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.5","prompt":"For screw-down style valves, EXAMINE seating\nand fit new washers. For packed gland variants,\nFIT new gland packing.","input":null,"possible_fault":"Washer or gland faulty","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.5 - Valve washers/glands not replaced or worn","severity_level":"non-critical","fault_id":"rec4MfkoWWQMpJQbd","prompt_id":"rec4MfkoWWQMpJQbd_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"27bfbf4a-2e44-46d1-903f-f9a163b6c9dd","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.3","prompt":"(b) VERIFY that the valve position indicators\nare securely mounted and indicate correctly.","input":null,"possible_fault":"Indicator not mounted/correct","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.3 - Valve indicators not secure or indicate incorrectly","severity_level":"non-critical","fault_id":"recLYtqLURDmYxTeO","prompt_id":"recLYtqLURDmYxTeO_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"296addf0-558b-4da5-81ff-65b2aa38b311","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.12","prompt":"CHECK for legibility and appropriate location.","input":null,"possible_fault":"Block plan not legible/appropriately located","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.12 - Block plan not legible or appropriately located","severity_level":"non-conformance","fault_id":"recAZnwiM7egjRmiR","prompt_id":"recAZnwiM7egjRmiR_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"2acb327b-0afb-4dee-92f2-c6d7f362a56c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.4","prompt":"(a) CHANGE all washers on booster assembly\nconnection inlets.","input":null,"possible_fault":"Washers not replaced","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.4 - Booster inlet washers not renewed as required","severity_level":"recommendation","fault_id":"recEi2HDbIaZZphZy","prompt_id":"recEi2HDbIaZZphZy_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"358e367f-e48c-415d-9bd2-a2bd02594c15","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.7.A","prompt":"(b) a portable test apparatus at the most\nhydraulically disadvantaged hydrant\nvalve(s).\nNOTES:\n1 Where the water supply is the sole source of\nwater for both sprinkler and hydrant systems,\nboth sprinkler and hydrant demands should\nbe available simultaneously.\n2 In high-rise buildings where there are\nmultiple pressure zones, a water supply\nproving test should be carried out on the\nmost remote hydrant in each zone.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"reca43sNWwasLV1aC_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"39b0edd2-044d-4591-b7a9-848ab08315b1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.3.B","prompt":"(c) RECORD the pump cut-in pressures and\nverify that they are within the ranges required.","input":null,"possible_fault":"Cut-in pressures outside required range","possible_fault_description":"AS1851 2012 TABLE 4.4.1 ITEM 1.3 - Cut-in pressures not recorded/outside range","severity_level":"non-critical","fault_id":"recmPlwTKgsJRgXYT","prompt_id":"recmPlwTKgsJRgXYT_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"3a9abc34-8661-4cdd-911a-c5de04c8414b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.2","prompt":"CONDUCT a flow test through booster connection\nin accordance with AS 2419.1 or to approved\ndesign Standard.\nNOTE: Conduct the flow test after a satisfactory\n(pass) hydrostatic test.","input":null,"possible_fault":"Flow test fails or not done","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.2 - Booster flow test not done or fails AS2419.1","severity_level":"critical","fault_id":"recdB9TQNSXH1lnAy","prompt_id":"recdB9TQNSXH1lnAy_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"3df462f2-a1db-41df-b53c-d380d88eeef7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.7","prompt":"CHECK that all hydrant and booster connection\npoints are compatible with local brigade\nrequirements.","input":null,"possible_fault":"Connections not compatible with brigade","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.7 - Connections not compatible with local brigade","severity_level":"non-conformance","fault_id":"reclUiksESI4YHGdz","prompt_id":"reclUiksESI4YHGdz_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"3e5ec222-5f73-4e2c-9fca-cc7cb81d2dc9","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.6","prompt":"FIT new gland packing and lubricate spindle.","input":null,"possible_fault":"Gland packing worn","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.6 - Stop valve packing worn or not lubricated","severity_level":"non-critical","fault_id":"rec6Cc7NRUF7k1dXa","prompt_id":"rec6Cc7NRUF7k1dXa_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"3ff70c83-fdb6-4097-95cd-a7ad1a85d961","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.10","prompt":"(b) Following water supply proving test\n(Table 4.4.2 Item 2.6), CLEAN suction inlet\nstrainer(s). Lower raised screen and raise\nand clean ‘in-use’ screen.","input":null,"possible_fault":"Screens not cleaned","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.10 - Screens not cleaned after proving test","severity_level":"non-critical","fault_id":"recyoMRrcm3jv6PHx","prompt_id":"recyoMRrcm3jv6PHx_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"420608aa-59d6-40cc-803b-d800d75b9e30","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.5","prompt":"(c) Pressure gauges and blanking caps, where\nfitted, are in good condition.","input":null,"possible_fault":"Pressure gauges/blanking caps poor condition","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.5 - Booster pressure gauges/blanking caps poor condition","severity_level":"non-critical","fault_id":"recQdALzr46kZMEmD","prompt_id":"recQdALzr46kZMEmD_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"42252d8f-0e28-4582-9e03-d302c77bbf6d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.3","prompt":"(b) Hand-wheels are securely fitted.","input":null,"possible_fault":"Hand-wheels not securely fitted","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.3 - Above ground hydrant hand-wheels not secure","severity_level":"non-critical","fault_id":"recdtW2sBSeKq58If","prompt_id":"recdtW2sBSeKq58If_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"42f7b16d-3882-426c-ade7-40b6c4fc6184","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.7.B","prompt":"CONDUCT a water supply proving test for each\nwater supply verifying that the system flow and\npressure requirements meet the design criteria,\nusing either—\n(a) a fixed flow meter test facility; or\n\nNOTES:\n1 Where the water supply is the sole source of \nwater for both sprinkler and hydrant systems, \nboth sprinkler and hydrant demands should \nbe available simultaneously. \n2 In high-rise buildings where there are \nmultiple pressure zones, a water supply \nproving test should be carried out on the \nmost remote hydrant in each zone","input":null,"possible_fault":"Flow or pressure inadequate","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.7 - Fixed meter test fails flow/pressure criteria","severity_level":"critical","fault_id":"recG2TY5pUfVTqyB5","prompt_id":"recG2TY5pUfVTqyB5_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"4518fa2a-80d4-4c48-84c3-bf1947b355fc","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.8","prompt":"(b) VERIFY that the interface functions as\nrequired.\nNOTE: It is recommended that the\nresponsible entity coordinate testing the\ninterfaced fire protection systems.","input":null,"possible_fault":"Interface not functioning","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.8 - Interfaced systems fail during joint testing","severity_level":"critical","fault_id":"recUXTaaaF75YrsXA","prompt_id":"recUXTaaaF75YrsXA_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"4adfa9e4-c0c0-42b4-8fd5-a2ded10ae0c5","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.2","prompt":"(b) CHECK that pressure switches are securely\nmounted and are protected against the ingress\nof water, dust and insects.","input":null,"possible_fault":"Pressure switches not secure/protected","possible_fault_description":"AS1851 2012 TABLE 4.4.1 ITEM 1.2 - Pressure switches not secure/protected from ingress","severity_level":"non-critical","fault_id":"rec5SYl5tAVdYskvt","prompt_id":"rec5SYl5tAVdYskvt_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"4bf98f87-0873-4d6d-9e69-ee56cfb0007c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.4","prompt":"(d) Not leaking.","input":null,"possible_fault":"Hydrant valves leaking","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.4 - Below ground hydrant valves leaking","severity_level":"non-critical","fault_id":"recQoOTo8AHfUw4ix","prompt_id":"recQoOTo8AHfUw4ix_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"4d41ea2d-2ca4-4470-af12-76a63ed74b94","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.8","prompt":"(a) CONDUCT a functional system test via the\npressure switch or flow switch with other\ninterfaced fire systems.","input":null,"possible_fault":"Interface not triggered","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.8 - Fire system interface not activating via test","severity_level":"non-conformance","fault_id":"recOYLMwbUgauqOG6","prompt_id":"recOYLMwbUgauqOG6_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"4d6bf42d-52fc-4c41-ac37-92c10be82b9b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.9","prompt":"CHECK all pressure gauges against calibrated\ngauge.","input":null,"possible_fault":"Gauge out of calibration","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.9 - Pressure gauge differs from calibrated reference","severity_level":"non-critical","fault_id":"recruUJtUcEo9o7zu","prompt_id":"recruUJtUcEo9o7zu_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"4ec986b1-4acf-4645-bbc8-54e464ef2a8e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.11","prompt":"(a) Pipework—CHECK that exposed water\ndistribution system, including pipework,\npipe supports and valve, appears free from\ncorrosion and damage, not subject to\nexternal loads and pipework is properly\nsupported.","input":null,"possible_fault":"Pipework damaged/corroded","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.11 - Exposed pipework corroded, damaged or stressed","severity_level":"non-critical","fault_id":"recooy9ITcg5VFCgA","prompt_id":"recooy9ITcg5VFCgA_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"527d3561-b787-4e02-b57d-d17465f5d544","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.3","prompt":"(b) RESTART the pumpset using the manual\nstarting device and again run the compression\nignition engine in accordance with Section 3.\nWhere more than one starting device is\ninstalled, including the manual starting\ndevice, the test may be carried out on a\nrotating basis. The period between the\nexercising of each starting device is not to\nexceed 3 months. Where this would require\nthe pump to start more than 5 times in\nsuccession, the period may be extended to\n6 months (see also Table 3.4.3, Items 3.6 and\n3.7).","input":null,"possible_fault":"Manual starting device not operating","possible_fault_description":"AS1851 2012 TABLE 4.4.1 ITEM 1.3 - Manual starting device not operating correctly","severity_level":"critical","fault_id":"rec9GKM2kTTZaRIam","prompt_id":"rec9GKM2kTTZaRIam_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"53f00de2-c240-4dd2-b23d-d275d1f06c7a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.9","prompt":"(c) Foam concentrate containers are in good\ncondition, seals are intact and the labels are\nlegible.\nNOTE: Storage of foam concentrate in\naggressive environments may require testing\nor replacement of the concentrate.","input":null,"possible_fault":"Foam containers/seals/labels poor condition","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.9 - Foam containers/seals/labels poor condition","severity_level":"non-critical","fault_id":"rec8419u6AmhWPsgr","prompt_id":"rec8419u6AmhWPsgr_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"5df9d13b-b10b-48b0-848c-7e54d711011a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.10","prompt":"Perform routine service in accordance with\nSection 5.","input":null,"possible_fault":"Tank not serviced","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.10 - Water supply tank not serviced to Section 5","severity_level":"non-conformance","fault_id":"recfKZdusZaK6Nrg1","prompt_id":"recfKZdusZaK6Nrg1_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"624927f0-59a2-4df3-8a26-4b98f710350c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.7.B","prompt":"(b) a portable test apparatus at the most\nhydraulically disadvantaged hydrant\nvalve(s).\nNOTES:\n1 Where the water supply is the sole source of\nwater for both sprinkler and hydrant systems,\nboth sprinkler and hydrant demands should\nbe available simultaneously.\n2 In high-rise buildings where there are\nmultiple pressure zones, a water supply\nproving test should be carried out on the\nmost remote hydrant in each zone.","input":null,"possible_fault":"Poor flow at remote hydrant","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.7 - Portable test fails at worst-case hydrant","severity_level":"non-critical","fault_id":"recaUQU2siPD5uBvu","prompt_id":"recaUQU2siPD5uBvu_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"62c78d44-d36c-46ee-b66f-629b01d0b79e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.8","prompt":"RENEW water supply non-return valve seatings\nand gaskets.","input":null,"possible_fault":"Seatings or gaskets worn","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.8 - Non-return valve gaskets/seats not renewed","severity_level":"non-critical","fault_id":"recB9mTacSMqd71c7","prompt_id":"recB9mTacSMqd71c7_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"6b0250d0-bf16-48cd-bd74-13ad29b261e1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.11","prompt":"(b) Hydrant obstructions—CHECK for\nobstructions likely to impede hydrant valve\naccess.","input":null,"possible_fault":"Hydrant valve obstructed","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.11 - Hydrant access blocked by objects or structure","severity_level":"critical","fault_id":"reci5OeeAaHd3RSzS","prompt_id":"reci5OeeAaHd3RSzS_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"6c1a204c-090b-474f-aa76-9dbc3963d365","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.11","prompt":"CHECK pressure readings on the low side of\npressure-reducing and pressure-limiting valves for\ndeviations from designed operating pressure.\nNOTE: Gauges or facilities for gauges should\nbe installed immediately upstream and\ndownstream of the valve(s).","input":null,"possible_fault":"Pressure readings deviate from design","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.11 - Pressure readings deviate from design pressure","severity_level":"non-critical","fault_id":"rec2K3GGaPJ3XmzOy","prompt_id":"rec2K3GGaPJ3XmzOy_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"6dec0731-2c20-4f26-9ac6-b26df0954c17","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.2","prompt":"OPERATE (two full turns) all water supply stop\nvalves (including backflow prevention stop valves\nand underground key-operated valves except where\nowned by the water supply authority) and verify\nthey are fully open, secure in the open position\n(relaxed ¼ turn if appropriate) and are correctly\nlabelled.\nNOTES: ‘Text deleted’","input":null,"possible_fault":"Stop valves not operating or not secure","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.2 - Stop valves not operated/secured/labelled correctly","severity_level":"critical","fault_id":"recs7MTBtZE1KzRNO","prompt_id":"recs7MTBtZE1KzRNO_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"758823ad-7c9b-408d-88dd-9007a63270f9","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.1","prompt":"COMPLETE all monthly and six-monthly service\nactivities, as listed in Tables 4.4.1 and 4.4.2.","input":null,"possible_fault":"Required service not completed","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.1 - Routine monthly/six-monthly tests not completed","severity_level":"non-conformance","fault_id":"recLWKt9JtS9g7sEp","prompt_id":"recLWKt9JtS9g7sEp_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"7c76766c-9a88-4a69-a9ed-e9f1e034c7d1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.12","prompt":"(a) Occupancy—CHECK that hydrant design\nremains applicable for current building\narrangement or use.","input":null,"possible_fault":"Design no longer suitable","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.12 - Hydrant design invalid for current occupancy","severity_level":"non-conformance","fault_id":"recnBz1IGcLrv8Aa7","prompt_id":"recnBz1IGcLrv8Aa7_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"7da30e14-9232-4da6-a39f-228543b3607e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.9","prompt":"CHECK:\n(a) Equipment provided in the cabinet is in\naccordance with the cabinet contents list.","input":null,"possible_fault":"Equipment not per contents list","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.9 - Equipment not per cabinet contents list","severity_level":"non-conformance","fault_id":"recb3qWYOkJNI40iH","prompt_id":"recb3qWYOkJNI40iH_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"8430b38e-5e91-473a-8173-8f7e8d2a816d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.3","prompt":"(a) OPERATE (two full turns) all water supply\nvalves—above ground, underground key-\noperated valves (except where owned by the\nwater supply authority) and subsidiary stop\nvalves (e.g., floor isolation valves). Ensure\nthey are fully open and, where applicable,\nsecured in the open position (relaxed ¼ turn\nwhere applicable) and are correctly labelled.\nNOTE: Where underground key-operated\nvalves are owned by the water supply\nauthority, the owner should arrange for the\nwater supply authority to test the valve(s) to\nconfirm the valve(s) is operational and in the\ncorrect position.","input":null,"possible_fault":"Valve not open or labelled","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.3 - Water supply valves not open or labelled correctly","severity_level":"critical","fault_id":"recffb82yPcSKsr2E","prompt_id":"recffb82yPcSKsr2E_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"85663332-4f04-465c-8d4b-c4a1b47c6b0a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.1","prompt":"COMPLETE all monthly, six monthly and yearly\nservice activities, as listed in Tables 4.4.1, 4.4.2\nand 4.4.3.","input":null,"possible_fault":"Routine tests not completed","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.1 - Required routine services not completed","severity_level":"non-conformance","fault_id":"recL1PSUOP2dha5bv","prompt_id":"recL1PSUOP2dha5bv_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"882fb623-e583-4f5d-970c-ba4c5d383bb0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.6","prompt":"(a) OPERATE all pressure-reducing valves and\nverify correct operation under flow\nconditions.","input":null,"possible_fault":"Valve not reducing pressure","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.6 - Pressure-reducing valve not functioning in flow","severity_level":"critical","fault_id":"recuC7pfMEVkUjRtC","prompt_id":"recuC7pfMEVkUjRtC_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"89226c3e-ebdc-499c-b705-13d30cf141bc","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.5","prompt":"VERIFY all branch pipe, nozzles and hose\ncouplings waterways are unobstructed and in\ngood condition.","input":null,"possible_fault":"Obstructed or damaged hose","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.5 - Hydrant hose/nozzles obstructed or damaged","severity_level":"critical","fault_id":"rec06737YXuOvcRTG","prompt_id":"rec06737YXuOvcRTG_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"8df15875-70e4-422d-b1dc-641adff7df23","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.3","prompt":"(a) START each pumpset by reducing the applied\nwater pressure to the pump-starting device\nand run engine, in accordance with Section 3.","input":null,"possible_fault":"Diesel engine not starting by pressure drop","possible_fault_description":"AS1851 2012 TABLE 4.4.1 ITEM 1.3 - Diesel engine not starting by pressure reduction","severity_level":"critical","fault_id":"rec3Ewc1Yx8KveWFj","prompt_id":"rec3Ewc1Yx8KveWFj_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"8fa635d8-cef5-4e7f-ad14-fbf4ddead9a0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.9","prompt":"(b) Equipment items are compatible and in good\ncondition.","input":null,"possible_fault":"Equipment items poor condition/incompatible","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.9 - Equipment items poor condition or incompatible","severity_level":"non-critical","fault_id":"recnhwmfT3QusPord","prompt_id":"recnhwmfT3QusPord_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"9a308d4c-5187-4d72-b4e3-ef4226ac0b65","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.6.B","prompt":"(b) VERIFY that pressure readings on the low\npressure side of the valves are within the\nrange stated at the pressure-reducing valve\nstation.","input":null,"possible_fault":"Pressure outside range","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.6 - Low side pressure not within stated limits","severity_level":"non-critical","fault_id":"recrMCUAPviCO77dn","prompt_id":"recrMCUAPviCO77dn_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"9cef3fe7-a160-493c-b0c7-407ec49b3e45","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.6","prompt":"DEPRESSURIZE the hydrant system(s) at the most\nhydraulically disadvantaged hydrant and CHECK\nthat the pump starts.","input":null,"possible_fault":"Pump not starting from remote hydrant","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.6 - Pump not starting from disadvantaged hydrant","severity_level":"critical","fault_id":"recAiokxsMieBcPnf","prompt_id":"recAiokxsMieBcPnf_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"9e52cad2-5710-46c3-ba1d-f72e28fc30af","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.7.A","prompt":"CONDUCT a water supply proving test for each\nwater supply verifying that the system flow and\npressure requirements meet the design criteria,\nusing either—\n(a) a fixed flow meter test facility; or\n\nNOTES:\n1 Where the water supply is the sole source of \nwater for both sprinkler and hydrant systems, \nboth sprinkler and hydrant demands should \nbe available simultaneously. \n2 In high-rise buildings where there are \nmultiple pressure zones, a water supply \nproving test should be carried out on the \nmost remote hydrant in each zone","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recMSzd5gt0GGejns_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"9e55ded5-4ed4-4360-be29-b4310464a7d2","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.4.A","prompt":"(c) Where more than one starting device is\ninstalled, including the manual starting\ndevice, the test may be carried out on a\nrotating basis. The period between the\nexercising of each starting device is not to\nexceed 3 months. Where this would require\nthe pump to start more than 5 times in\nsuccession, the period may be extended to\n6 months.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recHv4lrgOmtc3wn2_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"9eba1843-e748-47d8-8a6d-86e72c32db4a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.4.B","prompt":"(c) Where more than one starting device is\ninstalled, including the manual starting\ndevice, the test may be carried out on a\nrotating basis. The period between the\nexercising of each starting device is not to\nexceed 3 months. Where this would require\nthe pump to start more than 5 times in\nsuccession, the period may be extended to\n6 months.","input":null,"possible_fault":"Starting devices not tested on rotation","possible_fault_description":"AS1851 2012 TABLE 4.4.1 ITEM 1.4 - Starting devices not tested on rotation basis","severity_level":"non-conformance","fault_id":"rec02YH5Mqz7J8BDe","prompt_id":"rec02YH5Mqz7J8BDe_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"a6086b8c-2d33-4b03-90f4-a78b7e2230db","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.2","prompt":"OPEN partially all hydrant valves in the system\nand prove the presence of water at each point.\nNOTE: To prevent water damage, it is\nrecommended that a suitable adapter to limit\nwater flow be used for this test on internal\nhydrants. Each hydrant in the system should be\nopened separately.","input":null,"possible_fault":"No water from hydrant","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.2 - Hydrant does not deliver water on partial open","severity_level":"critical","fault_id":"recmRgAPzERKWkzyu","prompt_id":"recmRgAPzERKWkzyu_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"a8fe84e6-42ee-4651-8011-4ce31abfc759","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.4","prompt":"(b) LUBRICATE internal non-return spring check\nvalves on a 10-yearly basis.","input":null,"possible_fault":"Valve not lubricated","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.4 - Internal check valves not lubricated (10 yearly)","severity_level":"recommendation","fault_id":"recfUxtvoKhz0Rlko","prompt_id":"recfUxtvoKhz0Rlko_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"addb6394-81bb-48c8-9bce-1e0dc0070ce7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.2","prompt":"(a) CHECK that all isolating valves to pump-\nstarting pressure devices are secured in the\nopen position.","input":null,"possible_fault":"Isolating valves not secured in open","possible_fault_description":"AS1851 2012 TABLE 4.4.1 ITEM 1.2 - Isolating valves to pump-starting devices not open","severity_level":"critical","fault_id":"recCIytrn0vewvHix","prompt_id":"recCIytrn0vewvHix_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"af0ea94a-31da-492e-8ca3-af39b4d34b29","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.9","prompt":"(d) Signage for legibility.","input":null,"possible_fault":"Cabinet signage not legible","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.9 - Cabinet signage not legible","severity_level":"non-conformance","fault_id":"recoQ2bwLwPtks8DS","prompt_id":"recoQ2bwLwPtks8DS_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"b6c4b25f-6b54-403f-b280-167b68f39b61","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.10","prompt":"CHECK that all hydrant and booster cabinets or\nenclosures are accessible, clear of extraneous\nmaterials, clearly and correctly marked and in\ngood condition.","input":null,"possible_fault":"Cabinets not accessible/marked/clear","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.10 - Cabinets not accessible/marked/clear","severity_level":"non-conformance","fault_id":"recj2JfAVaUQtTRXB","prompt_id":"recj2JfAVaUQtTRXB_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"bae6b4d3-46c0-4513-8a52-605cfe29f23c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.5","prompt":"(f) For legibility of hydrant system block plan\nwhere fitted.","input":null,"possible_fault":"Hydrant system block plan not legible","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.5 - Hydrant system block plan not legible","severity_level":"non-conformance","fault_id":"recu35xaW4RW3c1zt","prompt_id":"recu35xaW4RW3c1zt_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"bb502440-6b23-4f70-a520-30b13323fc9c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.3.A","prompt":"(c) RECORD the pump cut-in pressures and\nverify that they are within the ranges required.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recFxx3vIVipnfEAl_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"bcc75596-654c-4c01-89d9-ea3c79903fa5","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.10","prompt":"(a) CHECK suction inlet strainer(s) or screen(s).","input":null,"possible_fault":"Blocked/damaged strainer","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.10 - Inlet strainer blocked or damaged","severity_level":"non-critical","fault_id":"recTVwHZZXYDswtyv","prompt_id":"recTVwHZZXYDswtyv_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"bd35d261-47e5-4fc6-b6eb-10c9b4c3ab09","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.9","prompt":"Perform routine service in accordance with\nSection 5.","input":null,"possible_fault":"Tank not serviced per S5","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.9 - Water tank not maintained to Section 5","severity_level":"non-conformance","fault_id":"recFdxnpgYvlls0Ec","prompt_id":"recFdxnpgYvlls0Ec_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"c4412913-f443-4b09-a9fa-d06d20df6446","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.4","prompt":"(b) RESTART the pumpset using the manual\nstarting device and again run the motor in\naccordance with Section 3.","input":null,"possible_fault":"Manual starting device not operating","possible_fault_description":"AS1851 2012 TABLE 4.4.1 ITEM 1.4 - Manual starting device not operating correctly","severity_level":"critical","fault_id":"reclPlt0dkY8LLl2r","prompt_id":"reclPlt0dkY8LLl2r_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"c5288286-d703-4000-849a-ae71d00a6ac7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.12","prompt":"(b) Site documentation—CHECK that block\nplans, emergency instructions and pressure\nschedules contain the details required in\naccordance with AS 2419.1.","input":null,"possible_fault":"Docs non-compliant AS2419","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.12 - Site docs not compliant with AS2419.1 reqs","severity_level":"non-conformance","fault_id":"recejuX7jOYQh7ztR","prompt_id":"recejuX7jOYQh7ztR_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"d5f3cec3-51fe-4625-8489-57e6fe3f817a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.4","prompt":"VERIFY that all non-return valves are operating\nfreely and are seating correctly.","input":null,"possible_fault":"Valve stuck or not seating","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.4 - Non-return valve not operating or seating","severity_level":"critical","fault_id":"recN0bZT6kbbGigvL","prompt_id":"recN0bZT6kbbGigvL_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"dbfe4f8c-ca91-454f-aead-7f9c5a9356f1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.3","prompt":"(c) Blanking caps, where fitted, are in good\ncondition.","input":null,"possible_fault":"Blanking caps in poor condition","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.3 - Above ground hydrant blanking caps poor condition","severity_level":"non-critical","fault_id":"recJtGClDUzFy9037","prompt_id":"recJtGClDUzFy9037_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"dcedc405-64dc-45d9-a623-1ce98380434b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.4","prompt":"(a) START each pumpset by reducing the applied\nwater pressure to the starting device and run\nmotor in accordance with Section 3.","input":null,"possible_fault":"Electric motor not starting by pressure drop","possible_fault_description":"AS1851 2012 TABLE 4.4.1 ITEM 1.4 - Electric motor not starting by pressure reduction","severity_level":"critical","fault_id":"rec3llzTcqoCwO0T9","prompt_id":"rec3llzTcqoCwO0T9_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"de26b0bf-5930-49ca-8560-92a1a08c8d7d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.6.A","prompt":"(b) VERIFY that pressure readings on the low\npressure side of the valves are within the\nrange stated at the pressure-reducing valve\nstation.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"reclqUNwYUGqX1srw_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"debd0b3d-194f-4630-bf05-b996d82aa039","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.5","prompt":"CHECK all booster assemblies:\n(a) Are accessible.","input":null,"possible_fault":"Booster assemblies not accessible","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.5 - Booster assemblies not accessible","severity_level":"critical","fault_id":"recVK8O8kpbCdBrxl","prompt_id":"recVK8O8kpbCdBrxl_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"e6397286-52c8-42f1-91fd-01395fe5d048","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.4","prompt":"CHECK all hydrant valves:\n(a) Are accessible.","input":null,"possible_fault":"Hydrant valves not accessible","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.4 - Below ground hydrant valves not accessible","severity_level":"non-conformance","fault_id":"recKgVubfNIdhTy1C","prompt_id":"recKgVubfNIdhTy1C_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"ec0e5bb8-22c6-4168-bccb-c48a2c582b31","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.8","prompt":"CHECK all branch pipes, nozzles and hose\ncouplings are in good condition, compatible with\nthe hydrant valves and properly stowed.","input":null,"possible_fault":"Branch pipes/nozzles/hose poor condition","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.8 - Branch pipes/nozzles/hose couplings poor condition","severity_level":"non-critical","fault_id":"recywGTAPPxp8gKAg","prompt_id":"recywGTAPPxp8gKAg_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"f0e085a4-106b-48a5-9176-a44af266f83c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.5","prompt":"(d) For condition of washers on booster\nassembly connection inlets.","input":null,"possible_fault":"Connection inlet washers poor condition","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.5 - Booster assembly connection washers poor condition","severity_level":"non-critical","fault_id":"recnIdSzw6tLrsbvP","prompt_id":"recnIdSzw6tLrsbvP_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"f5b56f3d-a55a-4e3f-8989-52c0f41697df","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.3 YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"3.6","prompt":"(c) OPERATE pressure-relief valve and record\noperating pressure. If necessary, adjust the\nsetting to relieve at 50 kPa above the\noperating pressure of the pressure-reducing\nvalve. Replace the tamper seal if necessary.\nNOTE: The pressure-relief valve test may be\ncarried out using a portable test apparatus.","input":null,"possible_fault":"Relief valve not relieving","possible_fault_description":"AS1851 2012 TABLE 4.4.3 ITEM 3.6 - Relief valve does not open at correct pressure","severity_level":"critical","fault_id":"rec7C6xXmmbUMu8em","prompt_id":"rec7C6xXmmbUMu8em_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"f6da6398-b5af-4b8b-9746-31e20f5b8715","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"2.5","prompt":"(b) Hand-wheels are securely fitted.","input":null,"possible_fault":"Hand-wheels not securely fitted","possible_fault_description":"AS1851 2012 TABLE 4.4.2 ITEM 2.5 - Booster assembly hand-wheels not secure","severity_level":"non-critical","fault_id":"rec9FluTis993Kev5","prompt_id":"rec9FluTis993Kev5_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"6_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"f8f3c4de-896e-4126-98ba-10145b49d441","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"4.3","prompt":"Where a booster is fitted CONDUCT a hydrostatic\npressure test on the entire system at 1.5 times the\nsystem working pressure of the required design\nStandard.","input":null,"possible_fault":"Hydrostatic test fails","possible_fault_description":"AS1851 2012 TABLE 4.4.4 ITEM 4.3 - System fails 1.5× pressure hydrostatic test","severity_level":"critical","fault_id":"recpXZdrHvwRnwsO1","prompt_id":"recpXZdrHvwRnwsO1_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"5_year::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"},{"id":"fc2e54f0-61fa-4fcd-8026-3ea27e637298","standard_code":"au_as_1851_2012","version":"full","category":"Fire Hydrant Systems","category_id":"recgdjZcA59rW2yfM","group_header":"TABLE 4.4.1 MONTHLY SERVICE SCHEDULE FIRE HYDRANT SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Hydrant","variant":null,"variant_id":"recKv879KGEvHpA2l","item_no":"1.1","prompt":"Where pumpsets are fitted complete all pumpset\nmonthly service activities, as listed in Table 3.4.1.","input":null,"possible_fault":"Pumpset monthly service not completed","possible_fault_description":"AS1851 2012 TABLE 4.4.1 ITEM 1.1 - Pumpset monthly service activities not completed","severity_level":"non-conformance","fault_id":"recULhY3uZ6cGBVrB","prompt_id":"recULhY3uZ6cGBVrB_prompt","inspection_id":"c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM","grouping_key":"1_month::c_recKv879KGEvHpA2l_recgdjZcA59rW2yfM"}]}],"other_checklist_items":[]},{"id":"reckaTaCpZtHlVCq7","name":"Fire Pumpsets","asset_types":[{"id":"recer7HJaBbq7yIqD","name":"Fire Pumpset","checklist":[{"id":"01abe297-31de-4110-b02d-c6f0dd7e111a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.17","prompt":"(b) RESTART each pumpset using the manual starting device and run motor continuously for at least 3 minutes.","input":null,"possible_fault":"Manual start device fails","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.17 - Electric motor manual starting device fails","severity_level":"critical","fault_id":"recfPXL2rKCTJHodw","prompt_id":"recfPXL2rKCTJHodw_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"021f1b0b-3691-4fa5-af38-0679ee35cc49","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.7","prompt":"Monitor and engine start batteries. \n (a) CHECK monitor and engine start batteries and enclosures for corrosion, physical damage and secure mounting.","input":null,"possible_fault":"Battery corrosion or insecure mounting","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.7 - Battery/enclosure corroded/damaged/loose mounting","severity_level":"non-critical","fault_id":"recAuVZ3HWo1bMD3A","prompt_id":"recAuVZ3HWo1bMD3A_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"02f655a3-0aa1-44aa-9d26-7c394a556c23","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.A","prompt":"(B) Discharge pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec3BQ8dbLZQcejcB_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"030f1b35-e6ee-4f17-9f33-ae452900466d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.4.B","prompt":"CHECK that all pressure gauges are reading within the ranges required and record pressure.","input":null,"possible_fault":"Pressure readings outside required range","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.4 - Pressure gauges reading outside required ranges","severity_level":"non-critical","fault_id":"rec5QYffS7lekz4Y7","prompt_id":"rec5QYffS7lekz4Y7_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"03bfb319-d897-4096-ab66-3503663453da","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(g) Battery charger or alternator/generator is\n operating at required value within tolerances.","input":null,"possible_fault":"Charger/alternator not at required value","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Battery charger/alternator outside tolerance","severity_level":"non-critical","fault_id":"recW8WuNbxmmA31OD","prompt_id":"recW8WuNbxmmA31OD_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"05af0344-67a4-488b-bc34-3182f1adbb75","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.B","prompt":"During this period RECORD the following for Items (ii), (iii) and (iv) above:\n(A) Suction pressure.","input":null,"possible_fault":"Suction pressures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Electric suction pressures not recorded","severity_level":"non-conformance","fault_id":"rec6QxvtiY3UU8UhD","prompt_id":"rec6QxvtiY3UU8UhD_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"05e89800-28c0-4e4a-b726-485091da96a7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.A","prompt":"(D) Engine oil pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec8o6C6VthXdIFNh_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"06c4d9ad-088a-421a-a078-b1016d8814c8","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(e) FLUSH engine cooling system and refill using manufacturer’s approved corrosion inhibitor (water-cooled engines only).","input":null,"possible_fault":"Cooling system not flushed/refilled","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Cooling system not flushed/corrosion inhibitor","severity_level":"non-critical","fault_id":"recg0Jf14QQnpHSkJ","prompt_id":"recg0Jf14QQnpHSkJ_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"071f7838-3b42-4e80-971d-98ed3f0ebd4f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.A","prompt":"(D) Motor RPM.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recsKEprcCbCsBtXr_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"0afeaf83-2156-43c3-bf41-13159da63484","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.10","prompt":"(a) CHECK enclosure for corrosion and ingress of water, dust or insects.","input":null,"possible_fault":"Enclosure corroded or ingress present","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.10 - Controller enclosure corroded/water/dust/insect ingress","severity_level":"non-critical","fault_id":"recujbDvWI47QjLWZ","prompt_id":"recujbDvWI47QjLWZ_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"0bdefd88-bb38-479d-874d-b240011573a7","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.20","prompt":"After completion of testing procedures, RETURN all equipment to the operational condition.","input":null,"possible_fault":"Equipment not returned to operational","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.20 - Equipment not returned to operational condition","severity_level":"non-conformance","fault_id":"recojxsNLKL69I0TM","prompt_id":"recojxsNLKL69I0TM_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"0d0a7caf-d1f2-4f73-8815-336a50b8d90a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(h) REMOVE and CLEAN or REPLACE heat exchanger strainer(s).","input":null,"possible_fault":"Strainers not cleaned/replaced","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Heat exchanger strainers not cleaned/replaced","severity_level":"recommendation","fault_id":"recMRfukQSwq4UApI","prompt_id":"recMRfukQSwq4UApI_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"0eeeeb05-bc53-416f-b1cd-2d8295834b69","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.18","prompt":"(c) Out-of-balance condition or abnormal noises are not evident.","input":null,"possible_fault":"Out-of-balance or abnormal noises","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.18 - Electric pump out-of-balance/abnormal noises","severity_level":"non-critical","fault_id":"reclNoOtagbKXfkDV","prompt_id":"reclNoOtagbKXfkDV_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"100f45d0-f653-4587-8606-541d563d3bd9","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.B","prompt":"(C) Air temperature at the electric motor.","input":null,"possible_fault":"Motor air temperatures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Motor air temperatures not recorded","severity_level":"non-critical","fault_id":"recg7MNQi7IYsj19l","prompt_id":"recg7MNQi7IYsj19l_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"11df32f3-598b-41e9-97f6-2882aaf69b64","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.A","prompt":"(iii) Reduce the flow to the duty flow (sprinklers, hydrants or combined) for sufficient time to record the water supply proving test results.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recJBLw4iyJXUV2ZN_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"1396912b-89ee-4508-8bb6-d8c7a5e79d52","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.19","prompt":"(c) CHECK battery enclosure for corrosion, and the ingress of water, dust and insects.","input":null,"possible_fault":"Battery enclosure corroded/ingress","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.19 - Controller battery enclosure corroded/ingress present","severity_level":"non-critical","fault_id":"recHkt8UgNI4dtdcN","prompt_id":"recHkt8UgNI4dtdcN_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"15c1ffc5-3559-4b89-892f-dc6edc4dd5ad","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.B","prompt":"(iii) Reduce the flow to the duty flow (sprinklers, hydrants or combined) for sufficient time to record the water supply proving test results.","input":null,"possible_fault":"Fails duty flow test/recording","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Electric fails duty flow proving test","severity_level":"critical","fault_id":"recKGFF3yt94qN4gV","prompt_id":"recKGFF3yt94qN4gV_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"16569457-0fc5-4ed2-9cf7-9a14b715e38f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.9","prompt":"With all electrical equipment isolated from all power supplies:\n(a) INSPECT the condition of all exposed heavy current-carrying contacts. Report any item showing any signs of wear or corrosion.","input":null,"possible_fault":"Contacts showing wear/corrosion","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.9 - Heavy current contacts worn/corroded","severity_level":"non-critical","fault_id":"recN5bHs7NICh3m1f","prompt_id":"recN5bHs7NICh3m1f_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"177d2616-a9e0-496a-a17a-b941b8dfb279","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"2.2","prompt":"In addition to the requirement of Item 1.17 of Table 3.4.1, where alternative power supplies are provided, RUN the pump(s) continuously for not less than 3 minutes off the alternative supply.","input":null,"possible_fault":"Alternative supply fails/insufficient time","possible_fault_description":"AS1851 2012 TABLE 3.4.2 ITEM 2.2 - Alternative power supply fails/run <3min","severity_level":"critical","fault_id":"rec2gIPpWh9tKVsiM","prompt_id":"rec2gIPpWh9tKVsiM_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"6_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"18263c61-b63e-4697-a1d1-e3c36e1f1757","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.11","prompt":"SURVEY the system and equipment to identify external corrosion, and detail extent and location accordingly.","input":null,"possible_fault":"External corrosion not surveyed","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.11 - Pipework corrosion not surveyed/detailed","severity_level":"recommendation","fault_id":"reccT0tRJ5DzcG5Ql","prompt_id":"reccT0tRJ5DzcG5Ql_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"192bbab4-2b2e-4886-adbb-1625a35967d9","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"4.3","prompt":"(c) Engine cooling valve.","input":"YES/NO","possible_fault":"Engine cooling valve not overhauled","possible_fault_description":"AS1851 2012 TABLE 3.4.4 ITEM 4.3 - Engine cooling valve not overhauled per specs","severity_level":"recommendation","fault_id":"rec3inY7DZjIIh5Rt","prompt_id":"rec3inY7DZjIIh5Rt_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"5_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"19a18a07-528b-474b-9656-ab69efe8b411","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.8","prompt":"Where fitted, check engine warming device is working appropriately.","input":null,"possible_fault":"Warming device not working","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.8 - Engine warming device not working appropriately","severity_level":"non-critical","fault_id":"recrgCsp0SL6WZOU1","prompt_id":"recrgCsp0SL6WZOU1_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"1a00d914-f02d-452c-b492-d45e2bc324d1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.A","prompt":"(C) Air temperature at the electric motor.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recvzWtJIaeydxppx_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"1e839047-785a-47c0-8eb4-add9f4491dd0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14.B","prompt":"(k) Engine instrumentation is operating. Record \n the results.","input":null,"possible_fault":"Engine instrumentation not operating","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Engine instrumentation not operating properly","severity_level":"critical","fault_id":"recO0aD322SzLJxet","prompt_id":"recO0aD322SzLJxet_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"1e9880a5-cd67-4431-b526-94a98b8b98ab","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.18","prompt":"(b) Pump glands and drain or mechanical seal(s) operate efficiently.","input":null,"possible_fault":"Pump glands/seals inefficient","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.18 - Electric pump glands/mechanical seals inefficient","severity_level":"non-critical","fault_id":"recswqCQCEU5hSbxA","prompt_id":"recswqCQCEU5hSbxA_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"1ff3afed-96ae-4640-8b2c-eedccfeb077d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.6","prompt":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":"NUMBER/DATE","possible_fault":"Battery discharge test not performed","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.6 - Control battery condition not verified/tested","severity_level":"non-conformance","fault_id":"recNxhBM1PzdoZH75","prompt_id":"recNxhBM1PzdoZH75_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"2061012e-5e93-410a-8636-44648215fb6f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2","prompt":"(vi) While carrying out the above procedures, CHECK temperature of bearings and stuffing box leakage and note and report any abnormality.","input":null,"possible_fault":"Abnormal temperatures/leakage","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Bearing temp/stuffing box abnormal","severity_level":"critical","fault_id":"rec2QCYetO4zvyD7m","prompt_id":"rec2QCYetO4zvyD7m_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"20721396-d0af-4784-b82e-b8272f32db14","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.19","prompt":"(a) CHECK battery complies with details on identification plate fitted to the enclosure.","input":null,"possible_fault":"Battery not compliant with ID plate","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.19 - Controller battery not compliant with ID plate","severity_level":"non-conformance","fault_id":"recCi7a5QwEXCTnBV","prompt_id":"recCi7a5QwEXCTnBV_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"228b06d1-7921-4e72-a0ab-780bea1caba0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.13.B","prompt":"(c) RECORD the starting pressures, test run time and the hour meter reading at completion of the test.","input":null,"possible_fault":"Starting pressures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.13 - Starting pressures/run time/hour meter not recorded","severity_level":"critical","fault_id":"recE98qTv9E8FI3nh","prompt_id":"recE98qTv9E8FI3nh_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"22d34348-f607-4276-b2ce-f86f59876d57","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.5","prompt":"Perform routine service in accordance with Section 5.","input":null,"possible_fault":"Tank service not performed per Section 5","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.5 - Water supply tank routine service incomplete","severity_level":"non-conformance","fault_id":"recJ3DSxav8HH8C9z","prompt_id":"recJ3DSxav8HH8C9z_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"232d899a-4aa0-4878-90f2-8b4adea5df38","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"2.3.B","prompt":"CHECK accumulator air pressure.","input":null,"possible_fault":"Accumulator air pressure incorrect","possible_fault_description":"AS1851 2012 TABLE 3.4.2 ITEM 2.3 - Accumulator air pressure outside limits","severity_level":"non-critical","fault_id":"recQKRj5C4phWOng4","prompt_id":"recQKRj5C4phWOng4_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"6_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"23585e8f-b14e-45d6-a6f0-3172f86564a1","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(i) Belt drives are in good condition.","input":null,"possible_fault":"Belt drives not in good condition","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Belt drives not in good condition","severity_level":"non-critical","fault_id":"recUHOQEmzPeyb0gD","prompt_id":"recUHOQEmzPeyb0gD_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"23975697-1138-4b4f-b3b4-9c3dc5724bfa","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(i) CARRY out any other routine service procedures in accordance with the engine manufacturer’s requirements.","input":null,"possible_fault":"Manufacturer requirements not followed","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Engine manufacturer requirements not met","severity_level":"non-conformance","fault_id":"rec5UpBpi1e87JXSn","prompt_id":"rec5UpBpi1e87JXSn_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"249984ce-9d65-4857-a8fa-4c8f792cbf60","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.B","prompt":"(E) Amps (all three phases). \n NOTE Ensure current does not exceed full load current of the electric motor.","input":null,"possible_fault":"Motor amps exceed full load current","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Motor amps exceed full load/not recorded","severity_level":"non-critical","fault_id":"recQsgA5R788h9Gwo","prompt_id":"recQsgA5R788h9Gwo_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"2a7d7fd5-20a0-4fd6-8ef5-0f6ed6f0122e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(a) REPLACE engine oil with new oil that meets the engine manufacturer’s specification. More frequent oil changes shall be carried out if recommended by the engine manufacturer.","input":null,"possible_fault":"Engine oil not replaced/wrong spec","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Engine oil not replaced/wrong specification","severity_level":"recommendation","fault_id":"recBkvoAwN9P7jQ2b","prompt_id":"recBkvoAwN9P7jQ2b_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"2e82c934-6114-48f0-b89a-1aca5d9cae6f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(f) Water, oil and fuel leaks are not evident and\n fittings on ancillary equipment are secure.","input":null,"possible_fault":"Water/oil/fuel leaks present","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Water/oil/fuel leaks/loose fittings evident","severity_level":"non-critical","fault_id":"recLZHFGnfdIyW8PC","prompt_id":"recLZHFGnfdIyW8PC_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"2ff2d6f1-a589-41af-a1aa-fb9744c1fb83","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"2.3.A","prompt":"CHECK accumulator air pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recxn2sRLUMBnqa7G_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"6_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"30907acb-d408-4d40-b128-dad1c54aef1d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.7.A","prompt":"Test and record battery charger voltage output.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recpT6ehGm86qfy0j_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"322cada7-5187-4a2f-bc2f-18df219ade4d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(b) Pump gland and drain (where applicable)\n operates efficiently.","input":null,"possible_fault":"Pump gland/drain inefficient","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Pump gland/drain not operating efficiently","severity_level":"critical","fault_id":"rec1EZ2KAFpfpvfRL","prompt_id":"rec1EZ2KAFpfpvfRL_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"32c4fe4c-7b8f-432d-a5eb-d0ba4dc0cbd4","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.A","prompt":"(C) Engine running temperature.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec7KgVM5z8nK6joF_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"335795f6-89ce-47af-8672-0cc592bbe428","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(d) INSPECT engine cooling hoses and replace where necessary.","input":null,"possible_fault":"Cooling hoses not inspected/replaced","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Engine cooling hoses not inspected/replaced","severity_level":"recommendation","fault_id":"recZqKaSuel6S7Rc3","prompt_id":"recZqKaSuel6S7Rc3_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"355caee8-6872-417f-bfe7-02135f7010e8","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(j) Battery charger power failure alarm operates\n correctly.","input":null,"possible_fault":"Battery charger failure alarm not working","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Battery charger power failure alarm not operating","severity_level":"non-critical","fault_id":"recJiQIKSQvVrTWAH","prompt_id":"recJiQIKSQvVrTWAH_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"372cc625-fbf1-4a40-9a9f-a7320242e02d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.B","prompt":"(ii) RUN the pumpset at 130% of duty flow (sprinklers, hydrants or combined as applicable) for 10 min and record the result.","input":null,"possible_fault":"Fails 130% duty flow for 10min","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Diesel fails 130% flow test/recording","severity_level":"critical","fault_id":"recb0cu8G9EA22jVO","prompt_id":"recb0cu8G9EA22jVO_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"39e71776-f5be-466a-8f35-51d42018f4cb","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.A","prompt":"During this period RECORD the following for Items (ii), (iii) and (iv) above:\n(A) Suction pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recZV8Goi1VR2FaLn_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"3d17441d-0f8e-46c7-9d2d-eb8dbf65e7bc","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.5.A","prompt":"REPLACE all engine-starting batteries after a maximum of 2 years service, irrespective of condition. Record date of replacement on the new battery and the date the batteries were replaced in the service record.","input":"DATE","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recJXeLJGVByZlGQK_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"3dfaed9c-fcd1-4aa6-897a-2871debd2dcb","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.B","prompt":"(v) During this period RECORD the\n following for actions (ii), (iii) and (iv)\n above:\n (A) Suction pressures.","input":null,"possible_fault":"Suction pressures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Diesel suction pressures not recorded","severity_level":"non-conformance","fault_id":"rec2kt1f8X9GNSnDr","prompt_id":"rec2kt1f8X9GNSnDr_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"404832d6-90da-41b1-a2c1-8313e962387e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.5.A","prompt":"REPLACE all engine-starting batteries after a maximum of 2 years service, irrespective of condition. Record date of replacement on the new battery and the date the batteries were replaced in the service record.","input":null,"possible_fault":"Batteries not replaced after 2 years","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.5 - Engine batteries not replaced/dates recorded","severity_level":"recommendation","fault_id":"rec3MZIOk64YqlmdU","prompt_id":"rec3MZIOk64YqlmdU_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"44a34da4-9083-4462-8f8b-2a06020baf79","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.12","prompt":"(c) Where compression ignition engine driven pumpsets are installed, CHECK that water, oil, belt drives and exhaust condensate drains and cooling water valves are in the correct position. Check fuel water-trap/filter for water contamination. Rectify where required.","input":null,"possible_fault":"Water/oil/valves in incorrect position","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.12 - Water/oil/belt/exhaust/cooling valves incorrect position","severity_level":"critical","fault_id":"recVVDYTxgppRq2BL","prompt_id":"recVVDYTxgppRq2BL_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"461a2d90-3afb-4a21-b0dc-a5f86380c753","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.B","prompt":"(B) Discharge pressure.","input":null,"possible_fault":"Discharge pressures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Electric discharge pressures not recorded","severity_level":"non-conformance","fault_id":"recPK2a56UzyPpB9h","prompt_id":"recPK2a56UzyPpB9h_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"495bc1bc-abc9-4716-9748-53532c2bb110","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2","prompt":"(iv) Further reduce the flow until shut-off (zero flow) is achieved and continue to run the pumpset until total run time has reached 30 min.","input":null,"possible_fault":"Fails to complete 30min total run","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Diesel fails 30min total run time","severity_level":"critical","fault_id":"recIYknwvrY9IY04L","prompt_id":"recIYknwvrY9IY04L_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"4beb16a0-064c-4717-aa19-705f0baa0203","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.9","prompt":"CHECK that the fuel tank is full.","input":null,"possible_fault":"Fuel tank not full","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.9 - Fuel tank not full","severity_level":"non-critical","fault_id":"reclk5P6kZKr83Wsx","prompt_id":"reclk5P6kZKr83Wsx_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"4db9fb0a-d55d-4b14-a6a5-47c8c9764a58","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.15","prompt":"(b) CHECK enclosure for corrosion and ingress of water, dust or insects.","input":null,"possible_fault":"Enclosure corroded or ingress present","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.15 - Electric motor enclosure corroded/ingress present","severity_level":"non-conformance","fault_id":"reckNpzGjCenJ1FcF","prompt_id":"reckNpzGjCenJ1FcF_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"4ef9c627-8783-46e6-b8f6-16886c6819e6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.13.A","prompt":"(c) RECORD the starting pressures, test run time and the hour meter reading at completion of the test.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recEPiN6s7e5AjK6M_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"4fbcd1a0-127f-403c-b8d1-31438ecfc2a6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"4.3","prompt":"(b) Pressure-relief valves.","input":"YES/NO","possible_fault":"Pressure-relief valve not overhauled","possible_fault_description":"AS1851 2012 TABLE 3.4.4 ITEM 4.3 - Pressure-relief valve not overhauled per specs","severity_level":"recommendation","fault_id":"rec8DAMy55riDiDH1","prompt_id":"rec8DAMy55riDiDH1_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"5_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"5087e79e-6920-4731-90f7-4dec81ccb71b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(g) CHECK correct operation of the engine cooling system pressure-reducing valves, where fitted.","input":null,"possible_fault":"Pressure-reducing valves not checked","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Cooling pressure valves not checked","severity_level":"recommendation","fault_id":"recDhlT1ah7hYwDUo","prompt_id":"recDhlT1ah7hYwDUo_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"52ae4ffa-1edc-4b8f-a1a6-03bb77b30495","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.7.B","prompt":"(c) TEST the float charge voltage of both the monitor and engine start batteries and record result.","input":null,"possible_fault":"Float charge voltage outside limits","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.7 - Monitor/engine battery float charge voltage incorrect","severity_level":"non-critical","fault_id":"recNH11TZFncqTOel","prompt_id":"recNH11TZFncqTOel_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"53054c09-e253-4436-a913-d80e0fef837b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.17","prompt":"(c) RECORD the starting pressures and the run time at the completion of the test.","input":null,"possible_fault":"Starting pressures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.17 - Electric motor starting pressures/run time not recorded","severity_level":"non-conformance","fault_id":"reccKiytDPsp4CzqY","prompt_id":"reccKiytDPsp4CzqY_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"548b758e-8dfe-4e4a-b1ea-2d150244aec0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.9","prompt":"(d) Where the pump bearings are of the oil-lubricated type, REPLACE the bearing oil with new oil that meets the pump manufacturer’s specification (does not apply to turbine type vertical shaft centrifugal pumps).","input":null,"possible_fault":"Pump bearing oil not replaced","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.9 - Electric pump bearing oil not replaced","severity_level":"recommendation","fault_id":"recU9uSrhBR8YgRi8","prompt_id":"recU9uSrhBR8YgRi8_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"54c11f33-3d8c-4318-8893-d7501c1ff856","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.13","prompt":"(b) RESTART the pumpset using the manual starting device.","input":null,"possible_fault":"Manual starting device fails","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.13 - Manual starting device fails to operate","severity_level":"critical","fault_id":"recZ6aCZeCP86HdJI","prompt_id":"recZ6aCZeCP86HdJI_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"55658403-d245-44f6-bb44-cc8e65037082","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(b) REPLACE engine oil filter and fuel filters and, if required, air filters.","input":null,"possible_fault":"Oil/fuel/air filters not replaced","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Engine oil/fuel/air filters not replaced","severity_level":"non-critical","fault_id":"recPfHh6kss8ADcXg","prompt_id":"recPfHh6kss8ADcXg_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"57a70285-4c7d-4267-8ddf-f9bae2f379b0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.7.A","prompt":"(c) TEST the float charge voltage of both the monitor and engine start batteries and record result.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recIJ41wg4n5XXQCH_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"57d54b7b-a90a-4562-ab12-112c6403631a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.6","prompt":"CHECK for obvious signs of physical damage or deterioration.","input":null,"possible_fault":"Physical damage or deterioration found","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.6 - Obvious signs of physical damage/deterioration","severity_level":"non-critical","fault_id":"recMmy0HCvDwLodXo","prompt_id":"recMmy0HCvDwLodXo_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"5a5ed64b-e00b-419c-8bab-5ae12ec487ff","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.A","prompt":"(E) Amps (all three phases). \n NOTE Ensure current does not exceed full load current of the electric motor.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recvkWYNwJqCrY8jc_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"5b11db70-cd48-452c-a8d9-c0afe08c50f9","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.B","prompt":"(D) Engine oil pressure.","input":null,"possible_fault":"Oil pressures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Diesel engine oil pressures not recorded","severity_level":"non-conformance","fault_id":"recUjhsY3iYA8IAVm","prompt_id":"recUjhsY3iYA8IAVm_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"5ba8317d-85c0-4d83-9c06-994d389f8075","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.B","prompt":"(iv) Further reduce the flow until shut-off (zero flow) is achieved and continue to run the pumpset until total run time has reached 10 min.","input":null,"possible_fault":"Fails to complete 10min total run","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Electric fails 10min total run time","severity_level":"non-critical","fault_id":"recKiiNLphq3HRAJB","prompt_id":"recKiiNLphq3HRAJB_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"5c13dafd-71ce-49aa-95f4-6b6157276ff3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.18.A","prompt":"(a) Pump operates at the correct discharge pressures allowing for varying suction conditions. Record suction and discharge pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec1g748Fuk33x9Qu_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"5de2984d-5721-47c4-8320-ef5ac921bd21","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.14","prompt":"Operate engine overspeed test switch. Ensure the engine shuts down and engine, overspeed light illuminates on the controller.","input":null,"possible_fault":"Overspeed device/alarms not working","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.14 - Overspeed shutdown/light not operating","severity_level":"critical","fault_id":"recpvDApqzd53EwzS","prompt_id":"recpvDApqzd53EwzS_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"5f3f955b-2219-4fb5-a35c-39eea3f7ee22","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.12.B","prompt":"CHECK that the system pressure relief valve opens and closes at the pressure required. \n NOTE: Inappropriate settings for pressure-relief valves can result in very large quantities of water flowing to waste. Ensure settings are maintained to have pressures as identified and not higher than allowed by system component rated working pressures.","input":null,"possible_fault":"Relief valve not opening/closing correct","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.12 - Pressure relief valve not opening/closing","severity_level":"non-critical","fault_id":"recpUHvKRZpnYMYuF","prompt_id":"recpUHvKRZpnYMYuF_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"61ba49cb-d14a-4e28-b83d-9afccf1f6d9f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.12","prompt":"Prior to commencing any test function:⏎(a) CHECK all safety guards are in place and secure","input":null,"possible_fault":"Safety guards missing or insecure","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.12 - Safety guards not in place/secure","severity_level":"non-critical","fault_id":"recezi8J4lhG2kPz2","prompt_id":"recezi8J4lhG2kPz2_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"62f8cd0f-825b-4435-a92b-bf054b1f7874","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(c) Out-of-balance condition or abnormal noises\n are not evident.","input":null,"possible_fault":"Out-of-balance or abnormal noises","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Out-of-balance condition/abnormal noises present","severity_level":"non-critical","fault_id":"reccLM6PmuxllSGhi","prompt_id":"reccLM6PmuxllSGhi_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"63012e07-9359-4fa1-b91c-95b4b5f6e8b0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.2","prompt":"(a) CHECK pumpset warning sign “Danger this Pump Starts Automatically”.","input":null,"possible_fault":"Missing automatic start warning sign","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.2 - \"Danger Pump Starts Automatically\" sign missing","severity_level":"non-conformance","fault_id":"rec2a7C0gFwQnugTP","prompt_id":"rec2a7C0gFwQnugTP_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"641d6d3c-9589-464b-ae53-deba575602c0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(l) Flow is evident from the circulation relief\n valve when the pump is operating at shut-off\n head and ceases at the appropriate pressure.","input":null,"possible_fault":"Relief valve flow incorrect","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Circulation relief valve flow not evident/ceasing correctly","severity_level":"critical","fault_id":"rec5x5joTxyZPKfRa","prompt_id":"rec5x5joTxyZPKfRa_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"64239ae5-dbf4-43c1-8afd-149f786e500a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.A","prompt":"(B) Discharge pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recGqUXFedNhDkpRJ_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"643a52a0-5c57-4352-9417-5efdefe64c27","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.17.B","prompt":"(c) RECORD the starting pressures and the run time at the completion of the test.","input":null,"possible_fault":"Starting pressures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.17 - Electric motor starting pressures/run time not recorded","severity_level":"critical","fault_id":"recV2fXPRGno8ODTp","prompt_id":"recV2fXPRGno8ODTp_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"64595bf6-ae93-4f47-b169-7c4423e08793","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.A","prompt":"(F) Engine RPM, using both installed tachometer and calibrated tachometer. Record variations.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recOnApE5bgQ9Sa9P_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"661a733c-53b3-43b8-a28f-5fc6feb8a71d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.2 SIX-MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"2.1","prompt":"Complete all monthly service activities, as listed in Table 3.4.1.","input":null,"possible_fault":"Monthly service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 3.4.2 ITEM 2.1 - Monthly service activities not completed","severity_level":"non-conformance","fault_id":"recKtF3qZU0pyFjkJ","prompt_id":"recKtF3qZU0pyFjkJ_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"6_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"67017542-51e1-46e2-a722-0d10d41cc28d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.1","prompt":"Complete all monthly and six-monthly service activities as listed in Tables 3.4.1 and 3.4.2.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.1 - Monthly/six-monthly service incomplete","severity_level":"non-conformance","fault_id":"recRm4DrzPxMxWtI6","prompt_id":"recRm4DrzPxMxWtI6_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"6ea9bfbb-b81c-4812-a367-61084aceb31b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.10","prompt":"(b) CHECK operation of all visual indicators, switches and sounders.","input":null,"possible_fault":"Visual indicators/switches not working","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.10 - Visual indicators/switches/sounders not operating","severity_level":"non-critical","fault_id":"rechJFdJGVo0Oe1tm","prompt_id":"rechJFdJGVo0Oe1tm_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"6f314624-bc43-449f-a290-26e6670ae784","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.18.B","prompt":"(a) Pump operates at the correct discharge pressures allowing for varying suction conditions. Record suction and discharge pressure.","input":null,"possible_fault":"Incorrect discharge pressure","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.18 - Electric pump not at correct discharge pressure","severity_level":"critical","fault_id":"reczpv2qLGLnyvUsB","prompt_id":"reczpv2qLGLnyvUsB_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"75a694f9-c523-47d2-8cd8-ab141db28963","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(d) All local and remote ‘pump running’ alarms\n operate.","input":null,"possible_fault":"Local/remote alarms not operating","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Local/remote pump running alarms not operating","severity_level":"critical","fault_id":"recdp9ScIj1e9valJ","prompt_id":"recdp9ScIj1e9valJ_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"762ededc-de3e-4dfb-a3a0-34e95fa258d3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.A","prompt":"(ii) RUN the pumpset at 130% of duty flow (sprinklers, hydrants or combined as applicable) for 10 min and record the result.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recWqlEvVjGAst21C_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"7638bcfa-b06f-42df-bcc5-f9a5bb3b75ac","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(m) Exhaust system is leak free.","input":null,"possible_fault":"Exhaust system has leaks","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Exhaust system not leak free","severity_level":"non-critical","fault_id":"rec5gpmboMLP0BN0U","prompt_id":"rec5gpmboMLP0BN0U_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"76ccbc84-e34b-4dd7-9192-e86e57438e26","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.4","prompt":"(a) CHECK each battery for any condition likely to indicate an adverse effect on its function.","input":null,"possible_fault":"Battery condition adverse/defective","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.4 - Battery condition adverse/function affected","severity_level":"non-critical","fault_id":"recytcbBE3w2eHnjv","prompt_id":"recytcbBE3w2eHnjv_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"77ba464e-1a34-419e-9e53-3e74bcfa9f2a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(k) GREASE jump bearings to the manufacturer’s specifications where greased nipples are provided.","input":null,"possible_fault":"Pump bearings not greased per spec","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Pump bearings not greased to specification","severity_level":"recommendation","fault_id":"rec6zv0Mk96viqJmQ","prompt_id":"rec6zv0Mk96viqJmQ_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"7b31671f-6f5b-4de1-a7fa-3a66524e3a68","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.16","prompt":"Operate the pump start/stop functions from the remote location, and ensure the appropriate indications are received at the FIP/remote stop/start panel.","input":null,"possible_fault":"Remote functions/indications not working","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.16 - Remote start/stop/indications not working","severity_level":"non-critical","fault_id":"recscayo55GbHqpLw","prompt_id":"recscayo55GbHqpLw_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"7b9bcad8-aebb-4193-aafc-d4ba0510a353","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.A","prompt":"(iii) Reduce the flow to the duty flow (sprinklers, hydrants or combined) for sufficient time to record the water supply proving test results.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rect8ztnBFoKrNnuI_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"7f67415f-cc83-4d04-b938-64e3f3f4031b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.B","prompt":"(C) Engine running temperature.","input":null,"possible_fault":"Engine temperatures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Diesel engine temperatures not recorded","severity_level":"non-conformance","fault_id":"recIn2rVbRD3eYm8n","prompt_id":"recIn2rVbRD3eYm8n_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"7f82a48e-1473-4551-a62d-2272ab4d6825","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14.B","prompt":"During and after the running period CHECK:\n (a) Pump operates at the correct discharge pressure. Record suction and discharge pressure.\n NOTE: The discharge pressures may vary with varied suction static pressure. An excessive negative suction pressure may indicate a suction partial blockage or partially closed valve.","input":null,"possible_fault":"Incorrect discharge pressure","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Pump not operating at correct discharge pressure","severity_level":"non-conformance","fault_id":"rec10Me9IQIwQ7BRN","prompt_id":"rec10Me9IQIwQ7BRN_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"82260e3b-cf58-4046-ac8b-0fe631366702","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3","prompt":"(b) TEST correct operation of pump priming tanks and associated equipment, were fitted.","input":null,"possible_fault":"Priming tanks not operating correctly","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Electric priming tanks not operating","severity_level":"critical","fault_id":"rec8G22BB0aIYsQNy","prompt_id":"rec8G22BB0aIYsQNy_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"83d482be-d302-4a25-94b3-d4782ad3c8f2","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"4.3","prompt":"OVERHAUL the following valves in accordance with supplier’s specifications:\n(a) Circulation-relief valves.","input":"YES/NO","possible_fault":"Circulation-relief valve not overhauled","possible_fault_description":"AS1851 2012 TABLE 3.4.4 ITEM 4.3 - Circulation-relief valve not overhauled per specs","severity_level":"recommendation","fault_id":"recOx9NgWnvN5oCmH","prompt_id":"recOx9NgWnvN5oCmH_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"5_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"879753d6-647f-4d67-b5fb-690f802d97ba","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(f) PRESSURE TEST engine cooling system in accordance with the manufacturer’s recommendations (radiator and heat exchanger cooled engines only).","input":null,"possible_fault":"Cooling system not pressure tested","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Cooling system not pressure tested","severity_level":"non-conformance","fault_id":"recoPAbxk8ZUqF38L","prompt_id":"recoPAbxk8ZUqF38L_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"87c6e878-c8df-41d0-abd3-7fc60e938824","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.19.B","prompt":"(d) CHECK float voltage of the battery and record.","input":null,"possible_fault":"Battery float voltage incorrect","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.19 - Controller battery float voltage outside limits","severity_level":"non-critical","fault_id":"recLkviR8Der9WCL3","prompt_id":"recLkviR8Der9WCL3_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"87e2249a-039d-4114-bac6-16f745231b93","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(j) INSPECT pump/driver coupling for wear and alignment. Replace worn or damaged components.","input":null,"possible_fault":"Pump/driver coupling not inspected","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Pump/driver coupling not inspected/replaced","severity_level":"non-critical","fault_id":"recvKlK1vw4P8gNZ5","prompt_id":"recvKlK1vw4P8gNZ5_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"88945ec4-83cb-4c49-ab12-b2a4d86f3b8c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.15","prompt":"(a) CHECK all safety guards are in place and secure.","input":null,"possible_fault":"Safety guards missing or insecure","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.15 - Electric motor safety guards not in place/secure","severity_level":"non-critical","fault_id":"recfm5Qrm7spd4rsQ","prompt_id":"recfm5Qrm7spd4rsQ_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"894140dc-3562-4b68-9940-58d38698e60f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.A","prompt":"(E) Air temperature at the engine intake manifold. \n NOTE: If the pump room temperature rises more than 10°C above ambient temperature, this could indicate inadequate ventilation and possible reduction in engine power.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"reccR4o77Pyg9yX6O_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"8c51ec4e-6eb8-4fa5-91d2-03ca70174138","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(c) CHECK the condition of the fuel. NOTE: Visually check a sample of the fuel for foreign particles, contamination, fungal growth, appropriate smell and colour, etc. If suspect, report, replace or send the sample to an independent testing agent.","input":null,"possible_fault":"Fuel condition not checked/contaminated","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Fuel condition not checked/contaminated","severity_level":"non-critical","fault_id":"recuXSEphjHgwvDfe","prompt_id":"recuXSEphjHgwvDfe_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"8ede2487-480b-4db0-aea6-533fab6853be","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.12.A","prompt":"CHECK that the system pressure relief valve opens and closes at the pressure required. \n NOTE: Inappropriate settings for pressure-relief valves can result in very large quantities of water flowing to waste. Ensure settings are maintained to have pressures as identified and not higher than allowed by system component rated working pressures.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recBBlHEJ8MWA0KE7_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"8f7a198c-1043-447d-bfa4-df8639add54e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.12","prompt":"(b) CHECK the water supply availability—town main pressure adequate or suction tank is full.","input":null,"possible_fault":"Inadequate town main/empty suction tank","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.12 - Town main pressure low/suction tank not full","severity_level":"non-critical","fault_id":"recce5sAY36mCgVwc","prompt_id":"recce5sAY36mCgVwc_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"940098c5-ba5a-4748-ab0e-b9d481ffe964","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.4","prompt":"(b) Where batteries are replaced they shall comply with batteries manufactured in accordance with AS 4029 (series).","input":null,"possible_fault":"Replacement batteries non-compliant","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.4 - Replacement batteries not AS4029 compliant","severity_level":"non-conformance","fault_id":"recvz5leFeCHB5Zlj","prompt_id":"recvz5leFeCHB5Zlj_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"95471aa6-0c46-4305-b270-8b77d74f9545","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.17.A","prompt":"(c) RECORD the starting pressures and the run time at the completion of the test.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recVEzShm0phdMHGs_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"95bc54e2-974e-472b-a20c-b4f32ed31c19","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.B","prompt":"(ii) RUN the pumpset at 130% of duty flow (sprinklers, hydrants or combined as applicable) for 4 min and record the result.","input":null,"possible_fault":"Fails 130% duty flow for 4min","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Electric fails 130% flow test/recording","severity_level":"critical","fault_id":"recyVaRI6CqjG0Yqf","prompt_id":"recyVaRI6CqjG0Yqf_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"996f4ac1-c56e-4e98-bc6d-b5cd595a18a2","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.A","prompt":"(iv) Further reduce the flow until shut-off (zero flow) is achieved and continue to run the pumpset until total run time has reached 10 min.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recQDtOtz7EVTyzN0_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"9c383401-829a-4bec-95e5-fb698e692a93","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.4.A","prompt":"CHECK that all pressure gauges are reading within the ranges required and record pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recXP83dNLRJ9z8Hw_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"9cd5049e-7cab-420c-81b3-3a335dada8df","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.13","prompt":"(a) START each pumpset by reducing the applied water pressure to the starting device and for compression ignition engines run engine continuously for not less than 10 min on the first automatic start and check that the driver achieves full speed within 15 s of starting.","input":null,"possible_fault":"Engine fails to start or reach speed","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.13 - Engine fails start/achieve full speed within 15s","severity_level":"non-critical","fault_id":"recATER3BmNLogbOW","prompt_id":"recATER3BmNLogbOW_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"a0ed0f99-389c-4596-97d2-e0d9296af3dc","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"4.5","prompt":"Replace engine air filters. \n NOTE: The air filter should be marked with install date.","input":"YES/NO","possible_fault":"Engine air filters not replaced","possible_fault_description":"AS1851 2012 TABLE 3.4.4 ITEM 4.5 - Engine air filters not replaced/not marked with date","severity_level":"recommendation","fault_id":"recSwLHIO8eUeY2Wx","prompt_id":"recSwLHIO8eUeY2Wx_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"5_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"a0fef97f-44e2-4a07-afb8-c1701b2b5f3f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"4.2","prompt":"REPACK pump glands.","input":"YES/NO","possible_fault":"Pump glands not repacked","possible_fault_description":"AS1851 2012 TABLE 3.4.4 ITEM 4.2 - Pump glands not repacked as required","severity_level":"recommendation","fault_id":"receNq4w78yqpEecY","prompt_id":"receNq4w78yqpEecY_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"5_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"a3a6bc44-938a-4c3c-84bf-090f6da52f2c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.7","prompt":"(e) CHECK warning signage and rating (battery capacity)signage (where required).","input":null,"possible_fault":"Warning/rating signage missing","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.7 - Battery warning/capacity signage missing/unclear","severity_level":"non-conformance","fault_id":"recVfVC8sdtErLwpO","prompt_id":"recVfVC8sdtErLwpO_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"a6df6659-0622-41a6-985c-876c864d0578","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"4.1","prompt":"COMPLETE all monthly, six-monthly and yearly activities, as listed in Tables 3.4.1, 3.4.2 and 3.4.3.","input":"YES/NO","possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 3.4.4 ITEM 4.1 - Monthly/six-monthly/yearly activities not completed","severity_level":"non-conformance","fault_id":"rec5E0cubNwHC5A9p","prompt_id":"rec5E0cubNwHC5A9p_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"5_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"a6eaa03e-2c39-4aab-9873-05ecea48cbfa","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14.A","prompt":"During and after the running period CHECK:\n (a) Pump operates at the correct discharge pressure. Record suction and discharge pressure.\n NOTE: The discharge pressures may vary with varied suction static pressure. An excessive negative suction pressure may indicate a suction partial blockage or partially closed valve.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recLoj8O9Ytixfvzx_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"a7fe2e6f-e885-4ed7-94b4-2c76c9e011d3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.7","prompt":"(f) CHECK battery capacity or cold cranking amperage is appropriate.","input":null,"possible_fault":"Battery capacity inappropriate","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.7 - Battery capacity/cold cranking amperage inappropriate","severity_level":"non-critical","fault_id":"recgpsWTNowirz2YS","prompt_id":"recgpsWTNowirz2YS_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"a82c3768-402d-414b-a00c-eccbe506f035","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.1","prompt":"(a) CHECK that pump areas are unobstructed, not used for storage and lighting is adequate.","input":null,"possible_fault":"Areas obstructed or inadequate lighting","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.1 - Pump areas obstructed/used for storage/poor lighting","severity_level":"non-critical","fault_id":"rectwA1Q59wxeJs24","prompt_id":"rectwA1Q59wxeJs24_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"ab2925b7-c4cb-4519-9d1a-15df064c25d4","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(h) Engine stop mechanism returns to start\n position automatically.","input":null,"possible_fault":"Stop mechanism not returning to start","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Engine stop mechanism not returning to start position","severity_level":"non-critical","fault_id":"recL5QQjHVPaQRSs7","prompt_id":"recL5QQjHVPaQRSs7_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"aecaea88-0370-4dc8-b5ce-766a43ed9055","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.7","prompt":"(d) CHECK electrolyte levels and top up with distilled water as necessary.","input":null,"possible_fault":"Electrolyte levels low","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.7 - Battery electrolyte levels require topping up","severity_level":"non-critical","fault_id":"rec3UaXMniTTJC4si","prompt_id":"rec3UaXMniTTJC4si_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"afd59020-b63b-438e-bdfb-00d951245dce","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.2","prompt":"(c) CHECK each pump controller is labelled ‘Fire Pump Controller’, has clear operating instructions posted, has all operating components clearly identified, and has all indicating lights clearly labelled.","input":null,"possible_fault":"Controller not properly labeled","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.2 - Fire pump controller lacks proper labeling/instructions","severity_level":"non-critical","fault_id":"recVCwNIzltNBfjKI","prompt_id":"recVCwNIzltNBfjKI_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"affaba06-7090-4105-936a-4088b2555608","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.B","prompt":"(D) Motor RPM.","input":null,"possible_fault":"Motor RPM not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Motor RPM not recorded","severity_level":"non-conformance","fault_id":"rec9OT6ihQZSBdL2a","prompt_id":"rec9OT6ihQZSBdL2a_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"b03f38cd-c11a-497a-a53f-51bfb9b75967","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(n) Cooling water (heat exchanger cooled\n engines only) is discharging.","input":null,"possible_fault":"Cooling water not discharging","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Cooling water not discharging (heat exchanger engines)","severity_level":"non-critical","fault_id":"recmrpDGzSG9GnUsB","prompt_id":"recmrpDGzSG9GnUsB_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"b3e512eb-7e79-4e02-b5a4-e77a8059f87c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.19.A","prompt":"(d) CHECK float voltage of the battery and record.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec1gwY2xm1sk4HHi_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"b6c5f7c6-750f-4646-a05b-b2ded768577f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3.A","prompt":"(ii) RUN the pumpset at 130% of duty flow (sprinklers, hydrants or combined as applicable) for 4 min and record the result.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recQhZJ6EeQTrdVMi_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"b8dda60c-25f0-4f94-9e72-643cbfe0c51f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.B","prompt":"(E) Air temperature at the engine intake manifold. \n NOTE: If the pump room temperature rises more than 10°C above ambient temperature, this could indicate inadequate ventilation and possible reduction in engine power.","input":null,"possible_fault":"Air temperatures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Air intake temperatures not recorded","severity_level":"non-critical","fault_id":"recZIIrVUBhmdHyKD","prompt_id":"recZIIrVUBhmdHyKD_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"ba4c721b-e25b-45db-8e91-5ce423ca3587","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.18","prompt":"(d) Both local and remote ‘pump running’ alarms and lights operate.","input":null,"possible_fault":"Local/remote alarms not operating","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.18 - Electric pump running alarms/lights not operating","severity_level":"critical","fault_id":"recbwrSazYAD8Pwnq","prompt_id":"recbwrSazYAD8Pwnq_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"bc702ee3-b660-4eac-9671-409208effe30","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.15","prompt":"Operate the pump at 50% of duty flow and 100% of duty flow, and ensure duty head is not exceeded by more than 10%.","input":null,"possible_fault":"Speed control exceeds 10% duty head","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.15 - Variable speed exceeds 10% duty head limit","severity_level":"non-critical","fault_id":"recL40X5gXJoq1DZJ","prompt_id":"recL40X5gXJoq1DZJ_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"bde129fc-2a7b-41a1-be32-2ca92b444de4","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.17","prompt":"(a) START each pumpset by reducing the applied water pressure to the starting device and run motor continuously for at least 3 minutes.","input":null,"possible_fault":"Motor fails to start/run 3 minutes","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.17 - Electric motor fails start/run continuously 3 min","severity_level":"non-critical","fault_id":"recOfwmrrN1M2MNSN","prompt_id":"recOfwmrrN1M2MNSN_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"c311bd19-3270-4dfc-90ca-176612584ac4","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"4.4","prompt":"(b) For ball and butterfly valves, CHECK for leakage and replace if necessary.","input":"YES/NO","possible_fault":"Ball/butterfly valves leaking","possible_fault_description":"AS1851 2012 TABLE 3.4.4 ITEM 4.4 - Ball/butterfly valves leaking and not replaced","severity_level":"non-critical","fault_id":"rec0OxAZzfsR00EDn","prompt_id":"rec0OxAZzfsR00EDn_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"5_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"cc83e283-f8e3-4403-b9d2-f2deec61507b","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.B","prompt":"(iii) Reduce the flow to the duty flow (sprinklers, hydrants or combined) for sufficient time to record the water supply proving test results.","input":null,"possible_fault":"Fails duty flow test/recording","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Diesel fails duty flow proving test","severity_level":"critical","fault_id":"recKPBfWCCefqOIvB","prompt_id":"recKPBfWCCefqOIvB_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"ce379a62-28ed-4cb8-a723-083418e99e87","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.13","prompt":"After completion of testing procedures, RETURN all equipment to the operational condition.","input":null,"possible_fault":"Equipment not returned to operational","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.13 - Equipment not returned to operational","severity_level":"non-conformance","fault_id":"reccyWht6x8KwgwvA","prompt_id":"reccyWht6x8KwgwvA_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"ce4db4dd-97f5-458c-ab72-c5d2293df187","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14","prompt":"(e) Running speed is correct, and record the\n result.","input":null,"possible_fault":"Running speed incorrect","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.14 - Running speed not correct","severity_level":"non-critical","fault_id":"recvqRpe5zIABSAJb","prompt_id":"recvqRpe5zIABSAJb_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"ceae1b2d-d984-4757-a277-6e604b9990bf","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.9","prompt":"(b) INSPECT pump/driver coupling for wear and alignment. Report worn or damaged components.","input":null,"possible_fault":"Coupling not inspected/worn/damaged","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.9 - Electric coupling not inspected/worn/damaged","severity_level":"non-critical","fault_id":"recpFexzLY1yaGaRP","prompt_id":"recpFexzLY1yaGaRP_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"cfb5f17d-b605-4300-a36c-97ce3b3c6584","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.A","prompt":"(B) Discharge pressure.","input":null,"possible_fault":"Discharge pressures not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Diesel discharge pressures not recorded","severity_level":"non-conformance","fault_id":"rec8RJJCRdnFv0Tid","prompt_id":"rec8RJJCRdnFv0Tid_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"d395ff0f-2f86-4a43-977c-4aa63a1cd270","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(m) REPLACE the oil in right-angle gearboxes\n with new oil that meets the manufacturer’s specification.","input":null,"possible_fault":"Gearbox oil not replaced/wrong spec","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Gearbox oil not replaced/wrong specification","severity_level":"recommendation","fault_id":"recEADpplEaHD8NMs","prompt_id":"recEADpplEaHD8NMs_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"da0487dd-ba90-43d1-aec1-aef0557929c3","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"4.6","prompt":"After completion of testing procedures, RETURN all equipment to the operational condition.","input":"YES/NO","possible_fault":"Equipment not restored to operational","possible_fault_description":"AS1851 2012 TABLE 3.4.4 ITEM 4.6 - Equipment not returned to operational condition","severity_level":"non-conformance","fault_id":"rech6Nfxnmgxp4KWK","prompt_id":"rech6Nfxnmgxp4KWK_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"5_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"da3c4057-afb9-4f1d-b46e-5c739ff2888a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.8","prompt":"(l) Where the pump bearings are of the oil-lubricated type, REPLACE the bearing oil with new oil that meets the pump manufacturer’s specification (does not apply to turbine type vertical shaft centrifugal pumps).","input":null,"possible_fault":"Pump bearing oil not replaced","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.8 - Pump bearing oil not replaced/wrong spec","severity_level":"non-critical","fault_id":"recx8hjAzoSQLGGfe","prompt_id":"recx8hjAzoSQLGGfe_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"db0d33f7-011a-42de-9886-c64e8fcdcae8","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2","prompt":"(b) SIMULATE an engine fail to start and ensure that engine-start cycling requirements and alarm activations are satisfied.","input":null,"possible_fault":"Fail start cycling/alarms not working","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Engine fail start cycling/alarms fail","severity_level":"critical","fault_id":"recM84jmQ6Z2zjpsT","prompt_id":"recM84jmQ6Z2zjpsT_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"db14fd41-b8db-4d7a-9837-3f971572d0be","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.1","prompt":"(b) CHECK that pressure-relief valve discharge will not cause flooding or water damage.","input":null,"possible_fault":"Potential flooding or water damage risk","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.1 - Relief valve discharge causes flooding/damage","severity_level":"non-critical","fault_id":"recSmA3nAJsgdznyV","prompt_id":"recSmA3nAJsgdznyV_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"db70c0b0-4044-4e9a-baf1-c710685e7801","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"4.4","prompt":"(a) FIT new gland packing and lubricate spindles.","input":"YES/NO","possible_fault":"Gland packing not fitted or not lubricated","possible_fault_description":"AS1851 2012 TABLE 3.4.4 ITEM 4.4 - New gland packing not fitted/spindles not lubricated","severity_level":"non-critical","fault_id":"recpgx2HR3ffZ4164","prompt_id":"recpgx2HR3ffZ4164_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"5_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"dcb71bd4-1081-4609-932c-e523482dc7a8","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.A","prompt":"(v) During this period RECORD the\n following for actions (ii), (iii) and (iv)\n above:\n (A) Suction pressures.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recpvSV0lrd06WLIS_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"dd0f1efc-e50a-4c9a-9283-a9d29fd3c659","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2","prompt":"(a) With the pump room door(s) closed, and the pump testing technician present:\n (i) RUN the pumpset at shut-off (zero flow) for 10 min to allow all equipment to attain normal operating temperature.","input":null,"possible_fault":"Fails to run 10min at shut-off","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Diesel fails 10min shut-off run","severity_level":"critical","fault_id":"rectjsv8FkI090oG7","prompt_id":"rectjsv8FkI090oG7_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"dd6e1dc1-ebc6-4691-a543-67bc433afdee","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.11","prompt":"(b) CHECK all lights are functional by pressing the indicator test button, where fitted.","input":null,"possible_fault":"Indicator lights not functional","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.11 - Indicator lights not functional during test","severity_level":"non-critical","fault_id":"recUcIDD01OMNqRR7","prompt_id":"recUcIDD01OMNqRR7_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"de537e73-8cbb-475d-958d-4379c998bfb6","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.16","prompt":"CHECK that the main isolating switch is in the ON position and secured in position where facilities are provided and, where fitted, the green power supply lamps are illuminated and that no red warning lamps are on. Ensure all lights are functional by pressing the lamp test button, where fitted.","input":null,"possible_fault":"Main switch not ON/warning lamps on","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.16 - Main switch not ON/secured, warning lamps on","severity_level":"non-critical","fault_id":"recSJIjdlYDHMyGZ7","prompt_id":"recSJIjdlYDHMyGZ7_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"e008ff4e-0586-4493-9663-c3c92efde26d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.19","prompt":"(b) CHECK battery for corrosion, physical damage and security.","input":null,"possible_fault":"Battery corroded/damaged/insecure","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.19 - Controller battery corroded/damaged/insecure","severity_level":"non-critical","fault_id":"recQ9t2OXhly9XKkZ","prompt_id":"recQ9t2OXhly9XKkZ_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"e12944bb-dc8a-4d5e-9792-1f00d51d73aa","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2.B","prompt":"(F) Engine RPM, using both installed tachometer and calibrated tachometer. Record variations.","input":null,"possible_fault":"RPM variations not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Engine RPM/variations not recorded","severity_level":"non-conformance","fault_id":"reccqlHFdXdA1NiWU","prompt_id":"reccqlHFdXdA1NiWU_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"e557b4de-f514-403b-9787-76ebc02661eb","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.11","prompt":"(a) CHECK the main isolating switch is in the ‘ON’ position and secured in position where facilities are provided and, where fitted, the green power supply indicators are illuminated and that no red warning lamps are on.","input":null,"possible_fault":"Switch not in ON position/unsecured","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.11 - Main switch not ON/secured, warning lamps on","severity_level":"non-critical","fault_id":"recHXWJzPWq0l34Ju","prompt_id":"recHXWJzPWq0l34Ju_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"e800c104-02d9-4128-9fa1-376cd185a2c2","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.2","prompt":"(b) CHECK that there are readily seen and clearly legible ID plates on each controller, driver (diesel and electric), pumpset (on base plate) and pump (on the pump).","input":null,"possible_fault":"ID plates missing or illegible","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.2 - Controller/driver/pump ID plates not visible/legible","severity_level":"non-conformance","fault_id":"recjWyLqDDQyyOyKB","prompt_id":"recjWyLqDDQyyOyKB_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"eb63f444-3689-4a8b-88cb-955b4b716c33","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.7.B","prompt":"Test and record battery charger voltage output.","input":null,"possible_fault":"Charger voltage output not recorded","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.7 - Battery charger voltage output not tested/recorded","severity_level":"non-conformance","fault_id":"recApv0gF0weOEiHN","prompt_id":"recApv0gF0weOEiHN_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"eb9eaec1-af04-4553-9630-537e4ed5aecc","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.7","prompt":"(b) REMOVE any corrosion from battery \n terminals as required.","input":null,"possible_fault":"Corrosion present on battery terminals","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.7 - Battery terminal corrosion requires removal","severity_level":"non-critical","fault_id":"recoQvnW98m1iNZ1b","prompt_id":"recoQvnW98m1iNZ1b_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"ec5595fd-c5b6-4e76-9a64-2f8defc0a17c","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.4 FIVE-YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"4.3","prompt":"(d) Pressure regulating valve.","input":"YES/NO","possible_fault":"Pressure regulating valve not overhauled","possible_fault_description":"AS1851 2012 TABLE 3.4.4 ITEM 4.3 - Pressure regulating valve not overhauled per specs","severity_level":"non-conformance","fault_id":"recnFPfAmYV2YhAcb","prompt_id":"recnFPfAmYV2YhAcb_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"5_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"ecdb2f1e-3f01-49ed-b31b-d435122aa486","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.10","prompt":"ENSURE all non-return valves are operating freely and are seating correctly.","input":null,"possible_fault":"Non-return valves not operating/seating","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.10 - Non-return valves not operating/seating","severity_level":"critical","fault_id":"recPGSJroqYnxpEkg","prompt_id":"recPGSJroqYnxpEkg_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"f0687848-a10d-496a-815b-706c15b45767","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.2","prompt":"(c) TEST correct operation of pump priming tanks and associated equipment, where fitted.","input":null,"possible_fault":"Priming tanks not operating correctly","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.2 - Pump priming tanks not operating","severity_level":"critical","fault_id":"rec0Zgu2iYaiWoxan","prompt_id":"rec0Zgu2iYaiWoxan_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"f24632f6-24ac-40db-97ce-af3fb87dda93","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3","prompt":"While carrying out the above procedure, CHECK temperature of bearings and stuffing box leakage and note and report any abnormality.","input":null,"possible_fault":"Abnormal temperatures/leakage","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Electric bearing temp/stuffing abnormal","severity_level":"non-critical","fault_id":"receWdZzI57S2Nz2v","prompt_id":"receWdZzI57S2Nz2v_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"f2815ecc-9205-41bb-b9e4-f8b993bd372a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.3","prompt":"(a) With the pump room door(s) closed and the pump testing technician present: \n (i) RUN the pumpset at shut-off (zero flow) for 3 min.","input":null,"possible_fault":"Fails to run 3min at shut-off","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.3 - Electric fails 3min shut-off run","severity_level":"critical","fault_id":"recwutWb9y3s1EZmP","prompt_id":"recwutWb9y3s1EZmP_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"f3cbea40-d93a-47ae-8529-9bb9efd9a73e","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.3","prompt":"CHECK that all valves are in the open position or the closed position, as labelled, and secured, where applicable.","input":null,"possible_fault":"Valves not in correct position/unsecured","possible_fault_description":"AS1851 2012 TABLE 3.4.1 ITEM 1.3 - Valves not open/closed as labeled or unsecured","severity_level":"critical","fault_id":"recp2EzJeYlxDKL5c","prompt_id":"recp2EzJeYlxDKL5c_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"fd5cff8b-9c66-436a-b009-8f94fd5d7567","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.3 YEARLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"3_year","inspection_period_frequency":3,"inspection_period_interval":"year","inspection_period_in_days":1095,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"3.9","prompt":"(c) Where grease nipples are provided, GREASE pump and motor bearings to the manufacturer’s specifications.","input":null,"possible_fault":"Motor/pump bearings not greased","possible_fault_description":"AS1851 2012 TABLE 3.4.3 ITEM 3.9 - Electric motor/pump bearings not greased","severity_level":"recommendation","fault_id":"rec5mMF3ACNnImbZ0","prompt_id":"rec5mMF3ACNnImbZ0_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"3_year::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"},{"id":"ff95ae2d-e0fa-4093-9a3b-363f28d70ce8","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.1 MONTHLY SERVICE SCHEDULE FIRE PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Pumpset","variant":null,"variant_id":"recer7HJaBbq7yIqD","item_no":"1.14.A","prompt":"(k) Engine instrumentation is operating. Record \n the results.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec9zHApoS9ts3nnl_prompt","inspection_id":"c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recer7HJaBbq7yIqD_reckaTaCpZtHlVCq7"}]},{"id":"recrf1xCIxeQtYrX2","name":"Hose reel and pressure maintenance/jacking pumpsets","checklist":[{"id":"2fcb6e51-2930-4827-88a2-7ea321fed4ad","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.1 MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"5.1","prompt":"(a) CHECK that pump areas are unobstructed, not used for storage and lighting is adequate.","input":"YES/NO","possible_fault":"Pump area obstructed or inadequate lighting","possible_fault_description":"AS1851 2012 TABLE 3.4.5.1 ITEM 5.1 - Pump areas obstructed/poor lighting/used for storage","severity_level":"non-critical","fault_id":"recAUjHDUZCZvpa2t","prompt_id":"recAUjHDUZCZvpa2t_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"},{"id":"32b81f73-bcb8-43ec-986c-4a030267d3e8","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.1 MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"5.5","prompt":"(a) VERIFY operation (manual and automatic).","input":"YES/NO","possible_fault":"Pump not operating manually or automatically","possible_fault_description":"AS1851 2012 TABLE 3.4.5.1 ITEM 5.5 - Manual/automatic pump operation failure","severity_level":"critical","fault_id":"recmh6peb0bUDx3aR","prompt_id":"recmh6peb0bUDx3aR_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"},{"id":"5af32bd3-80eb-4888-b427-23f4833decfb","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.1 MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"5.4","prompt":"CHECK that the main isolating switch is in the on position and secured (where facilities are provided), the green power supply lamps are illuminated and that no red warning lamps are on. Ensure all lights are functional by pressing the lamp test button, where fitted.","input":"YES/NO","possible_fault":"Controller switch off or warning lamps on","possible_fault_description":"AS1851 2012 TABLE 3.4.5.1 ITEM 5.4 - Isolating switch off/power lamps off/warning on","severity_level":"non-critical","fault_id":"recg5CoZhPJUuzxP4","prompt_id":"recg5CoZhPJUuzxP4_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"},{"id":"5d58722f-afeb-48e9-b7bb-b17e00e2b77a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.2 SIX-MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"6.1","prompt":"COMPLETE all monthly service activities, as listed in Table 3.4.5.1.","input":"YES/NO","possible_fault":"Monthly service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 3.4.5.2 ITEM 6.1 - All monthly service activities not completed","severity_level":"non-conformance","fault_id":"rec3R84av5414gfzd","prompt_id":"rec3R84av5414gfzd_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"6_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"},{"id":"67aff2b4-2201-4aee-b8d2-7f487939cf19","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.1 MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"5.3","prompt":"CHECK that the water supply tank is full.","input":"YES/NO","possible_fault":"Water supply tank not full","possible_fault_description":"AS1851 2012 TABLE 3.4.5.1 ITEM 5.3 - Water supply tank level insufficient","severity_level":"critical","fault_id":"recHlxqtqb2IbZpa5","prompt_id":"recHlxqtqb2IbZpa5_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"},{"id":"68f04f43-9748-4b23-bb8f-66c2ea219b79","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.1 MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"5.5.A","prompt":"(b) RECORD cut-in and cut-out pressures.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recRQrB453CGegAUt_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"},{"id":"7e778c3a-e7fb-4c71-8424-14cae2bce011","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.2 SIX-MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"6.2","prompt":"VERIFY that the air pressure is correct.","input":"Yes/No","possible_fault":"Air pressure incorrect in accumulator","possible_fault_description":"AS1851 2012 TABLE 3.4.5.2 ITEM 6.2 - Hydro-pneumatic accumulator air pressure incorrect","severity_level":"non-critical","fault_id":"recqbsLJ2UkQ3qhCS","prompt_id":"recqbsLJ2UkQ3qhCS_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"6_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"},{"id":"c6397240-61d9-4d3b-86b5-0e76dedf94b0","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.1 MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"5.1","prompt":"(b) Where pump pressure-relief valves are fitted, CHECK that the discharge will not cause flooding or water damage.","input":"YES/NO","possible_fault":"Relief valve discharge causing flooding risk","possible_fault_description":"AS1851 2012 TABLE 3.4.5.1 ITEM 5.1 - Pressure-relief valve discharge causing water damage","severity_level":"critical","fault_id":"recIBN0rWLiR85gju","prompt_id":"recIBN0rWLiR85gju_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"},{"id":"d38647d4-5041-4287-9927-730177d30f2a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.1 MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"5.2","prompt":"ENSURE that all valves are in the open position or the closed position, as labelled, and secured where applicable.","input":"YES/NO","possible_fault":"Valves not in correct open/closed position","possible_fault_description":"AS1851 2012 TABLE 3.4.5.1 ITEM 5.2 - Valves not in labelled position or unsecured","severity_level":"critical","fault_id":"recXAYClp9oZhagUi","prompt_id":"recXAYClp9oZhagUi_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"},{"id":"daaba083-8ba1-4cc0-bc41-9a0952b4765d","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.1 MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"5.5.B","prompt":"(b) RECORD cut-in and cut-out pressures.","input":null,"possible_fault":"Cut-in/cut-out pressures outside spec","possible_fault_description":"AS1851 2012 TABLE 3.4.5.1 ITEM 5.5 - Cut-in/cut-out pressures not recorded/incorrect","severity_level":"non-critical","fault_id":"rec7V1e322mFJrlXY","prompt_id":"rec7V1e322mFJrlXY_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"},{"id":"e6baa13c-bf4c-4990-ac7e-d64139a6fe93","standard_code":"au_as_1851_2012","version":"full","category":"Fire Pumpsets","category_id":"reckaTaCpZtHlVCq7","group_header":"TABLE 3.4.5.1 MONTHLY SERVICE SCHEDULE HOSE REEL AND PRESSURE MAINTENANCE/JACKING PUMPSETS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Hose reel and pressure maintenance/jacking pumpsets","variant":null,"variant_id":"recrf1xCIxeQtYrX2","item_no":"5.1","prompt":"(c) CHECK for any obvious signs of physical damage or deterioration and that all safety guards are in place and secure.","input":"YES/NO","possible_fault":"Physical damage or missing safety guards","possible_fault_description":"AS1851 2012 TABLE 3.4.5.1 ITEM 5.1 - Physical damage/deterioration/missing safety guards","severity_level":"critical","fault_id":"recJiP5jcUlmvh1os","prompt_id":"recJiP5jcUlmvh1os_prompt","inspection_id":"c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7","grouping_key":"1_month::c_recrf1xCIxeQtYrX2_reckaTaCpZtHlVCq7"}]}],"other_checklist_items":[]},{"id":"recktUgpH1ACT3K9e","name":"Fire Blankets","asset_types":[{"id":"recSkqyhfPouyc79m","name":"Fire Blankets","checklist":[{"id":"11c7de01-c5f9-4920-be2c-9d00022449ac","standard_code":"au_as_1851_2012","version":"full","category":"Fire Blankets","category_id":"recktUgpH1ACT3K9e","group_header":"TABLE 11.4 SIX-MONTHLY SERVICE SCHEDULE FIRE BLANKETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Blankets","variant":null,"variant_id":"recSkqyhfPouyc79m","item_no":"1.4","prompt":"REMOVE the fire blanket from the container\n and check:\n (a) For any damage or contamination to the\n fire blanket (refer also Clause 11.2.4).\n (b) For unsecured or damaged hand-holding\n devices.\n (c) That the fire blanket is correctly folded.\n Where the fire blanket conforms to the above,\n REPACK the blanket into the container as\n recommended by the manufacturer.\n NOTE: It is important that fire blankets are\n always folded in the manner prescribed by the\n manufacturer in order that they can be\n removed from the container quickly (see\n AS/NZS 3504).","input":null,"possible_fault":"Blanket damaged/contaminated\nHand-holding devices damaged\nBlanket incorrectly folded","possible_fault_description":"AS1851 2012 TABLE 11.4 ITEM 1.4 - Fire blanket damaged or contaminated\nAS1851 2012 TABLE 11.4 ITEM 1.4 - Hand-holding devices unsecured or damaged\nAS1851 2012 TABLE 11.4 ITEM 1.4 - Fire blanket not correctly folded","severity_level":"non-critical","fault_id":"recVgYFrPtGH22raa","prompt_id":"recVgYFrPtGH22raa_prompt","inspection_id":"c_recSkqyhfPouyc79m_recktUgpH1ACT3K9e","grouping_key":"6_month::c_recSkqyhfPouyc79m_recktUgpH1ACT3K9e"},{"id":"2da6a4d1-9db3-4718-a07c-be44ef82cc4a","standard_code":"au_as_1851_2012","version":"full","category":"Fire Blankets","category_id":"recktUgpH1ACT3K9e","group_header":"TABLE 11.4 SIX-MONTHLY SERVICE SCHEDULE FIRE BLANKETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Blankets","variant":null,"variant_id":"recSkqyhfPouyc79m","item_no":"1.2","prompt":"CHECK that the location sign is visible and\n correct.","input":null,"possible_fault":"Location sign incorrect/not visible","possible_fault_description":"AS1851 2012 TABLE 11.4 ITEM 1.2 - Location sign not visible or incorrect","severity_level":"non-conformance","fault_id":"reckI9KbMNMoLQJ2H","prompt_id":"reckI9KbMNMoLQJ2H_prompt","inspection_id":"c_recSkqyhfPouyc79m_recktUgpH1ACT3K9e","grouping_key":"6_month::c_recSkqyhfPouyc79m_recktUgpH1ACT3K9e"},{"id":"433fce49-c62d-4b66-996d-3fc805b7146f","standard_code":"au_as_1851_2012","version":"full","category":"Fire Blankets","category_id":"recktUgpH1ACT3K9e","group_header":"TABLE 11.4 SIX-MONTHLY SERVICE SCHEDULE FIRE BLANKETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Blankets","variant":null,"variant_id":"recSkqyhfPouyc79m","item_no":"1.3","prompt":"CHECK that the fire blanket container:\n (a) Is securely and correctly supported.\n (b) Is clean and free from damage.\n (c) Has clear and legible instructions thereon.\n (d) Has a service record tag/label attached.","input":null,"possible_fault":"Container not securely supported\nContainer dirty/damaged\nInstructions unclear/illegible\nService tag/label missing","possible_fault_description":"AS1851 2012 TABLE 11.4 ITEM 1.3 - Container not securely/correctly supported\nAS1851 2012 TABLE 11.4 ITEM 1.3 - Container not clean or damaged\nAS1851 2012 TABLE 11.4 ITEM 1.3 - Instructions not clear and legible\nAS1851 2012 TABLE 11.4 ITEM 1.3 - Service record tag/label not attached","severity_level":"non-conformance","fault_id":"recTmX0eBgxRuAvrW","prompt_id":"recTmX0eBgxRuAvrW_prompt","inspection_id":"c_recSkqyhfPouyc79m_recktUgpH1ACT3K9e","grouping_key":"6_month::c_recSkqyhfPouyc79m_recktUgpH1ACT3K9e"},{"id":"8f741a88-9540-48db-aebe-d9d095ee0b79","standard_code":"au_as_1851_2012","version":"full","category":"Fire Blankets","category_id":"recktUgpH1ACT3K9e","group_header":"TABLE 11.4 SIX-MONTHLY SERVICE SCHEDULE FIRE BLANKETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Blankets","variant":null,"variant_id":"recSkqyhfPouyc79m","item_no":"1.1","prompt":"CHECK that the fire blanket is:\n (a) Conspicuous.\n (b) In its assigned location.\n (c) Readily accessible.\n (d) Installed in accordance with AS 2444.","input":null,"possible_fault":"Fire blanket not conspicuous\nNot in assigned location\nAccess restricted/blocked\nNot installed per AS 2444","possible_fault_description":"AS1851 2012 TABLE 11.4 ITEM 1.1 - Fire blanket not conspicuous\nAS1851 2012 TABLE 11.4 ITEM 1.1 - Fire blanket not in assigned location\nAS1851 2012 TABLE 11.4 ITEM 1.1 - Fire blanket not readily accessible\nAS1851 2012 TABLE 11.4 ITEM 1.1 - Fire blanket not installed per AS2444","severity_level":"non-conformance","fault_id":"recIS41KmLzKXYlIp","prompt_id":"recIS41KmLzKXYlIp_prompt","inspection_id":"c_recSkqyhfPouyc79m_recktUgpH1ACT3K9e","grouping_key":"6_month::c_recSkqyhfPouyc79m_recktUgpH1ACT3K9e"}]}],"other_checklist_items":[]},{"id":"recllMaGwCBycgLb8","name":"Automatic Fire Sprinkler Systems","asset_types":[{"id":"recH9hrBvqyEZ98HW","name":"Fire Spinkler : Deluge and Water Spray Systems","checklist":[{"id":"0a405c90-fe8f-4e4e-8ec9-175826c97f73","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"3.6","prompt":"REMOVE and CLEAN strainer.","input":null,"possible_fault":"Compressor fails to maintain pressure","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.6 - Air compressor not operating to specification","severity_level":"critical","fault_id":"rec4LSQezNcj2gtuG","prompt_id":"rec4LSQezNcj2gtuG_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"0e07c2ea-2d47-4c15-9ca7-38bfb5bdcffb","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.5","prompt":"RESTORE units to operational status.","input":null,"possible_fault":"Control units not restored to operation","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.5 - Electrical control units not restored","severity_level":"critical","fault_id":"recLBLtQOcWy8ll7M","prompt_id":"recLBLtQOcWy8ll7M_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"0e0ad678-acbe-468e-8449-3693ee227de7","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"3.3","prompt":"Where practicable, CONDUCT full discharge test to check all open sprinklers and nozzles are unobstructed and provide appropriate coverage.","input":null,"possible_fault":"Water distribution pipes incorrectly pitched","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.3 - Pipework not correctly pitched to drain","severity_level":"non-conformance","fault_id":"recbwerzgfKeYzio7","prompt_id":"recbwerzgfKeYzio7_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"10a2c387-97c9-45ec-915c-8f591e2ee094","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.2","prompt":"(f) Where an isolation valve has not been fitted above the alarm valve, the main stop valve should be closed, enabling a partial test of the alarm valve. NOTE: Consider full testing at the first opportunity (at which time the isolation test valve should be installed).","input":null,"possible_fault":"Main stop valve not closed for test","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.2 - Main stop valve not closed for partial test","severity_level":"non-critical","fault_id":"recPCGeLkvGF6Ciim","prompt_id":"recPCGeLkvGF6Ciim_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"1acf06e4-2c9e-40fe-8111-cc5ae691fab2","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.8.B","prompt":"(a) Low air pressure alarm operates at predetermined levels.","input":null,"possible_fault":"Alarm operates at incorrect pressure","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.8 - Low air pressure alarm activation level incorrect","severity_level":"non-critical","fault_id":"recxqzaMth3IVwpFk","prompt_id":"recxqzaMth3IVwpFk_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"23703539-15d0-4181-b093-8fd93628a11e","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.6.A","prompt":"(a) RECORD readings from each pressure gauge.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recqpmQtu43yxb5lq_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"266e42b7-5265-4f88-ad55-77a511d0a050","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"3.5","prompt":"CHECK and clean foam concentrate strainer (fitted upstream of proportioning device).","input":null,"possible_fault":"Valve clapper seat damaged/worn","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.5 - Dry pipe valve components require maintenance","severity_level":"non-critical","fault_id":"recguVyadZRbyivGX","prompt_id":"recguVyadZRbyivGX_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"28bbe993-b6e2-4e6d-b99d-5295694d3b81","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.2.A","prompt":"CHECK that all pressure gauge readings are within the ranges required and RECORD reading from each pressure gauge.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recvyjSkZ1cFeMeAt_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"3764218c-e3d9-4b2f-8b74-949063ffdcd0","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.4","prompt":"RESET deluge valve and RESTORE detector sprinkler line pressure. OPEN and SECURE main stop valve. OPEN and secure test-isolating valve (where fitted) in an open position.","input":null,"possible_fault":"Detector line pressure not restored","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.4 - Detector sprinkler line pressure not restored","severity_level":"non-critical","fault_id":"recLYneghQFmG2UXC","prompt_id":"recLYneghQFmG2UXC_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"3a54f40a-27d1-4ff0-ab8e-4af1a704c139","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.2","prompt":"(a) Where fitted, CLOSE isolation valve located above deluge valve (prevents entry of water into system piping).","input":null,"possible_fault":"Isolation valve not closed","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.2 - Isolation valve above deluge valve not closed","severity_level":"non-critical","fault_id":"recFxlaym8I6fI4mK","prompt_id":"recFxlaym8I6fI4mK_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"3e023348-c380-4522-a065-5e37c3f17187","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.4","prompt":"INSPECT and TEST in accordance with Section 6.","input":null,"possible_fault":"Electrical detection system malfunction","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.4 - Electrical detection not operating per Section 6","severity_level":"critical","fault_id":"rec1fsrYaxgw5kuji","prompt_id":"rec1fsrYaxgw5kuji_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"44785b23-eb34-4ec2-9cef-dd23573133f7","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.6.A","prompt":"VERIFY that air compressor operates at specified cut-in and cut-out pressures.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"reciVkadVDLxRKwjb_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"489b2c78-6bd5-4b8e-85db-a997ee162e2e","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"3.2","prompt":"COMPLETE all yearly wet pipe service activities listed in Table 2.4.2.3 that are applicable to a deluge and water spray system.","input":null,"possible_fault":"Desiccators not replaced","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.2 - Air desiccators not replaced annually","severity_level":"recommendation","fault_id":"recWBC0YHmSHrUS6c","prompt_id":"recWBC0YHmSHrUS6c_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"5447b9bc-33eb-41a4-a6dc-176645c1d125","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"4.4","prompt":"FIT a new diaphragm, unless otherwise specified by the manufacturer.","input":null,"possible_fault":"New diaphragm not fitted","possible_fault_description":"AS1851 2012 TABLE 2.4.4.4 ITEM 4.4 - Diaphragm valve diaphragm not replaced","severity_level":"recommendation","fault_id":"recLXoqhuozwfENPN","prompt_id":"recLXoqhuozwfENPN_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"5_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"56c3f293-e9d8-483f-a37e-0820cb265466","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"3.9","prompt":"CHECK that system layout remains appropriate for protected hazard. Check for possible misalignment of spray nozzles.","input":null,"possible_fault":"Water not draining completely\nControl valves not fully open","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.9 - System drainage inadequate or blocked\nAS1851 2012 TABLE 2.4.3.3 ITEM 3.10 - Control valves not in correct position","severity_level":"non-critical","fault_id":"recvmlnKhJRVCbNu1","prompt_id":"recvmlnKhJRVCbNu1_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"57498265-7700-460a-8776-4df4c0094584","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.2","prompt":"(b) OPERATE each deluge valve by releasing the system via each installed means.","input":null,"possible_fault":"Deluge valve does not operate","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.2 - Deluge valve not operating via installed means","severity_level":"critical","fault_id":"recKpp0lFfgnEdenQ","prompt_id":"recKpp0lFfgnEdenQ_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"59dd59a1-3ef9-4250-b9e6-bf4eeaa28326","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.9","prompt":"(a) GENERATE a test of the alarm signalling equipment and local alarm in accordance with the manufacturer’s operating manual. NOTE: Where fitted, bypass valve may be used for this test.","input":null,"possible_fault":"Alarm signalling equipment malfunction","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.9 - Local alarm signalling not operating per manual","severity_level":"critical","fault_id":"recxyHYFNPfPSwCPV","prompt_id":"recxyHYFNPfPSwCPV_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"5af332ee-4b97-4242-92e8-4feaa802a856","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"3.7","prompt":"INSPECT and test in accordance with yearly requirements in Section 6.","input":null,"possible_fault":"Alarm fails to activate","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.7 - Low air pressure alarm not functioning","severity_level":"critical","fault_id":"recIr4PV7evDkN3hz","prompt_id":"recIr4PV7evDkN3hz_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"61a6e9a9-06fc-4a83-b18b-4bba2a98f139","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.2","prompt":"(e) VERIFY correct operation of the fire brigade alarms from each deluge valve or group of deluge assemblies. Where the system is monitored, ensure the alarm has activated the alarm signalling equipment. NOTE: Where multiple deluge valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.","input":null,"possible_fault":"Fire brigade alarm not transmitting","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.2 - Fire brigade alarm transmission failure","severity_level":"critical","fault_id":"recT4vJG3Y9U4My56","prompt_id":"recT4vJG3Y9U4My56_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"6c6e5770-5fdf-4cf9-83dc-88ae6e01668c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"3.8","prompt":"To the extent practicable, CHECK that pipe hangers are secure and open sprinklers and spray nozzles are unobstructed. Where applicable, check for missing nozzle dust plugs/caps.","input":null,"possible_fault":"Damaged/corroded sprinkler heads","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.8 - Sprinkler heads require replacement","severity_level":"critical","fault_id":"recymsGIZyi7CoETy","prompt_id":"recymsGIZyi7CoETy_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"6d6a6930-8fe4-4b91-ba5b-d4d95a351f17","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.3","prompt":"(a) CHECK oil level is correct and visually assess condition of oil.","input":null,"possible_fault":"Low oil level or contaminated oil","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.3 - Air compressor oil level/condition inadequate","severity_level":"non-critical","fault_id":"rectLz7idDRaA7DiM","prompt_id":"rectLz7idDRaA7DiM_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"71f87605-afa9-46e3-9b7f-99547e0783f0","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.2","prompt":"(d) RECORD times to operation of alarm(s) and verify that these do not exceed 30 s.","input":null,"possible_fault":"Alarm operation exceeds 30 seconds","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.2 - Alarm operation time exceeds 30s requirement","severity_level":"non-critical","fault_id":"recwJZLt6xdtXk40H","prompt_id":"recwJZLt6xdtXk40H_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"72b5ea2a-cdcb-4301-8f01-3b66fb2b5bfe","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"4.5","prompt":"GENERATE foam through delivery device (nozzle, monitor) or test foam maker and check:","input":null,"possible_fault":"Foam not generated through delivery device","possible_fault_description":"AS1851 2012 TABLE 2.4.4.4 ITEM 4.5 - Foam not generated through nozzle/monitor","severity_level":"critical","fault_id":"recXhgs32o0CU7uHL","prompt_id":"recXhgs32o0CU7uHL_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"5_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"77373d7a-be15-4cf0-bdae-05042850b6ab","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"4.5","prompt":"(a) Proportioning ratio (using conductivity meter or refractometer).","input":null,"possible_fault":"Proportioning ratio incorrect","possible_fault_description":"AS1851 2012 TABLE 2.4.4.4 ITEM 4.5 - Foam proportioning ratio not verified","severity_level":"non-critical","fault_id":"recBGoplfv0TSxuTb","prompt_id":"recBGoplfv0TSxuTb_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"5_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"7a221767-254a-47cd-9585-1de4f31bb0be","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.7","prompt":"TEST solenoid valves for correct operations.","input":null,"possible_fault":"Solenoid valve malfunction","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.7 - Solenoid valves not operating correctly","severity_level":"critical","fault_id":"recrrez95Ix3qf9Fy","prompt_id":"recrrez95Ix3qf9Fy_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"7b90e1e8-cf8f-4b07-8bab-fa5d23ba96b8","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.6","prompt":"(b) VERIFY pressure gauge readings are within the ranges required.","input":null,"possible_fault":"Pressure readings outside required ranges","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.6 - Pressure gauge readings outside specifications","severity_level":"non-critical","fault_id":"recCTB9seyt9FaZza","prompt_id":"recCTB9seyt9FaZza_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"89da039e-9ae0-4826-8ed8-5681aac8ba38","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"4.5","prompt":"(c) Expansion ratio.","input":null,"possible_fault":"Expansion ratio out of specification","possible_fault_description":"AS1851 2012 TABLE 2.4.4.4 ITEM 4.5 - Foam expansion ratio not within specifications","severity_level":"non-critical","fault_id":"rec1QOXSq3As8vvOu","prompt_id":"rec1QOXSq3As8vvOu_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"5_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"9c325638-2694-4c64-bda4-a42908a4b328","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.1","prompt":"COMPLETE all monthly wet pipe service activities listed in Table 2.4.2.1 that are applicable to a deluge and water spray system.","input":null,"possible_fault":"Wet pipe service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.1 - Required wet pipe service activities not completed","severity_level":"non-conformance","fault_id":"recgGUQ1DgrhUgFpg","prompt_id":"recgGUQ1DgrhUgFpg_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"ab70c9ec-9fa9-4722-8ea2-0df7a9e076a7","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.2.B","prompt":"CHECK that all pressure gauge readings are within the ranges required and RECORD reading from each pressure gauge.","input":null,"possible_fault":"Pressure readings outside required ranges","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.2 - Pilot/diaphragm/main valve pressures incorrect","severity_level":"non-critical","fault_id":"recrOcn5slYJt7DUC","prompt_id":"recrOcn5slYJt7DUC_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"ac89f435-5644-42d5-beda-0e357e7c4ae8","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.6.B","prompt":"(a) RECORD readings from each pressure gauge.","input":null,"possible_fault":"Pressure readings not recorded","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.6 - Pressure gauge readings not recorded","severity_level":"non-conformance","fault_id":"rec8sUqQIbzgKrH5x","prompt_id":"rec8sUqQIbzgKrH5x_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"aef23c65-fc09-4433-ad76-3d3a1d5ccd04","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.8.A","prompt":"(a) Low air pressure alarm operates at predetermined levels.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recjsbiJNFwNOroym_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"b0e3fd06-bc64-4ec6-a533-330b6caacc82","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.1","prompt":"COMPLETE all monthly service activities listed in Table 2.4.4.1 and all six-monthly wet pipe service activities listed in Table 2.4.2.2 that are applicable to a deluge and water spray system.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.1 - Monthly/six-monthly service activities not completed","severity_level":"non-conformance","fault_id":"recHTe7CMiFHKynpf","prompt_id":"recHTe7CMiFHKynpf_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"b277c7c3-2bba-4999-b72b-ce31ab8cf234","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.7","prompt":"SECURE all valves and alarm cocks in the open position or the closed position as labelled.","input":null,"possible_fault":"Valves/cocks not secured correctly","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.7 - Valves/alarm cocks not secured per labels","severity_level":"non-critical","fault_id":"recs9iqzVkW9FZ63d","prompt_id":"recs9iqzVkW9FZ63d_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"b70d4b43-ecc2-4ae8-9703-f79fef940b71","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"3.1","prompt":"COMPLETE all monthly and six-monthly service activities, listed in Tables 2.4.4.1 and 2.4.4.2.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.1 - Required service activities not completed","severity_level":"non-conformance","fault_id":"recj1X8vzXOSMuh99","prompt_id":"recj1X8vzXOSMuh99_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"c5ee0272-de8d-4fd5-9e9f-6fd1de9cda3f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"3.4","prompt":"DRAW a sample and verify condition in accordance with NFPA 11 (pH, specific gravity, sediment, expansion ratio, 25% drain time).","input":null,"possible_fault":"System air pressure below minimum","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.4 - Air pressure not maintained per requirements","severity_level":"critical","fault_id":"recLWjR0kIsctwObL","prompt_id":"recLWjR0kIsctwObL_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"c7b8ba57-d702-470d-aad1-3e452f2922c0","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.6.B","prompt":"VERIFY that air compressor operates at specified cut-in and cut-out pressures.","input":null,"possible_fault":"Incorrect cut-in/cut-out pressures","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.6 - Air compressor pressures outside specifications","severity_level":"non-critical","fault_id":"recviOUvSRiK7xxku","prompt_id":"recviOUvSRiK7xxku_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"cea58896-506b-48ef-94bf-e223d5212a01","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"4.3","prompt":"FIT new deluge valve seats and seals. Check and clean operating mechanism. Fit new faceplate gasket.","input":null,"possible_fault":"New valve components not fitted","possible_fault_description":"AS1851 2012 TABLE 2.4.4.4 ITEM 4.3 - Deluge valve seats/seals/gasket not replaced","severity_level":"recommendation","fault_id":"recCP9mETO5kXZPIc","prompt_id":"recCP9mETO5kXZPIc_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"5_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"cfc89d2a-896d-4cbe-b698-77fe421ed77c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"4.5","prompt":"(b) 25% drainage time.","input":null,"possible_fault":"25% drainage time out of specification","possible_fault_description":"AS1851 2012 TABLE 2.4.4.4 ITEM 4.5 - Foam 25% drainage time not within limits","severity_level":"non-critical","fault_id":"recAWZP61apZ7Xkhi","prompt_id":"recAWZP61apZ7Xkhi_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"5_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"dcbc147d-9c70-48f7-af32-2af4d14d1408","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.2","prompt":"(c) CHECK for correct operation of alarm.","input":null,"possible_fault":"Alarm not operating correctly","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.2 - Alarm system not operating correctly","severity_level":"critical","fault_id":"recqhEBP3JJXK98g0","prompt_id":"recqhEBP3JJXK98g0_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"de084658-a0c6-4814-9785-3865a6956c63","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"2.3","prompt":"CLOSE main stop valve. CLOSE drain and RESET manual operating valve.","input":null,"possible_fault":"Valve not reset correctly","possible_fault_description":"AS1851 2012 TABLE 2.4.4.2 ITEM 2.3 - Deluge valve reset procedure not completed","severity_level":"non-critical","fault_id":"recndWZGTdnVmlv95","prompt_id":"recndWZGTdnVmlv95_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"6_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"e7606b14-c12a-42c5-afda-aaafbc80d650","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.8","prompt":"(b) Low pressure alarm(s) visual indicator and sounders are optional.","input":null,"possible_fault":"Visual/audio alarm not operational","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.8 - Low pressure alarm indicators/sounders not working","severity_level":"critical","fault_id":"recqDmVyZdrZtt2Cg","prompt_id":"recqDmVyZdrZtt2Cg_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"ed33109d-fdc9-4251-b750-f66f83a2017d","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.9","prompt":"(b) OBSERVE correct operation of the fire brigade alarm from each deluge and water spray valve or group of deluge and water spray valves. Where the system is monitored, ensure the alarm has activated the alarm signalling equipment.\n NOTE: Where multiple deluge and water spray valve assemblies are separately identified at the FIP, only one transmission from the FIP to the monitoring station is required.","input":null,"possible_fault":"Fire brigade alarm not transmitting","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.9 - Fire brigade alarm transmission failure from valve","severity_level":"critical","fault_id":"rec4JqJfs8SfwnNxo","prompt_id":"rec4JqJfs8SfwnNxo_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"f0a8b600-20c5-4f54-879f-f14cc7c953d6","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"4.1","prompt":"COMPLETE all monthly, six-monthly and yearly service activities, listed in Tables 2.4.4.1, 2.4.4.2 and 2.4.4.3.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.4.4 ITEM 4.1 - Required service activities not completed","severity_level":"non-conformance","fault_id":"recvLzsQFBO3juXRq","prompt_id":"recvLzsQFBO3juXRq_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"5_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"f4e49f2e-5843-40f0-a91a-44a197a1ad7f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.5","prompt":"CHECK detector sprinkler line valves are in the correct operating position.","input":null,"possible_fault":"Valves in incorrect operating position","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.5 - Detector sprinkler line valves not positioned correctly","severity_level":"critical","fault_id":"recpvkFV2moBSpGEz","prompt_id":"recpvkFV2moBSpGEz_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"f5e8858d-4ae1-4752-b8c6-f1204af879c6","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS  DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"1.3","prompt":"(b) CHECK regulator is locked and set in the correct position.","input":null,"possible_fault":"Regulator unlocked or incorrect setting","possible_fault_description":"AS1851 2012 TABLE 2.4.4.1 ITEM 1.3 - Air compressor regulator not locked/set correctly","severity_level":"non-critical","fault_id":"rec5t1BV5cfj491HK","prompt_id":"rec5t1BV5cfj491HK_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"1_month::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"},{"id":"f96da406-1d8a-422b-bb31-0b43cbf30ad7","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.4.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DELUGE AND WATER SPRAY SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Deluge and Water Spray Systems","variant":null,"variant_id":"recH9hrBvqyEZ98HW","item_no":"4.2","prompt":"COMPLETE all five-yearly wet pipe service activities listed in Table 2.4.2.4 that are applicable to a deluge and water spray system.","input":null,"possible_fault":"Wet pipe five-yearly tasks not done","possible_fault_description":"AS1851 2012 TABLE 2.4.4.4 ITEM 4.2 - Applicable wet pipe five-yearly tasks incomplete","severity_level":"non-conformance","fault_id":"recKXlnmsdZsWIAAA","prompt_id":"recKXlnmsdZsWIAAA_prompt","inspection_id":"c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8","grouping_key":"5_year::c_recH9hrBvqyEZ98HW_recllMaGwCBycgLb8"}]},{"id":"recvUb7ks9fiR4fCf","name":"Fire Spinkler : Pre-actions Systems","checklist":[{"id":"1ba2a41a-1b37-46b9-ae89-662f68489bb4","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.5.A","prompt":"(a) RECORD readings from each pressure gauge.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec8KydvgmtANVS9a_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"20beb49e-90ac-456e-92af-1d3082fc94b6","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.7","prompt":"TEST solenoid valves for correct operations.","input":null,"possible_fault":"Solenoid valve malfunction","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.7 - Solenoid valves not operating correctly","severity_level":"critical","fault_id":"recGL83rs4g72re8U","prompt_id":"recGL83rs4g72re8U_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"28ef328c-edf3-4a2b-9454-39ea456fbd9f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.2","prompt":"(a) Where fitted, CLOSE isolation valve located above pre-action valve (prevents entry of water into system piping).","input":null,"possible_fault":"Isolation valve not closed","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.2 - Isolation valve above pre-action valve not closed","severity_level":"non-conformance","fault_id":"recIwGrYxNWNWxxsH","prompt_id":"recIwGrYxNWNWxxsH_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"2c966b49-4f1d-4ac0-afab-bfd83d5004c0","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.6","prompt":"(b) CHECK regulator is locked and set in correct position.","input":null,"possible_fault":"Regulator unlocked or incorrect setting","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.6 - Nitrogen regulator not locked/set correctly","severity_level":"non-critical","fault_id":"recXkT8d8Hbtf2m76","prompt_id":"recXkT8d8Hbtf2m76_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"2f1b08a1-692d-468b-8c16-978c9ce4f031","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.2","prompt":"(c) CHECK for correct operation of alarm.","input":null,"possible_fault":"Alarm not operating correctly","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.2 - Alarm system not operating correctly","severity_level":"critical","fault_id":"recs2G4Ff3kZJLmZl","prompt_id":"recs2G4Ff3kZJLmZl_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"33b599d8-9099-48cf-a414-40025a6cedae","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.8","prompt":"(b) Low air pressure alarm(s) visual indicator and sounders are optional.","input":null,"possible_fault":"Visual/audio alarm not operational","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.8 - Low pressure alarm indicators/sounders not working","severity_level":"critical","fault_id":"recBvPGdFMZOcoGVA","prompt_id":"recBvPGdFMZOcoGVA_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"3d2f7172-e4cf-40ae-b282-556d379a04ed","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.4","prompt":"RESTORE units to operational status.","input":null,"possible_fault":"Control units not restored to operation","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.4 - Electrical control units not restored","severity_level":"non-conformance","fault_id":"recOHE3fHCKSjPy3Y","prompt_id":"recOHE3fHCKSjPy3Y_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"4a819764-6991-4cc2-a440-617690a37df4","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.6.A","prompt":"(a) CHECK cylinder contents per pressure gauge.","input":"NUMBER","possible_fault":"Low nitrogen cylinder pressure","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.6 - Nitrogen cylinder pressure below requirements","severity_level":"critical","fault_id":"rec5B3XCMzCv8cHbP","prompt_id":"rec5B3XCMzCv8cHbP_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"4c536445-81e0-48f2-9404-3c0386f3b828","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.9","prompt":"(a) GENERATE a test of the alarm signalling equipment and local alarm in accordance with the manufacturer’s operating manual.\n NOTE: Where fitted, bypass valve may be used for this test.","input":null,"possible_fault":"Alarm signalling equipment malfunction","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.9 - Local alarm signalling not operating per manual","severity_level":"critical","fault_id":"recnFYk8IN2uXia9c","prompt_id":"recnFYk8IN2uXia9c_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"6030aff6-07f9-410e-baf0-7e4a18ee90fe","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.1","prompt":"COMPLETE all monthly service activities listed in Table 2.4.5.1 and all six-monthly wet pipe service activities listed in Table 2.4.2.2 that are applicable to a pre-action system.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.1 - Monthly/six-monthly service activities not completed","severity_level":"non-conformance","fault_id":"recGHTk8YlQPBiXSS","prompt_id":"recGHTk8YlQPBiXSS_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"655272b8-f560-43d2-9f49-f10db3c4f332","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.6","prompt":"SECURE all valves and alarm cocks in the open position or the closed position as labelled.","input":null,"possible_fault":"Valves/cocks not secured correctly","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.6 - Valves/alarm cocks not secured per labels","severity_level":"non-critical","fault_id":"recNIxJSK5kQaxuLj","prompt_id":"recNIxJSK5kQaxuLj_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"6821aaec-f573-4c92-9e70-794b2acf6059","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.2.A","prompt":"(d) RECORD time(s) to operation of alarms and verify that these do not exceed 180 s.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recW3JrGruDYjtdXC_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"7a492fba-cfc9-4226-a17a-95e8dc995cbf","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.8.A","prompt":"(a) Low air pressure alarm operates at predetermined levels.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recP8gxiX2PpORYJ3_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"805b3abe-4702-4f9e-a5cd-1f8b39bf4279","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.5","prompt":"(b) VERIFY pressure gauge readings are within the ranges required.","input":null,"possible_fault":"Pressure readings outside required ranges","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.5 - Pressure gauge readings outside specifications","severity_level":"non-critical","fault_id":"recISNFHz2YBrPLV2","prompt_id":"recISNFHz2YBrPLV2_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"87e07001-c244-491b-a70d-1c62d8f1087b","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"4.3","prompt":"FIT new pre-action valve seats and seals. CHECK and CLEAN operating mechanism. FIT new cover plate gasket.","input":"YES/NO","possible_fault":"Valve seats/seals not replaced\nOperating mechanism not serviced\nCover plate gasket not replaced","possible_fault_description":"AS1851 2012 TABLE 2.4.5.4 ITEM 4.3 - New pre-action valve seats and seals not fitted\nAS1851 2012 TABLE 2.4.5.4 ITEM 4.3 - Operating mechanism not checked and cleaned\nAS1851 2012 TABLE 2.4.5.4 ITEM 4.3 - New cover plate gasket not fitted","severity_level":"non-conformance","fault_id":"recdC0LZ1SBVnsWJg","prompt_id":"recdC0LZ1SBVnsWJg_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"5_year::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"88086d74-2c66-4eba-a731-97efb7125c6b","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.2","prompt":"(e) OBSERVE correct operation of the fire brigade alarms from each pre-action valve or group of pre-action assemblies. Where the system is monitored, ensure the alarm has activated the alarm signalling equipment.\n NOTE: Where multiple pre-action valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.","input":null,"possible_fault":"Fire brigade alarm not transmitting","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.2 - Fire brigade alarm transmission failure","severity_level":"critical","fault_id":"recp9nfXq5ZKvJVpE","prompt_id":"recp9nfXq5ZKvJVpE_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"8a1993fa-87c5-4932-9a41-67c6b7064646","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.5.A","prompt":"VERIFY that air compressor operates at specified cut-in and cut-out pressures.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recDA0Ojg6bEZWff4_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"90411185-8421-4fe8-b72d-1e44a093fbb8","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"4.1","prompt":"COMPLETE all monthly, six-monthly and yearly service activities, listed in Tables 2.4.5.1, 2.4.5.2 and 2.4.5.3.","input":"YES/NO","possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.5.4 ITEM 4.1 - Monthly/six-monthly/yearly service activities incomplete","severity_level":"non-conformance","fault_id":"rectoPa9mYkDJyZGW","prompt_id":"rectoPa9mYkDJyZGW_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"5_year::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"91398b97-5d28-49dc-953b-898b16adbe6a","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"4.2","prompt":"COMPLETE all five-yearly wet pipe service activities listed in Table 2.4.2.4 that are applicable to a pre-action system.","input":"YES/NO","possible_fault":"Wet pipe service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.5.4 ITEM 4.2 - Five yearly wet pipe service activities not completed","severity_level":"non-conformance","fault_id":"recgf9gTNQixeRueM","prompt_id":"recgf9gTNQixeRueM_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"5_year::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"93059b4f-f27e-4d00-a3be-95b8c64dd83f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.5.B","prompt":"VERIFY that air compressor operates at specified cut-in and cut-out pressures.","input":null,"possible_fault":"Incorrect cut-in/cut-out pressures","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.5 - Air compressor pressures outside specifications","severity_level":"non-critical","fault_id":"recV1l4T3a0oHvyoi","prompt_id":"recV1l4T3a0oHvyoi_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"976c705a-1102-4c23-8e16-1263a88538c2","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.1","prompt":"COMPLETE all monthly wet pipe service activities listed in Table 2.4.2.1 that are applicable to a pre-action system.","input":null,"possible_fault":"Wet pipe service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.1 - Required wet pipe service activities not completed","severity_level":"non-conformance","fault_id":"reck4AVAXiyZYfWo9","prompt_id":"reck4AVAXiyZYfWo9_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"a8710c9e-906b-44b0-bc7f-804e3fd9d775","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.2.B","prompt":"(d) RECORD time(s) to operation of alarms and verify that these do not exceed 180 s.","input":null,"possible_fault":"Alarm operation exceeds 180 seconds","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.2 - Alarm operation time exceeds 180s requirement","severity_level":"non-critical","fault_id":"recKKMNWxzF1stRdA","prompt_id":"recKKMNWxzF1stRdA_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"b806358f-90a3-4cbf-8004-8dea178bf09d","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.3","prompt":"RESET pre-action valve and restore supervisory air pressure.","input":null,"possible_fault":"Supervisory air pressure not restored","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.3 - Pre-action valve/supervisory air pressure not restored","severity_level":"non-critical","fault_id":"recwK1jOb1fegMHPt","prompt_id":"recwK1jOb1fegMHPt_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"b89d1fa0-60d4-4f5c-88a6-6d4263500ab0","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.2","prompt":"(f) Where an isolation valve has not been fitted above the alarm valve, the main stop valve should be closed, enabling a partial test of the alarm valve.\n NOTE: Consider full testing at the first opportunity (at which time the isolation test valve should be installed).","input":null,"possible_fault":"Main stop valve not closed for test","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.2 - Main stop valve not closed for partial test","severity_level":"non-critical","fault_id":"recHmpRVgkDF0WWhL","prompt_id":"recHmpRVgkDF0WWhL_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"d3429ea0-991e-47b9-9b39-ee585c261d1c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.3","prompt":"(a) CHECK oil level is correct and visually assess condition of oil.","input":null,"possible_fault":"Low oil level or contaminated oil","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.3 - Air compressor oil level/condition inadequate","severity_level":"non-critical","fault_id":"rec1qIVXwF0MkogYK","prompt_id":"rec1qIVXwF0MkogYK_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"d370ea14-7b97-4d43-b25f-9f71e72de5be","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.8.B","prompt":"(a) Low air pressure alarm operates at predetermined levels.","input":null,"possible_fault":"Alarm operates at incorrect pressure","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.8 - Low air pressure alarm activation level incorrect","severity_level":"non-critical","fault_id":"recxcWj40FgPdCW0n","prompt_id":"recxcWj40FgPdCW0n_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"d42d7f2b-7a4c-44b4-b06e-323f5c75c41b","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.9","prompt":"(b) VERIFY correct operation of the fire brigade alarm from each pre-action valve or group of pre-action valves. Where the system is monitored, ensure the alarm has activated the alarm signalling equipment.\n NOTE: Where multiple pre-action valve assemblies are separately identified at the FIP, only one transmission from the FIP to the monitoring station is required.","input":null,"possible_fault":"Fire brigade alarm not transmitting","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.9 - Fire brigade alarm transmission failure from valve","severity_level":"critical","fault_id":"reclSHy8MG9OG0F0r","prompt_id":"reclSHy8MG9OG0F0r_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"d95debc6-38a6-4d74-8d30-239218b22224","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.6.B","prompt":"(a) CHECK cylinder contents per pressure gauge.","input":null,"possible_fault":"Low nitrogen cylinder pressure","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.6 - Nitrogen cylinder pressure below requirements","severity_level":"critical","fault_id":"recTutCCLToX6YNxB","prompt_id":"recTutCCLToX6YNxB_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"e4529a62-08ae-4047-8cf9-2984b811451a","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.5.B","prompt":"(a) RECORD readings from each pressure gauge.","input":null,"possible_fault":"Pressure readings not recorded","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.5 - Pressure gauge readings not recorded","severity_level":"non-conformance","fault_id":"recT2FlvLGwJIXHS8","prompt_id":"recT2FlvLGwJIXHS8_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"e50c5ca8-b521-4d2f-9063-fdedf34ce4a3","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.3","prompt":"(b) CHECK regulator is locked and set in the correct position.","input":null,"possible_fault":"Regulator unlocked or incorrect setting","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.3 - Air compressor regulator not locked/set correctly","severity_level":"non-critical","fault_id":"rec3LLGaxShq4718u","prompt_id":"rec3LLGaxShq4718u_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"f51a395b-e202-42df-bc4e-1d246f9dfd42","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.2.A","prompt":"CHECK that all pressure gauge readings are within the ranges required and RECORD readings from each pressure gauge.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recYoNdhqHkGu6ySX_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"f9fef669-beac-4559-86aa-8911333f9324","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.4","prompt":"INSPECT and TEST in accordance with Section 6.","input":null,"possible_fault":"Electrical detection system malfunction","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.4 - Electrical detection not operating per Section 6","severity_level":"critical","fault_id":"recXsmD43fvLGts5o","prompt_id":"recXsmD43fvLGts5o_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"fb03438f-70da-47e2-8f8e-9aca39f527af","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE ACTION SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"2.2","prompt":"(b) OPERATE each pre-action valve by releasing the system via electrical detection subsystem.","input":null,"possible_fault":"Pre-action valve does not operate","possible_fault_description":"AS1851 2012 TABLE 2.4.5.2 ITEM 2.2 - Pre-action valve not operating via electrical detection","severity_level":"critical","fault_id":"recJOVhmsxTE6VPvR","prompt_id":"recJOVhmsxTE6VPvR_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"6_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"},{"id":"fc85c399-b8f8-443e-932a-09040450bd73","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.5.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS PRE-ACTION SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Pre-actions Systems","variant":null,"variant_id":"recvUb7ks9fiR4fCf","item_no":"1.2.B","prompt":"CHECK that all pressure gauge readings are within the ranges required and RECORD readings from each pressure gauge.","input":null,"possible_fault":"Pressure readings outside required ranges","possible_fault_description":"AS1851 2012 TABLE 2.4.5.1 ITEM 1.2 - Supervisory/diaphragm/stop pressures incorrect","severity_level":"non-critical","fault_id":"reczUtURkLnfIdVHV","prompt_id":"reczUtURkLnfIdVHV_prompt","inspection_id":"c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8","grouping_key":"1_month::c_recvUb7ks9fiR4fCf_recllMaGwCBycgLb8"}]},{"id":"recw9mfMuplsVem7l","name":"Fire Spinkler : Dry Pipe Systems","checklist":[{"id":"095f8d01-239b-4c8a-bbf5-9468ff789acc","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"4.3","prompt":"FIT new dry pipe valve seats and seals. FIT new faceplate gasket (perishable items).","input":null,"possible_fault":"New valve components not fitted","possible_fault_description":"AS1851 2012 TABLE 2.4.3.4 ITEM 4.3 - Dry pipe valve seats/seals/gasket not replaced","severity_level":"recommendation","fault_id":"recK5wpPKAikfFN89","prompt_id":"recK5wpPKAikfFN89_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"5_year::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"153accb0-509d-41b4-8aad-7e9dec4fdebd","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.5.A","prompt":"(a) RECORD reading from each pressure gauge. \n(b) VERIFY pressure gauge readings are within the ranges required.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recNTeE5XOhrg3zb6_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"1a9cc71a-405c-49bb-a932-1d73dc705a4c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.2.B","prompt":"(d) RECORD time(s) to operation of alarms gong(s) and verify that these do not exceed 180 s.","input":null,"possible_fault":"Alarm gong time exceeds 180 seconds","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.2(d) - Alarm gong operation time >180 seconds","severity_level":"non-critical","fault_id":"recqr2fJVIn00jERB","prompt_id":"recqr2fJVIn00jERB_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"28e06753-961c-4ea7-8266-42cd8fe3321b","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.5.B","prompt":"(a) RECORD reading from each pressure gauge. \n(b) VERIFY pressure gauge readings are within the ranges required.","input":null,"possible_fault":"Pressure gauge readings not recorded\nPressure readings outside required range","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.5(a) - Pressure gauge readings not recorded\nAS1851 2012 TABLE 2.4.3.2 ITEM 2.5(b) - Pressure gauge readings not within range","severity_level":"non-conformance","fault_id":"recWw8A7pkWstw6NY","prompt_id":"recWw8A7pkWstw6NY_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"2c22dce4-cf0d-4d50-b421-f77ea43f3b87","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.2","prompt":"(e) VERIFY correct operation of the fire brigade alarms from each control assembly or group of control assemblies. Where the system is monitored, ensure the alarm has activated the alarm signalling equipment. NOTE: Where multiple control valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.","input":null,"possible_fault":"Brigade alarms not operating correctly","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.2(e) - Fire brigade alarms/ASE not activating properly","severity_level":"critical","fault_id":"recYqCSf7xU6N3rCC","prompt_id":"recYqCSf7xU6N3rCC_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"2cdab97f-443b-4683-90c2-49cf385a61b6","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"3.3","prompt":"CHECK that the water distribution pipe work is correctly pitched to drain.","input":null,"possible_fault":"Water distribution pipes incorrectly pitched","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.3 - Pipework not correctly pitched to drain","severity_level":"non-conformance","fault_id":"recAotdi6pRoxzfFy","prompt_id":"recAotdi6pRoxzfFy_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_year::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"30c346ba-1376-47f2-939a-b440aa64c994","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.8","prompt":"DRAIN condensate from condensate trap.","input":null,"possible_fault":"Condensate not drained from trap","possible_fault_description":"AS1851 2012 TABLE 2.4.3.1 ITEM 1.8 - Condensate accumulation in condensate trap","severity_level":"non-critical","fault_id":"rec9t7GHO36vjOqkn","prompt_id":"rec9t7GHO36vjOqkn_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"36edb6ad-9895-4983-ae87-aba2dc1f9243","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.1","prompt":"COMPLETE all monthly wet pipe service activities listed in Table 2.4.2.1 that are applicable to a dry pipe system.","input":null,"possible_fault":"Wet pipe activities not completed","possible_fault_description":"AS1851 2012 TABLE 2.4.3.1 ITEM 1.1 - Applicable wet pipe monthly tasks incomplete","severity_level":"non-conformance","fault_id":"recm3KT077bPBaAF9","prompt_id":"recm3KT077bPBaAF9_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"3fb348a0-6f59-4aaf-9648-ad5bc80e9a57","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.4","prompt":"RESTORE FIP/ASE to operational status.","input":null,"possible_fault":"FIP/ASE not restored to operational","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.4 - FIP/ASE not restored to operational status","severity_level":"non-conformance","fault_id":"recsFt1wuoz0geDL5","prompt_id":"recsFt1wuoz0geDL5_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"4007778e-46f4-481c-8dd3-52a1c7288280","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.5.B","prompt":"VERIFY that air compressor operates at specified cut-in and cut-out pressures.","input":null,"possible_fault":"Cut-in/cut-out pressures incorrect","possible_fault_description":"AS1851 2012 TABLE 2.4.3.1 ITEM 1.5 - Compressor pressures not at specified levels","severity_level":"non-critical","fault_id":"reccZ9pLS8pEUlnHQ","prompt_id":"reccZ9pLS8pEUlnHQ_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"4494108b-499d-4fde-8220-a72fc5c8464d","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"4.1","prompt":"COMPLETE all monthly, six-monthly and yearly service activities, listed in Tables 2.4.3.1, 2.4.3.2 and 2.4.3.3.","input":null,"possible_fault":"Service activities not completed","possible_fault_description":"AS1851 2012 TABLE 2.4.3.4 ITEM 4.1 - Monthly/six-monthly/yearly tasks incomplete","severity_level":"non-conformance","fault_id":"recmaUKM0EU9nFC4q","prompt_id":"recmaUKM0EU9nFC4q_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"5_year::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"57699a7b-99f9-439d-8379-3ba2b963891e","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.2.A","prompt":"CHECK system air pressure is reading within the range required.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec4yvyk0TSdrluqx_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"58da7932-3d1d-40e7-94a3-e4bc7c81fb75","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.6","prompt":"VERIFY: \n(b) Low air pressure alarm(s) visual indicator and sounders are operational.","input":null,"possible_fault":"Visual/audible alarms not operational","possible_fault_description":"AS1851 2012 TABLE 2.4.3.1 ITEM 1.6(b) - Low air alarm indicators/sounders inoperative","severity_level":"critical","fault_id":"reczUAJdUYD0t0oBs","prompt_id":"reczUAJdUYD0t0oBs_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"5cc26873-4f48-4423-a1b8-aa094907c32f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.4","prompt":"CHECK oil level and visually assess condition of oil.","input":null,"possible_fault":"Oil level low/oil condition poor","possible_fault_description":"AS1851 2012 TABLE 2.4.3.1 ITEM 1.4 - Compressor oil level low or oil quality poor","severity_level":"non-critical","fault_id":"rec0DEWNXqpxetZf6","prompt_id":"rec0DEWNXqpxetZf6_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"63041cab-edd1-4d2e-811f-b6133a9e51bb","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.2","prompt":"(b) OPERATE each alarm valve by releasing air from system.","input":null,"possible_fault":"Alarm valve fails to operate","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.2(b) - Alarm valve not operating when air released","severity_level":"critical","fault_id":"recROsAPDqRyem3Ug","prompt_id":"recROsAPDqRyem3Ug_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"6855861c-66d7-467b-ab50-95521dc42047","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"3.2","prompt":"REPLACE the desiccators.","input":null,"possible_fault":"Desiccators not replaced","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.2 - Air desiccators not replaced annually","severity_level":"recommendation","fault_id":"recWXSLF6GWzYIeGa","prompt_id":"recWXSLF6GWzYIeGa_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_year::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"6a07a8f1-ea87-422b-a642-963879f6098f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.5.A","prompt":"VERIFY that air compressor operates at specified cut-in and cut-out pressures.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recTxEAHZQJuI9CjH_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"81ca5841-ac51-49da-9c48-e3313e722b09","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.2","prompt":"(c) CHECK for correct operation of alarms and accelerator or exhauster.","input":null,"possible_fault":"Alarms/accelerator not operating","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.2(c) - Alarms/accelerator/exhauster incorrect operation","severity_level":"critical","fault_id":"recBp9dnw1qz7PwfR","prompt_id":"recBp9dnw1qz7PwfR_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"8c5cf14d-95b7-44de-a547-7925f16d07fc","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"4.4","prompt":"FIT new seals as appropriate. CHECK and CLEAN operating mechanism. FIT a new faceplate.","input":null,"possible_fault":"New seals/mechanism/faceplate not fitted","possible_fault_description":"AS1851 2012 TABLE 2.4.3.4 ITEM 4.4 - Accelerator/exhauster components not serviced","severity_level":"non-critical","fault_id":"recvbtxLaI5JqKsvs","prompt_id":"recvbtxLaI5JqKsvs_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"5_year::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"925a4feb-e4f7-48ee-88ae-140027ff5ccf","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.4 FIVE-YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"4.2","prompt":"COMPLETE all five-yearly wet pipe service activities listed in Table 2.4.2.4 that are applicable to a dry pipe system.","input":null,"possible_fault":"Wet pipe five-yearly tasks not done","possible_fault_description":"AS1851 2012 TABLE 2.4.3.4 ITEM 4.2 - Applicable wet pipe five-yearly tasks incomplete","severity_level":"non-conformance","fault_id":"recnpp0tNeO06o7Ka","prompt_id":"recnpp0tNeO06o7Ka_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"5_year::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"a1048754-b345-44ed-ab63-10f1eb81ebd6","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.3","prompt":"CHECK desiccant condition and replace if necessary.","input":null,"possible_fault":"Desiccant condition poor/needs replace","possible_fault_description":"AS1851 2012 TABLE 2.4.3.1 ITEM 1.3 - Desiccant condition deteriorated/saturated","severity_level":"recommendation","fault_id":"rec16upzEOPtt3AFh","prompt_id":"rec16upzEOPtt3AFh_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"c122fb1a-aa80-4786-87ee-70f3ef142258","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.7","prompt":"SIMULATE operation of dry pipe alarm valve and OPERATE local and fire brigade alarms through the bypass valve(s). Where the system is monitored, ensure the alarm has activated the alarm signalling equipment. (Refer to manufacturer’s operating manual.) NOTE: Where multiple control valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.","input":null,"possible_fault":"Alarms fail to operate via bypass","possible_fault_description":"AS1851 2012 TABLE 2.4.3.1 ITEM 1.7 - Dry pipe alarm simulation failed via bypass","severity_level":"critical","fault_id":"recvdN9LWcD9OI5Vs","prompt_id":"recvdN9LWcD9OI5Vs_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"c779b044-a9b8-42b9-a62d-ba589f439aa1","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.3 YEARLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"3.1","prompt":"COMPLETE all monthly and six-monthly service activities listed in Tables 2.4.3.1 and 2.4.3.2 and all yearly wet pipe service activities listed in Table 2.4.2.3 that are applicable to a dry pipe system.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.3.3 ITEM 3.1 - Required service activities not completed","severity_level":"non-conformance","fault_id":"recMUqbNDX3P0S7KD","prompt_id":"recMUqbNDX3P0S7KD_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_year::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"d33d58bb-1b4e-4f32-83c6-4da724280d41","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.1","prompt":"COMPLETE all monthly service activities listed in Table 2.4.3.1 and all six-monthly wet pipe service activities listed in Table 2.4.2.2 that are applicable to a dry pipe system.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.1 - Monthly/six-monthly tasks not completed","severity_level":"non-conformance","fault_id":"recpIfyPQMj6ye2zT","prompt_id":"recpIfyPQMj6ye2zT_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"d73e2370-a7ba-4183-98f6-edc038d58539","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.2.B","prompt":"CHECK system air pressure is reading within the range required.","input":null,"possible_fault":"Air pressure outside required range","possible_fault_description":"AS1851 2012 TABLE 2.4.3.1 ITEM 1.2 - System air pressure not within specified range","severity_level":"non-critical","fault_id":"recRqi1akfccDTE8a","prompt_id":"recRqi1akfccDTE8a_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"dfb26779-0880-4cb4-90c8-8edb3649b4eb","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.6","prompt":"RESET and SECURE all valve and alarms cocks in the open position or the closed position, as labelled.","input":null,"possible_fault":"Valves/alarm cocks not properly reset","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.6 - Control assemblies not reset/secured correctly","severity_level":"non-critical","fault_id":"recAK6v7eW5WMS5qd","prompt_id":"recAK6v7eW5WMS5qd_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"e03e0ee9-74cd-482a-bdee-fbb0b3d0ad8c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.2","prompt":"(f) Where an isolation valve has not been fitted above the alarm valve, the main stop valve should be mostly closed, enabling a partial test of the alarm valve. NOTE: Consider full testing at the first opportunity (at which time the isolation test valve should be installed).","input":null,"possible_fault":"Main stop valve not properly adjusted","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.2(f) - Main stop valve not mostly closed for test","severity_level":"non-critical","fault_id":"rec4EiotNE3EcQnH9","prompt_id":"rec4EiotNE3EcQnH9_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"e83d85fd-3d4d-4d48-9ccd-9ccd505daab5","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.3","prompt":"RESTORE system air pressure and verify the alarm has reseated.","input":null,"possible_fault":"System pressure not restored/not reseat","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.3 - Air pressure not restored or alarm not reseated","severity_level":"non-critical","fault_id":"recmua3qNu1jMWKmr","prompt_id":"recmua3qNu1jMWKmr_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"ec6bfe9e-ad53-42f2-aa05-90963e7d4ea3","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.6.B","prompt":"VERIFY: (a) Low air pressure alarm operates at predetermined levels.","input":null,"possible_fault":"Alarm operates at wrong pressure","possible_fault_description":"AS1851 2012 TABLE 2.4.3.1 ITEM 1.6(a) - Low air alarm not at predetermined levels","severity_level":"non-critical","fault_id":"recjjPhbShn3UKvdT","prompt_id":"recjjPhbShn3UKvdT_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"ecc96c1f-7caa-464c-bacb-0ab236819adc","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.2.A","prompt":"(d) RECORD time(s) to operation of alarms gong(s) and verify that these do not exceed 180 s.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recJCj5EXSMWcpmxj_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"ed2e20fa-83be-45c8-a3de-77121bc937ec","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.2 SIX-MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"2.2","prompt":"(a) Where fitted, CLOSE isolation valve located above alarm valve (to prevent entry of water into system piping).","input":null,"possible_fault":"Isolation valve not closed properly","possible_fault_description":"AS1851 2012 TABLE 2.4.3.2 ITEM 2.2(a) - Isolation valve above alarm valve not closed","severity_level":"non-critical","fault_id":"reckA5OjX6iBbYw3l","prompt_id":"reckA5OjX6iBbYw3l_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"6_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"},{"id":"f5b316df-b0d6-4bfc-97b7-08779d274708","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.3.1 MONTHLY SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS DRY PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Dry Pipe Systems","variant":null,"variant_id":"recw9mfMuplsVem7l","item_no":"1.6.A","prompt":"VERIFY: (a) Low air pressure alarm operates at predetermined levels.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rechGo2jRFOeKvPYC_prompt","inspection_id":"c_recw9mfMuplsVem7l_recllMaGwCBycgLb8","grouping_key":"1_month::c_recw9mfMuplsVem7l_recllMaGwCBycgLb8"}]},{"id":"recXnAJDdJ3cQuUpx","name":"Fire Spinkler : Wet Pipe Systems","checklist":[{"id":"0671c2bf-3157-4860-a4a1-04f35958e4cd","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.11.A","prompt":"(a) RECORD reading from each pressure \ngauge.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recGQSangL6U2cxNT_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"0912b808-bf44-4a2d-82be-1c5bafd7349c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.3.A","prompt":"(b) OPERATE all subsidiary stop valves (floor\n isolation valves, tail-end valves).Ensure that\n they are fully open and, where applicable,\n secured in the open position and are\n correctly labelled.\n NOTE: ‘Text deleted’.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec13WjS93iE5cUUw_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"0aff8f9a-f37b-41e0-984b-d2f25c8da866","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.13","prompt":"INSPECT accumulated spray residue on sprinklers and reapply protective medium (petroleum jelly/paper bags). \nNOTE: The required frequency of inspection depends upon the amount of spraying being done and could be accomplished at the same time as the cleaning of booth.","input":null,"possible_fault":"Spray residue on sprinklers","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.13 - Spray residue accumulated on sprinklers","severity_level":"non-critical","fault_id":"rec9UAjXr3CE5zPaN","prompt_id":"rec9UAjXr3CE5zPaN_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"0cbefff6-f072-4d62-a540-8bbddc06e0d4","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.18","prompt":"Perform routine service in accordance with \nSection 5.","input":null,"possible_fault":"Low water level, tank damage, fitting fault","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.18 - Water supply tank level/condition not meeting AS2941 requirements.","severity_level":"critical","fault_id":"recSQABqXd8hnhUvy","prompt_id":"recSQABqXd8hnhUvy_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"0de8e867-505b-4928-8094-f3401837e0d8","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.7","prompt":"CHECK each pressure switch and ensure that the \ncover is in place, correctly labelled, securely \nmounted and free from any condition likely to \nadversely affect its function.","input":null,"possible_fault":"Missing cover, loose mount, no label","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.7. - Pressure switch cover missing or mounting insecure.","severity_level":"non-critical","fault_id":"recqe0w5O4TmSzAvk","prompt_id":"recqe0w5O4TmSzAvk_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"0ee903e2-0539-455a-bfe4-086318d28f90","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.11.B","prompt":"Where an ASE is standalone and is connected to a power supply unit and batteries: (a) CHECK the batteries for any condition likely to adversely affect its function and (b) Where the battery has not been replaced in the previous two years, VERIFY the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":"DATE","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recgx5qAyEVXxjbeF_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"10b1b323-eb49-4360-a6c9-8c631ad6e069","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.5.A","prompt":"(ii) Reduce the water flow through the flow-measuring device to that corresponding to the most unfavourable duty point. Record the flowing pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"reck96HnyL6q3wpJX_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"163dd685-1435-4baf-9869-92e6488e2479","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.5","prompt":"INSPECT hand pump seatings and FIT new pump washers and path cock washers. FIT new gland packing. For electric jacking pumps, maintain as per manufacturer’s instructions.","input":null,"possible_fault":"Pump washers/gland packing worn","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.5 - Jacking pump components require renewal","severity_level":"non-critical","fault_id":"recgt7S0KQgGo3s73","prompt_id":"recgt7S0KQgGo3s73_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"1934d1b2-ed5f-4ba3-a3f0-0fdb513e201c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.5.B","prompt":"(iii) Shut off water flow to flow-measuring device. Record static pressure.","input":null,"possible_fault":"Static pressure insufficient","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.5(iii) - Static pressure after flow test inadequate","severity_level":"non-critical","fault_id":"recqWNuZgHYnyBIh2","prompt_id":"recqWNuZgHYnyBIh2_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"1ab70c97-db0d-4d21-9b6b-1ca65f5bce86","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.14","prompt":"INSPECT for the correct operation of each \nDSEP/DBEP strobe indicator, where fitted.","input":null,"possible_fault":"Strobe not operating, damaged unit","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.14. - DSEP/DBEP strobe indicator failed to operate during test.","severity_level":"critical","fault_id":"rec3wVTVTAMBjBOKn","prompt_id":"rec3wVTVTAMBjBOKn_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"1d0b772d-c2a8-4127-988a-306a8692d894","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.11.C","prompt":"Where an ASE is standalone and is connected to a power supply unit and batteries: (a) CHECK the batteries for any condition likely to adversely affect its function and (b) Where the battery has not been replaced in the previous two years, VERIFY the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":null,"possible_fault":"Battery condition deteriorated","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.11 - ASE battery condition/test unsatisfactory","severity_level":"non-critical","fault_id":"recTnYtWwplbPY405","prompt_id":"recTnYtWwplbPY405_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"1ec03cac-5381-4807-948c-7934de12e4a0","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.6","prompt":"CHECK that each isolating valve to each \nautomatic pump start device is locked in the \nopen position.","input":null,"possible_fault":"Valve not locked open, damaged lock","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.6 - Isolating valve not properly locked in open position.","severity_level":"non-conformance","fault_id":"recxGJTEwifDOVLzd","prompt_id":"recxGJTEwifDOVLzd_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"209a633f-4693-4a25-bb9c-5f3acfbbbecf","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.10","prompt":"(a) OPERATE (two full turns) all water supply \nstop valves (including backflow prevention \nstop valves but excluding underground key￾operated valves) and verify they are fully \nopen, secure in the open position (relaxed \n¼ turn if appropriate) and are correctly \nlabelled. \nNOTES:\n1 Where more than 12 water supply stop \nvalves are distributed throughout a \nhigh-rise building, forming part of a \ncombined sprinkler/hydrant system, the \nactions under actions (a) and (b) may be \nconducted on a rotating basis. \n2 The period between testing of all water \nsupply stop valves should not exceed \n3 months","input":null,"possible_fault":"Valve seized, incorrect position, no label","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.10 - Water supply valve not fully open or incorrectly labelled.","severity_level":"critical","fault_id":"recTibcbTuInBPrTj","prompt_id":"recTibcbTuInBPrTj_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"27b12b79-dcf3-4bf5-83aa-36b3583c004a","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.12.B","prompt":"CONDUCT a water supply test through a flow-measuring device or other appropriate methods that the flow corresponds to the required quick fill-rate.","input":null,"possible_fault":"Quick fill rate insufficient","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.12 - Tank quick fill rate below requirements","severity_level":"non-critical","fault_id":"reccipsNYeGrwAA23","prompt_id":"reccipsNYeGrwAA23_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"2b963d44-bfc3-48d6-a08a-77e4b804da68","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.26","prompt":"(b) CHECK for shrink wrapping (encapsulation) where not employed previously.","input":null,"possible_fault":"New shrink wrapping present","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.26(b) - Shrink wrapping now used but not in design","severity_level":"non-critical","fault_id":"recsHrdEbvSvNLyjr","prompt_id":"recsHrdEbvSvNLyjr_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"2d05205a-292d-499b-8016-5574855ae3bc","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.1","prompt":"COMPLETE all monthly service activities, as listed in Table 2.4.2.1.","input":null,"possible_fault":"Monthly items not completed, defects found","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.1 - Monthly service items incomplete or showing defects.","severity_level":"non-conformance","fault_id":"recQNVhcbdxlonW61","prompt_id":"recQNVhcbdxlonW61_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"2d2938a2-dcd1-4cf2-a1ca-2c465c1a7096","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.1","prompt":"COMPLETE all monthly, six-monthly and yearly service activities, as listed in Tables 2.4.2.1, 2.4.2.2 and 2.4.2.3.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.1 - Required monthly/six-monthly/yearly tasks not done","severity_level":"non-conformance","fault_id":"rec4nGSODgJSnnCdF","prompt_id":"rec4nGSODgJSnnCdF_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"2e322de2-a55d-4f2b-adfb-ad862cd7bc68","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.3","prompt":"(b) For packed gland variants, FIT new gland packing.","input":null,"possible_fault":"Gland packing worn/leaking","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.3(b) - Packed gland variants require new packing","severity_level":"non-critical","fault_id":"recnfHhtoHpulogvb","prompt_id":"recnfHhtoHpulogvb_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"2fb8df6a-0faa-4d13-9436-fa6c516e37a9","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.7","prompt":"CHECK suction inlet strainer(s) or screen(s) for any condition likely to affect its function. Where blocked, CLEAN the suction inlet strainers or screens.","input":null,"possible_fault":"Blocked strainer, damaged screen","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.7 - Suction inlet strainer/screen blocked or damaged affecting function.","severity_level":"non-critical","fault_id":"rec2ysVi0LqN5H3Hh","prompt_id":"rec2ysVi0LqN5H3Hh_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"310fbd7d-32d3-4764-a25c-b3d7d8926ea2","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.19","prompt":"At 30 years and every 10 years thereafter:\n (a) Single MJC installed for alarm purposes only or to control a group of distributors, CHECK\n in situ for evidence of paint loading, corrosion, etc. Replace if necessary.","input":null,"possible_fault":"Paint loading/corrosion on MJC","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.19(a) - Single MJC shows paint/corrosion damage","severity_level":"non-critical","fault_id":"recwRr1QyEXVu8rHW","prompt_id":"recwRr1QyEXVu8rHW_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"10_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"31c39416-b2d9-4581-b5e1-911bc272aa40","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.4.B","prompt":"Test each valve monitor by operating the valve and VERIFY the correct indication at the CIE.","input":null,"possible_fault":"No indication, wrong indication at CIE","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.4. - Valve monitor failed to indicate correctly at CIE.","severity_level":"critical","fault_id":"recsWykRLQE1BkWN8","prompt_id":"recsWykRLQE1BkWN8_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"32aebf39-78ab-4d47-8c01-964a485ca5ab","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.15.B","prompt":"(a) RECORD reading from each pressure \ngauge.","input":null,"possible_fault":"Gauge unreadable, no reading possible","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.15 - System pressure gauge unreadable after alarm test.","severity_level":"non-critical","fault_id":"recOiPxo6GGO2189p","prompt_id":"recOiPxo6GGO2189p_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"32f4ad20-1429-43dc-b04a-31ad0712eb5a","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.17","prompt":"CHECK that exposed water distribution system, including pipework, pipe supports and valves, appear free from corrosion and damage, not subject to external loads and pipework is properly supported.","input":null,"possible_fault":"Corrosion/damage to system","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.17 - Pipework shows corrosion/damage/poor support","severity_level":"non-critical","fault_id":"recyzGPbrZpmWpjPJ","prompt_id":"recyzGPbrZpmWpjPJ_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"337dd7a5-2efb-43c8-b1f4-2d94c37cf557","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.17","prompt":"TEST each manual pump starting device and \npump operation in accordance with Section 3.","input":null,"possible_fault":"Manual start failed, pump not responding","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.17. - Manual pump start device failed to operate pump.","severity_level":"critical","fault_id":"recM8nJdzFGrFLWhH","prompt_id":"recM8nJdzFGrFLWhH_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"33bea9a4-79ab-4c96-8a6f-50507552d814","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.21","prompt":"(a) CHECK for presence of unprotected areas such as mezzanines, platforms and building extensions.","input":null,"possible_fault":"Unprotected areas present","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.21(a) - Mezzanines/platforms unprotected","severity_level":"critical","fault_id":"recGfXc64UDmH4KJ7","prompt_id":"recGfXc64UDmH4KJ7_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"3467ad52-7676-4c9d-9982-34a738325681","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.9","prompt":"CLEAN the strainer and lubricate the external gong mechanism.","input":null,"possible_fault":"Strainer dirty/mechanism stiff","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.9 - Gong strainer/mechanism requires cleaning","severity_level":"non-critical","fault_id":"rec8NY434PG5tECNX","prompt_id":"rec8NY434PG5tECNX_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"353d9524-8222-4b9e-9e15-9ea1e7c18002","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.14","prompt":"Perform routine service in accordance with Section 5.","input":null,"possible_fault":"Tank service requirements not met","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.14 - Atmospheric tanks require Section 5 service","severity_level":"non-conformance","fault_id":"recupG2ADVqcKsaK8","prompt_id":"recupG2ADVqcKsaK8_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"3792cb61-2e08-4b91-9037-884c09e78848","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.2.A","prompt":"(b) VERIFY that pressure readings on the low pressure side of the valves are within the range stated at the pressure-reducing valve station.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recJlPUbT40ihibCX_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"379c49e7-b419-4607-86b4-63e2108c70b2","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1","prompt":"CHECK that control valve assembly area is \nunobstructed and free of any condition that may \nadversely affect the operation or access.","input":null,"possible_fault":"Obstructed access, debris, physical damage","possible_fault_description":"Physical obstruction or damage preventing valve operation. AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.","severity_level":"non-critical","fault_id":"recQQxtyYWRqTXkCH","prompt_id":"recQQxtyYWRqTXkCH_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"3973571e-d9cd-479b-9fbb-edff45c4c79f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.16","prompt":"GENERATE foam through test foam maker or by other means. Check proportioning ratio (refractometer or conductivity test) and drainage rate. Top up foam concentrate tank.","input":null,"possible_fault":"Foam proportioning/drainage rate incorrect","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.16 - Foam system performance outside specifications","severity_level":"non-critical","fault_id":"recEIDRwvnx3vYOdR","prompt_id":"recEIDRwvnx3vYOdR_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"3b8baaba-5375-48ff-a0d6-28aedfd5116c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.21","prompt":"(c) CHECK for the need to install sprinkler guards.","input":null,"possible_fault":"Guards needed but not installed","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.21(c) - Sprinkler guards required but missing","severity_level":"recommendation","fault_id":"recDBrjqOfJkYTETr","prompt_id":"recDBrjqOfJkYTETr_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"3d6dfa25-3713-4d23-9ff0-0892b1209f70","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.11","prompt":"(b) VERIFY pressure gauge readings are within \nthe ranges required.","input":null,"possible_fault":"Pressure out of range, gauge faulty","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.11 - System pressure outside specified operating parameters.","severity_level":"non-critical","fault_id":"recG69xbQnLcb4bnM","prompt_id":"recG69xbQnLcb4bnM_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"3d815700-e091-4a73-b9d1-dfc63d82d28e","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.15.A","prompt":"(b) VERIFY pressure gauge readings are within \nthe ranges required.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rechtNh7MxX4KnsJY_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"3e5822f7-f9cc-483d-8feb-b05d507678c4","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.2","prompt":"CHECK that there are spare sprinklers of \nappropriate quantity and type including a \nmatching sprinkler spanner for each type of \nsprinkler fitted, available.","input":null,"possible_fault":"Insufficient spares, wrong type, no spanner","possible_fault_description":"Missing or inadequate spare sprinklers/tools per AS3786. AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.2.","severity_level":"non-conformance","fault_id":"rec5e5hbmEw0zS4KK","prompt_id":"rec5e5hbmEw0zS4KK_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"3e811d40-7e4d-4f32-86c7-023be8577f6d","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.20","prompt":"CHECK for obstructions likely to impede sprinkler discharge and for adequate clear space below sprinklers.","input":null,"possible_fault":"Obstructions impede discharge","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.20 - Obstructions present/inadequate clearance","severity_level":"critical","fault_id":"recM6brAISVbCeXEV","prompt_id":"recM6brAISVbCeXEV_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"3fee6616-20ae-4c18-a2ff-9df6e9dfa41f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.3","prompt":"(a) For screw-down style valves, EXAMINE seating and fit new washers.","input":null,"possible_fault":"Valve seating/washers worn","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.3(a) - Screw-down valve seating/washers require renewal","severity_level":"non-critical","fault_id":"rec71PzP7FCbnMUVi","prompt_id":"rec71PzP7FCbnMUVi_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"3ff03d80-fcf0-4b9a-95aa-ef0b5453625f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.6","prompt":"(d) VERIFY that the time for pressure recovery aligns with previously recorded value. NOTE: Where the building exceeds four storeys in height, care should be taken to ensure that the static head of the installation does not excessively elevate the residual pressure reading.\nNOTE: Where the building exceeds four storeys in height, care should be taken to ensure that the static head of the installation does not excessively elevate the residual pressure reading.","input":null,"possible_fault":"Recovery time changed significantly","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.6 - Pressure recovery time differs from previous recordings.","severity_level":"non-critical","fault_id":"recZBtKS8k0oN6FaK","prompt_id":"recZBtKS8k0oN6FaK_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"40c6d637-cffa-4440-9368-c43714dee02b","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.3.B","prompt":"OPERATE pressure-relief valve and note operating pressure is within the range stated on the nameplate provided at the reducing valve station. \nNOTES: 1 This test of the pressure-relief valve may be carried out using a portable test apparatus. \n2 Inappropriate settings for pressure-relief valves can result in very large quantities of water flowing to waste. Ensure settings are maintained to have pressures as identified and not higher than allowed by system component rated working pressures.","input":null,"possible_fault":"Operating pressure outside range","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.3 - Relief valve pressure not within nameplate range","severity_level":"non-critical","fault_id":"rec0Wzjno5uGAfavA","prompt_id":"rec0Wzjno5uGAfavA_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"4287f91c-7e09-45b3-8e9f-6e61f067547b","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.5","prompt":"(b) VERIFY that the system flow and pressure requirements are satisfied.","input":null,"possible_fault":"System requirements not satisfied","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.5(b) - System flow/pressure requirements not met","severity_level":"non-conformance","fault_id":"recg80OSTSzqIIhtq","prompt_id":"recg80OSTSzqIIhtq_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"45b0e1f3-53d3-4983-b6b8-da2d223058bf","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.5","prompt":"(c) COMPLETE a water supply test report in accordance with AS 2118.1. \nNOTE: This test should be conducted by substituting the installation and below stop valve pressure gauges with calibrated gauges of known accuracy. Where pumpsets are fitted, the water supply flow test should be performed combined with the pumpset load test requirements in Section 3.","input":null,"possible_fault":"Report not completed per AS2118.1","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.5(c) - Water supply test report incomplete","severity_level":"non-conformance","fault_id":"recuIeYwFeSooFIcS","prompt_id":"recuIeYwFeSooFIcS_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"47f20529-3fe0-4da4-b76a-57669a347c84","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.5.A","prompt":"(i) Discharge water through the flow-measuring device at the flow corresponding to the hydraulically most favourable duty flow. Record the flowing pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recIKwut0sLGjHsVd_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"48f195c1-3f18-4e72-a74a-99af7100334d","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.6.A","prompt":"(b) VERIFY that residual water supply pressure, with drain valve open, is within 10% of the original value recorded.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec9topcI0rwwDpBC_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"4d4684b1-6078-4032-8e56-ec2880988c4a","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.5.A","prompt":"(iii) Shut off water flow to flow-measuring device. Record static pressure.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recrZgMz4ly6AQ90F_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"531fba76-bffa-486d-81be-b3d8f0ee9c22","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.5.A","prompt":"(a) CONDUCT a water supply test, subject to limitations imposed by the water agency controlling the supply source. The test may be a combination of physical testing and calculation as necessary.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rect7QcfgcJIkwK3E_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"54b7549a-dc03-4237-a7da-a66c99f280f2","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.10","prompt":"CLEAN out well of direct brigade alarm, clear water jet, renew gasket, flush drain pipe, remove gear train, check operation of main spindle, remove excess grease and then lubricate.","input":null,"possible_fault":"Brigade alarm blocked/parts worn","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.10 - Direct brigade alarm requires overhaul","severity_level":"non-critical","fault_id":"recHcew2DQHsxrVCT","prompt_id":"recHcew2DQHsxrVCT_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"58bbe31e-dcd9-4fbf-993a-ebed288393dd","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.3","prompt":"(c) For ball valves, CHECK for leakage and replace if leaking.","input":null,"possible_fault":"Ball valve leaking","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.3(c) - Ball valve replacement required due to leakage","severity_level":"non-critical","fault_id":"recdD86WCWvu3448n","prompt_id":"recdD86WCWvu3448n_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"591c16db-36f0-43ce-a988-161d06c067c4","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.5.A","prompt":"RECORD reading from each pressure gauge. VERIFY pressure gauge readings are within the ranges required.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recVXtPDCt8gtQ6Xm_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"5c3bbb2c-4ef8-4c97-ad9d-dd50060170d6","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.3","prompt":"CHECK for damage, legibility and appropriate \nlocation of required signage.","input":null,"possible_fault":"Damaged signs, illegible text, missing signs","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.3 - Signage not compliant with AS1851 marking requirements.","severity_level":"non-conformance","fault_id":"recxHi02GViUJWWpk","prompt_id":"recxHi02GViUJWWpk_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"5d980a3b-1170-4e18-8411-572d8e47b27c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.19","prompt":"CHECK that the concentrate level is correct and \nlevel indicator reads correctly.","input":null,"possible_fault":"Low concentrate level, faulty indicator","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.19 - Foam concentrate level incorrect or indicator reading wrong.","severity_level":"non-critical","fault_id":"rectAN5vH381HxWgb","prompt_id":"rectAN5vH381HxWgb_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"5e7d992d-130e-46ee-b576-1b84d1566ffc","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.15","prompt":"DRAW a sample and verify condition in accordance with NFPA 11 (pH, specific gravity, sediment, expansion ratio, 25% drain time).","input":null,"possible_fault":"Foam concentrate condition poor","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.15 - Foam concentrate fails NFPA 11 tests","severity_level":"non-critical","fault_id":"rech0Zuk5bQoo4Skw","prompt_id":"rech0Zuk5bQoo4Skw_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"5e89d97d-8efb-499e-b06e-a7560167dad6","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.4.A","prompt":"Test each valve monitor by operating the valve and VERIFY the correct indication at the CIE.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec1fnU6xH2VvAwqp_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"5ff67266-7d79-41cd-a1e2-4c00776a95b8","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.14","prompt":"INSPECT all sprinklers inside kitchen hoods and ducts and CLEAN if necessary to remove accumulated grease and any other foreign matter and verify that the sprinkler head is appropriate for this application.","input":null,"possible_fault":"Grease accumulation on sprinklers","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.14 - Kitchen sprinklers contaminated with grease","severity_level":"non-critical","fault_id":"reczTWCgGHbmZgld8","prompt_id":"reczTWCgGHbmZgld8_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"602bf1ad-c2a4-4c66-aef4-2cdbb5579fc9","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.1","prompt":"COMPLETE all monthly and six-monthly service activities, as listed in Tables 2.4.2.1 and 2.4.2.2.","input":null,"possible_fault":"Service activities not completed","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.1 - Previous monthly/six-monthly tasks incomplete","severity_level":"non-conformance","fault_id":"recFAxkssMFMlJy6k","prompt_id":"recFAxkssMFMlJy6k_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"618ffe21-8c8d-48b1-b49a-5a347b5aa511","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.6","prompt":"(a) OPERATE the alarm valve by opening each remote test valve.","input":null,"possible_fault":"Remote test valve fails to operate","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.6(a) - Alarm valve remote test valve inoperable","severity_level":"critical","fault_id":"recZLHRwIpjUsIlHc","prompt_id":"recZLHRwIpjUsIlHc_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"65902868-03b6-4c99-9b9c-decb8dab9f5d","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.6.B","prompt":"(b) RECORD time(s) to operation of alarm gong(s) and verify that time does not exceed 360 s for AS 2118.1 and 180 s for AS 2118.4 systems.","input":null,"possible_fault":"Gong operation time exceeds limit","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.6(b) - Gong time >360s AS2118.1 or >180s AS2118.4","severity_level":"non-critical","fault_id":"reckV1FJXHGUIsfiS","prompt_id":"reckV1FJXHGUIsfiS_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"6746f4a6-ff24-4d6a-b77d-74823dc84b7c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.6.A","prompt":"(b) RECORD time(s) to operation of alarm gong(s) and verify that time does not exceed 360 s for AS 2118.1 and 180 s for AS 2118.4 systems.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recTbuKqpPkj2dz0g_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"6be1d714-14dc-4d9b-9cab-87df9a425d18","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.24","prompt":"CHECK for new building structures, yard storage or the like, exposing unprotected openings, non-fire resistant walls that may require the provision for external sprinklers.","input":null,"possible_fault":"New exposures require protection","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.24 - New structures expose unprotected openings","severity_level":"recommendation","fault_id":"recSi1Wi3OHw5u92Y","prompt_id":"recSi1Wi3OHw5u92Y_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"6f2f9fe6-cd51-4b89-9073-418a9ba0086a","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.2","prompt":"(b) VERIFY correct flow switch indication at the CIE.","input":null,"possible_fault":"Wrong indication, no indication at CIE","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.2 - Flow switch indication incorrect or missing at CIE.","severity_level":"non-conformance","fault_id":"recpeKNsziQxzMALq","prompt_id":"recpeKNsziQxzMALq_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"741ed5cc-f04b-44f0-a5bb-8f781e8583a6","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.6.B","prompt":"(c) CLOSE main drain valve and record time for pressure recovery.","input":null,"possible_fault":"Slow recovery, valve won't close","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.6 - Pressure recovery time excessive or valve closure failed.","severity_level":"non-critical","fault_id":"recy6QQsZR3zqSsBj","prompt_id":"recy6QQsZR3zqSsBj_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"7555d061-bbde-469e-bf2a-25a23f596c41","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.21","prompt":"(b) CHECK for sprinkler spacing and location relative to wall, bulkhead and partition alterations and the introduction of fixtures and fittings shielding sprinkler discharge.","input":null,"possible_fault":"Poor spacing/shielding present","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.21(b) - Sprinkler spacing/discharge shielding issues","severity_level":"non-critical","fault_id":"recsI5XqCD6AXQYG1","prompt_id":"recsI5XqCD6AXQYG1_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"76fd3534-0915-4049-abc6-65ac15566771","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.13","prompt":"VERIFY the correct operation of each alarm \nsignal. Where the system is monitored ensure the \nalarm has activated the alarm signalling \nequipment.","input":null,"possible_fault":"No alarm signal, ASE not activated","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.13 - Alarm signal failed to operate or activate monitoring equipment.","severity_level":"critical","fault_id":"reckSe0E7SuJpyRbU","prompt_id":"reckSe0E7SuJpyRbU_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"7a445655-d0e0-4966-998d-861d7fa77e03","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.2.B","prompt":"(b) VERIFY that pressure readings on the low pressure side of the valves are within the range stated at the pressure-reducing valve station.","input":null,"possible_fault":"Pressure readings outside range","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.2(b) - Low pressure side readings exceed stated range","severity_level":"non-critical","fault_id":"recHP38c295lHZjZ4","prompt_id":"recHP38c295lHZjZ4_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"7d9948ee-adc0-488d-8474-b5ec026ab758","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.15.A","prompt":"(a) RECORD reading from each pressure \ngauge.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recWLCl4HYY7nh6a9_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"80b41554-5852-4945-9d40-43ba2ba026d5","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.8","prompt":"(b) VERIFY that the interface functions as required.","input":null,"possible_fault":"Interface not functioning correctly","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.8(b) - Interface function not operating as required","severity_level":"non-critical","fault_id":"recfUnO2YVDM1pekU","prompt_id":"recfUnO2YVDM1pekU_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"81424203-6190-4026-89c0-a4e1d6fd80a2","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.11","prompt":"CHECK all pressure gauges against a master gauge of known accuracy. Verify that the reading of the gauge under test is within ±30 kPa of the reading of the master gauge at the nominal pressure.","input":null,"possible_fault":"Pressure gauges reading incorrectly","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.11 - Gauges outside ±30kPa accuracy requirement","severity_level":"non-critical","fault_id":"recJVkL6w30FgRJCn","prompt_id":"recJVkL6w30FgRJCn_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"85a3c4c9-d3f3-417e-80e3-0328aeb79296","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.9","prompt":"CLEAN strainer on inlet line, clear water jet, flush drain, renew gasket, check operation of main spindle and striker, remove excess grease and then lubricate.","input":null,"possible_fault":"Alarm gong strainer blocked/parts worn","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.9 - Water motor alarm gong requires service","severity_level":"non-critical","fault_id":"recsgpk8kf2vpxlwE","prompt_id":"recsgpk8kf2vpxlwE_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"8601f124-49c5-4a01-ac66-a9a8fc3d371c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.22","prompt":"CHECK that sprinklers within a compartment are of similar operating characteristics (e.g. area coverage, RTI and temperature rating).","input":null,"possible_fault":"Incompatible sprinklers present","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.22 - Sprinklers have different operating characteristics","severity_level":"non-conformance","fault_id":"recSOkheRcEnLmEF6","prompt_id":"recSOkheRcEnLmEF6_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"875983d8-48d0-49be-9d6b-ef0183a22987","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.11.B","prompt":"(a) RECORD reading from each pressure \ngauge.","input":null,"possible_fault":"Gauge unreadable, no reading possible","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.11 - System pressure gauge unreadable or damaged.","severity_level":"non-critical","fault_id":"recE8dy3aV2HfORls","prompt_id":"recE8dy3aV2HfORls_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"89638210-89dc-4bb0-bdc5-029980df91d9","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.2","prompt":"(a) OPERATE each flow switch test arrangement (automatic or manual).","input":null,"possible_fault":"Flow switch won't operate, no activation","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.2. - Flow switch test arrangement failed to operate.","severity_level":"critical","fault_id":"recAtaaHb8tUWvE4l","prompt_id":"recAtaaHb8tUWvE4l_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"8b93ac06-4c5c-4492-87cf-29c44ea5ede0","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.25","prompt":"CHECK that sprinkler design remains applicable for the occupancy hazard classification and the category of storage involved.","input":null,"possible_fault":"Design not suitable for occupancy","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.25 - Sprinkler design unsuitable for current occupancy","severity_level":"non-conformance","fault_id":"rechetmIdPL4n1bf0","prompt_id":"rechetmIdPL4n1bf0_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"8ca3edc1-2d56-400e-9816-51fa2d026a5f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.3.A","prompt":"OPERATE pressure-relief valve and note operating pressure is within the range stated on the nameplate provided at the reducing valve station. \nNOTES: 1 This test of the pressure-relief valve may be carried out using a portable test apparatus. \n2 Inappropriate settings for pressure-relief valves can result in very large quantities of water flowing to waste. Ensure settings are maintained to have pressures as identified and not higher than allowed by system component rated working pressures.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recXJUCameZTOKNSk_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"8d4e2dd8-0d67-4221-a4bf-6be24d70e14d","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.16","prompt":"(a) TEST each automatic pump starting device \nand pump operation by reducing the applied \nwater pressure to the starting device and run \npump, in accordance with Section 3. \nWhere more than one starting device is \ninstalled, including the manual starting \ndevice, the test may be carried out on a \nrotating basis. The period between the \nexercising of each starting device is not to \nexceed 3 months. Where this would require \nthe pump to start more than 5 times in \nsuccession, the period may be extended to \n6 months.","input":null,"possible_fault":"Pump failed to start, no response","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.16 - Automatic pump start device failed to operate pump.","severity_level":"critical","fault_id":"recaAWgCGAEiRxD96","prompt_id":"recaAWgCGAEiRxD96_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"8df4f055-e34b-4798-b3b0-039ef9a53683","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.5.B","prompt":"RECORD reading from each pressure gauge. VERIFY pressure gauge readings are within the ranges required.","input":null,"possible_fault":"Pressure gauge reading out of range","possible_fault_description":"AS 1851:2012 TABLE 2.4.2.2 ITEM 2.5.B - Gauge reading outside required operating range","severity_level":"non-conformance","fault_id":"recpvsmlWGr0usb3D","prompt_id":"recpvsmlWGr0usb3D_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"8f277d92-9084-4ce6-aa1a-9d9d040f864f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.5","prompt":"INSPECT each main stop valve and alarm cock \nfor each control assembly is secured in the open \nposition and the main stop valve is correctly \nlabelled. \nNOTES: ‘Text deleted’","input":null,"possible_fault":"Valve closed, loose, unlabelled","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.5 - Main stop valve not secured open or incorrectly labelled.","severity_level":"critical","fault_id":"recS6fgh3GUFRf2Ev","prompt_id":"recS6fgh3GUFRf2Ev_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"93a9030b-b571-4035-8c47-f94fadf6f88f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.2","prompt":"(a) OPERATE all pressure-reducing valves and verify correct operation under flow conditions.","input":null,"possible_fault":"Valve fails to operate under flow","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.2(a) - PRV not operating correctly under flow conditions","severity_level":"critical","fault_id":"recJPuJllh5EEL3s4","prompt_id":"recJPuJllh5EEL3s4_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"978d8758-e881-4392-b155-3f477af485ef","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.23","prompt":"CHECK for localized changes in ambient temperatures, which may require different sprinkler temperature ratings (e.g. exposure to freezing or high temperature conditions).","input":null,"possible_fault":"Ambient temp changes affect rating","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.23 - Ambient temperature changes require rating review","severity_level":"informational","fault_id":"recPS0fpbB7Zxx6T2","prompt_id":"recPS0fpbB7Zxx6T2_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"98aec0aa-a929-440c-9707-07f66c315b90","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.5.B","prompt":"(i) Discharge water through the flow-measuring device at the flow corresponding to the hydraulically most favourable duty flow. Record the flowing pressure.","input":null,"possible_fault":"Flow/pressure below requirements","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.5(i) - Most favourable duty point not achieved","severity_level":"critical","fault_id":"recv9WEruVmDyahrM","prompt_id":"recv9WEruVmDyahrM_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"995d32aa-d154-49ce-8e6b-e76341254201","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.26","prompt":"(a) CHECK that sprinkler design remains applicable for storage heights. If height limits are exceeded, check for in-rack (intermediate) sprinklers.","input":null,"possible_fault":"Storage exceeds design height","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.26(a) - Storage height exceeds design/no in-rack sprinklers","severity_level":"non-conformance","fault_id":"rec8Mtp9fCPDEPZHn","prompt_id":"rec8Mtp9fCPDEPZHn_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"9ee7bfb0-4404-4ee6-936c-578f03429360","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.8","prompt":"CHECK the alarm signalling equipment to \nensure that it is securely mounted, free from any \ncondition likely to adversely affect its function \nand is not indicating alarm, fault, loss of \nconnection, or isolated","input":null,"possible_fault":"Loose mounting, fault indication, isolation","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.8 - ASE showing fault/isolation or insecure mounting.","severity_level":"non-critical","fault_id":"rec1n1ZY39s04OFkJ","prompt_id":"rec1n1ZY39s04OFkJ_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"a02ec7a3-9bae-4997-8532-f63326e72485","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.6","prompt":"(a) OPEN the sprinkler control assembly main drain valve without pump(s) running. In the case of grouped valve sets, open one only.","input":null,"possible_fault":"Drain valve seized, won't open fully","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.6 - Main drain valve failed to open or operate correctly.","severity_level":"non-critical","fault_id":"recmyjRwrV3p8gOqQ","prompt_id":"recmyjRwrV3p8gOqQ_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"a163960c-1f69-40f7-8af9-3a51657d17cd","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.6.B","prompt":"(b) VERIFY that residual water supply pressure, with drain valve open, is within 10% of the original value recorded.","input":null,"possible_fault":"Pressure drop >10%, inadequate supply","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.6. - Water supply pressure drop exceeds 10% of original value.","severity_level":"critical","fault_id":"recMbrcA0lkq3Oco0","prompt_id":"recMbrcA0lkq3Oco0_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"a2b1a92b-03ad-485c-8351-8e3865e1e273","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.6.A","prompt":"(c) CLOSE main drain valve and record time for pressure recovery.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recAc1nHzG8zzanCc_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"a52d1e04-2865-4924-a2d3-c586295c8361","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.6","prompt":"(c) CLOSE remote test valve(s) and verify that alarm valve has reseated.","input":null,"possible_fault":"Alarm valve fails to reseat","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.6(c) - Alarm valve not reseating after test","severity_level":"critical","fault_id":"recih2rKSCygnod4x","prompt_id":"recih2rKSCygnod4x_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"a630a3d6-c847-4702-8fa4-de943587e8bf","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.12","prompt":"(c) RESET the alarm test valve on completion \nof each test.","input":null,"possible_fault":"Test valve won't close, system won't reset","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.12. - Test valve failed to close or system failed to reset.","severity_level":"critical","fault_id":"recKfwvGhz0pZcaRJ","prompt_id":"recKfwvGhz0pZcaRJ_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"a7a4e106-8d13-4b9d-8117-d40379859216","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.6","prompt":"CLEAN orifice, check seals and overhaul, where indicated, by a functional test.","input":null,"possible_fault":"Retard chamber orifice blocked/seals worn","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.6 - Retard chamber requires cleaning/overhaul","severity_level":"non-critical","fault_id":"recNwHA5bOGBvTmr4","prompt_id":"recNwHA5bOGBvTmr4_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"ab3066de-24cb-40f1-96a4-5c3e93cfb720","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.15.B","prompt":"(b) VERIFY pressure gauge readings are within \nthe ranges required.","input":null,"possible_fault":"Pressure drop, system not reset","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.15 - System pressure not restored to normal after alarm test.","severity_level":"critical","fault_id":"recQ0hTn9LxWztXyW","prompt_id":"recQ0hTn9LxWztXyW_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"ab6b1d11-63de-45f6-b0a5-e13f9bbb2e32","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.12.A","prompt":"CONDUCT a water supply test through a flow-measuring device or other appropriate methods that the flow corresponds to the required quick fill-rate.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"reccd71a9D9ewM8nb_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"abdabdc6-822d-4b78-a596-ed18bba42cc6","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.27","prompt":"(a) CHECK that block plans and emergency instructions contain the required details.","input":null,"possible_fault":"Documentation incomplete/incorrect","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.27 - Block plans/emergency instructions incomplete","severity_level":"non-conformance","fault_id":"rec0TNBdybu0kbn2z","prompt_id":"rec0TNBdybu0kbn2z_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"ac1172a4-110c-4749-a203-144efeddcfbb","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.7","prompt":"(b) VERIFY correct specific gravity and top up to correct solution level.","input":null,"possible_fault":"Incorrect specific gravity/level","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.7(b) - Anti-freeze gravity/level incorrect","severity_level":"non-critical","fault_id":"rec9qiZfz7oluLIQI","prompt_id":"rec9qiZfz7oluLIQI_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"aecb78f2-d991-4e6a-825f-ec3387586031","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.18","prompt":"(b) Functional test.","input":null,"possible_fault":"Sprinkler fails to operate correctly","possible_fault_description":null,"severity_level":"critical","fault_id":"recnK8cZCVRNxLHC4","prompt_id":"recnK8cZCVRNxLHC4_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"10_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"b13a3ae8-368f-45f4-86ed-8642b06a85c4","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.7","prompt":"(a) DRAW a sample of anti-freeze solution.","input":null,"possible_fault":"Unable to draw sample","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.7(a) - Anti-freeze solution sample not obtained","severity_level":"non-critical","fault_id":"recSzZDZdwfRoZB6W","prompt_id":"recSzZDZdwfRoZB6W_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"b5ec46a8-e301-4bd2-ad58-cd20e8894619","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.4","prompt":"Perform routine service in accordance with Section 5.","input":null,"possible_fault":"Tank service deficiencies","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.4 - Tank service per Section 5 not performed","severity_level":"non-conformance","fault_id":"recTgEEaSDZCQUruF","prompt_id":"recTgEEaSDZCQUruF_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"b5edae67-90c6-48c2-85be-8c8973d4168c","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.16","prompt":"CHECK and clean foam concentrate strainer (fitted upstream of proportioning device).","input":null,"possible_fault":"Strainer blocked/dirty","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.16 - Foam concentrate strainer requires cleaning","severity_level":"non-critical","fault_id":"recgOqS8gKfwCWSCQ","prompt_id":"recgOqS8gKfwCWSCQ_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"b629f940-9b6b-457b-9e55-6c48a6e594c5","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.3.B","prompt":"(b) OPERATE all subsidiary stop valves (floor\n isolation valves, tail-end valves).Ensure that\n they are fully open and, where applicable,\n secured in the open position and are\n correctly labelled.\n NOTE: ‘Text deleted’.","input":null,"possible_fault":"Valve not fully open, loose, no label","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.3 - Subsidiary valve not fully open or secured correctly.","severity_level":"non-critical","fault_id":"recjrsCMOFqNs1ffu","prompt_id":"recjrsCMOFqNs1ffu_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"b988f22a-9bae-44d6-99ca-933f7b6a099e","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.13","prompt":"DRAIN tail-end anti-freeze systems, including individual sprinkler heads on droppers and refill with new solution.","input":null,"possible_fault":"Anti-freeze solution contaminated","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.13 - Anti-freeze system requires drain/refill","severity_level":"non-critical","fault_id":"recChhlRz4KRp4Sfj","prompt_id":"recChhlRz4KRp4Sfj_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"ba986cc2-1d2d-4de3-8273-1be86a88b0ff","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.11.A","prompt":"Where an ASE is standalone and is connected to a power supply unit and batteries: (a) CHECK the batteries for any condition likely to adversely affect its function and (b) Where the battery has not been replaced in the previous two years, VERIFY the battery condition by carrying out a battery discharge test in accordance with Appendix F.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recIwgs1gtt3emeDh_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"bb9b0e06-932a-454a-aca2-c0bab9023a41","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.18","prompt":"Subject the sample sprinklers to the following tests conducted by a registered testing authority:\n (a) Release temperature.","input":null,"possible_fault":"Release temperature outside range","possible_fault_description":null,"severity_level":"non-critical","fault_id":"recvKiEOyPd0nAext","prompt_id":"recvKiEOyPd0nAext_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"10_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"bf6a8f0f-930c-4a55-bbae-1d19a6a75e16","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.12","prompt":"(d) Where multiple control valve assemblies are \nseparately identified at an FIP, only one \ntransmission from the FIP to the monitoring \nstation is required.","input":null,"possible_fault":"Multiple transmissions, no transmission","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.12 - FIP transmission to monitoring station incorrect.","severity_level":"non-conformance","fault_id":"reco4jVHbnJfvtExZ","prompt_id":"reco4jVHbnJfvtExZ_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"c0f3b4c4-f6b3-4674-aa6d-723a35ec7f19","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.7","prompt":"(b) For ball and butterfly valves, CHECK for leakage and replace if necessary.","input":null,"possible_fault":"Ball/butterfly valve leaking","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.7(b) - Ball/butterfly valve replacement required","severity_level":"non-critical","fault_id":"reciWOHBFaHYLte6t","prompt_id":"reciWOHBFaHYLte6t_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"c80d2ef6-fd72-417e-af1e-43e3e710fcbd","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.18","prompt":"(c) Leak resistance test—Maximum system design\n pressure test.\n REMOVE and TEST a representative sample of\n sprinklers at the following intervals:\n (i) Dry pendent sprinklers (representative sample),\n every 10 years.\n (ii) All other sprinklers (not less than 14 samples),\n at 25 years, then every 10 years.\n NOTE: For all the above sprinklers, using\n ISO 6182-6, ISO 6182-7 and ISO 6182-12\n component Standards, sample sprinklers should be\n selected from the range of site environmental\n conditions to which the system(s) is subjected\n (i.e. office, factory, boiler house environments, etc.).\n Should one or more sprinklers fail any of the above\n tests, further sampling and testing should be\n conducted until the results can be considered truly\n representative. The extent of sprinkler replacement,\n if any, will be dependent on the results of testing.","input":null,"possible_fault":"System component not operating as required","possible_fault_description":"AS 1851:2012 TABLE 2.4.2.4 ITEM 4.18(c)  - Component failed test or is not in correct operating condition","severity_level":"critical","fault_id":"recpDuFAmbPnaXSnL","prompt_id":"recpDuFAmbPnaXSnL_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"10_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"c8c42b74-a6fa-416f-9443-170f98f6cc5f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.12.A","prompt":"(b) RECORD time(s) to operation of alarm \ngong(s) and verify that time does not exceed \n180 s for general systems or 90 s for \nresidential sprinkler systems.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rec6nT3x5NMp93b86_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"d0ea9d3c-7205-4ec9-8933-ae9cd54ca93b","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.2 SIX-MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEM","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"2.3","prompt":"(a) Except where owned by the water supply\n authority, OPERATE (two full turns) all\n underground key-operated valves and verify\n they are fully open, secure in the open\n position (relaxed ¼ turn if appropriate) and\n are correctly labelled.\n NOTE: Where underground key-operated\n valves are owned by the water supply\n authority, the owner should arrange for the\n water supply authority to test the valve(s) to\n confirm the valve(s) is operational and in\n the correct position.","input":null,"possible_fault":"Valve seized, not fully open, no label","possible_fault_description":"AS1851 2012 TABLE 2.4.2.2 ITEM NO 2.3 - Underground valve not fully open or incorrectly labelled.","severity_level":"critical","fault_id":"recrz2lk4HoW9EUiH","prompt_id":"recrz2lk4HoW9EUiH_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"6_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"d28814ec-3fdc-406a-b64c-8b9c0e5995ab","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.4","prompt":"CHECK that the booster connection or enclosure \nis unobstructed and for any condition that may \nadversely affect the operation or access. \nCHECK that the booster connection coupling \ntype is as per the local fire brigade requirements","input":null,"possible_fault":"Booster connection obstructed or incorrect","possible_fault_description":"AS 1851:2012 TABLE 2.4.2.1 ITEM 1.4 - Booster obstructed or not per brigade requirements","severity_level":"non-conformance","fault_id":"recJc35mQtohWsCpP","prompt_id":"recJc35mQtohWsCpP_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"d73938e8-9bf8-45e8-96e6-cf7a9caff920","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.19","prompt":"CHECK for poorly fitting or missing escutcheons or cover plates, damaged guards, and attachment of foreign material.","input":null,"possible_fault":"Missing/damaged escutcheons","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.19 - Escutcheons/guards missing/damaged","severity_level":"non-critical","fault_id":"rec1dJzeEwnhcwqVL","prompt_id":"rec1dJzeEwnhcwqVL_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"d791db37-6fab-4ae9-9767-e62319693c76","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.5.B","prompt":"(ii) Reduce the water flow through the flow-measuring device to that corresponding to the most unfavourable duty point. Record the flowing pressure.","input":null,"possible_fault":"Flow/pressure below requirements","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.5(ii) - Most unfavourable duty point not achieved","severity_level":"critical","fault_id":"recZXi5haubuQnFuL","prompt_id":"recZXi5haubuQnFuL_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"da8efeb7-178c-4168-8b35-976159427d2b","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.19","prompt":"(b) Multiple MJC installed for alarm purposes only\n or to control groups of distributors, REPLACE a\n representative sample. Subject the sample to the\n following tests conducted by a registered testing\n laboratory:\n (i) Leak resistance test.\n (ii) Maximum system design pressure test\n (nominally 1200 kPa or 2000 kPa).\n (iii) Functional test.\n Use ISO 6182-1.\n NOTE: Should the sample MJC fail any of the\n above tests, further sampling and testing should\n be conducted until the results can be considered\n truly representative.","input":null,"possible_fault":"MJC representative sample fails\n(i) MJC fails leak resistance test\n(ii) MJC fails at 1200kPa/2000kPa\n(iii) MJC fails functional operation","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.19(b) - Multiple MJC sample failed lab testing","severity_level":"critical","fault_id":"rec0OUthpnS6Rlxvf","prompt_id":"rec0OUthpnS6Rlxvf_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"10_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"df0ea120-86a0-4bd4-b1f4-e5b11d0b1223","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.7","prompt":"(a) FIT new gland packing and lubricate spindle.","input":null,"possible_fault":"Stop valve gland packing worn","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.7(a) - Stop valve requires new gland packing","severity_level":"non-critical","fault_id":"rec6CtGmhTbedvGGV","prompt_id":"rec6CtGmhTbedvGGV_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"df2c2759-23f2-4b67-9808-69da75385485","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.4","prompt":"REMOVE alarm cock barrels, clean, lap in, grease and reinstall. For packed gland variants, fit new gland packing.","input":null,"possible_fault":"Alarm cock barrel/packing worn","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.4 - Alarm cock requires cleaning/new gland packing","severity_level":"non-critical","fault_id":"recqsgYB69H7ef5qA","prompt_id":"recqsgYB69H7ef5qA_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"e10ccdf0-78f0-44d0-afc7-bf9e39ce80d0","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.9","prompt":"CHECK the sprinkler system alarm interface \nwith other systems is not isolated, inhibited or \ndisabled.","input":null,"possible_fault":"Interface isolated, inhibited, disabled","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.9- System interface isolated/disabled preventing alarm transmission.","severity_level":"non-conformance","fault_id":"recWPnW6V7hZ3f0aH","prompt_id":"recWPnW6V7hZ3f0aH_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"e141e371-df1b-417a-959e-7b1c4921f2dc","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.10","prompt":"CLEAN the strainer.","input":null,"possible_fault":"Strainer requires cleaning","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.10 - Brigade alarm strainer dirty","severity_level":"recommendation","fault_id":"rece2UEOsx3rMKYKq","prompt_id":"rece2UEOsx3rMKYKq_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"e2e95e02-fe54-455b-9b49-a285e426298f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.18","prompt":"CHECK sprinklers for any condition, including physical damage, contamination, and paint on operating elements or cover plates, likely to adversely affect their function. \nNOTE: Sprinkler frames may be painted as part of the manufacturing process; however, the heat response elements should not be painted as this will delay or prevent operation and paint accumulated at the seat of the sprinkler may affect operation. Minor spatter on the fusible elements may be acceptable but operation should be checked if doubt exists.","input":null,"possible_fault":"Sprinkler damage/contamination","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.18 - Sprinklers damaged/contaminated/painted elements","severity_level":"non-critical","fault_id":"reclh4OgS3A8hbiFM","prompt_id":"reclh4OgS3A8hbiFM_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"e4f08416-9a93-4b32-9e52-893ae93200ca","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.5.B","prompt":"(a) CONDUCT a water supply test, subject to limitations imposed by the water agency controlling the supply source. The test may be a combination of physical testing and calculation as necessary.","input":null,"possible_fault":"Inadequate static pressure","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.5(a) - Static supply pressure insufficient","severity_level":"critical","fault_id":"rect70yabf8sbfOyM","prompt_id":"rect70yabf8sbfOyM_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"e8bbad1c-4e90-47c1-9618-e31ed45a3a76","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.10","prompt":"(b) VERIFY that the valve position indicators \nare securely mounted and indicate correctly","input":null,"possible_fault":"Loose indicator, incorrect indication","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.10. - Valve position indicator insecure or showing wrong position.","severity_level":"non-critical","fault_id":"recr10z4vi9C0EbeY","prompt_id":"recr10z4vi9C0EbeY_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"eb7688ee-8b56-49a0-b64d-5d83da700948","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.27","prompt":"(b) CHECK that up-to-date sprinkler plans are available on site.","input":null,"possible_fault":"Sprinkler plans not available/outdated","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 3.27(b) - Current sprinkler plans not maintained on site","severity_level":"non-conformance","fault_id":"rec375xZIECRiPrP9","prompt_id":"rec375xZIECRiPrP9_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"ee55d003-5661-4d03-8944-38974cee305e","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.15","prompt":"SERVICE the air compressor assembly in accordance with the manufacturer’s instructions. [Periodic hydrostatic testing of air receivers is not required (see AS/NZS 3788)].","input":null,"possible_fault":"Air compressor not per manufacturer specs","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.15 - Air compressor requires manufacturer service","severity_level":"non-critical","fault_id":"recff3gEQfV3ctqU2","prompt_id":"recff3gEQfV3ctqU2_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"ee789134-b31a-4f95-9c49-f928d03ea30f","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.12","prompt":"(a) OPERATE each alarm valve by opening \neach 15 mm test valve or 10 mm for \nresidential sprinkler systems serving \nbuildings up to 4 storeys in height. \nWhere more than 12 control assemblies are \ndistributed throughout a high-rise building \nforming part of a combined \nsprinkler/hydrant system, and initiate the \nfire brigade alarm, testing may be conducted \non a rotating basis. \nThe period between testing of all control \nassemblies shall not exceed 3 months.","input":null,"possible_fault":"Test valve seized, no flow, valve damage","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.12 - Test valve failed to operate or allow flow.","severity_level":"critical","fault_id":"recNA2eBK2TsPmiYl","prompt_id":"recNA2eBK2TsPmiYl_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"efc43cef-3cfc-484d-b8c1-15e78c6286f5","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.12.B","prompt":"(b) RECORD time(s) to operation of alarm \ngong(s) and verify that time does not exceed \n180 s for general systems or 90 s for \nresidential sprinkler systems.","input":null,"possible_fault":"Alarm delay >180s (90s residential), no gong","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.12. - Alarm gong response time exceeds AS3786 requirements.","severity_level":"critical","fault_id":"recQGBtU1qZMlBAJT","prompt_id":"recQGBtU1qZMlBAJT_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"f25f646b-1cc5-413d-ae9d-714c2ee48e69","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.3 YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"3.8","prompt":"(a) CONDUCT a functional system test via the pressure switch or flow switch with each interfaced system.","input":null,"possible_fault":"Interface system fails test","possible_fault_description":"AS1851 2012 TABLE 2.4.2.3 ITEM 3.8(a) - Interface control test via switch failed","severity_level":"critical","fault_id":"rec9OlfHIFYS3GiHN","prompt_id":"rec9OlfHIFYS3GiHN_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"f7a1ef30-a609-4c04-a5fa-bada71cd4888","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.2","prompt":"FIT new alarm valve seating or port seating (perishable items), check and clean annular groove and outlet ports, polish and lubricate seating spindle/shaft, and check operation of compensator valve if fitted. Fit a new alarm valve faceplate gasket.","input":null,"possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recVfauHJKgJc9shx_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"fc65a9d5-ee6d-43da-a9cf-625ac5eafb83","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.1 MONTHLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKLER SYSTEMS WET PIPE SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"1.16","prompt":"(b) RECORD the pump cut-in pressures and \nverify that they are within the ranges \nrequired","input":null,"possible_fault":"Wrong cut-in pressure, out of range","possible_fault_description":"AS1851 2012 TABLE 2.4.2.1 ITEM NO 1.16. - Pump start pressure outside specified range per AS2941.","severity_level":"non-critical","fault_id":"recywLTKfWexhcvuZ","prompt_id":"recywLTKfWexhcvuZ_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"1_month::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"fcd806f9-bac3-4357-8313-21a2fd3899e8","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.12","prompt":"OVERHAUL all pressure-reducing valves, pressure-relief valves, tail-end system valves, and any other special valves that are installed in accordance with suppliers’ specifications.","input":null,"possible_fault":"Special valve components worn","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.12 - Special valves require overhaul per specs","severity_level":"non-critical","fault_id":"recLblnDQDS2FGqOt","prompt_id":"recLblnDQDS2FGqOt_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"fe933dda-21a8-44ae-baa1-8c4c35e9531e","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.8","prompt":"RENEW water supply non-return valve seatings and gaskets.","input":null,"possible_fault":"Non-return valve seatings/gaskets worn","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.8 - Non-return valve components require renewal","severity_level":"non-critical","fault_id":"recXvnN1q13ni8JFZ","prompt_id":"recXvnN1q13ni8JFZ_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"},{"id":"ff23c9d2-b519-4d9b-93c5-01b3fe671872","standard_code":"au_as_1851_2012","version":"full","category":"Automatic Fire Sprinkler Systems","category_id":"recllMaGwCBycgLb8","group_header":"TABLE 2.4.2.4 FIVE-YEARLY, TEN-YEARLY, TWENTY-FIVE-YEARLY AND THIRTY-YEARLY ROUTINE SERVICE SCHEDULE AUTOMATIC FIRE SPRINKER SYSTEMS WET PIPE SYSTEM","inspection_period":"5_year","inspection_period_frequency":5,"inspection_period_interval":"year","inspection_period_in_days":1825,"asset_type":"Fire Spinkler : Wet Pipe Systems","variant":null,"variant_id":"recXnAJDdJ3cQuUpx","item_no":"4.17","prompt":"Perform routine service in accordance with Section 5.","input":null,"possible_fault":"Pressure tank service requirements not met","possible_fault_description":"AS1851 2012 TABLE 2.4.2.4 ITEM 4.17 - Pressure tanks require Section 5 service","severity_level":"non-conformance","fault_id":"recDXyIcDBKPP9EOS","prompt_id":"recDXyIcDBKPP9EOS_prompt","inspection_id":"c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8","grouping_key":"5_year::c_recXnAJDdJ3cQuUpx_recllMaGwCBycgLb8"}]}],"other_checklist_items":[]},{"id":"recm1n45PNTmariNC","name":"Delivery Lay Flat Fire Hose","asset_types":[{"id":"recPXdkO0TUFaIxvl","name":"Delivery Lay Flat Hose","checklist":[{"id":"46b54cb9-9096-4744-b66d-08062ea4e3ff","standard_code":"au_as_1851_2012","version":"full","category":"Delivery Lay Flat Fire Hose","category_id":"recm1n45PNTmariNC","group_header":"TABLE 8.4 YEARLY ROUTINE SERVICE AND RECORDS SCHEDULE DELIVERY LAY FLAT HOSE","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Delivery Lay Flat Hose","variant":null,"variant_id":"recPXdkO0TUFaIxvl","item_no":"1.6","prompt":"DRY the wet hose prior to storage unless it is an\n extruded type.\n NOTE: Where the hose is dried by heating:\n (a) The hose temperature should not exceed 40°C.\n (b) The heating should be accompanied by a\n natural or forced air draught through the hose.\n (c) The hose should not be exposed to the drying\n temperature for more than 12 h.","input":null,"possible_fault":"Improper drying procedures","possible_fault_description":"AS1851 2012 TABLE 8.4 ITEM 1.6 - Wet hose not properly dried or drying temperature exceeds 40°C or exposure time exceeds 12 hours","severity_level":"recommendation","fault_id":"recKJ63pOjmquIHey","prompt_id":"recKJ63pOjmquIHey_prompt","inspection_id":"c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC","grouping_key":"1_year::c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC"},{"id":"76f2995a-0336-434c-ba97-1d1bfd41d1f0","standard_code":"au_as_1851_2012","version":"full","category":"Delivery Lay Flat Fire Hose","category_id":"recm1n45PNTmariNC","group_header":"TABLE 8.4 YEARLY ROUTINE SERVICE AND RECORDS SCHEDULE DELIVERY LAY FLAT HOSE","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Delivery Lay Flat Hose","variant":null,"variant_id":"recPXdkO0TUFaIxvl","item_no":"1.2","prompt":"INSPECT hose couplings for damage or distortion\n to threads, lugs or gaskets.","input":null,"possible_fault":"Damage or distortion to threads, lugs or gaskets","possible_fault_description":"AS1851 2012 TABLE 8.4 ITEM 1.2 - Inspect hose couplings for damage or distortion","severity_level":"non-critical","fault_id":"rec6VBmj46fkfW18L","prompt_id":"rec6VBmj46fkfW18L_prompt","inspection_id":"c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC","grouping_key":"1_year::c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC"},{"id":"7d168e5d-b7a2-4deb-b341-18621734ff4f","standard_code":"au_as_1851_2012","version":"full","category":"Delivery Lay Flat Fire Hose","category_id":"recm1n45PNTmariNC","group_header":"TABLE 8.4 YEARLY ROUTINE SERVICE AND RECORDS SCHEDULE DELIVERY LAY FLAT HOSE","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Delivery Lay Flat Hose","variant":null,"variant_id":"recPXdkO0TUFaIxvl","item_no":"1.3","prompt":"CHECK that the hose is stored as follows:\n (a) Its folds do not recur in the same position.\n (b) For normal industry use, on bollards or flaked.\n (c) Where personnel have the appropriate training,\n rolled on a bight, with both ends accessible, as\n an alternative to Action (b) above.\n (d) With the service tag visible and readily\n accessible.","input":null,"possible_fault":"Improper storage configuration","possible_fault_description":"AS1851 2012 TABLE 8.4 ITEM 1.3 - Hose not stored with non-recurring folds, on bollards/flaked, or service tag not visible","severity_level":"non-conformance","fault_id":"recSK2766xjDjmWgv","prompt_id":"recSK2766xjDjmWgv_prompt","inspection_id":"c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC","grouping_key":"1_year::c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC"},{"id":"b453b2fa-2f3d-419b-b665-56e00972a751","standard_code":"au_as_1851_2012","version":"full","category":"Delivery Lay Flat Fire Hose","category_id":"recm1n45PNTmariNC","group_header":"TABLE 8.4 YEARLY ROUTINE SERVICE AND RECORDS SCHEDULE DELIVERY LAY FLAT HOSE","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Delivery Lay Flat Hose","variant":null,"variant_id":"recPXdkO0TUFaIxvl","item_no":"1.1","prompt":"CHECK hose when laid out, preferably straight and\n on a flat clean surface, for obvious defects such as\n cuts, abrasion, burns or contamination.\n NOTE: The hose should be free of dirt, abrasives\n and contaminants prior to inspection.","input":null,"possible_fault":"Cuts, abrasion, burns or contamination found","possible_fault_description":"AS1851 2012 TABLE 8.4 ITEM 1.1 - Check hose when laid out straight on flat clean surface for defects","severity_level":"non-critical","fault_id":"recQiAB1DXqdS5iuz","prompt_id":"recQiAB1DXqdS5iuz_prompt","inspection_id":"c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC","grouping_key":"1_year::c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC"},{"id":"df5196a0-07cb-4eae-bd26-32a428a965a5","standard_code":"au_as_1851_2012","version":"full","category":"Delivery Lay Flat Fire Hose","category_id":"recm1n45PNTmariNC","group_header":"TABLE 8.4 YEARLY ROUTINE SERVICE AND RECORDS SCHEDULE DELIVERY LAY FLAT HOSE","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Delivery Lay Flat Hose","variant":null,"variant_id":"recPXdkO0TUFaIxvl","item_no":"1.4","prompt":"PRESSURE TEST the hose to a hydrostatic\n pressure test as follows:\n (a) LAY the hose out straight on a flat clean\n surface.\n (b) MARK the hose/coupling joints so that any\n movement between the two will be obvious.\n (c) FASTEN the hose ends to limit movement in\n the event of rupture.\n (d) CHARGE the hose with water to a nominal\n pressure of 500 kPa, taking care to vent all air.\n (e) INCREASE the pressure gradually, over a\n period of not less than 20 s and not more than\n 2 min, until the required maximum working\n pressure is reached:\n For Class L hose—1000 kPa\n For Class M hose—1400 kPa\n For Class H hose—2100 kPa\n (f) SUSTAIN this working pressure for not less\n than 3 min while examining the hose for\n defects, leakage, and movement of the\n couplings.","input":null,"possible_fault":"Hose fails hydrostatic pressure test","possible_fault_description":"AS1851 2012 TABLE 8.4 ITEM 1.4 - Hose shows defects, leakage, or coupling movement during pressure test at maximum working pressure (Class L: 1000kPa, Class M: 1400kPa, Class H: 2100kPa)","severity_level":"critical","fault_id":"recOo8ycfiKKLWs9U","prompt_id":"recOo8ycfiKKLWs9U_prompt","inspection_id":"c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC","grouping_key":"1_year::c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC"},{"id":"f4ad17a2-e6c6-46f0-a63e-e65c4c95d3c3","standard_code":"au_as_1851_2012","version":"full","category":"Delivery Lay Flat Fire Hose","category_id":"recm1n45PNTmariNC","group_header":"TABLE 8.4 YEARLY ROUTINE SERVICE AND RECORDS SCHEDULE DELIVERY LAY FLAT HOSE","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Delivery Lay Flat Hose","variant":null,"variant_id":"recPXdkO0TUFaIxvl","item_no":"1.5","prompt":"CLEAN dirty hose to avoid dirt, abrasives and\n contaminants that can seriously damage hoses.\n NOTE: Care should be taken not to damage the\n hose during cleaning. The manufacturer should be\n consulted in case of doubt.","input":null,"possible_fault":"Hose contaminated with dirt/abrasives","possible_fault_description":"AS1851 2012 TABLE 8.4 ITEM 1.5 - Dirty hose with contaminants that can damage hose integrity","severity_level":"non-critical","fault_id":"recAFdZy5JFHtQh8E","prompt_id":"recAFdZy5JFHtQh8E_prompt","inspection_id":"c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC","grouping_key":"1_year::c_recPXdkO0TUFaIxvl_recm1n45PNTmariNC"}]}],"other_checklist_items":[]},{"id":"recNGiNklGR6gJP5j","name":"Passive Fire and Smoke Systems","asset_types":[{"id":"rec21IZiCY2ATu9Xb","name":"Fire shutters","checklist":[{"id":"17a07942-645b-4694-9382-0de451b3bac1","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.4","prompt":"(a) CHECK guide tracks are securely fixed to the\n walls.","input":null,"possible_fault":"Guide tracks loose/insecure fixing","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.4(a) - Guide tracks not securely fixed to walls","severity_level":"non-critical","fault_id":"recvp56rhlqcR4ECx","prompt_id":"recvp56rhlqcR4ECx_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"1d2e952c-178d-4c1b-b87b-e49b1ceaff0c","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.3","prompt":"(b) CHECK barrel assembly is mounted so that the\n rolled-up curtain on the barrel sits higher than\n the top level of the guide tracks.","input":null,"possible_fault":"Curtain sits below guide track level","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.3(b) - Rolled curtain lower than guide track top level","severity_level":"non-critical","fault_id":"recvFvmsqTr5ayz2K","prompt_id":"recvFvmsqTr5ayz2K_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"24ad2ce9-987c-44c4-8d69-4333ae98228e","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.1","prompt":"INSPECT against drawings and all schedules (see\n Clause 12.2.5) that no fire shutters have been added,\n removed or modified.","input":null,"possible_fault":"Shutters added/removed/modified without approval","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.1 - Unauthorised shutters/modifications affecting fire rating","severity_level":"non-conformance","fault_id":"rec3O2VsYedqTR9eW","prompt_id":"rec3O2VsYedqTR9eW_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"3b9964af-ce54-407b-8dee-1be6813b0ebe","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.5","prompt":"INSPECT that the threshold is of concrete or similar\n approved material deemed non-combustible.","input":null,"possible_fault":"Non-compliant/combustible threshold material","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.5 - Threshold not concrete/combustible material","severity_level":"non-conformance","fault_id":"recrfDdS2wdbms3Dc","prompt_id":"recrfDdS2wdbms3Dc_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"4d86a3a1-61b3-4e64-af97-4edb4497580b","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.2","prompt":"CHECK fire shutters and frames are tagged in\n accordance with AS 1905.2.","input":null,"possible_fault":"Tags missing/incorrect/signage non-compliant","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.2 - Tags missing/illegible/non-compliant signage","severity_level":"non-conformance","fault_id":"rec86E8OVQlKEh7GV","prompt_id":"rec86E8OVQlKEh7GV_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"60e8a810-8967-495f-8d4f-06c6404d5413","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.6","prompt":"(a) INSPECT that the fire shutter is fitted with a\n fusible link (if applicable) of not greater than\n 80ºC (57ºC in the case of a drenched fire shutter)\n and the fusible link is in good and operational\n condition.","input":null,"possible_fault":"Link damaged/wrong temperature rating","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.6(a) - Fusible link >80°C/damaged/non-operational","severity_level":"non-critical","fault_id":"recZCKRhuOlyTt6pR","prompt_id":"recZCKRhuOlyTt6pR_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"62aeb94e-fd24-4895-a689-b048575870c7","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.7","prompt":"(b) TEST that under simulated automatic operation\n the curtain does not rebound creating a gap\n greater than 25 mm between the bottom rail and\n the threshold.","input":null,"possible_fault":"Rebound gap exceeds 25mm","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.7(b) - Curtain rebound gap >25mm at threshold","severity_level":"non-critical","fault_id":"recJc6JP4QwkndvMj","prompt_id":"recJc6JP4QwkndvMj_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"72615001-65dd-4ea3-8325-cb22b7b63845","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.4","prompt":"(c) CHECK the gap between the end of the slats,\n including end clips and the guide track, is no\n more that 10 mm.","input":null,"possible_fault":"Gap exceeds 10mm limit","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.4(c) - Gap between slats and guide track >10mm","severity_level":"non-critical","fault_id":"recZFF65SXWXDBG8E","prompt_id":"recZFF65SXWXDBG8E_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"9f85fc7c-8e18-483f-a1cc-9288a8544d74","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.4","prompt":"(b) CHECK guide tracks are mounted such that the\n curtain overlaps equally the jamb on each side of\n the opening.","input":null,"possible_fault":"Unequal overlap/inadequate coverage","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.4(b) - Curtain overlap unequal on jamb sides","severity_level":"non-critical","fault_id":"recHbzOxdrWJVPHT1","prompt_id":"recHbzOxdrWJVPHT1_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"abf635e2-df1b-426c-84a0-69db75320289","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.7","prompt":"(a) TEST that under simulated automatic operation\n the fire shutter curtain descends to the threshold\n at an average speed of between 0.15 m/s and\n 0.3 m/s.","input":null,"possible_fault":"Speed outside 0.15-0.3 m/s range","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.7(a) - Descent speed outside 0.15-0.3 m/s range","severity_level":"non-critical","fault_id":"rec3MWw4n6VXq4Opb","prompt_id":"rec3MWw4n6VXq4Opb_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"d7262724-24f2-49f2-afec-403b8b27e3fd","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.7","prompt":"(c) CHECK shutter slats, bottom rail and brake\n release mechanism, illuminated warning signs,\n sounders and release delays (where fitted) are\n free from damage and the slats are not binding\n on each other when opening and closing.","input":null,"possible_fault":"Slats/rail/brake damaged/binding on operation","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.7(c) - Components damaged/slats binding/brake failure","severity_level":"non-critical","fault_id":"recF1Goay73QAWS6e","prompt_id":"recF1Goay73QAWS6e_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"f258f73d-41dc-4708-a8ff-7ce962157090","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.3","prompt":"(a) CHECK brackets are securely fixed to the walls.","input":null,"possible_fault":"Brackets loose/insecure wall fixing","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.3(a) - Brackets not securely fixed/loose wall anchors","severity_level":"non-critical","fault_id":"recJs1LarTD8cukLG","prompt_id":"recJs1LarTD8cukLG_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"f8520ffd-2c3a-4c4c-84f9-892b877664bb","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.4","prompt":"(d) CHECK that the shutter moves freely in the\n guide tracks without jamming under normal\n operation.","input":null,"possible_fault":"Shutter jams/binds in guide tracks","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.4(d) - Shutter jamming/binding in guide tracks","severity_level":"non-critical","fault_id":"rectJTVu3j9gokK6n","prompt_id":"rectJTVu3j9gokK6n_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"},{"id":"fe09e301-8296-4f22-85f4-38f4e3af548b","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.5 YEARLY SERVICE SCHEDULE FIRE SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire shutters","variant":null,"variant_id":"rec21IZiCY2ATu9Xb","item_no":"5.6","prompt":"(b) REPLACE all fusible links every 25 years from\n the date of manufacture.\n NOTE: In lieu of replacing all fusible links, a\n representative sample may be tested as per\n Section 2.","input":null,"possible_fault":"Links over 25 years old/overdue replacement","possible_fault_description":"AS1851 TABLE 12.4.5 ITEM 5.6(b) - Fusible links over 25 years old/overdue","severity_level":"recommendation","fault_id":"recroBMQKqTDH1CeA","prompt_id":"recroBMQKqTDH1CeA_prompt","inspection_id":"c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec21IZiCY2ATu9Xb_recNGiNklGR6gJP5j"}]},{"id":"rec2oTGr7pr54Qhur","name":"Fire-protected structural members","checklist":[{"id":"26576582-bbb6-4310-9bd0-6aa9023d6f0d","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.2 YEARLY SERVICE SCHEDULE FIRE-PROTECTED STRUCTURAL MEMBERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected structural members","variant":null,"variant_id":"rec2oTGr7pr54Qhur","item_no":"2.2","prompt":"(a) CHECK condition of fire protection system or\n coating.","input":null,"possible_fault":"Fire protection system deteriorated/damaged","possible_fault_description":"AS1851 2012 TABLE 12.4.2 ITEM 2.2(a) - Fire protection system or coating shows deterioration, damage, or failure","severity_level":"critical","fault_id":"recOru3QejDAGlWPn","prompt_id":"recOru3QejDAGlWPn_prompt","inspection_id":"c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j"},{"id":"63815c86-8fba-4db0-a520-9759725b3ace","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.2 YEARLY SERVICE SCHEDULE FIRE-PROTECTED STRUCTURAL MEMBERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected structural members","variant":null,"variant_id":"rec2oTGr7pr54Qhur","item_no":"2.3","prompt":"(a) INSPECT visually for areas of deterioration\n against vermiculite, cement, mineral fibre and\n plaster (or combinations of) spray’s loss of\n adhesion.","input":null,"possible_fault":"Spray protection lost adhesion/failed","possible_fault_description":"AS1851 2012 TABLE 12.4.2 ITEM 2.3(a) -Vermiculite, cement, mineral fibre, plaster spray shows adhesion loss/deterioration","severity_level":"critical","fault_id":"reccoOWeCn9Azh1N5","prompt_id":"reccoOWeCn9Azh1N5_prompt","inspection_id":"c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j"},{"id":"7a8dd6ac-651e-4e72-bf82-2641a41f90cd","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.2 YEARLY SERVICE SCHEDULE FIRE-PROTECTED STRUCTURAL MEMBERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected structural members","variant":null,"variant_id":"rec2oTGr7pr54Qhur","item_no":"2.3","prompt":"(b) CHECK for intumescent coating visual damage to\n the surface (e.g. bubbling, peeling, flaking and\n scratches).","input":null,"possible_fault":"Coating bubbling/peeling/flaking/scratched","possible_fault_description":"AS1851 2012 TABLE 12.4.2 ITEM 2.3(b) -Intumescent coating shows surface damage: bubbling, peeling, flaking, scratches","severity_level":"non-critical","fault_id":"recofobHlDpuEoEBV","prompt_id":"recofobHlDpuEoEBV_prompt","inspection_id":"c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j"},{"id":"b25566fc-4206-4cb5-a8d0-f68eea07c68a","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.2 YEARLY SERVICE SCHEDULE FIRE-PROTECTED STRUCTURAL MEMBERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected structural members","variant":null,"variant_id":"rec2oTGr7pr54Qhur","item_no":"2.1","prompt":"INSPECT against drawings (see Clause 12.2.5) that no\n structural steel members have been added, removed or\n modified.","input":null,"possible_fault":"Structural members added/removed/modified","possible_fault_description":"AS1851 2012 TABLE 12.4.2 ITEM 2.1 -  - Structural steel members don't match drawings - unauthorized modifications detected","severity_level":"non-conformance","fault_id":"recdPbhkIHlAB1nA6","prompt_id":"recdPbhkIHlAB1nA6_prompt","inspection_id":"c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j"},{"id":"dbef133a-b552-49bd-a0f8-651aa0692ac2","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.2 YEARLY SERVICE SCHEDULE FIRE-PROTECTED STRUCTURAL MEMBERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected structural members","variant":null,"variant_id":"rec2oTGr7pr54Qhur","item_no":"2.3","prompt":"(c) CHECK fire-protective boards and cladding for\n missing boards or loss of adhesion.","input":null,"possible_fault":"Boards missing/lost adhesion/failed","possible_fault_description":"AS1851 2012 TABLE 12.4.2 ITEM 2.3(c) - Fire-protective boards/cladding missing, lost adhesion, or system integrity failed","severity_level":"non-critical","fault_id":"rec8x6nxaLq4VwlKM","prompt_id":"rec8x6nxaLq4VwlKM_prompt","inspection_id":"c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j"},{"id":"fc469c20-ac66-4dcb-808f-acc0f2e13a98","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.2 YEARLY SERVICE SCHEDULE FIRE-PROTECTED STRUCTURAL MEMBERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected structural members","variant":null,"variant_id":"rec2oTGr7pr54Qhur","item_no":"2.2","prompt":"(b) CHECK for mechanical damage.","input":null,"possible_fault":"Physical/mechanical damage to protection","possible_fault_description":"AS1851 2012 TABLE 12.4.2 ITEM 2.2(b) -Mechanical damage to fire protection from impact, maintenance, or accidental causes","severity_level":"non-critical","fault_id":"recAoWCh5YwJVmLrY","prompt_id":"recAoWCh5YwJVmLrY_prompt","inspection_id":"c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rec2oTGr7pr54Qhur_recNGiNklGR6gJP5j"}]},{"id":"recaNgsM0omlzvLsJ","name":"Ceilings, service penetrations and control joints","checklist":[]},{"id":"recbiBQelzVodmYCL","name":"Fire-rated glazing","checklist":[{"id":"009b06c3-5c5c-401d-950e-f8dc6dd217fa","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.6 YEARLY SERVICE SCHEDULE FIRE-RATED GLAZING","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-rated glazing","variant":null,"variant_id":"recbiBQelzVodmYCL","item_no":"6.2","prompt":"(b) INSPECT for impact crazing or cracking over\n entire surface area of glass.","input":null,"possible_fault":"Impact crazing/cracking on glass surface","possible_fault_description":"AS1851 TABLE 12.4.6 ITEM 6.2(b) - Impact crazing/cracking over glass surface area","severity_level":"non-critical","fault_id":"recn4GxCNb6DJLnHt","prompt_id":"recn4GxCNb6DJLnHt_prompt","inspection_id":"c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j"},{"id":"096c855d-3bff-42b5-9116-21e21c2a075c","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.6 YEARLY SERVICE SCHEDULE FIRE-RATED GLAZING","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-rated glazing","variant":null,"variant_id":"recbiBQelzVodmYCL","item_no":"6.1","prompt":"INSPECT against drawings (see Clause 12.2.5) that no\n fire-rated glazing has been added, removed or\n modified.","input":null,"possible_fault":"Glazing added/removed/modified without approval","possible_fault_description":"AS1851 TABLE 12.4.6 ITEM 6.1 - Unauthorised glazing/modifications affecting fire rating","severity_level":"non-conformance","fault_id":"rec6DWyV1WOvHe58Y","prompt_id":"rec6DWyV1WOvHe58Y_prompt","inspection_id":"c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j"},{"id":"0bbfe816-7aa8-41bb-ba78-2ed8f1b7f739","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.6 YEARLY SERVICE SCHEDULE FIRE-RATED GLAZING","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-rated glazing","variant":null,"variant_id":"recbiBQelzVodmYCL","item_no":"6.3","prompt":"(a) VERIFY that frame is free from distortion at any\n point along the frame section.","input":null,"possible_fault":"Frame distorted at any point","possible_fault_description":"AS1851 TABLE 12.4.6 ITEM 6.3(a) - Frame distortion at any point along sections","severity_level":"non-critical","fault_id":"recPlAbV1oPmYK3gw","prompt_id":"recPlAbV1oPmYK3gw_prompt","inspection_id":"c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j"},{"id":"765b64c3-0749-4a6c-89c4-fabccf97b184","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.6 YEARLY SERVICE SCHEDULE FIRE-RATED GLAZING","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-rated glazing","variant":null,"variant_id":"recbiBQelzVodmYCL","item_no":"6.2","prompt":"(a) INSPECT for any crazing or cracking around\n perimeter of glass.","input":null,"possible_fault":"Crazing/cracks around glass perimeter","possible_fault_description":"AS1851 TABLE 12.4.6 ITEM 6.2(a) - Crazing/cracking around glass perimeter edges","severity_level":"non-critical","fault_id":"recpouDbnMc1rUVrN","prompt_id":"recpouDbnMc1rUVrN_prompt","inspection_id":"c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j"},{"id":"cc71d882-1d7f-473f-b360-7e44df36b28b","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.6 YEARLY SERVICE SCHEDULE FIRE-RATED GLAZING","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-rated glazing","variant":null,"variant_id":"recbiBQelzVodmYCL","item_no":"6.3","prompt":"(b) INSPECT frame is securely anchored and free\n from any visible defects or corrosion.","input":null,"possible_fault":"Frame insecure/visible defects/corrosion","possible_fault_description":"AS1851 TABLE 12.4.6 ITEM 6.3(b) - Frame not anchored/visible defects/corrosion","severity_level":"non-critical","fault_id":"recTTMM0OayMJ9ELk","prompt_id":"recTTMM0OayMJ9ELk_prompt","inspection_id":"c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j"},{"id":"ccdcf49f-eca7-4e80-95a5-827a722e2d4e","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.6 YEARLY SERVICE SCHEDULE FIRE-RATED GLAZING","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-rated glazing","variant":null,"variant_id":"recbiBQelzVodmYCL","item_no":"6.4","prompt":"INSPECT glazing seals are present and have not\n deteriorated.","input":null,"possible_fault":"Seals missing/deteriorated","possible_fault_description":"AS1851 TABLE 12.4.6 ITEM 6.4 - Glazing seals missing/deteriorated condition","severity_level":"non-critical","fault_id":"recFlOx96BqJhuZLm","prompt_id":"recFlOx96BqJhuZLm_prompt","inspection_id":"c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j"},{"id":"fee0e495-ef1c-4f33-9e8b-ac4891ffafb4","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.6 YEARLY SERVICE SCHEDULE FIRE-RATED GLAZING","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-rated glazing","variant":null,"variant_id":"recbiBQelzVodmYCL","item_no":"6.3","prompt":"(c) INSPECT perimeter to ensure no through-gaps\n are visible and the frame has been fire stopped\n where it meets bounding construction.","input":null,"possible_fault":"Visible gaps/inadequate fire stopping","possible_fault_description":"AS1851 TABLE 12.4.6 ITEM 6.3(c) - Through-gaps visible/inadequate fire stopping","severity_level":"non-conformance","fault_id":"recxTfw7UoL0zJCnF","prompt_id":"recxTfw7UoL0zJCnF_prompt","inspection_id":"c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recbiBQelzVodmYCL_recNGiNklGR6gJP5j"}]},{"id":"recBIKJKuGI2NhUw7","name":"Hinged and pivoted fire-resistant doorsets (SOU)","checklist":[{"id":"013934b9-79dc-4f46-9ebe-d7dfaa2abbb2","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.9","prompt":"(e) CHECK condition of frame.","input":null,"possible_fault":"Frame damaged or corroded","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.9(e) - Structural or surface frame damage weakens support and affects door operation","severity_level":"non-critical","fault_id":"recDvfsszlgsBZ5aM","prompt_id":"recDvfsszlgsBZ5aM_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"04ce9055-b9be-45e7-a1a6-6555ddbf3623","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.4","prompt":"(b) INSPECT all hardware is located correctly, securely attached and operational with the correct fittings in  accordance with the requirements of AS 1905.1 or  the relevant test report.","input":null,"possible_fault":"Hardware loose or detached","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.4(b) - Hardware is not securely fixed, affecting door operation and compromising fire integrity.","severity_level":"critical","fault_id":"rec85xuMxa4H70VLk","prompt_id":"rec85xuMxa4H70VLk_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"071dedad-4988-4028-b2eb-6c5c6956bd26","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.1","prompt":"INSPECT to determine if the fire-resistant doorset has\n been modified since the previous routine service.","input":null,"possible_fault":"Doorset modified without approval","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.1 - Unauthorized alterations may compromise fire resistance or invalidate certification","severity_level":"non-conformance","fault_id":"recMpfRBtmDcD7JeS","prompt_id":"recMpfRBtmDcD7JeS_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"0e082800-c68a-4f41-91ea-ff8b7a246d5b","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.13","prompt":"(b) INSPECT kickplates are securely fixed\n (where fitted).","input":null,"possible_fault":"Kickplates loose or missing","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.13(b) - Loose kickplates may obstruct door operation or expose core materials to damage","severity_level":"non-critical","fault_id":"recNP68LafCcDEWLM","prompt_id":"recNP68LafCcDEWLM_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"123ac0c3-7133-44fa-937a-15432f77c5b2","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.3","prompt":"(a) CHECK that gaps between the edge of the door leaf\n and the door frame are in accordance with\n AS 1905.1 or the relevant test report.","input":null,"possible_fault":"Gaps exceed AS 1905.1 limits","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.3(a) - Excessive or inconsistent gaps may permit smoke/fire spread or compromise the sealing effectiveness","severity_level":"non-conformance","fault_id":"recilKF5p5raGui3r","prompt_id":"recilKF5p5raGui3r_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"12e0c821-5ad7-4ade-b300-139b78db03ae","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.7","prompt":"INSPECT any installed door seals are approved for use\n on the proprietary door type, functioning as intended and\n are not damaged.","input":null,"possible_fault":"Seal not approved or damaged","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.7 - Damaged or incompatible seals fail to block smoke, voiding fire protection at gaps","severity_level":"non-critical","fault_id":"recvB6HVH8dsI1pUX","prompt_id":"recvB6HVH8dsI1pUX_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"21970884-4f5e-4443-8a9c-2d0159f44285","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.8","prompt":"(a) CHECK doors for any visible delamination,\n buckling, warping, bowing, twisting or significant\n damage.","input":null,"possible_fault":"Door delaminated or warped","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.8(a) - Structural defects such as bowing or twisting impair door fit and reduce fire resistance","severity_level":"non-critical","fault_id":"rec0FRbQbUwz8TS9s","prompt_id":"rec0FRbQbUwz8TS9s_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"2e67f966-c832-43b3-9d6f-be3dc40cb90e","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.9","prompt":"(c) CHECK door frame is free from excessive\n distortion at any point along frame sections.","input":null,"possible_fault":"Frame distorted or warped","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.9(c) - Frame deformation can prevent closure and affect latch/seal integrity","severity_level":"non-critical","fault_id":"rechCPZPbcTfJlpbG","prompt_id":"rechCPZPbcTfJlpbG_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"2f512fbd-9bc6-4943-a9a1-d75948718d49","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.10","prompt":"(c) CHECK to ensure perimeter trim and framing are\n secure and in sound condition, and all fixing screws\n are in place and consistent with the fire test\n approvals for the propriety door type.","input":null,"possible_fault":"Trim/framing loose or missing","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.10(c) - Loose or absent components can dislodge during fire, causing loss of seal around glass","severity_level":"non-critical","fault_id":"recScC0D7P9hbXDSD","prompt_id":"recScC0D7P9hbXDSD_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"3d407b03-25ff-4fd9-bcb7-56e62d0e8e86","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.4","prompt":"(c) INSPECT the door leaf and door frame are free from non-approved fittings, fixings or attachments and free from damage caused by relocation of  hardware items.","input":null,"possible_fault":"Non-approved fittings attached","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.4(c) - Door/frame has unapproved modifications impairing its fire resistance.","severity_level":"critical","fault_id":"reccfNbN0I6CzW6vu","prompt_id":"reccfNbN0I6CzW6vu_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"3ed6311a-2d15-413a-aba8-e9daefc1bc42","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.13","prompt":"(a) INSPECT the threshold for the door leaf is free\n from the addition of any combustible covering since\n installation or previous inspection.","input":null,"possible_fault":"Combustible threshold covering","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.13(a) - Coverings may ignite or compromise threshold fire performance","severity_level":"non-critical","fault_id":"reco55LVVq3B6lIkc","prompt_id":"reco55LVVq3B6lIkc_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"433c7ab2-a139-4e36-9ba4-689012cbb665","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.14","prompt":"INSPECT to ensure that meeting stile astragals are\n correct for the proprietary door type, installed as per\n manufacturer’s instructions, are in good working order\n and incorporate seals where required.","input":null,"possible_fault":"Astragal missing or incorrect","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.14 - Incorrect astragals may leave a gap between doors, allowing fire/smoke spread","severity_level":"non-critical","fault_id":"recZiuXVrhkAGNkEO","prompt_id":"recZiuXVrhkAGNkEO_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"4831f904-3477-48fb-b028-bfa417bb759d","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.2","prompt":"(b) INSPECT to ensure relevant statutory signage has\n been applied and that the location of the signage is\n in accordance with regulatory requirements.","input":null,"possible_fault":"Statutory signage missing","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.2(b) - Missing, damaged, or incorrectly placed signage may cause regulatory breaches or user confusion in emergencies","severity_level":"non-conformance","fault_id":"rec2bnNxO5eTibeHa","prompt_id":"rec2bnNxO5eTibeHa_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"49decce8-144c-4a6a-b653-b50732a801d5","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.9","prompt":"(b) CHECK steel door frames are back-filled as\n required for the proprietary door type and FRL.\n NOTE: See AS 1905.1.","input":null,"possible_fault":"Steel frames not back-filled","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.9(b) - Unfilled frames may allow fire spread through gaps and invalidate tested fire resistance","severity_level":"non-critical","fault_id":"reciKWbml3p0UMEe0","prompt_id":"reciKWbml3p0UMEe0_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"529889f4-0a03-4558-b12a-73ef6f0dfebd","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.9","prompt":"(a) CHECK door stop dimensions are approved for the\n proprietary door type and FRL.","input":null,"possible_fault":"Door stop dimensions incorrect","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.9(a) - Inaccurate stop sizes may prevent full seal contact and reduce fire containment","severity_level":"non-critical","fault_id":"rec0IE9wmS2shsjR5","prompt_id":"rec0IE9wmS2shsjR5_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"59f89348-9bd2-42f7-9d33-b9f2610e794c","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.5","prompt":"(c) Where passage sets or knobs are incorporated,\n INSPECT that the minimum clearance of 35 mm to\n the door stop is present.","input":null,"possible_fault":"Clearance < 35mm to stop","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.5(c) - Inadequate clearance may prevent full closure or allow flame/smoke leakage at latch points","severity_level":"non-critical","fault_id":"recknaqfwsIKj57bm","prompt_id":"recknaqfwsIKj57bm_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"5b1bc89e-1e77-47ea-be34-8a1aeb4d7a6d","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.12","prompt":"Where required, VERIFY travel limiting device is\n installed in accordance with AS 1905.1.","input":null,"possible_fault":"Travel limiter missing/faulty","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.12 - Missing or poorly positioned limiters may damage hinges or compromise door control under pressure","severity_level":"non-critical","fault_id":"recQjp6OqqavmLQOW","prompt_id":"recQjp6OqqavmLQOW_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"619bf94a-1e5e-4a28-a180-7676b3bfa643","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.6","prompt":"(b) INSPECT the door closer (body and arm) is free\n from obstruction by walls, fixtures and is operating\n freely throughout its swing.","input":null,"possible_fault":"Closer obstructed or jammed","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.6(b) - Physical obstruction or interference can limit door swing or delay closure in emergencies","severity_level":"critical","fault_id":"rec5ckgAViJmFQME1","prompt_id":"rec5ckgAViJmFQME1_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"6e3649cf-e57b-413a-aea6-55068dc78193","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.11","prompt":"CHECK proprietary door type is approved for use with\n the fire-resistant air transfer grille or fire damper and is\n installed as per manufacturer’s instructions.\n NOTE: Where a damper is incorporated in a fire door\n it is considered to be a fire-rated air transfer grille.","input":null,"possible_fault":"Grille/damper not approved","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.11 - Unapproved or incorrectly installed grilles may enable fire passage through the door","severity_level":"non-conformance","fault_id":"recQgPsoeGqFms6kg","prompt_id":"recQgPsoeGqFms6kg_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"732144a7-e47c-4828-8a4a-4541946d2c03","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.8","prompt":"(b) CHECK door edges are in good condition and free\n from any splitting or damage on all sides.","input":null,"possible_fault":"Door edges split or damaged","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.8(b) - Edge damage weakens door integrity and may affect closing/sealing performance","severity_level":"non-critical","fault_id":"recauwGSrbQC8jrPJ","prompt_id":"recauwGSrbQC8jrPJ_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"7503dd31-42c7-416b-a01d-d56cb6a64285","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.3","prompt":"(b) CHECK that the gap between the bottom edge of\n the door leaf and the finished floor level is in\n accordance with AS 1905.1 or the relevant test\n report.","input":null,"possible_fault":"Gap exceeds AS 1905.1 limits","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.3(b) - Large or uneven bottom gaps can hinder fire resistance or mechanical operation","severity_level":"non-conformance","fault_id":"rec1bzfkUY0zIynbI","prompt_id":"rec1bzfkUY0zIynbI_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"815dcbb6-f758-4589-8d97-afd90d16d8bd","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.4","prompt":"(a) INSPECT all hardware required for suspension,\n closing and latching is fitted and is a make and\n model that has been fire-tested for the specific fire-\n resistant door.","input":null,"possible_fault":"Hardware not fire-tested","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.4(a) - Unapproved or incompatible hardware may fail under fire conditions and void fire certification","severity_level":"non-conformance","fault_id":"recuDcR1hSZUXt4Sy","prompt_id":"recuDcR1hSZUXt4Sy_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"9deb12c8-8ef6-40bf-9280-cf3c15b54f96","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.2","prompt":"(a) INSPECT door leaves and door frames are tagged in\n accordance with AS 1905.1.","input":null,"possible_fault":"Tags missing or illegible","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.2(a) - Missing or non-compliant tags prevent verification of approved fire door construction","severity_level":"non-conformance","fault_id":"reclPeNKlJr2MzXTW","prompt_id":"reclPeNKlJr2MzXTW_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"bd2248dd-bc6e-40dc-8484-83f5dd48e8c8","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.9","prompt":"(d) CHECK to ensure doorframe incorporates a door\n striker plate.","input":null,"possible_fault":"Striker plate missing/damaged","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.9(d) - Missing or incorrect striker plates compromise latching and fire door performance","severity_level":"non-critical","fault_id":"recFd7oRfTAj2P0cL","prompt_id":"recFd7oRfTAj2P0cL_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"d75f5e20-99a9-4ed6-9a67-4e7720f7c971","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.10","prompt":"(b) CHECK to ensure glass is approved for the\n proprietary door type, in a sound condition and free\n from cracks.","input":null,"possible_fault":"Glass cracked or not rated","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.10(b) - Damaged or non-compliant glass may fail during fire exposure and compromise barrier integrity","severity_level":"non-critical","fault_id":"recgCEuCBcqPjmOvN","prompt_id":"recgCEuCBcqPjmOvN_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"d8d55ec9-f4d1-430a-938b-fba7561054c0","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.6","prompt":"(a) CHECK closers are free from oil leakages.","input":null,"possible_fault":"Oil leakage from closer","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.6(a) - Leaking hydraulic fluid may impair closer operation or indicate internal failure","severity_level":"non-critical","fault_id":"receVJdFk7Y6bfNuU","prompt_id":"receVJdFk7Y6bfNuU_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"d8ea232c-3f79-48a5-8f01-f7e6b4a40077","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.10","prompt":"(a) CHECK proprietary door type is approved for use\n of a vision panel.","input":null,"possible_fault":"Door not certified for panel","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.10(a) - Installing a vision panel in non-approved doors may reduce the fire-resistance level (FRL)","severity_level":"non-conformance","fault_id":"recfMA45cz0JeOZZI","prompt_id":"recfMA45cz0JeOZZI_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"dba4b970-ff77-4b69-b7c4-42b1e1c6fa82","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.5","prompt":"(a) VERIFY the opening and closing forces are such\n that the doors can be easily opened and closed in\n normal conditions and in fire mode, taking into\n account any pressurization systems within the\n building.","input":null,"possible_fault":"Excessive force required","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.5(a) - Difficult or inconsistent operation can prevent timely door closure, especially under fire or pressure conditions","severity_level":"non-critical","fault_id":"recCVkbT0M5gMvBTl","prompt_id":"recCVkbT0M5gMvBTl_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"dd612eaf-0292-469a-98e1-f4ed9e216947","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.15","prompt":"TEST that doors held in the open position, which require\n activation of detection system to close, to ensure the\n door closes satisfactorily upon power failure or detector\n activation.","input":null,"possible_fault":"Door fails to close on trigger","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.15 - Hold-open devices must release and allow full closure upon power failure or detection system activation","severity_level":"critical","fault_id":"recQd3U44UGbUKlmh","prompt_id":"recQd3U44UGbUKlmh_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"},{"id":"fe5dcf18-f634-4142-9c25-983553669614","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS (1 YEARLY FOR SOU)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Hinged and pivoted fire-resistant doorsets (SOU)","variant":null,"variant_id":"recBIKJKuGI2NhUw7","item_no":"1.5","prompt":"(b) INSPECT the doorset is self-closing and self-\n latching, if appropriate.","input":null,"possible_fault":"Door not self-closing/latching","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.5(b) - Faulty closing or latching prevents full engagement and compromises compartmentation","severity_level":"non-critical","fault_id":"reczBd5hqYFnPq0YT","prompt_id":"reczBd5hqYFnPq0YT_prompt","inspection_id":"c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recBIKJKuGI2NhUw7_recNGiNklGR6gJP5j"}]},{"id":"receY5fSkLOPKGxSx","name":"Horizontal sliding doors","checklist":[{"id":"03837684-7e49-45ea-bd5f-d86355b68ea6","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.9","prompt":"INSPECT floor and/or track and/or wall-mounted guides\n and stops and all travel-limiting devices at door open\n and close locations are adequate and soundly mounted.","input":null,"possible_fault":"Guides or stops damaged; limiters missing or loose","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.9 - INSPECT all guides, stops, and limiting devices are soundly mounted and effective in both open and closed positions.","severity_level":"non-critical","fault_id":"rec06AyVs0AjNnmZG","prompt_id":"rec06AyVs0AjNnmZG_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"0531405e-132d-40e7-a4fe-8a52472055b9","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.5","prompt":"CHECK forces to open and close door leaves do not\n exceed maximum 110 N for a door in the path of travel\n to an exit and 180 N from the closed position and 135 N\n through its full travel in other places.","input":null,"possible_fault":"Forces exceed 110N/180N/135N","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.5 - CHECK that door leaf forces do not exceed: 110N (path of travel to exit), 180N (from closed), and 135N (through full travel).","severity_level":"non-critical","fault_id":"rec5lyAt5cvHFNZIB","prompt_id":"rec5lyAt5cvHFNZIB_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"0dfc07be-5a1a-4fd3-b7b2-b01c6b459369","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.4","prompt":"INSPECT clearances and overlaps of door panel(s) are\n in accordance with AS 1905.1.","input":null,"possible_fault":"Gaps exceed limits or overlaps insufficient","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.4 - INSPECT clearances and overlaps of door panels are in accordance with AS 1905.1.","severity_level":"non-critical","fault_id":"recPRYMHN2Ls9Hc9p","prompt_id":"recPRYMHN2Ls9Hc9p_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"137d8521-9889-442d-a6a6-694942f43aec","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.13","prompt":"(b) CHECK the sill under the door leaf is free from the\n addition of any combustible covering since\n installation or previous inspection.","input":null,"possible_fault":"Combustible materials added to sill","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.13(b) - CHECK sill under the door is free from combustible coverings since last inspection.","severity_level":"non-critical","fault_id":"recpRHyEIGB2VSpUN","prompt_id":"recpRHyEIGB2VSpUN_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"16824725-77fa-4474-8ee3-ac51cb982ee1","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.2","prompt":"INSPECT against drawings and all schedules (see Clause 12.2.5) to ensure that no fire doors has been added, removed or modified.","input":null,"possible_fault":"Fire door location mismatch with drawings","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.2 – Fire door location differs from approved drawings/schedule","severity_level":"non-conformance","fault_id":"recqWksH0zsN2XFex","prompt_id":"recqWksH0zsN2XFex_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"294be84b-d679-4c17-a68b-4486cff12cbe","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.8","prompt":"(a) CHECK fusible links, where fitted, are intact and\n unpainted.","input":null,"possible_fault":"Fusible links missing, painted or damaged","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.8(a) - CHECK fusible links are intact, functional, and free of paint.","severity_level":"critical","fault_id":"rec3GDWWRiWgsUERG","prompt_id":"rec3GDWWRiWgsUERG_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"2e2eb9b1-bb64-47dc-80b3-5ecdb0310555","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.8","prompt":"(f) CHECK operation to ensure the door fully closes\n from one intermediary position.","input":null,"possible_fault":"Door fails to close fully from mid-position","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.8(f) - CHECK the door fully closes when released from an intermediary position.","severity_level":"non-critical","fault_id":"recxLyjJB8LLnWnj1","prompt_id":"recxLyjJB8LLnWnj1_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"3035ca3f-53d6-4d85-a09c-9a8e6eb7a0d7","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.7","prompt":"(a) INSPECT hardware required for suspension and\n operation is fitted and is as per manufacturer’s\n specifications.","input":null,"possible_fault":"Hardware missing or incorrect","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.7(a) - INSPECT all hardware required for suspension and operation matches manufacturer's specifications.","severity_level":"non-conformance","fault_id":"recXT82wUwm9qYHSD","prompt_id":"recXT82wUwm9qYHSD_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"3bdc26dc-078e-48b6-819a-36793907c224","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.7","prompt":"(b) INSPECT hardware is securely attached with the\n correct fittings in accordance with the requirements\n of AS 1905.1.","input":null,"possible_fault":"Loose or incorrect fixings","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.7(b) - INSPECT hardware is securely fixed using appropriate fittings as per AS 1905.1.","severity_level":"non-critical","fault_id":"recUspEz9FpeSIJHa","prompt_id":"recUspEz9FpeSIJHa_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"3d7136c0-7656-4521-a124-b8c7b10efeea","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.8","prompt":"(b) CHECK pulley cables are free from fraying, kinks,\n excessive stretching and corrosion.","input":null,"possible_fault":"Cables frayed, kinked or corroded","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.8(b) - CHECK pulley cables for signs of fraying, kinks, over-stretching or corrosion.","severity_level":"non-critical","fault_id":"recyDSFOnjH7yyj7u","prompt_id":"recyDSFOnjH7yyj7u_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"59880a60-330f-46f6-900e-90ebefc8df82","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.13","prompt":"(a) CHECK service access panels for cavity sliders are\n suitable and accessible.","input":null,"possible_fault":"Panels missing, inaccessible or unsuitable","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.13(a) - CHECK that cavity slider access panels are accessible and appropriately designed.","severity_level":"non-conformance","fault_id":"reclmqqoSRMz9SbRd","prompt_id":"reclmqqoSRMz9SbRd_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"5a2edba7-d066-4c50-ad29-7e5b7357e6f4","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.6","prompt":"INSPECT restraint brackets and/or interlocking steel\n sections are as per manufacturer’s specifications, fixed\n adequately and functional.","input":null,"possible_fault":"Loose brackets or damaged flame guards","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.6 - INSPECT brackets and interlocking sections are per manufacturer's specifications, fixed adequately, and functional.","severity_level":"non-critical","fault_id":"recidnyPymCb4cVJ5","prompt_id":"recidnyPymCb4cVJ5_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"5eca6c07-80b2-4acf-afbe-4fcc66468c7d","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.3","prompt":"(a) INSPECT door leaves and door frames (where\n applicable) are tagged in accordance with\n AS 1905.1.","input":null,"possible_fault":"Tags missing, illegible or non-compliant","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.3(a) - INSPECT door leaves and frames (if applicable) are tagged in accordance with AS 1905.1.","severity_level":"non-conformance","fault_id":"recTUvAMRrpeL7qr7","prompt_id":"recTUvAMRrpeL7qr7_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"81645186-e70c-4f47-88ca-20f44d412b3a","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.16","prompt":"Power-assisted sliding doors are to be serviced in\n accordance with the manufacturer’s maintenance\n procedures.","input":null,"possible_fault":"Maintenance not per manufacturer or overdue","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.16 - Power-assisted doors must be serviced as per the manufacturer's maintenance guidelines.","severity_level":"non-conformance","fault_id":"rec0O5hJdw305N97X","prompt_id":"rec0O5hJdw305N97X_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"864b7b61-2048-40c7-a623-72bbb0800012","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.8","prompt":"(e) PERFORM a full operational test (mechanically\n and electrically) as appropriate to ensure correct\n automatic closing of the door is achieved.","input":null,"possible_fault":"Auto-closing mechanism failed","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.8(e) - PERFORM a full operational test to verify the auto-closing mechanism functions correctly.","severity_level":"critical","fault_id":"recL4Ikyim9iglzoG","prompt_id":"recL4Ikyim9iglzoG_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"8875a1c4-ce00-41d8-a942-ebd8ceb038ce","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.11","prompt":"(b) CHECK door leaf or leaves is/are free from any\n non-approved fittings, fixings and attachments.","input":null,"possible_fault":"Non-approved fixings or fittings present","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.11(b) - CHECK door leaves are free from any unauthorised or non-compliant fixings or attachments.","severity_level":"non-conformance","fault_id":"recWUHC56tHdfOYw0","prompt_id":"recWUHC56tHdfOYw0_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"8db9162c-ca77-4745-9e74-83c9c243c814","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.11","prompt":"(a) INSPECT door leaf or leaves are free from any\n delamination, any other damage and all perimeter\n edge capping is complete and sound.","input":null,"possible_fault":"Door delaminated or edge capping incomplete","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.11(a) - INSPECT that door leaves are free from delamination or damage and have complete perimeter edge capping.","severity_level":"non-critical","fault_id":"recEdsJawBt1L17Cg","prompt_id":"recEdsJawBt1L17Cg_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"9969c7ed-ba84-4213-80cd-49b98d20ed45","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.10","prompt":"(b) CHECK flush pulls, handles or grips are securely\n fixed.","input":null,"possible_fault":"Handles loose or improperly attached","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.10(b) - CHECK that flush pulls, handles or grips are securely fixed and serviceable.","severity_level":"non-critical","fault_id":"recgL6lM3Szshrfnq","prompt_id":"recgL6lM3Szshrfnq_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"a47a221b-99cc-4f2f-8832-1db8f63e7889","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.8","prompt":"(d) REPLACE all fusible links every 25 years from the\n date of manufacture.\n NOTE: In lieu of replacing all fusible links, a\n representative sample may be tested as per\n Section 2.","input":null,"possible_fault":"Fusible links expired or test failed","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.8(d) - REPLACE all fusible links every 25 years. Alternatively, test a representative sample as per Section 2.","severity_level":"critical","fault_id":"rec8pGHx6NHuFsHE6","prompt_id":"rec8pGHx6NHuFsHE6_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"a573168d-c0a3-4204-a8d7-f1750381898f","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.1","prompt":"SIMULATE a full operational test (mechanically and\n electronically) as appropriate to ensure correct\n automatic closing of the door is achieved.\n CHECK operation to ensure the door fully closes from\n the fully open position and from one intermediary\n position.","input":null,"possible_fault":"Door doesn't close fully or auto-close fails","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.1 - SIMULATE a full operational test (mechanically and electronically) to ensure correct automatic closing of the door is achieved. CHECK that it fully closes from both fully open and intermediary positions.","severity_level":"non-critical","fault_id":"recq3j5FgqHQeFNIY","prompt_id":"recq3j5FgqHQeFNIY_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"3_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"acd3bf5a-7b67-40e6-a51e-a28ba8d61321","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.10","prompt":"(a) CHECK arrows indicating opening direction are\n fixed to each side of the door leaves.","input":null,"possible_fault":"Direction arrows missing or incorrectly attached","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.10(a) - CHECK direction arrows indicating opening direction are fixed to both sides of door leaves.","severity_level":"non-conformance","fault_id":"rec1CDcCCh7XzZnqN","prompt_id":"rec1CDcCCh7XzZnqN_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"b28e65c0-465f-4d07-9e48-428a062f2a7b","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.12","prompt":"CHECK door frame is adequately anchored to the\n opening.","input":null,"possible_fault":"Frame loose or inadequately secured","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.12 - CHECK door frame is structurally anchored to the wall opening.","severity_level":"non-critical","fault_id":"recKpREK7S6aa3fhI","prompt_id":"recKpREK7S6aa3fhI_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"b29b4c89-b9cd-43ea-b2e6-a5ed52db4e2d","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.3","prompt":"(b) INSPECT to ensure relevant statutory signage has\n been applied and that the location of the signage is\n in accordance with regulatory requirements.","input":null,"possible_fault":"Signage missing, damaged or incorrectly located","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.3(b) - INSPECT that statutory signage is applied and correctly located as per regulatory requirements.","severity_level":"non-conformance","fault_id":"recIALgu9VO1rHqh2","prompt_id":"recIALgu9VO1rHqh2_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"b56f50c6-d204-41c5-8e6a-d9f61a225f89","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.14","prompt":"In addition to the above, INSPECT overlaps or jointing\n of individual door leaf panels at meeting stiles are in\n proper alignment and comply with manufacturer’s\n specifications.","input":null,"possible_fault":"Overlaps misaligned or non-compliant","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.14 - INSPECT alignment and overlap of multi-leaf doors at stiles meet manufacturer specifications.","severity_level":"non-conformance","fault_id":"recW5iIxuxdgVt0c5","prompt_id":"recW5iIxuxdgVt0c5_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"d2c2a2fa-a1e3-4497-acd0-a8f4fd257707","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.15","prompt":"INSPECT wicket or personnel access doors operate\n satisfactorily in accordance with the hinged door leaf\n requirements, and in accordance with the manufacturer’s\n test approval.\n NOTE: These doors are usually found integrated\n within the sliding door leaf or leaves and are typically\n side-hung doors.","input":null,"possible_fault":"Wicket doors not operating per hinged door specs","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.15 - INSPECT wicket or personnel doors function per hinged door specs and manufacturer test approval.","severity_level":"non-critical","fault_id":"recdYG7CETziro4gO","prompt_id":"recdYG7CETziro4gO_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"e38380e8-e803-4c06-a6f2-1e7949770f5a","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.8","prompt":"(g) TEST operation of illuminated sliding doors,\n warning signs, sounders and release delays, as\n appropriate.","input":null,"possible_fault":"Warning systems inoperative or delay time incorrect","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.8(g) - TEST operation of illuminated signage, sounders, and release delay systems, as applicable.","severity_level":"critical","fault_id":"recntA3tJAXDW2pZs","prompt_id":"recntA3tJAXDW2pZs_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"},{"id":"f615ca54-9124-465a-ac01-8c066958d718","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.2 THREE-MONTHLY AND SIX-MONTHLY SERVICE SCHEDULE HORIZONTAL SLIDING DOORS FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Horizontal sliding doors","variant":null,"variant_id":"receY5fSkLOPKGxSx","item_no":"2.8","prompt":"(c) CHECK pulleys are free to rotate.","input":null,"possible_fault":"Pulleys seized or obstructed","possible_fault_description":"AS1851 2012 TABLE 12.4.3.2 ITEM 2.8(c) - CHECK pulleys are free-rotating and unobstructed.","severity_level":"non-critical","fault_id":"recWyG9qhvriK7G8S","prompt_id":"recWyG9qhvriK7G8S_prompt","inspection_id":"c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j","grouping_key":"6_month::c_receY5fSkLOPKGxSx_recNGiNklGR6gJP5j"}]},{"id":"recG8NFpzAHWcvBng","name":"Hinged and pivoted smoke doors","checklist":[]},{"id":"recGMslnFtOuh6mkF","name":"Hinged and pivoted smoke doors (SOU)","checklist":[]},{"id":"rechOWZYAlVujBFIf","name":"Fire and smoke rated access panels and hatches","checklist":[{"id":"30113577-f1c7-4ae1-83aa-f4a15e5d928e","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.4 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FIRE AND SMOKE RATED ACCESS PANELS AND HATCHES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke rated access panels and hatches","variant":null,"variant_id":"rechOWZYAlVujBFIf","item_no":"4.3","prompt":"(b) VERIFY that doorframe is free from excessive\n distortion at any point along frame sections.","input":null,"possible_fault":"Frame distorted affecting seal integrity","possible_fault_description":"AS1851 2012 TABLE 12.4.1.4 ITEM 4.3(b) - Doorframe shows excessive distortion at any point along frame sections","severity_level":"non-critical","fault_id":"recMu3qJxqqGDMqxH","prompt_id":"recMu3qJxqqGDMqxH_prompt","inspection_id":"c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j"},{"id":"38f61c15-b81a-4326-82f1-5a6a31c436e5","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.4 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FIRE AND SMOKE RATED ACCESS PANELS AND HATCHES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke rated access panels and hatches","variant":null,"variant_id":"rechOWZYAlVujBFIf","item_no":"4.3","prompt":"(a) INSPECT access panel frame is adequately\n anchored to surrounding structure.","input":null,"possible_fault":"Frame not adequately anchored to structure","possible_fault_description":"AS1851 2012 TABLE 12.4.1.4 ITEM 4.3(a) - Access panel frame inadequately anchored to surrounding structural elements","severity_level":"non-critical","fault_id":"recG6TaG4o83WBREe","prompt_id":"recG6TaG4o83WBREe_prompt","inspection_id":"c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j"},{"id":"57a517f4-323e-4ca1-aed0-62e1474d14cf","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.4 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FIRE AND SMOKE RATED ACCESS PANELS AND HATCHES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke rated access panels and hatches","variant":null,"variant_id":"rechOWZYAlVujBFIf","item_no":"4.6","prompt":"INSPECT that any added laminates and/or hardware\n do not interfere with the function of the access panel.","input":null,"possible_fault":"Additions interfering with panel operation","possible_fault_description":"AS1851 2012 TABLE 12.4.1.4 ITEM 4.6 - Added laminates/hardware interfere with access panel function and operation","severity_level":"non-conformance","fault_id":"recEHo2bGTrtM5jtI","prompt_id":"recEHo2bGTrtM5jtI_prompt","inspection_id":"c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j"},{"id":"754f6eda-b18d-4598-91ae-0ceaafeb0650","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.4 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FIRE AND SMOKE RATED ACCESS PANELS AND HATCHES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke rated access panels and hatches","variant":null,"variant_id":"rechOWZYAlVujBFIf","item_no":"4.5","prompt":"(b) INSPECT no visible through-gap is created\n around lock/latch, and that the correct number of\n hinges and locks are present.","input":null,"possible_fault":"Visible gaps/incorrect hardware quantity","possible_fault_description":"AS1851 2012 TABLE 12.4.1.4 ITEM 4.5(b) - Through-gaps around locks/latches or incorrect number of hinges/locks present","severity_level":"non-critical","fault_id":"recri6LevA5kllX0O","prompt_id":"recri6LevA5kllX0O_prompt","inspection_id":"c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j"},{"id":"9e16b7ba-1306-49f1-b919-9264ca9b0a29","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.4 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FIRE AND SMOKE RATED ACCESS PANELS AND HATCHES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke rated access panels and hatches","variant":null,"variant_id":"rechOWZYAlVujBFIf","item_no":"4.1","prompt":"INSPECT against drawings (see Clause 12.2.5) that\n access panels or hatches, including resistance to\n incipient spread of fire, have been added, removed or\n modified.","input":null,"possible_fault":"Access panels added/removed/modified","possible_fault_description":"AS1851 2012 TABLE 12.4.1.4 ITEM 4.1 - Access panels/hatches including incipient spread resistance don't match drawings","severity_level":"non-conformance","fault_id":"recDgb5DhjbzMdsMB","prompt_id":"recDgb5DhjbzMdsMB_prompt","inspection_id":"c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j"},{"id":"a513bb92-7299-45c6-bc37-066ba70c8e47","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.4 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FIRE AND SMOKE RATED ACCESS PANELS AND HATCHES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke rated access panels and hatches","variant":null,"variant_id":"rechOWZYAlVujBFIf","item_no":"4.5","prompt":"(a) INSPECT to ensure hinges are in good working\n order and any latches are operational.","input":null,"possible_fault":"Hinges/latches not working properly","possible_fault_description":"AS1851 2012 TABLE 12.4.1.4 ITEM 4.5(a) - Hinges not in good working order or latches not operational as required","severity_level":"non-critical","fault_id":"recRd3niM0oKNSSJN","prompt_id":"recRd3niM0oKNSSJN_prompt","inspection_id":"c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j"},{"id":"a626d3fd-5fb7-449f-9921-d681f3c40bbf","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.4 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FIRE AND SMOKE RATED ACCESS PANELS AND HATCHES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke rated access panels and hatches","variant":null,"variant_id":"rechOWZYAlVujBFIf","item_no":"4.4","prompt":"INSPECT to ensure screw fixings are all present and\n engaged in the frame securely.","input":null,"possible_fault":"Screw fixings missing/loose/inadequate","possible_fault_description":"AS1851 2012 TABLE 12.4.1.4 ITEM 4.4 -Screw fixings missing, loose, or not properly engaged in frame securely","severity_level":"non-critical","fault_id":"recTKT48pBz5CJb19","prompt_id":"recTKT48pBz5CJb19_prompt","inspection_id":"c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j"},{"id":"c41c378d-803f-455c-89b3-1542960a2a5a","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.4 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FIRE AND SMOKE RATED ACCESS PANELS AND HATCHES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke rated access panels and hatches","variant":null,"variant_id":"rechOWZYAlVujBFIf","item_no":"4.2","prompt":"(a) INSPECT panel to ensure it is free of any visible\n delamination, and other damage.","input":null,"possible_fault":"Panel delamination/visible damage detected","possible_fault_description":"AS1851 2012 TABLE 12.4.1.4 ITEM 4.2(a) -Panel shows visible delamination or other damage compromising fire rating integrity","severity_level":"non-critical","fault_id":"recOqss9C5pjhdwGP","prompt_id":"recOqss9C5pjhdwGP_prompt","inspection_id":"c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j"},{"id":"e345ff74-55e7-4a07-b925-524627a4d742","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.4 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FIRE AND SMOKE RATED ACCESS PANELS AND HATCHES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke rated access panels and hatches","variant":null,"variant_id":"rechOWZYAlVujBFIf","item_no":"4.2","prompt":"(b) INSPECT that the any perimeter seal is in good\n condition and not damaged.","input":null,"possible_fault":"Perimeter seal damaged/missing/deteriorated","possible_fault_description":"AS1851 2012 TABLE 12.4.1.4 ITEM 4.2(b) - Perimeter seal shows damage, deterioration, or installation defects affecting integrity","severity_level":"non-critical","fault_id":"recaMtkT4l5um3M7m","prompt_id":"recaMtkT4l5um3M7m_prompt","inspection_id":"c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j","grouping_key":"1_year::c_rechOWZYAlVujBFIf_recNGiNklGR6gJP5j"}]},{"id":"recI7nTr2kH2VBSsV","name":"Floors, service penetrations and control joints","checklist":[]},{"id":"recnrMixWMp1DbCR6","name":"Hinged and pivoted fire-resistant doorsets","checklist":[{"id":"15b175d1-a3c2-4001-92af-48cabf7bf3b5","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.8","prompt":"(a) CHECK doors for any visible delamination,\n buckling, warping, bowing, twisting or significant\n damage.","input":null,"possible_fault":"Door delaminated or warped","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.8(a) - Structural defects such as bowing or twisting impair door fit and reduce fire resistance","severity_level":"non-critical","fault_id":"recAX1hsDFiQM7bPm","prompt_id":"recAX1hsDFiQM7bPm_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"1d7f0305-ff5d-4b7b-b126-3fa47c32778f","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.5","prompt":"(b) INSPECT the doorset is self-closing and self-\n latching, if appropriate.","input":null,"possible_fault":"Door not self-closing/latching","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.5(b) - Faulty closing or latching prevents full engagement and compromises compartmentation","severity_level":"non-critical","fault_id":"recu8ZBoAk66jAXv4","prompt_id":"recu8ZBoAk66jAXv4_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"30891e22-c2cd-4012-8b2a-572d63116215","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.9","prompt":"(a) CHECK door stop dimensions are approved for the\n proprietary door type and FRL.","input":null,"possible_fault":"Door stop dimensions incorrect","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.9(a) - Inaccurate stop sizes may prevent full seal contact and reduce fire containment","severity_level":"non-critical","fault_id":"recQGpM9k9lL06y0x","prompt_id":"recQGpM9k9lL06y0x_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"3beb2fab-92dc-4a5a-83c5-cde4a40a909c","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.4","prompt":"(a) INSPECT all hardware required for suspension,\n closing and latching is fitted and is a make and\n model that has been fire-tested for the specific fire-\n resistant door.","input":null,"possible_fault":"Hardware not fire-tested","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.4(a) - Unapproved or incompatible hardware may fail under fire conditions and void fire certification","severity_level":"non-conformance","fault_id":"recfRLo1QuLF9w83O","prompt_id":"recfRLo1QuLF9w83O_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"4168c21a-0a40-4e5f-9c62-e2e1dfeb1476","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.2","prompt":"(a) INSPECT door leaves and door frames are tagged in\n accordance with AS 1905.1.","input":null,"possible_fault":"Tags missing or illegible","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.2(a) - Missing or non-compliant tags prevent verification of approved fire door construction","severity_level":"non-conformance","fault_id":"recNat4zS0uIKJaaF","prompt_id":"recNat4zS0uIKJaaF_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"426d510f-62ee-4d06-8082-356db5e0e145","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.3","prompt":"(a) CHECK that gaps between the edge of the door leaf\n and the door frame are in accordance with\n AS 1905.1 or the relevant test report.","input":null,"possible_fault":"Gaps exceed AS 1905.1 limits","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.3(a) - Excessive or inconsistent gaps may permit smoke/fire spread or compromise the sealing effectiveness","severity_level":"non-conformance","fault_id":"recAJAabIfR1mPwad","prompt_id":"recAJAabIfR1mPwad_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"43ba6b69-7d6f-465c-b729-f243c40c6112","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.9","prompt":"(b) CHECK steel door frames are back-filled as\n required for the proprietary door type and FRL.\n NOTE: See AS 1905.1.","input":null,"possible_fault":"Steel frames not back-filled","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.9(b) - Unfilled frames may allow fire spread through gaps and invalidate tested fire resistance","severity_level":"non-critical","fault_id":"recwnvbBmz1ts3nJK","prompt_id":"recwnvbBmz1ts3nJK_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"44db0282-d17e-4b42-b9c7-0729ced61562","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.5","prompt":"(c) Where passage sets or knobs are incorporated,\n INSPECT that the minimum clearance of 35 mm to\n the door stop is present.","input":null,"possible_fault":"Clearance < 35mm to stop","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.5(c) - Inadequate clearance may prevent full closure or allow flame/smoke leakage at latch points","severity_level":"non-critical","fault_id":"recKSE32NcJVcEEe5","prompt_id":"recKSE32NcJVcEEe5_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"4954a0fb-c64f-4000-adc2-885cd7b86e4e","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.1","prompt":"INSPECT to determine if the fire-resistant doorset has\n been modified since the previous routine service.","input":null,"possible_fault":"Doorset modified without approval","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.1 - Unauthorized alterations may compromise fire resistance or invalidate certification","severity_level":"non-conformance","fault_id":"recgooWb2T9guYKWc","prompt_id":"recgooWb2T9guYKWc_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"4b7abd74-7165-497e-a326-fba11fc200ec","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.10","prompt":"(a) CHECK proprietary door type is approved for use\n of a vision panel.","input":null,"possible_fault":"Door not certified for panel","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.10(a) - Installing a vision panel in non-approved doors may reduce the fire-resistance level (FRL)","severity_level":"non-conformance","fault_id":"rec0uKF7bXcqkrER0","prompt_id":"rec0uKF7bXcqkrER0_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"4e6282a7-1ba0-452f-921c-b7f6753f650b","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.4","prompt":"(c) INSPECT the door leaf and door frame are free\n from non-approved fittings, fixings or attachments\n and free from damage caused by relocation of\n hardware items.","input":null,"possible_fault":"Non-approved fittings present","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.4(c) - Unauthorised fittings or hardware relocation damage may degrade door integrity","severity_level":"non-conformance","fault_id":"rec1zlZUCbTA7RHGX","prompt_id":"rec1zlZUCbTA7RHGX_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"504b28db-b3c5-4174-874d-faf8f27ea9cd","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.5","prompt":"(a) VERIFY the opening and closing forces are such\n that the doors can be easily opened and closed in\n normal conditions and in fire mode, taking into\n account any pressurization systems within the\n building.","input":null,"possible_fault":"Excessive force required","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.5(a) - Difficult or inconsistent operation can prevent timely door closure, especially under fire or pressure conditions","severity_level":"non-critical","fault_id":"recErXS2t0jmGZolH","prompt_id":"recErXS2t0jmGZolH_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"526d2584-84f9-4d6b-a64b-df3f23ed20af","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.3","prompt":"(b) CHECK that the gap between the bottom edge of\n the door leaf and the finished floor level is in\n accordance with AS 1905.1 or the relevant test\n report.","input":null,"possible_fault":"Gap exceeds AS 1905.1 limits","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.3(b) - Large or uneven bottom gaps can hinder fire resistance or mechanical operation","severity_level":"non-conformance","fault_id":"recsxbPfCUz7oBfOE","prompt_id":"recsxbPfCUz7oBfOE_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"5db7966a-158a-4ac2-845e-39e7ea19b038","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.4","prompt":"(b) INSPECT all hardware is located correctly, securely\n attached and operational with the correct fittings in\n accordance with the requirements of AS 1905.1 or\n the relevant test report.","input":null,"possible_fault":"Hardware incorrectly located","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.4(b) - Incorrect positioning or insecure fixing may affect operation and compromise fire door performance","severity_level":"non-critical","fault_id":"reclVDKG9XLaqtPHd","prompt_id":"reclVDKG9XLaqtPHd_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"5e0a8165-3113-45b8-83c3-6a0f0de0f1a1","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.15","prompt":"TEST that doors held in the open position, which require\n activation of detection system to close, to ensure the\n door closes satisfactorily upon power failure or detector\n activation.","input":null,"possible_fault":"Door fails to close on trigger","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.15 - Hold-open devices must release and allow full closure upon power failure or detection system activation","severity_level":"critical","fault_id":"recm7KB0WAxVX8WTl","prompt_id":"recm7KB0WAxVX8WTl_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"6d2a9c25-b61c-4627-8507-63d7e10ce066","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.8","prompt":"(b) CHECK door edges are in good condition and free\n from any splitting or damage on all sides.","input":null,"possible_fault":"Door edges split or damaged","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.8(b) - Edge damage weakens door integrity and may affect closing/sealing performance","severity_level":"non-critical","fault_id":"rec4xHwYQKiahR0Pe","prompt_id":"rec4xHwYQKiahR0Pe_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"7a146661-8f5b-49d1-8d06-7fbaf4eb0688","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.12","prompt":"Where required, VERIFY travel limiting device is\n installed in accordance with AS 1905.1.","input":null,"possible_fault":"Travel limiter missing/faulty","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.12 - Missing or poorly positioned limiters may damage hinges or compromise door control under pressure","severity_level":"non-critical","fault_id":"recRNYV9c74467pfa","prompt_id":"recRNYV9c74467pfa_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"7a928e84-8a43-4127-afd8-11dd01161b5f","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.13","prompt":"(b) INSPECT kickplates are securely fixed\n (where fitted).","input":null,"possible_fault":"Kickplates loose or missing","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.13(b) - Loose kickplates may obstruct door operation or expose core materials to damage","severity_level":"non-critical","fault_id":"recTB6PcgLqwjohUQ","prompt_id":"recTB6PcgLqwjohUQ_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"8e0b0ad0-e9ea-4969-a8f4-301e6c5f3eb9","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.13","prompt":"(a) INSPECT the threshold for the door leaf is free\n from the addition of any combustible covering since\n installation or previous inspection.","input":null,"possible_fault":"Combustible threshold covering","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.13(a) - Coverings may ignite or compromise threshold fire performance","severity_level":"non-critical","fault_id":"recVwYpxrxzHKogEy","prompt_id":"recVwYpxrxzHKogEy_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"9b167f4c-1596-415f-aa35-ee185c777152","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.11","prompt":"CHECK proprietary door type is approved for use with\n the fire-resistant air transfer grille or fire damper and is\n installed as per manufacturer’s instructions.\n NOTE: Where a damper is incorporated in a fire door\n it is considered to be a fire-rated air transfer grille.","input":null,"possible_fault":"Grille/damper not approved","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.11 - Unapproved or incorrectly installed grilles may enable fire passage through the door","severity_level":"non-conformance","fault_id":"recec5JgMuBmJ3x2m","prompt_id":"recec5JgMuBmJ3x2m_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"9cf9133a-90b9-4ea1-8e6f-0aebddf01b7e","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.10","prompt":"(b) CHECK to ensure glass is approved for the\n proprietary door type, in a sound condition and free\n from cracks.","input":null,"possible_fault":"Glass cracked or not rated","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.10(b) - Damaged or non-compliant glass may fail during fire exposure and compromise barrier integrity","severity_level":"non-critical","fault_id":"recljQ1z4T8r2wS2u","prompt_id":"recljQ1z4T8r2wS2u_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"9d19d1c2-fe00-4478-b4b3-2cc37c9b8314","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.14","prompt":"INSPECT to ensure that meeting stile astragals are\n correct for the proprietary door type, installed as per\n manufacturer’s instructions, are in good working order\n and incorporate seals where required.","input":null,"possible_fault":"Astragal missing or incorrect","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.14 - Incorrect astragals may leave a gap between doors, allowing fire/smoke spread","severity_level":"non-critical","fault_id":"recY5IcQ6X8GKZcz9","prompt_id":"recY5IcQ6X8GKZcz9_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"b91c0590-2d09-45e5-9040-351dbdd4baf0","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.6","prompt":"(a) CHECK closers are free from oil leakages.","input":null,"possible_fault":"Oil leakage from closer","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.6(a) - Leaking hydraulic fluid may impair closer operation or indicate internal failure","severity_level":"non-critical","fault_id":"rec20qAkctrlK510e","prompt_id":"rec20qAkctrlK510e_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"b99301ab-8dba-418b-bf53-b048e771ca85","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.9","prompt":"(d) CHECK to ensure doorframe incorporates a door\n striker plate.","input":null,"possible_fault":"Striker plate missing/damaged","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.9(d) - Missing or incorrect striker plates compromise latching and fire door performance","severity_level":"non-critical","fault_id":"recqYUIk9U10iLa3T","prompt_id":"recqYUIk9U10iLa3T_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"c6996a9f-a6eb-4fd6-a85e-5ec4c022b059","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.2","prompt":"(b) INSPECT to ensure relevant statutory signage has\n been applied and that the location of the signage is\n in accordance with regulatory requirements.","input":null,"possible_fault":"Statutory signage missing","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.2(b) - Missing, damaged, or incorrectly placed signage may cause regulatory breaches or user confusion in emergencies","severity_level":"non-conformance","fault_id":"recTaWPdSUcw6AtWH","prompt_id":"recTaWPdSUcw6AtWH_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"c948ec13-cc70-4f45-a1bc-44e2f8e148b3","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.7","prompt":"INSPECT any installed door seals are approved for use\n on the proprietary door type, functioning as intended and\n are not damaged.","input":null,"possible_fault":"Seal not approved or damaged","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.7 - Damaged or incompatible seals fail to block smoke, voiding fire protection at gaps","severity_level":"non-critical","fault_id":"recgZKIYpfZsAeItM","prompt_id":"recgZKIYpfZsAeItM_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"c9b2443e-3496-4ce4-8e93-07c398ddb66e","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.10","prompt":"(c) CHECK to ensure perimeter trim and framing are\n secure and in sound condition, and all fixing screws\n are in place and consistent with the fire test\n approvals for the propriety door type.","input":null,"possible_fault":"Trim/framing loose or missing","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.10(c) - Loose or absent components can dislodge during fire, causing loss of seal around glass","severity_level":"non-critical","fault_id":"recbzS9ZMa6237EFn","prompt_id":"recbzS9ZMa6237EFn_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"d7cc0ffd-f9a8-426f-8253-64a9119ad918","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.6","prompt":"(b) INSPECT the door closer (body and arm) is free\n from obstruction by walls, fixtures and is operating\n freely throughout its swing.","input":null,"possible_fault":"Closer obstructed or jammed","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.6(b) - Physical obstruction or interference can limit door swing or delay closure in emergencies","severity_level":"critical","fault_id":"rec3D83GJKss4Dit8","prompt_id":"rec3D83GJKss4Dit8_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"d965a4ff-76ae-4dc7-b5c7-dd1c3fc2ea42","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.9","prompt":"(e) CHECK condition of frame.","input":null,"possible_fault":"Frame damaged or corroded","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.9(e) - Structural or surface frame damage weakens support and affects door operation","severity_level":"non-critical","fault_id":"recyI5whm4rsYd9ai","prompt_id":"recyI5whm4rsYd9ai_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"},{"id":"ea3a6e54-7705-47a5-bd40-eaadd5c43084","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.3.1 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED FIRE-RESISTANT DOORSETS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted fire-resistant doorsets","variant":null,"variant_id":"recnrMixWMp1DbCR6","item_no":"1.9","prompt":"(c) CHECK door frame is free from excessive\n distortion at any point along frame sections.","input":null,"possible_fault":"Frame distorted or warped","possible_fault_description":"AS1851 2012 TABLE 12.4.3.1 ITEM 1.9(c) - Frame deformation can prevent closure and affect latch/seal integrity","severity_level":"non-critical","fault_id":"recp6Pscs55RRESod","prompt_id":"recp6Pscs55RRESod_prompt","inspection_id":"c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recnrMixWMp1DbCR6_recNGiNklGR6gJP5j"}]},{"id":"recXj6wDu0oglV5PY","name":"Fire-protected air ducts","checklist":[{"id":"023d13d0-c7b0-4a5b-b623-f812974ea645","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.7 YEARLY SERVICE SCHEDULE FIRE-PROTECTED AIR DUCTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected air ducts","variant":null,"variant_id":"recXj6wDu0oglV5PY","item_no":"7.5","prompt":"(a) Report to the owner or owner’s representative or\n occupier where any deficiency is identified.","input":null,"possible_fault":"Failure to report identified defects","possible_fault_description":"AS1851 TABLE 12.4.7 ITEM 7.5(a) - Deficiencies not reported to owner","severity_level":"non-conformance","fault_id":"reczcVJKmh80Jm9Fa","prompt_id":"reczcVJKmh80Jm9Fa_prompt","inspection_id":"c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j"},{"id":"181ba174-cdf2-4772-b136-b0dbe06a79ed","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.7 YEARLY SERVICE SCHEDULE FIRE-PROTECTED AIR DUCTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected air ducts","variant":null,"variant_id":"recXj6wDu0oglV5PY","item_no":"7.2","prompt":"(b) CHECK for mechanical damage.","input":null,"possible_fault":"Physical damage to duct/protection system","possible_fault_description":"AS1851 TABLE 12.4.7 ITEM 7.2(b) - Mechanical damage to ducts/protection","severity_level":"non-critical","fault_id":"recjyVPhx5c1ZM4gO","prompt_id":"recjyVPhx5c1ZM4gO_prompt","inspection_id":"c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j"},{"id":"1d6276ff-0271-4fb4-a115-97e6b660db55","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.7 YEARLY SERVICE SCHEDULE FIRE-PROTECTED AIR DUCTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected air ducts","variant":null,"variant_id":"recXj6wDu0oglV5PY","item_no":"7.4","prompt":"For damper operation refer to Section 13 of this\n Standard.","input":null,"possible_fault":"Refer to damper operation requirements","possible_fault_description":"AS1851 TABLE 12.4.7 ITEM 7.4 - Damper operation issues - see Section 13","severity_level":"recommendation","fault_id":"reclhAe0vMpHMgD76","prompt_id":"reclhAe0vMpHMgD76_prompt","inspection_id":"c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j"},{"id":"43b6e6bd-2f09-4701-80f2-1eff2936adde","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.7 YEARLY SERVICE SCHEDULE FIRE-PROTECTED AIR DUCTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected air ducts","variant":null,"variant_id":"recXj6wDu0oglV5PY","item_no":"7.2","prompt":"(a) INSPECT fire-resistant ducts from drawings,\n plans and schedule for condition of fire protection\n system or coating, including supports.","input":null,"possible_fault":"Protection system/coating deteriorated","possible_fault_description":"AS1851 TABLE 12.4.7 ITEM 7.2(a) - Fire protection system/coating deteriorated/damaged","severity_level":"non-critical","fault_id":"recrsSGKFvsKJQtVy","prompt_id":"recrsSGKFvsKJQtVy_prompt","inspection_id":"c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j"},{"id":"4adc6a0e-3a84-4181-bf79-a940bd6dc5ae","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.7 YEARLY SERVICE SCHEDULE FIRE-PROTECTED AIR DUCTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected air ducts","variant":null,"variant_id":"recXj6wDu0oglV5PY","item_no":"7.3","prompt":"(a) INSPECT visually for areas of deterioration,\n vermiculite, cement, mineral fibre and plaster (or\n combinations thereof) spray’s loss of adhesion.","input":null,"possible_fault":"Spray material lost adhesion/deteriorated","possible_fault_description":"AS1851 TABLE 12.4.7 ITEM 7.3(a) - Spray protection adhesion loss/deterioration","severity_level":"non-critical","fault_id":"recDhqebpNLjAKHgd","prompt_id":"recDhqebpNLjAKHgd_prompt","inspection_id":"c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j"},{"id":"6a88e2ce-925b-4db8-a4c3-5c2085b61c1a","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.7 YEARLY SERVICE SCHEDULE FIRE-PROTECTED AIR DUCTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected air ducts","variant":null,"variant_id":"recXj6wDu0oglV5PY","item_no":"7.5","prompt":"(b) Amend schedule as required to maintain accuracy.","input":null,"possible_fault":"Schedule not updated/inaccurate records","possible_fault_description":"AS1851 TABLE 12.4.7 ITEM 7.5(b) - Schedule not amended/inaccurate records","severity_level":"non-conformance","fault_id":"recCMaRLm6BHUghgt","prompt_id":"recCMaRLm6BHUghgt_prompt","inspection_id":"c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j"},{"id":"6e9b3c35-7c3f-4034-bd5f-8339b58ae797","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.7 YEARLY SERVICE SCHEDULE FIRE-PROTECTED AIR DUCTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected air ducts","variant":null,"variant_id":"recXj6wDu0oglV5PY","item_no":"7.1","prompt":"INSPECT against drawings and all schedules (see\n Clause 12.2.5) that no air duct has been added,\n removed or modified.","input":null,"possible_fault":"Ducts added/removed/modified without approval","possible_fault_description":"AS1851 TABLE 12.4.7 ITEM 7.1 - Unauthorised ducts/modifications affecting fire rating","severity_level":"non-conformance","fault_id":"recvYTJqS2Q67WNKJ","prompt_id":"recvYTJqS2Q67WNKJ_prompt","inspection_id":"c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j"},{"id":"8d6d37e3-a0ed-4750-9047-0ebf64ccc6ab","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.7 YEARLY SERVICE SCHEDULE FIRE-PROTECTED AIR DUCTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire-protected air ducts","variant":null,"variant_id":"recXj6wDu0oglV5PY","item_no":"7.3","prompt":"(b) CHECK fire protective boards and cladding for\n missing material or loss of adhesion.","input":null,"possible_fault":"Missing material/adhesion failure","possible_fault_description":"AS1851 TABLE 12.4.7 ITEM 7.3(b) - Protective boards missing/adhesion failure","severity_level":"non-critical","fault_id":"recFjoYazI5Dyfhvu","prompt_id":"recFjoYazI5Dyfhvu_prompt","inspection_id":"c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recXj6wDu0oglV5PY_recNGiNklGR6gJP5j"}]},{"id":"recyJ4V4XnfrB4BTn","name":"Walls, service penetrations and control joints","checklist":[]}],"other_checklist_items":[{"id":"02f0612e-3c26-422c-977f-87ba8d2de2f4","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.4","prompt":"(a) CHECK smoke seals are suitable for use on the\n door/assembly type.","input":null,"possible_fault":"Seals unsuitable for door/assembly type","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.4(a) – Seal type unsuitable for the door or frame","severity_level":"non-critical","fault_id":"recs3mqUMXQzNJNmU","prompt_id":"recs3mqUMXQzNJNmU_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"0eb587fc-3a47-4d5c-a4c3-56ec34836c77","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.2 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FLOORS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Floors, service penetrations and control joints\"","variant":null,"variant_id":"recI7nTr2kH2VBSsV","item_no":"2.2","prompt":"(c) IDENTIFY any penetration and control joints\n work that is unprotected, damaged or incorrectly\n installed.","input":null,"possible_fault":"Floor penetrations lack/damaged fire stopping","possible_fault_description":"AS1851 2012 TABLE 12.4.1.2 ITEM 2.2(c) - Unprotected, damaged or incorrectly installed floor penetrations and control joints","severity_level":"non-conformance","fault_id":"recUuYq6ZESAxxEoY","prompt_id":"recUuYq6ZESAxxEoY_prompt","inspection_id":"c_recI7nTr2kH2VBSsV_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recI7nTr2kH2VBSsV_recNGiNklGR6gJP5j"},{"id":"0fac8246-388d-4a21-be25-511836c291ef","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.10","prompt":"(b) CHECK hinges are securely fixed to the door\n leaf and frame.","input":null,"possible_fault":"Hinges loose or missing screws","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.10(b) – Hinges loose or screws missing","severity_level":"non-critical","fault_id":"recZC5LJm3wrLCw9h","prompt_id":"recZC5LJm3wrLCw9h_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"2230a9c9-ba0e-4e2a-bb9c-7785d898b793","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.2 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FLOORS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Floors, service penetrations and control joints\"","variant":null,"variant_id":"recI7nTr2kH2VBSsV","item_no":"2.1","prompt":"INSPECT against drawings (see Clause 12.2.5) that\n no fire-rated floors, including resistance to incipient\n spread of fire, have been added, removed or modified.","input":null,"possible_fault":"Fire-rated floors added/removed/modified","possible_fault_description":"AS1851 2012 TABLE 12.4.1.2 ITEM 2.1 - Fire-rated floors including incipient spread resistance don't match approved drawings","severity_level":"non-conformance","fault_id":"reclqiIgAODrrUKAN","prompt_id":"reclqiIgAODrrUKAN_prompt","inspection_id":"c_recI7nTr2kH2VBSsV_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recI7nTr2kH2VBSsV_recNGiNklGR6gJP5j"},{"id":"2be1363f-5890-4566-bdc7-76b329b8aab6","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.13","prompt":"(c) CHECK to ensure clear glass panels are\n appropriately identified.","input":null,"possible_fault":"Missing ID on clear glass","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.13(c) – Clear glazing missing etched ID","severity_level":"non-conformance","fault_id":"receGntykYmwFy5fd","prompt_id":"receGntykYmwFy5fd_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"33b244b2-4ff1-4158-8d83-bc32c382f9c7","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.3 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS CEILINGS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Ceilings, service penetrations and control joints\"","variant":null,"variant_id":"recaNgsM0omlzvLsJ","item_no":"3.2","prompt":"(c) IDENTIFY any penetration and control joints\n work that is unprotected, damaged or incorrectly\n installed.","input":null,"possible_fault":"Ceiling penetrations lack/damaged stopping","possible_fault_description":"AS1851 2012 TABLE 12.4.1.3 ITEM 3.2(c) - Unprotected, damaged or incorrectly installed ceiling penetrations and control joints","severity_level":"non-conformance","fault_id":"recgCIKuFHtI9AZ70","prompt_id":"recgCIKuFHtI9AZ70_prompt","inspection_id":"c_recaNgsM0omlzvLsJ_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recaNgsM0omlzvLsJ_recNGiNklGR6gJP5j"},{"id":"35f9bc55-8f71-4d1e-bc4e-1d257412fbe0","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.2","prompt":"(c) INSPECT to ensure relevant statutory signage\n has been applied and that the location of the\n signage is in accordance with regulatory\n requirements.","input":null,"possible_fault":"Signage missing/incorrectly located","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.2(c) – Signage missing or incorrectly placed","severity_level":"non-conformance","fault_id":"recrEKu1CSpaoKoeo","prompt_id":"recrEKu1CSpaoKoeo_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"39a786f8-cd46-4305-938e-34b250d01f80","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.2","prompt":"(b) CHECK that doors are self closing.","input":null,"possible_fault":"Doors not self-closing/closer failed","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.2(b) – Door fails to self-close or closer not working","severity_level":"non-critical","fault_id":"rechSF1z9aaRLu6GU","prompt_id":"rechSF1z9aaRLu6GU_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"3a6331d2-dc8a-4890-8433-ff226007aba9","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.5","prompt":"(b) CHECK seals are securely fixed.","input":null,"possible_fault":"Seals not fixed or loose","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.5(b) – Smoke seals not fixed or loose","severity_level":"non-critical","fault_id":"recGz2XTvKcU3SfGA","prompt_id":"recGz2XTvKcU3SfGA_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"4d43766e-9cab-4dc3-aa5a-2d8b382a2558","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.1 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS WALLS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Walls, service penetrations and control joints\"","variant":null,"variant_id":"recyJ4V4XnfrB4BTn","item_no":"1.2","prompt":"(a) INSPECT against drawings and associated\n penetration schedules that no penetrations have\n been added, removed or modified.","input":null,"possible_fault":"Unauthorised penetrations added/approved penetrations removed/penetrations modified without documentation/penetration schedules outdated","possible_fault_description":"AS1851 2012 TABLE 12.4.1.1 ITEM 1.2(a) - Service penetrations don't match drawings/schedules - unauthorized modifications detected","severity_level":"non-conformance","fault_id":"recQEkKC1m5Jf6Uvx","prompt_id":"recQEkKC1m5Jf6Uvx_prompt","inspection_id":"c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j"},{"id":"5c911acb-95f8-46b4-9997-11f353073704","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.3 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS CEILINGS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Ceilings, service penetrations and control joints\"","variant":null,"variant_id":"recaNgsM0omlzvLsJ","item_no":"3.2","prompt":"(a) INSPECT against drawings and associated\n penetration schedules that no penetrations have\n been added, removed or modified.\n NOTE: All light fittings and access\n panels/ceiling hatches should be inspected.","input":null,"possible_fault":"Unauthorized ceiling penetrations/fittings","possible_fault_description":"AS1851 2012 TABLE 12.4.1.3 ITEM 3.2(a) - Ceiling penetrations, light fittings, access panels don't match drawings/schedules","severity_level":"non-conformance","fault_id":"recXVQ16mk2GtYslh","prompt_id":"recXVQ16mk2GtYslh_prompt","inspection_id":"c_recaNgsM0omlzvLsJ_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recaNgsM0omlzvLsJ_recNGiNklGR6gJP5j"},{"id":"5ec7b828-00c8-4ec4-95e8-6111fd08ce32","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.12","prompt":"(b) CHECK door frame is free from excessive\n distortion at any point along frame sections.","input":null,"possible_fault":"Frame warped or twisted","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.12(b) – Frame warped, twisted or out of shape","severity_level":"non-critical","fault_id":"recY7gnlECcsJLR4q","prompt_id":"recY7gnlECcsJLR4q_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"62d0733c-4408-4abf-bb60-e185710bca9a","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.2 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FLOORS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Floors, service penetrations and control joints\"","variant":null,"variant_id":"recI7nTr2kH2VBSsV","item_no":"2.3","prompt":"INSPECT for any damage that will cause loss of fire\n resistance.","input":null,"possible_fault":"Physical/structural damage to floor surfaces","possible_fault_description":"AS1851 2012 TABLE 12.4.1.2 ITEM 2.3 - Floor damage identified that will cause loss of fire resistance capability","severity_level":"non-critical","fault_id":"rec5irq0RZRfyStC7","prompt_id":"rec5irq0RZRfyStC7_prompt","inspection_id":"c_recI7nTr2kH2VBSsV_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recI7nTr2kH2VBSsV_recNGiNklGR6gJP5j"},{"id":"65d78d24-5c4b-4872-928b-3f952e66338a","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.10","prompt":"(a) CHECK hinges are free from any undue wear\n and tear and are correctly aligned and operating\n smoothly and freely.","input":null,"possible_fault":"Hinges worn, misaligned or binding","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.10(a) – Hinges binding, misaligned or worn","severity_level":"non-critical","fault_id":"rect0aRtVm0Yp94eX","prompt_id":"rect0aRtVm0Yp94eX_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"7a699eea-9752-4520-b4db-4da66b8ae826","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.4","prompt":"(b) CHECK that any seal is in good condition and\n not damaged.","input":null,"possible_fault":"Seals damaged or deteriorated","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.4(b) – Smoke seals worn or deteriorated","severity_level":"non-critical","fault_id":"recWuu7zdFHJqJ4c7","prompt_id":"recWuu7zdFHJqJ4c7_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"7e136bd4-bfff-4350-925a-8608a1dbfb5c","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.2 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FLOORS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Floors, service penetrations and control joints\"","variant":null,"variant_id":"recI7nTr2kH2VBSsV","item_no":"2.2","prompt":"(a) INSPECT against drawings and associated\n penetration schedules that no penetrations have\n been added, removed or modified.","input":null,"possible_fault":"Unauthorized floor penetrations detected","possible_fault_description":"AS1851 2012 TABLE 12.4.1.2 ITEM 2.2(a) -Floor penetrations don't match drawings/schedules - unauthorized modifications found","severity_level":"non-conformance","fault_id":"recO3eEF4DYOi5agi","prompt_id":"recO3eEF4DYOi5agi_prompt","inspection_id":"c_recI7nTr2kH2VBSsV_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recI7nTr2kH2VBSsV_recNGiNklGR6gJP5j"},{"id":"7f70b0ba-73f7-4308-a32e-8330e6bcbb00","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.9","prompt":"(c) CHECK screw fixing and mounting\n arrangements for door closer are secured to the\n door leaf and door frame.","input":null,"possible_fault":"Loose or misaligned closer","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.9(c) – Door closer loose or misaligned","severity_level":"non-critical","fault_id":"recNuquMNKSbVPkMS","prompt_id":"recNuquMNKSbVPkMS_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"808b9b80-372d-415f-810a-53189e3f0188","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.3","prompt":"(b) CHECK bottom—gaps between the door bottom\n and threshold are as per door assembly and seal\n manufacturers’ recommendations.","input":null,"possible_fault":"Bottom gaps exceed manufacturer limits","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.3(b) – Bottom door gap exceeds allowed tolerance","severity_level":"non-critical","fault_id":"recPRimomEDjDvnSb","prompt_id":"recPRimomEDjDvnSb_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"8495a361-fc48-4f35-a589-ee03b5b98b50","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.3 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS CEILINGS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Ceilings, service penetrations and control joints\"","variant":null,"variant_id":"recaNgsM0omlzvLsJ","item_no":"3.1","prompt":"INSPECT against drawings (see Clause 12.2.5) that no\n fire-rated ceilings, including resistance to incipient\n spread of fire, have been added, removed or modified.","input":null,"possible_fault":"Fire-rated ceilings added/removed/modified","possible_fault_description":"AS1851 2012 TABLE 12.4.1.3 ITEM 3.1 - Fire-rated ceilings including incipient spread resistance don't match drawings","severity_level":"non-conformance","fault_id":"recV27eeoyIOAU4dT","prompt_id":"recV27eeoyIOAU4dT_prompt","inspection_id":"c_recaNgsM0omlzvLsJ_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recaNgsM0omlzvLsJ_recNGiNklGR6gJP5j"},{"id":"8643ca39-801a-456d-8998-92b98a3acd6a","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.13","prompt":"(b) CHECK perimeter trim and framing to ensure\n they are secure and in sound condition and that\n all fixings are in place.","input":null,"possible_fault":"Loose trim or missing fixings","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.13(b) – Door trim loose or fixings missing","severity_level":"non-critical","fault_id":"rec6OpODyWvWBs3C9","prompt_id":"rec6OpODyWvWBs3C9_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"8d9baf46-9549-4b62-ad79-d55afc654672","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.2 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS FLOORS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Floors, service penetrations and control joints\"","variant":null,"variant_id":"recI7nTr2kH2VBSsV","item_no":"2.2","prompt":"(b) CHECK that reference drawings and penetration\n schedules correctly represent the installed\n penetrations.","input":null,"possible_fault":"Drawings don't match floor installations","possible_fault_description":"AS1851 2012 TABLE 12.4.1.2 ITEM 2.2(b) - Reference drawings/schedules don't accurately represent installed floor penetrations","severity_level":"non-conformance","fault_id":"rec5WyE8SPqXXiSOx","prompt_id":"rec5WyE8SPqXXiSOx_prompt","inspection_id":"c_recI7nTr2kH2VBSsV_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recI7nTr2kH2VBSsV_recNGiNklGR6gJP5j"},{"id":"91a4e963-dca7-40f9-af78-4ccb614488a4","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.1 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS WALLS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Walls, service penetrations and control joints\"","variant":null,"variant_id":"recyJ4V4XnfrB4BTn","item_no":"1.1","prompt":"INSPECT against drawings (see Clause 12.2.5) that no\n fire and/or smoke walls have been added, removed or\n modified.","input":null,"possible_fault":"Fire/smoke walls added without approval/walls removed compromising fire barriers/wall modifications affecting fire rating/drawings not updated","possible_fault_description":"AS1851 2012 TABLE 12.4.1.1 ITEM 1.1 - Fire/smoke walls not matching approved drawings - unauthorized changes compromising barriers","severity_level":"non-conformance","fault_id":"recwQqdhBxWgeJuml","prompt_id":"recwQqdhBxWgeJuml_prompt","inspection_id":"c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j"},{"id":"9bde902c-7eca-48ad-912e-c5e9a04147f2","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.5","prompt":"(a) CHECK to ensure meeting stile astragals or door\n meeting edges incorporate smoke seals.","input":null,"possible_fault":"Meeting stiles lack smoke seals","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.5(a) – Meeting stiles missing smoke seals","severity_level":"non-critical","fault_id":"rec6RzTdbiTvEemsM","prompt_id":"rec6RzTdbiTvEemsM_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"a00a191e-f80b-44e5-bc2b-071deaa7e982","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.16","prompt":"CHECK to ensure any essential meeting stile\n astragals are installed and in good working order and\n incorporate smoke seals where required.","input":null,"possible_fault":"Astragals or seals missing/damaged","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.16 – Astragals/seals missing or damaged","severity_level":"non-critical","fault_id":"recuNnrvPvH0ZhcvK","prompt_id":"recuNnrvPvH0ZhcvK_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"a9f0da6e-a2ff-4006-b905-1c37c67f218e","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.7","prompt":"(b) CHECK all hardware is attached and is securely\n fixed.","input":null,"possible_fault":"Hardware loose or insecure","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.7(b) – Door hardware is loose or not secure","severity_level":"non-critical","fault_id":"recgz4RhcebtNQfYB","prompt_id":"recgz4RhcebtNQfYB_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"aa25dfdd-d5a0-4ec9-9454-1db75ea21573","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.9","prompt":"(b) CHECK any closer free from oil leakages.","input":null,"possible_fault":"Leaking closer mechanism","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.9(b) – Door closer leaking fluid or oil","severity_level":"non-critical","fault_id":"recjauiL7VGX6R6pH","prompt_id":"recjauiL7VGX6R6pH_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"ae082e3a-4d32-4d00-be6a-cbe31ab22a42","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.11","prompt":"(a) INSPECT that door is free from any visible\n delamination, buckling, warping, bowing,\n twisting or significant damage.","input":null,"possible_fault":"Delamination, buckling or warping","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.11(a) – Door warped, buckled or delaminating","severity_level":"non-critical","fault_id":"recoDNzUaytwVrsFd","prompt_id":"recoDNzUaytwVrsFd_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"b34a1c8e-a1e7-490b-ac72-8ab727ae002c","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.6","prompt":"TEST smoke doors held in the open position, which\n require activation of detection system to close, to\n ensure that they close satisfactorily upon power\n failure or detector activation.","input":null,"possible_fault":"Doors don’t release or fail to close","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.6 – Door fails to release or close on activation","severity_level":"critical","fault_id":"recay1hicrunBbjpw","prompt_id":"recay1hicrunBbjpw_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"b7a2cc94-2b1c-458f-b3a2-b9f03042913a","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.11","prompt":"(b) INSPECT that door edges are in good condition\n and free from any splitting or damage on all\n sides.","input":null,"possible_fault":"Edges split, cracked or chipped","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.11(b) – Door edges cracked, chipped or split","severity_level":"non-critical","fault_id":"recIFfTFWG2ebejKh","prompt_id":"recIFfTFWG2ebejKh_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"c27b5730-265c-4d26-98b2-4278b61fce01","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.8","prompt":"VERIFY the opening and closing forces are such that\n the doors can be easily opened and closed in normal\n conditions and in fire mode, taking into account any\n pressurization systems within the building.","input":null,"possible_fault":"Operation difficult or forces excessive","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.8 – Door difficult to operate or excessive force needed","severity_level":"non-critical","fault_id":"rec3jCtYsYSMNHiSB","prompt_id":"rec3jCtYsYSMNHiSB_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"c2e9e18a-ab7a-4a66-816b-b2d33292a2fb","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.4","prompt":"(c) CHECK perimeter and bottom—perimeter and\n door bottom seals are correctly fitted in\n accordance with manufacturer’s\n recommendations and that the sealing elements\n are in continuous contact with the\n door/frame/floor.","input":null,"possible_fault":"Seals incorrectly fitted or interrupted","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.4(c) – Smoke seals interrupted or incorrectly fitted","severity_level":"non-critical","fault_id":"reco6FshjXtnVXWJN","prompt_id":"reco6FshjXtnVXWJN_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"caa3fa75-d412-4ccc-be34-4f087af9cfee","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.3","prompt":"(a) CHECK perimeter—gaps between the door leaf\n and the door frame are as per door assembly and\n seal manufacturers’ recommendations.","input":null,"possible_fault":"Gaps exceed manufacturer limits","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.3(a) – Perimeter gaps exceed manufacturer limits","severity_level":"non-conformance","fault_id":"recxWMTCAV1k5v1WP","prompt_id":"recxWMTCAV1k5v1WP_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"cb0013a2-2335-45b7-98cd-e46c0ae12ff9","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.1 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS WALLS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Walls, service penetrations and control joints\"","variant":null,"variant_id":"recyJ4V4XnfrB4BTn","item_no":"1.2","prompt":"(c) IDENTIFY any penetration and control joints work\n that is unprotected, damaged or incorrectly\n installed.","input":null,"possible_fault":"Penetrations lack fire stopping/fire stopping damaged or deteriorated/incorrect installation methods/non-compliant materials used","possible_fault_description":"AS1851 2012 TABLE 12.4.1.1 ITEM 1.2(c) - Unprotected, damaged or incorrectly installed penetrations and control joints identified","severity_level":"non-conformance","fault_id":"recHxe5yKgCpucdYF","prompt_id":"recHxe5yKgCpucdYF_prompt","inspection_id":"c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j"},{"id":"cca9e57c-6a9e-4bad-8d52-92f052dc17b2","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.1 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS WALLS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Walls, service penetrations and control joints\"","variant":null,"variant_id":"recyJ4V4XnfrB4BTn","item_no":"1.2","prompt":"(b) CHECK that reference drawings and penetration\n schedules correctly represent the installed\n penetrations.","input":null,"possible_fault":"Drawings don't match actual installations/penetration schedules incorrect/as-built documentation missing/discrepancies between plans and reality","possible_fault_description":"AS1851 2012 TABLE 12.4.1.1 ITEM 1.2(b) - Reference drawings and schedules don't accurately represent installed penetrations","severity_level":"non-conformance","fault_id":"recuERJy7xv6t0AaO","prompt_id":"recuERJy7xv6t0AaO_prompt","inspection_id":"c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j"},{"id":"ce10fdf0-3575-4aa3-b674-a3ed1a6ce8d9","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.3 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS CEILINGS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Ceilings, service penetrations and control joints\"","variant":null,"variant_id":"recaNgsM0omlzvLsJ","item_no":"3.2","prompt":"(b) CHECK that reference drawings and penetration\n schedules represent as-installed penetrations.","input":null,"possible_fault":"Drawings don't match ceiling installations","possible_fault_description":"AS1851 2012 TABLE 12.4.1.3 ITEM 3.2(b) - Reference drawings/schedules don't represent as-installed ceiling penetrations","severity_level":"non-conformance","fault_id":"rec5CFh8EHv1Byd54","prompt_id":"rec5CFh8EHv1Byd54_prompt","inspection_id":"c_recaNgsM0omlzvLsJ_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recaNgsM0omlzvLsJ_recNGiNklGR6gJP5j"},{"id":"cea1fb34-10a7-4039-aa08-26fb2c91a74c","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.12","prompt":"(a) CHECK door frames are adequately anchored to\n the walling and restrained against rotational\n movement about their longitudinal axes.","input":null,"possible_fault":"Loose or insufficient anchoring","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.12(a) – Door frame not securely anchored","severity_level":"non-critical","fault_id":"recHMmvNsbgCgWerh","prompt_id":"recHMmvNsbgCgWerh_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"cfa2818f-5653-4c9b-a0c2-dbacbad1d3cb","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.15","prompt":"CHECK for doors that require correct sequencing to\n self close and ensure the sequencing device operates\n correctly.","input":null,"possible_fault":"Sequencing device failed or misaligned","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.15 – Sequencing device not working or aligned","severity_level":"non-critical","fault_id":"recLhUleFzcd3SL2p","prompt_id":"recLhUleFzcd3SL2p_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"d3533a85-9ebf-4aa3-aad3-350b118d4bf7","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.1","prompt":"INSPECT against drawings and all schedules (see\n Clause 12.2.5) that no smoke doors have been added,\n removed or modified.","input":null,"possible_fault":"Doors added/removed/modified unauthorised","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.1 – Door modified/added/removed without approval","severity_level":"non-conformance","fault_id":"recvlHhwm4FfRQMgq","prompt_id":"recvlHhwm4FfRQMgq_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"d91c916f-09c4-4fb4-be6c-bbe10168ed7b","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.14","prompt":"CHECK to ensure kickplates are securely fixed.","input":null,"possible_fault":"Kickplates loose or detached","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.14 – Kickplates detached or loose","severity_level":"non-critical","fault_id":"recHMrzuwoxocRP2u","prompt_id":"recHMrzuwoxocRP2u_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"ddaaf173-f94a-42c0-8522-76cdc38601bc","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.2","prompt":"(a) CHECK that the smoke door complies to\n appropriate door design specification, is at least\n 35 mm thick solid core door or in accordance\n with the requirement of the ‘building approval’.","input":null,"possible_fault":"Door not 35mm solid core/non-compliant","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.2(a) – Door not solid core or doesn’t meet approval","severity_level":"non-conformance","fault_id":"rechSPOWFpem2I8Ab","prompt_id":"rechSPOWFpem2I8Ab_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"df007668-ea22-43bb-be19-207c37b7a2c8","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.1 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS WALLS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Walls, service penetrations and control joints\"","variant":null,"variant_id":"recyJ4V4XnfrB4BTn","item_no":"1.3","prompt":"(b) INSPECT for any damage that will cause loss of\n fire resistance.","input":null,"possible_fault":"Physical damage to wall surfaces/structural damage compromising integrity/moisture damage/impact damage affecting fire rating","possible_fault_description":"AS1851 2012 TABLE 12.4.1.1 ITEM 1.3(b) - Wall damage identified that compromises fire resistance performance capability","severity_level":"critical","fault_id":"recuNe6BE65jDuVkL","prompt_id":"recuNe6BE65jDuVkL_prompt","inspection_id":"c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j"},{"id":"e03236cb-8a11-4b78-984c-12a6a7e91ff5","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.5","prompt":"(c) CHECK smoke seals do not impede the correct\n operation of the door.","input":null,"possible_fault":"Seals obstructing movement","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.5(c) – Seals obstruct door movement","severity_level":"non-critical","fault_id":"recQ2FSGX69xkLbdm","prompt_id":"recQ2FSGX69xkLbdm_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"ecfd8259-eb5e-4ec0-98bf-b2f69469e3c5","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.1.1 YEARLY SERVICE SCHEDULE FIRE AND SMOKE BARRIERS WALLS, SERVICE PENETRATIONS AND CONTROL JOINTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Walls, service penetrations and control joints\"","variant":null,"variant_id":"recyJ4V4XnfrB4BTn","item_no":"1.3","prompt":"(a) INSPECT that walls continue up to the next\n horizontal fire-resistant barrier or to the underside\n of the roof above.","input":null,"possible_fault":"Walls don't extend full height/gaps above walls/fire barrier continuity compromised/incomplete wall construction","possible_fault_description":"AS1851 2012 TABLE 12.4.1.1 ITEM 1.3(a) -Walls must continue to next horizontal fire barrier or roof underside - gaps found","severity_level":"critical","fault_id":"reciYcCxokJohdMP8","prompt_id":"reciYcCxokJohdMP8_prompt","inspection_id":"c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j","grouping_key":"1_year::c_recyJ4V4XnfrB4BTn_recNGiNklGR6gJP5j"},{"id":"f4466991-50b2-4321-a1c2-f7846daf0fe1","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.13","prompt":"(a) CHECK glass to ensure it is in sound condition,\n and free from cracks.","input":null,"possible_fault":"Glass cracked or damaged","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.13(a) – Vision panel glass cracked or damaged","severity_level":"non-critical","fault_id":"recOyKUSlYlb4LlVM","prompt_id":"recOyKUSlYlb4LlVM_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"f4ddccae-f913-49b2-a1eb-fbbc469be674","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.9","prompt":"(a) CHECK the door closer (body and arm) is free\n from obstructions by walls or fixtures and is\n operating freely throughout its swing.","input":null,"possible_fault":"Closer blocked or jammed","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.9(a) – Door closer obstructed or jammed","severity_level":"critical","fault_id":"recMp4yS8aXAgJkk9","prompt_id":"recMp4yS8aXAgJkk9_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"},{"id":"f82763d7-3a1a-41cc-82a8-63e808964e98","standard_code":"au_as_1851_2012","version":"full","category":"Passive Fire and Smoke Systems","category_id":"recNGiNklGR6gJP5j","group_header":"TABLE 12.4.4 SIX-MONTHLY SERVICE SCHEDULE HINGED AND PIVOTED SMOKE DOORS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Hinged and pivoted smoke doors,Hinged and pivoted smoke doors (SOU)","variant":null,"variant_id":"recG8NFpzAHWcvBng, recGMslnFtOuh6mkF","item_no":"4.7","prompt":"(a) CHECK all essential hardware required for\n suspension, closing and latching (as appropriate)\n is fitted.","input":null,"possible_fault":"Required hardware missing","possible_fault_description":"AS1851 2012 TABLE 12.4.4 ITEM 4.7(a) – Latching or closing hardware missing","severity_level":"non-conformance","fault_id":"recLAk60AGUKCuBuD","prompt_id":"recLAk60AGUKCuBuD_prompt","inspection_id":"c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j","grouping_key":"6_month::c_recG8NFpzAHWcvBng:recGMslnFtOuh6mkF_recNGiNklGR6gJP5j"}]},{"id":"recqtR7qwPwfCBtQh","name":"Emergency Planning in Facilities","asset_types":[{"id":"rec8OKcWFS01C7S7m","name":"Critical emergency evacuation system elements","checklist":[{"id":"19ab9b53-8375-4454-af12-3ebbf8752c8a","standard_code":"au_as_1851_2012","version":"full","category":"Emergency Planning in Facilities","category_id":"recqtR7qwPwfCBtQh","group_header":"TABLE 14.4.3 YEARLY INSPECTION, TEST AND RECORDS SCHEDULE CRITICAL EMERGENCY EVACUATION SYSTEM ELEMENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Critical emergency evacuation system elements","variant":null,"variant_id":"rec8OKcWFS01C7S7m","item_no":"2.1","prompt":"INSPECT the emergency plan and check for\nrelevancy to the facility.","input":null,"possible_fault":"Plan outdated or incorrect","possible_fault_description":"AS1851 TABLE 14.4.3 ITEM 2.1 – Emergency plan outdated or irrelevant.","severity_level":"non-conformance","fault_id":"rec8g3Gp377zcOKMv","prompt_id":"rec8g3Gp377zcOKMv_prompt","inspection_id":"c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh","grouping_key":"1_year::c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh"},{"id":"54f675d7-819b-4a63-b397-2cadac3275a8","standard_code":"au_as_1851_2012","version":"full","category":"Emergency Planning in Facilities","category_id":"recqtR7qwPwfCBtQh","group_header":"TABLE 14.4.2 SIX-MONTHLY INSPECTION, TEST AND RECORDS SCHEDULE CRITICAL EMERGENCY EVACUATION SYSTEM ELEMENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Critical emergency evacuation system elements","variant":null,"variant_id":"rec8OKcWFS01C7S7m","item_no":"1.1","prompt":"INSPECT the ECO list and check for compliance\nwith the emergency plan.","input":null,"possible_fault":"ECO list outdated","possible_fault_description":"AS1851 TABLE 14.4.2 ITEM 1.1 – ECO list not aligned with emergency plan.","severity_level":"non-conformance","fault_id":"recD7CSlWt0uL8hHj","prompt_id":"recD7CSlWt0uL8hHj_prompt","inspection_id":"c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh","grouping_key":"6_month::c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh"},{"id":"567c561d-0009-47f6-befb-191a80f2dc96","standard_code":"au_as_1851_2012","version":"full","category":"Emergency Planning in Facilities","category_id":"recqtR7qwPwfCBtQh","group_header":"TABLE 14.4.2 SIX-MONTHLY INSPECTION, TEST AND RECORDS SCHEDULE CRITICAL EMERGENCY EVACUATION SYSTEM ELEMENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Critical emergency evacuation system elements","variant":null,"variant_id":"rec8OKcWFS01C7S7m","item_no":"1.3","prompt":"INSPECT training records and check for\ncompliance with the emergency plan.","input":null,"possible_fault":"Training outdated/incomplete","possible_fault_description":"AS1851 TABLE 14.4.2 ITEM 1.3 – Training records not up to date.","severity_level":"non-conformance","fault_id":"recKpEE0MbY5ekGT4","prompt_id":"recKpEE0MbY5ekGT4_prompt","inspection_id":"c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh","grouping_key":"6_month::c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh"},{"id":"6a7ff4db-d9b8-4ca8-849b-618979f5114a","standard_code":"au_as_1851_2012","version":"full","category":"Emergency Planning in Facilities","category_id":"recqtR7qwPwfCBtQh","group_header":"TABLE 14.4.2 SIX-MONTHLY INSPECTION, TEST AND RECORDS SCHEDULE CRITICAL EMERGENCY EVACUATION SYSTEM ELEMENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Critical emergency evacuation system elements","variant":null,"variant_id":"rec8OKcWFS01C7S7m","item_no":"1.2","prompt":"INSPECT the emergency evacuation equipment\nand check for compliance with the emergency plan.","input":null,"possible_fault":"Equipment missing/faulty","possible_fault_description":"AS1851 TABLE 14.4.2 ITEM 1.2 – Evacuation equipment not compliant.","severity_level":"non-critical","fault_id":"recQNBOO0zK2b9BEh","prompt_id":"recQNBOO0zK2b9BEh_prompt","inspection_id":"c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh","grouping_key":"6_month::c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh"},{"id":"70393e4c-2ca6-4c57-af9d-5a66780e8f16","standard_code":"au_as_1851_2012","version":"full","category":"Emergency Planning in Facilities","category_id":"recqtR7qwPwfCBtQh","group_header":"TABLE 14.4.3 YEARLY INSPECTION, TEST AND RECORDS SCHEDULE CRITICAL EMERGENCY EVACUATION SYSTEM ELEMENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Critical emergency evacuation system elements","variant":null,"variant_id":"rec8OKcWFS01C7S7m","item_no":"2.2","prompt":"INSPECT evacuation exercise records and check\nfor compliance with the emergency plan.","input":null,"possible_fault":"Drill not conducted or documented","possible_fault_description":"AS1851 TABLE 14.4.3 ITEM 2.2 – Evacuation drill records incomplete.","severity_level":"non-conformance","fault_id":"recvZ5V9mLDHKzeq4","prompt_id":"recvZ5V9mLDHKzeq4_prompt","inspection_id":"c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh","grouping_key":"1_year::c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh"},{"id":"76095ce7-58ca-4cc4-bc2c-c99021ea3a69","standard_code":"au_as_1851_2012","version":"full","category":"Emergency Planning in Facilities","category_id":"recqtR7qwPwfCBtQh","group_header":"TABLE 14.4.2 SIX-MONTHLY INSPECTION, TEST AND RECORDS SCHEDULE CRITICAL EMERGENCY EVACUATION SYSTEM ELEMENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Critical emergency evacuation system elements","variant":null,"variant_id":"rec8OKcWFS01C7S7m","item_no":"1.5","prompt":"INSPECT the emergency response diagrams for\nrelevancy and check for compliance with the\nemergency plan.","input":null,"possible_fault":"Outdated/missing diagrams","possible_fault_description":"AS1851 TABLE 14.4.2 ITEM 1.5 – Evacuation diagrams non-compliant.","severity_level":"non-conformance","fault_id":"recgSTk0Wzaq13hAf","prompt_id":"recgSTk0Wzaq13hAf_prompt","inspection_id":"c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh","grouping_key":"6_month::c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh"},{"id":"865158b6-4ec9-4adc-b4d5-0140b8ee2904","standard_code":"au_as_1851_2012","version":"full","category":"Emergency Planning in Facilities","category_id":"recqtR7qwPwfCBtQh","group_header":"TABLE 14.4.2 SIX-MONTHLY INSPECTION, TEST AND RECORDS SCHEDULE CRITICAL EMERGENCY EVACUATION SYSTEM ELEMENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Critical emergency evacuation system elements","variant":null,"variant_id":"rec8OKcWFS01C7S7m","item_no":"1.4","prompt":"TEST the ECO for relevance to the facility by\ninitiating an alarm and checking the response for\ncompliance with the emergency procedures.","input":null,"possible_fault":"No response or improper response","possible_fault_description":"AS1851 TABLE 14.4.2 ITEM 1.4 – ECO response inadequate during drill.","severity_level":"critical","fault_id":"recZLCeiLNGzI9bTK","prompt_id":"recZLCeiLNGzI9bTK_prompt","inspection_id":"c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh","grouping_key":"6_month::c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh"},{"id":"9e73fb8b-48f4-4638-a86d-620d074443e3","standard_code":"au_as_1851_2012","version":"full","category":"Emergency Planning in Facilities","category_id":"recqtR7qwPwfCBtQh","group_header":"TABLE 14.4.2 SIX-MONTHLY INSPECTION, TEST AND RECORDS SCHEDULE CRITICAL EMERGENCY EVACUATION SYSTEM ELEMENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Critical emergency evacuation system elements","variant":null,"variant_id":"rec8OKcWFS01C7S7m","item_no":"1.7","prompt":"INSPECT the emergency procedures testing for\nrelevancy to the facility or to a nominated incident\ncovered by the emergency procedures by\nconducting an evacuation exercise.","input":null,"possible_fault":"Incomplete or failed drill","possible_fault_description":"AS1851 TABLE 14.4.2 ITEM 1.7 – Emergency procedures not validated.","severity_level":"non-conformance","fault_id":"rechRUvtD5jglmAta","prompt_id":"rechRUvtD5jglmAta_prompt","inspection_id":"c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh","grouping_key":"6_month::c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh"},{"id":"a5d0d8b0-490a-422d-967d-f0534d83869a","standard_code":"au_as_1851_2012","version":"full","category":"Emergency Planning in Facilities","category_id":"recqtR7qwPwfCBtQh","group_header":"TABLE 14.4.2 SIX-MONTHLY INSPECTION, TEST AND RECORDS SCHEDULE CRITICAL EMERGENCY EVACUATION SYSTEM ELEMENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Critical emergency evacuation system elements","variant":null,"variant_id":"rec8OKcWFS01C7S7m","item_no":"1.6","prompt":"INSPECT the nominated assembly area(s) and test\nfor relevance to the facility and compliance with\nthe emergency plan.","input":null,"possible_fault":"Area not designated or inaccessible","possible_fault_description":"AS1851 TABLE 14.4.2 ITEM 1.6 – Assembly area not relevant or compliant.","severity_level":"non-conformance","fault_id":"recxmwfsAHZKxVTPb","prompt_id":"recxmwfsAHZKxVTPb_prompt","inspection_id":"c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh","grouping_key":"6_month::c_rec8OKcWFS01C7S7m_recqtR7qwPwfCBtQh"}]}],"other_checklist_items":[]},{"id":"recSlH9Co2P4eozgV","name":"Special Hazard Systems","asset_types":[{"id":"recoMHFXU1KocjaUB","name":"Special Hazards Systems","checklist":[{"id":"012e2e56-5081-4007-a012-007a753a5bd0","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.6","prompt":"TEST to ensure correct operation of all pneumatic\n controls.","input":null,"possible_fault":"Pneumatic controls malfunction","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.6 - Pneumatic controls not operating correctly","severity_level":"non-critical","fault_id":"recf1OnOdaAdEukv3","prompt_id":"recf1OnOdaAdEukv3_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"06fcc37c-b18b-435f-abc8-c4a4137b82ef","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.1","prompt":"COMPLETE all monthly service activities as listed\n in Table 7.4.2.","input":null,"possible_fault":"Monthly service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.1 - Monthly service activities not completed","severity_level":"non-conformance","fault_id":"recBTINApigAysjau","prompt_id":"recBTINApigAysjau_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"07e1384f-e51b-4073-8e7b-9cb622e0657b","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"1.6","prompt":"CHECK that the lock-off valve is correctly labelled\n and accessible.","input":null,"possible_fault":"Lock-off valve not labelled/accessible","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.6 - Lock-off valve not correctly labelled/accessible","severity_level":"non-conformance","fault_id":"recuQWbNLiDWXPD3C","prompt_id":"recuQWbNLiDWXPD3C_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"168af088-47d7-4213-8afa-97ac4f310502","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.4","prompt":"CHECK operation and lubricate as necessary.","input":null,"possible_fault":"Release system malfunction","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.4 - Mechanical release system operation check and lubrication failed","severity_level":"critical","fault_id":"recyzfndCsyARd2Ab","prompt_id":"recyzfndCsyARd2Ab_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"176fe6bd-5ab2-4b57-814f-3319c8720eb6","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.16.B","prompt":"COMPLETE an enclosure integrity test for\n total flooding systems in accordance with\n AS ISO 14520.1 for gaseous systems, and\n CONFIRM that the results satisfy the\n requirements.\n NOTE: Where an integrity test cannot be\n conducted due to factors such as physical\n dimensional constraints, or large\n unclosable openings, confirm enclosure\n integrity by visual inspection.","input":null,"possible_fault":"Failed integrity test\nVisual integrity failure","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.16 - Enclosure integrity test per AS ISO 14520.1 failed\nAS1851 2012 TABLE 7.4.4 ITEM 3.16 - Enclosure integrity visual inspection failed (where test not possible)","severity_level":"critical","fault_id":"reczwCFUO1BOSd1SW","prompt_id":"reczwCFUO1BOSd1SW_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"18a37998-73ee-4a6e-b230-f4bf28f06f16","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.2","prompt":"Perform routine service in accordance with\n Section 6.","input":null,"possible_fault":"Control system malfunction","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.2 - Electrical detection/control systems not serviced per Section 6","severity_level":"critical","fault_id":"recKvxSPmcjoTXZ1h","prompt_id":"recKvxSPmcjoTXZ1h_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"1911e802-f729-4de4-a50e-8d4177605a11","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.5 TEN-YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"4.3","prompt":"Hydrostatically pressure TEST cylinders that have exceeded 10 years since the last test in accordance with the procedure in AS 2030.1 (see Note 1). Note 1 The hydrostatic test is to be completed at 10-yearly intervals. The initial hydrotest is due 10 years after the date of the first fill or, where this is not available, the date of cylinder manufacture.","input":null,"possible_fault":"Cylinder failed hydrostatic test","possible_fault_description":"AS1851 2012 TABLE 7.4.5 ITEM 4.3 – Cylinders must be tested hydrostatically after 10 years from fill/manufacture date under AS 2030.1","severity_level":"critical","fault_id":"reccqeHw1y6eznIf7","prompt_id":"reccqeHw1y6eznIf7_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"10_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"211d8b9b-c85d-4f24-bd61-8069b51bc61d","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.17.A","prompt":"TEST and record the pressure at which\n pressure-relief vent operates.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"reccIe4fOkAzEnRUZ_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"21a686bb-6d76-4724-b011-0abc8839aef0","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.9","prompt":"CHECK that all discharge nozzles (including\n aerosol generators) are clear and unobstructed,\n correctly aimed and secured.","input":null,"possible_fault":"Nozzles blocked/obstructed\nAerosol generators obstructed\nNozzles incorrectly aimed\nAerosol generators incorrectly aimed\nNozzles not secured\nAerosol generators not secured","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.9 - Discharge nozzles/aerosol generators obstructed\nAS1851 2012 TABLE 7.4.3 ITEM 2.9 - Aerosol generators obstructed\nAS1851 2012 TABLE 7.4.3 ITEM 2.9 - Discharge nozzles incorrectly aimed\nAS1851 2012 TABLE 7.4.3 ITEM 2.9 - Aerosol generators incorrectly aimed\nAS1851 2012 TABLE 7.4.3 ITEM 2.9 - Discharge nozzles not secured\nAS1851 2012 TABLE 7.4.3 ITEM 2.9 - Aerosol generators not secured","severity_level":"critical","fault_id":"recricNoGwngKDVA9","prompt_id":"recricNoGwngKDVA9_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"24f78def-5a55-4fa1-8d84-3f7e08aa7811","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.5","prompt":"CHECK the integrity of all pneumatic piping and\n fittings.","input":null,"possible_fault":"Pneumatic piping/fitting damaged","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.5 - Pneumatic piping/fittings integrity compromised","severity_level":"non-critical","fault_id":"recp96GTzJjd3gyV9","prompt_id":"recp96GTzJjd3gyV9_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"2a394047-cdf7-4494-8914-9c2386b9ebd1","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.9","prompt":"CLEAN nozzles that have been subjected to\n the deposit of contaminants.","input":null,"possible_fault":"Nozzles contaminated","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.9 - Nozzles subjected to contaminant deposits not cleaned","severity_level":"non-critical","fault_id":"recZQoS4aZCeyO9sv","prompt_id":"recZQoS4aZCeyO9sv_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"2d1f80dd-1d3a-4878-8d1e-c59c10d8e285","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.5 TEN-YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"4.1","prompt":"COMPLETE all monthly, six-monthly and yearly\n service activities, as listed in Tables 7.4.2, 7.4.3\n and 7.4.4.","input":null,"possible_fault":"Routine services not completed","possible_fault_description":"AS1851 2012 TABLE 7.4.5 ITEM 4.1 – All periodic maintenance per Tables 7.4.2–7.4.4 must be performed","severity_level":"non-conformance","fault_id":"rec69QEInfxqJOcHf","prompt_id":"rec69QEInfxqJOcHf_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"10_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"306f5d00-2ffc-4124-995f-05b9d0acf8c0","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.13","prompt":"VERIFY volumes (gross and net).","input":null,"possible_fault":"Incorrect volume calculation","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.13 - Total flooding system volumes (gross/net) verification failed","severity_level":"non-conformance","fault_id":"recNWGVSu4iwuSiaB","prompt_id":"recNWGVSu4iwuSiaB_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"37b6b9ee-172b-47e7-81b9-3e0342721a6e","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"1.5","prompt":"(a) CHECK that all release anti-tamper seals/pull\n pins are in place and secure.\n (b) CHECK that all release mechanisms, including\n gas container valves, actuators and drop\n weights, are undamaged, accessible and\n unimpeded.","input":null,"possible_fault":"Anti-tamper seals/pins missing\nRelease mechanisms damaged","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.5 - Release anti-tamper seals/pull pins not secure\nAS1851 2012 TABLE 7.4.2 ITEM 1.5 - Release mechanisms damaged/inaccessible/impeded","severity_level":"critical","fault_id":"recSUS5DR1cCh6wtE","prompt_id":"recSUS5DR1cCh6wtE_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"3e9f4fd8-c2fd-4f6e-95e2-aa2f2b392538","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.12","prompt":"VERIFY fuel class and type.","input":null,"possible_fault":"Incorrect fuel class/type","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.12 - Fuel class and type verification failed","severity_level":"non-conformance","fault_id":"rec6zCadJtg5Oxcxf","prompt_id":"rec6zCadJtg5Oxcxf_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"42b62dc9-1f27-4641-8fcb-bbc2c845cc26","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.1","prompt":"COMPLETE all monthly and six-monthly\n service activities, as listed in Tables 7.4.2\n and 7.4.3.","input":null,"possible_fault":"Previous service activities incomplete","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.1 - Monthly/six-monthly service activities not completed","severity_level":"non-conformance","fault_id":"recjUEc1DwTo6aVSw","prompt_id":"recjUEc1DwTo6aVSw_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"4818bd09-0b30-4d31-bc43-e3b9f6f046f0","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"1.4","prompt":"(a) CHECK that all containers are secure,\n accessible, free from damage and mounted to\n allow free passage of air around the base.\n (b) CHECK each container pressure indicator and\n verify that any loss in pressure is not greater\n than 10% of the nominal charge pressure.\n Where there is no container pressure indicator,\n check that the system discharge indicator has\n not operated.","input":null,"possible_fault":"Containers not secure/damaged\nPressure loss exceeds 10%","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.4 - Containers not secure/accessible/damaged/poor air passage\nAS1851 2012 TABLE 7.4.2 ITEM 1.4 - Container pressure loss >10% or discharge indicator operated","severity_level":"non-critical","fault_id":"recVuHCFno6LlMGt6","prompt_id":"recVuHCFno6LlMGt6_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"4949daa7-6d6d-495a-98ee-2413e0062219","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.3","prompt":"CHECK all mechanical and pneumatic detection\n devices for any condition that is likely to adversely\n affect their function.","input":null,"possible_fault":"Mechanical detection device impaired","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.3 - Mechanical/pneumatic detection device function impaired","severity_level":"critical","fault_id":"recETE33agXruduse","prompt_id":"recETE33agXruduse_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"50323412-ff87-4448-baea-a3be51e04976","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"1.3","prompt":"CHECK the storage container enclosure is\n accessible, adequately illuminated, ventilated and\n secured against unauthorized entry.","input":null,"possible_fault":"Enclosure not accessible/secured","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.3 - Container enclosure not accessible/illuminated/ventilated/secured","severity_level":"non-critical","fault_id":"recTsXjuTOzkq6Eya","prompt_id":"recTsXjuTOzkq6Eya_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"5085ed4e-7c2b-47cb-a7c4-374a8936c7a7","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.5","prompt":"CHECK operation and lubricate as necessary.","input":null,"possible_fault":"Detection system failure","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.5 - Mechanical detection system operation check and lubrication failed","severity_level":"critical","fault_id":"rec8JkzpUARnWR9xl","prompt_id":"rec8JkzpUARnWR9xl_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"58409326-977c-479a-8f86-09a0f2ba7b3a","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.11","prompt":"CHECK that the discharge from all pressure-relief\n devices and vent valves does not create a hazard to\n personnel.","input":null,"possible_fault":"Pressure-relief discharge hazard\nVent valve discharge hazard","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.11 - Pressure-relief device discharge creates hazard\nAS1851 2012 TABLE 7.4.3 ITEM 2.11 - Vent valve discharge creates personnel hazard","severity_level":"non-critical","fault_id":"recQLTY1TfHh3btxl","prompt_id":"recQLTY1TfHh3btxl_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"5f5379ae-2786-43af-82d1-819e8e86d230","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.5 TEN-YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"4.4","prompt":"Internally inspect vessels in accordance with the\n procedure in AS/NZS 3788 (see Note 2).\nNote 2 The internal inspection is to be completed at 10-yearly intervals. The initial inspection is due 10 years after the date of \ncylinder manufacture.","input":null,"possible_fault":"Internal corrosion or vessel damage","possible_fault_description":"AS1851 2012 TABLE 7.4.5 ITEM 4.4 – Inspect internals every 10 years from manufacture date per AS/NZS 3788","severity_level":"critical","fault_id":"recLnhILXE8c4f2oG","prompt_id":"recLnhILXE8c4f2oG_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"10_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"694db7ee-d77b-47e1-bad8-c6cbacf5fcca","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.22","prompt":"SIMULATE a system operation and confirm\nthat directional valves operate as required.","input":null,"possible_fault":"Valves fail to operate","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.22 - Directional valves simulation test shows incorrect operation","severity_level":"critical","fault_id":"recgBJBl22lWoyEkS","prompt_id":"recgBJBl22lWoyEkS_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"6b5844ee-0efb-4ba0-969b-5345835a472f","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.18","prompt":"INSPECT all areas adjacent to the protected\n area to ensure that migration of extinguishing\n agent does not create a hazard to personnel.","input":null,"possible_fault":"Agent migration hazard","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.18 - Adjacent areas inspection shows extinguishing agent migration hazard","severity_level":"informational","fault_id":"recMXsCILkhMCoui4","prompt_id":"recMXsCILkhMCoui4_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"6dcaf82d-463b-44f3-ae37-8c063404e223","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.13.A","prompt":"CONFIRM by weighing, or using liquid level\n determination, that each storage container is\n correctly charged, that is, any mass loss is not\n greater than 5% of the nominal charge mass in the\n case of halocarbons, and not greater than 10% of\n the nominal charge mass in the case of carbon\n dioxide, water and nitrogen.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"rechzBAySmTE1ZnyW_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"71ebe127-2d1e-4613-9037-c1f7c03cc5a3","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"1.2","prompt":"CHECK that all warning signs are readily visible\n and legible.","input":null,"possible_fault":"Warning signs not visible/legible","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.2 - Warning signs not readily visible and legible","severity_level":"non-conformance","fault_id":"recMUACnmnHafsLvm","prompt_id":"recMUACnmnHafsLvm_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"7642aab2-06ff-4eb7-9895-32aadf3637dd","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"1.7","prompt":"INSPECT the protected area to check that the risk\n has not changed (e.g. volume, fuel type, change of\n use).","input":null,"possible_fault":"Protected area risk changed","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.7 - Protected area risk changed (volume/fuel/use)","severity_level":"informational","fault_id":"recYClxr0tBD7xyO6","prompt_id":"recYClxr0tBD7xyO6_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"8747bc16-63c3-43cb-98fe-1dfbf85a2422","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.3","prompt":"Record last pressure test or inspection date of\n gas storage containers. Report to owner if\n ten-yearly pressure test or inspection will be\n due in the next year. See Table 7.4.5\n Items 4.3 and 4.4.","input":null,"possible_fault":"Pressure test overdue","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.3 - Gas storage containers pressure test/inspection due within year","severity_level":"non-conformance","fault_id":"recfds72790OG1UMC","prompt_id":"recfds72790OG1UMC_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"9061ccfb-69f8-4ebd-8c0e-c9ed2ee0fc8f","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.23","prompt":"(a) CONDUCT a functional system test with\n other interfaced fire systems (e.g.\n HVAC, EWS).\n (b) VERIFY that the interface functions as\n required.\n NOTE: It is recommended that the\n responsible entity coordinate testing the\n interfaced fire protection systems.","input":null,"possible_fault":"Interface system failure\nInterface malfunction","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.23a - Functional test with interfaced fire systems failed\nAS1851 2012 TABLE 7.4.4 ITEM 3.23b - System interface function verification failed","severity_level":"critical","fault_id":"reclvoNovSikVt0Xk","prompt_id":"reclvoNovSikVt0Xk_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"96cfaf6f-72bc-4baa-890c-3d81adeb1d10","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.2","prompt":"Perform routine service in accordance with\n Section 6.","input":null,"possible_fault":"Electrical system service incomplete","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.2 - Electrical detection/control service not per Section 6","severity_level":"non-conformance","fault_id":"rece78VhIGYp5s4AS","prompt_id":"rece78VhIGYp5s4AS_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"988145d0-b7d1-484b-8ef6-287ae7b80880","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.5 TEN-YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"10_year","inspection_period_frequency":10,"inspection_period_interval":"year","inspection_period_in_days":3650,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"4.2","prompt":"TEST for free and unobstructed flow from each\n nozzle, using a continuous flow of nitrogen or\n suitable alternative.","input":null,"possible_fault":"Nozzle blocked or restricted","possible_fault_description":"AS1851 2012 TABLE 7.4.5 ITEM 4.2 – Confirm unobstructed flow at each nozzle using continuous nitrogen or equivalent","severity_level":"critical","fault_id":"reckth16k8pHreVch","prompt_id":"reckth16k8pHreVch_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"10_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"a432a7a3-4d2f-475d-be85-179ede10ff7e","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.17.B","prompt":"TEST and record the pressure at which\n pressure-relief vent operates.","input":null,"possible_fault":"Relief vent malfunction","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.17 - Pressure-relief vent operation pressure test/record failed","severity_level":"non-critical","fault_id":"recbxZNbtw2CLPDPN","prompt_id":"recbxZNbtw2CLPDPN_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"a7a783cd-361b-46d8-8b69-3dab136b70a0","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.21","prompt":"TEST the operation of the post-discharge  ventilation system.","input":null,"possible_fault":"Ventilation system failure","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.21 - Post-discharge ventilation system operation test failed","severity_level":"critical","fault_id":"rec7KveS0QjZS8Wh8","prompt_id":"rec7KveS0QjZS8Wh8_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"acfcef64-64aa-43b5-8d45-f7ed9267a059","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.4","prompt":"CHECK operation and lubricate as necessary.","input":null,"possible_fault":"Actuator fails to operate","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.4 - Mechanical actuator operation check and lubrication failed","severity_level":"critical","fault_id":"recevkoa9iz7tLrSw","prompt_id":"recevkoa9iz7tLrSw_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"aff1dde5-6838-4412-a40d-9afcecae8148","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.12","prompt":"CHECK that all directional valves and check valves\n are correctly oriented.","input":null,"possible_fault":"Directional valves incorrectly oriented\nCheck valves incorrectly oriented","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.12 - Directional valves not correctly oriented\nAS1851 2012 TABLE 7.4.3 ITEM 2.12 - Check valves not correctly oriented","severity_level":"non-critical","fault_id":"reckJxcpuxeL12RLZ","prompt_id":"reckJxcpuxeL12RLZ_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"b3945630-65e5-472b-a001-b41d90e27340","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"1.1","prompt":"Perform routine service in accordance with\n Section 6.","input":null,"possible_fault":"Electrical systems not serviced","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.1 - Electrical detection/control not serviced per Section 6","severity_level":"non-conformance","fault_id":"rec3EAl0GF0zBYRWD","prompt_id":"rec3EAl0GF0zBYRWD_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"c257d6d1-9af4-4e97-8812-f0cfa891f22b","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.4","prompt":"TEST operation of automatic mechanical detection\n systems and confirm the alarm activates the\n warning system and is capable of initiating\n suppression system discharge.","input":null,"possible_fault":"Detection system fails to operate\nAlarm does not activate warning system\nSystem cannot initiate suppression","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.4 - Automatic mechanical detection system not operating\nAS1851 2012 TABLE 7.4.3 ITEM 2.4 - Alarm fails to activate warning system\nAS1851 2012 TABLE 7.4.3 ITEM 2.4 - System cannot initiate suppression discharge","severity_level":"critical","fault_id":"recgGE4lcrmUhkkN9","prompt_id":"recgGE4lcrmUhkkN9_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"c40bfdfe-de84-4b96-bf5f-9aa8cf148619","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.10","prompt":"CLEAN dampers that have been subjected to\n the deposit of contaminants.","input":null,"possible_fault":"Dampers contaminated","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.10 - Dampers subjected to contaminant deposits not cleaned","severity_level":"non-critical","fault_id":"reckqDHSjuyA5Xdn8","prompt_id":"reckqDHSjuyA5Xdn8_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"ca30aff0-d394-42b0-adc1-fbde4e57251f","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.14","prompt":"VERIFY design concentration or application\n density.","input":null,"possible_fault":"Incorrect design parameters","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.14 - Design concentration/application density verification failed","severity_level":"non-conformance","fault_id":"recMPDjslG4dqH9oP","prompt_id":"recMPDjslG4dqH9oP_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"cce5bd9c-f61d-4157-a224-77948df77e33","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.7","prompt":"CHECK that all mechanical and pneumatic\n detection devices are spaced and located as\n required.","input":null,"possible_fault":"Incorrect spacing/location","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.7 - Mechanical/pneumatic detection devices not spaced/located as required","severity_level":"non-conformance","fault_id":"rectJ6HFYHoVEQzjb","prompt_id":"rectJ6HFYHoVEQzjb_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"d0fc6197-6910-4e7b-bdc7-bf1ee493f1ef","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.8","prompt":"REPLACE any actuator that will exceed its\n listed service life prior to the next scheduled\n routine service.","input":null,"possible_fault":"Actuator exceeds service life","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.8 - Pyrotechnic actuator exceeds listed service life","severity_level":"recommendation","fault_id":"recL8OS9AEs9oqklC","prompt_id":"recL8OS9AEs9oqklC_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"d59e6d3e-8745-4a80-843e-072111605683","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.13.B","prompt":"CONFIRM by weighing, or using liquid level\n determination, that each storage container is\n correctly charged, that is, any mass loss is not\n greater than 5% of the nominal charge mass in the\n case of halocarbons, and not greater than 10% of\n the nominal charge mass in the case of carbon\n dioxide, water and nitrogen.","input":null,"possible_fault":"Halocarbon mass loss >5% nominal\nCO2 mass loss >10% nominal\nWater mass loss >10% nominal\nNitrogen mass loss >10% nominal\nExpellant mass loss exceeds limits\nLiquid level below required minimum","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.13 - Halocarbon container mass loss >5% nominal\nAS1851 2012 TABLE 7.4.3 ITEM 2.13 - Carbon dioxide container mass loss >10% nominal\nAS1851 2012 TABLE 7.4.3 ITEM 2.13 - Water container mass loss >10% nominal\nAS1851 2012 TABLE 7.4.3 ITEM 2.13 - Nitrogen container mass loss >10% nominal\nAS1851 2012 TABLE 7.4.3 ITEM 2.13 - Expellant container mass loss exceeds limits\nAS1851 2012 TABLE 7.4.3 ITEM 2.13 - Container liquid level below required minimum","severity_level":"critical","fault_id":"recxeGo7Y9EXEgNy8","prompt_id":"recxeGo7Y9EXEgNy8_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"d6248d5f-9031-4484-947b-da8aec48aa80","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.10","prompt":"TEST operation of the system lock-off valve and\n confirm system inoperative visual warning device\n operates.","input":null,"possible_fault":"Lock-off valve does not operate\nVisual warning device failure","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.10 - System lock-off valve not operating\nAS1851 2012 TABLE 7.4.3 ITEM 2.10 - System visual warning device not operating","severity_level":"critical","fault_id":"rec8YD8JzKh0TU8V1","prompt_id":"rec8YD8JzKh0TU8V1_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"da4aa9b5-f0c8-4197-aadb-5cf8f35cb65e","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.16.A","prompt":"COMPLETE an enclosure integrity test for\n total flooding systems in accordance with\n AS ISO 14520.1 for gaseous systems, and\n CONFIRM that the results satisfy the\n requirements.\n NOTE: Where an integrity test cannot be\n conducted due to factors such as physical\n dimensional constraints, or large\n unclosable openings, confirm enclosure\n integrity by visual inspection.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recBjuHCRhgG2fN4S_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"dc25fb6f-f8d1-4ac0-8bb1-e0542eb95853","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.8","prompt":"CHECK that all pipework, flexible connectors and\n manifolds are free from damage and adequately\n secured.","input":null,"possible_fault":"Pipework damaged\nFlexible connectors damaged\nManifolds damaged\nPipework inadequately secured\nFlexible connectors not secured\nManifolds inadequately secured","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.8 - Pipework/flexible connectors damaged\nAS1851 2012 TABLE 7.4.3 ITEM 2.8 - Flexible connectors damaged\nAS1851 2012 TABLE 7.4.3 ITEM 2.8 - Manifolds damaged\nAS1851 2012 TABLE 7.4.3 ITEM 2.8 - Pipework inadequately secured\nAS1851 2012 TABLE 7.4.3 ITEM 2.8 - Flexible connectors inadequately secured\nAS1851 2012 TABLE 7.4.3 ITEM 2.8 - Manifolds inadequately secured","severity_level":"non-critical","fault_id":"recdIE5oNdMmAQq48","prompt_id":"recdIE5oNdMmAQq48_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"dd7c7187-2d37-413e-9a81-0a6996867176","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.20","prompt":"NOTE: For special hazard system interfaces  with HVAC systems, see Clause 1.12 and  Section 13.","input":null,"possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recL2W3bQId7fkMW2_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"de7963dc-83e2-4e7e-8ce1-675f7ea1b685","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.11","prompt":"CHECK for any condition that could cause\n inadvertent discharge of the extinguishing\n agent.","input":null,"possible_fault":"Risk of inadvertent discharge","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.11 - Conditions present that could cause inadvertent discharge","severity_level":"critical","fault_id":"recJj25IkGCJrembS","prompt_id":"recJj25IkGCJrembS_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"ea5b463b-5552-4d4e-bf2d-0a1672110a8f","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"2.7","prompt":"TEST operation of all manual release systems.","input":null,"possible_fault":"Manual release system failure","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.7 - Manual release systems not operating correctly","severity_level":"critical","fault_id":"recvti1qZlCOAkVnl","prompt_id":"recvti1qZlCOAkVnl_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"edca25e2-5b2c-4c3b-82bc-fc6da5457ff6","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.19","prompt":"Test operation of automatically operated\n ventilation dampers.","input":null,"possible_fault":"Dampers fail to operate","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.19 - Automatically operated ventilation dampers operation test failed","severity_level":"critical","fault_id":"recVUYd4MeZFOfFKO","prompt_id":"recVUYd4MeZFOfFKO_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"f03057de-5348-4650-935b-0836645c2878","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.6","prompt":"REPLACE any detection device or sensing\n element that will exceed its listed service life\n prior to the next scheduled routine service.","input":null,"possible_fault":"Device exceeds service life","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.6 - Detection device/sensing element exceeds listed service life","severity_level":"non-critical","fault_id":"recoHX1evg3vyjoOs","prompt_id":"recoHX1evg3vyjoOs_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"},{"id":"f59797a4-02a0-40f2-8f6d-39f2fd31c5b3","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazards Systems","variant":null,"variant_id":"recoMHFXU1KocjaUB","item_no":"3.15","prompt":"VERIFY dimensions.","input":null,"possible_fault":"Incorrect dimensions","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.15 - Local application system protected object dimensions verification failed","severity_level":"non-critical","fault_id":"recPMmw74YkUrijNc","prompt_id":"recPMmw74YkUrijNc_prompt","inspection_id":"c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recoMHFXU1KocjaUB_recSlH9Co2P4eozgV"}]},{"id":"recSANxXnNGt9CZfH","name":"Special Hazard Systems : Aerosol System","checklist":[{"id":"12589ae5-9e44-43d1-87f0-ee4bdf6e67bc","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazard Systems : Aerosol System","variant":null,"variant_id":"recSANxXnNGt9CZfH","item_no":"1.8","prompt":"CHECK that all aerosol generators have not been\n discharged and are secure.","input":null,"possible_fault":"Aerosol generators discharged/loose","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.8 - Aerosol generators discharged or not secure","severity_level":"critical","fault_id":"rec2VqymooMCXEjnD","prompt_id":"rec2VqymooMCXEjnD_prompt","inspection_id":"c_recSANxXnNGt9CZfH_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recSANxXnNGt9CZfH_recSlH9Co2P4eozgV"},{"id":"8bac88af-3bee-49d5-a71d-740084969e15","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazard Systems : Aerosol System","variant":null,"variant_id":"recSANxXnNGt9CZfH","item_no":"3.24","prompt":"REPLACE any generator that will exceed its\n listed service life prior to the next scheduled\n routine service.","input":null,"possible_fault":"Generator exceeds service life","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.24 - Aerosol generator exceeds listed service life","severity_level":"recommendation","fault_id":"recUmuTA6DerTt35Z","prompt_id":"recUmuTA6DerTt35Z_prompt","inspection_id":"c_recSANxXnNGt9CZfH_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recSANxXnNGt9CZfH_recSlH9Co2P4eozgV"},{"id":"932d7b74-fa8c-43de-ad9d-c4be8dca262c","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazard Systems : Aerosol System","variant":null,"variant_id":"recSANxXnNGt9CZfH","item_no":"1.9","prompt":"CHECK that all aerosol generator moisture seals\n are secure.","input":null,"possible_fault":"Moisture seals not secure","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.9 - Aerosol generator moisture seals not secure","severity_level":"non-critical","fault_id":"recj9AB8hhB43BLB5","prompt_id":"recj9AB8hhB43BLB5_prompt","inspection_id":"c_recSANxXnNGt9CZfH_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recSANxXnNGt9CZfH_recSlH9Co2P4eozgV"}]},{"id":"recSBPZsb9soMtNVb","name":"Special Hazard Systems : Water Mist System","checklist":[{"id":"1e4368e5-99a2-48e8-9d6f-81bff146a7de","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"3.25","prompt":"CONDUCT a full flow test to verify pressure  and flow of water supply in accordance with  the requirements of Section 3.","input":null,"possible_fault":"Inadequate pressure/flow","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.25 - Water supply full flow test shows inadequate pressure/flow","severity_level":"critical","fault_id":"reclFFEVz5xH4Hx1T","prompt_id":"reclFFEVz5xH4Hx1T_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"},{"id":"40f9571f-a0fa-480d-9004-5f2686cd1487","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"2.14","prompt":"TEST cycling system through a complete discharge\n cycle.","input":null,"possible_fault":"System fails complete discharge cycle","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.14 - Cycling system fails complete discharge cycle","severity_level":"critical","fault_id":"recCkfeiuxP6qRE41","prompt_id":"recCkfeiuxP6qRE41_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"},{"id":"4661189e-14ff-4906-aaec-1203779f6559","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"1.13","prompt":"Where air receivers form part of a water mist\n system, TEST compressor cut-in/cut-out pressures.","input":null,"possible_fault":"Compressor pressures incorrect","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.13 - Air compressor cut-in/cut-out pressures incorrect","severity_level":"non-critical","fault_id":"recxYEVWYloAeyduP","prompt_id":"recxYEVWYloAeyduP_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"},{"id":"5640dc11-15ae-4fa8-a394-3efb0c8a7b09","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"1.12","prompt":"TEST operational function of pumps and associated\n equipment in accordance with the requirements of\n Section 3.","input":null,"possible_fault":"Pump function test failed","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.12 - Pump operational function test failed per Section 3","severity_level":"critical","fault_id":"recJk7mvXMaKdS5rO","prompt_id":"recJk7mvXMaKdS5rO_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"},{"id":"81ec8eec-4702-44b0-859d-e7abb9f5d171","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"3.28","prompt":"DRAIN and inspect internal condition of  container. Refill including any additive if  required.","input":null,"possible_fault":"Container internal damage","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.28 - Water container drain/inspection shows internal condition issues","severity_level":"non-critical","fault_id":"recVDjOlMZd4aHm8h","prompt_id":"recVDjOlMZd4aHm8h_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"},{"id":"860f3767-e557-4d73-b87e-a2c14a7f45c3","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"2.16","prompt":"Perform routine service in accordance with\n Section 2.","input":null,"possible_fault":"Release valve service incomplete\nIsolating valve service incomplete\nControl valve service incomplete","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.16 - Release valve service not per Section 2\nAS1851 2012 TABLE 7.4.3 ITEM 2.16 - Isolating valve service not per Section 2\nAS1851 2012 TABLE 7.4.3 ITEM 2.16 - Control valve service not per Section 2","severity_level":"non-conformance","fault_id":"recTEL4CqQkVaGJbR","prompt_id":"recTEL4CqQkVaGJbR_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"},{"id":"913e8125-c0eb-44b9-b7d4-2394da141ff0","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"1.11","prompt":"CHECK in accordance with the requirements of\n Section 3.","input":null,"possible_fault":"Pumps/water supplies not checked","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.11 - Pumps/water supplies not checked per Section 3","severity_level":"non-conformance","fault_id":"recMIYlI7f5MAJEAM","prompt_id":"recMIYlI7f5MAJEAM_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"},{"id":"a351339e-cc43-4b26-9f49-35cea353b9a4","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"3.26","prompt":"DRAW OFF and check representative sample  and confirm correct concentration of  additive.","input":null,"possible_fault":"Incorrect additive concentration","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.26 - Water additives sample shows incorrect concentration","severity_level":"non-critical","fault_id":"recAT6mWnaib9aACU","prompt_id":"recAT6mWnaib9aACU_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"},{"id":"bbd606c2-da0f-465a-a40c-0c761a1c64d0","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.4 YEARLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"3.27","prompt":"CHECK and clean line strainers after any  system operation and yearly intervals. If  condition of line strainer so indicates, also  check and clean individual nozzle strainers.","input":null,"possible_fault":"Strainers/filters blocked","possible_fault_description":"AS1851 2012 TABLE 7.4.4 ITEM 3.27 - Line strainers/filters check and clean shows blockage","severity_level":"non-critical","fault_id":"rectsGMkj5w55Ts90","prompt_id":"rectsGMkj5w55Ts90_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"1_year::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"},{"id":"c90a88a2-925d-4179-91ab-7572bc5c94c1","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.3 SIX-MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"2.15","prompt":"Perform routine service in accordance with\n Section 3.","input":null,"possible_fault":"Pump service not per Section 3","possible_fault_description":"AS1851 2012 TABLE 7.4.3 ITEM 2.15 - Pump routine service not per Section 3","severity_level":"non-conformance","fault_id":"recKPCpcaZQCX0fYd","prompt_id":"recKPCpcaZQCX0fYd_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"6_month::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"},{"id":"e6ae5ea6-3b82-4baf-98b1-14913a154767","standard_code":"au_as_1851_2012","version":"full","category":"Special Hazard Systems","category_id":"recSlH9Co2P4eozgV","group_header":"TABLE 7.4.2 MONTHLY ROUTINE SERVICE SCHEDULE SPECIAL HAZARD SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Special Hazard Systems : Water Mist System","variant":null,"variant_id":"recSBPZsb9soMtNVb","item_no":"1.10","prompt":"CHECK for damage and correct setting.","input":null,"possible_fault":"Regulator damaged/incorrect setting","possible_fault_description":"AS1851 2012 TABLE 7.4.2 ITEM 1.10 - Pressure regulator damaged or incorrect setting","severity_level":"non-critical","fault_id":"recuWiP8ITHlX4JKx","prompt_id":"recuWiP8ITHlX4JKx_prompt","inspection_id":"c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV","grouping_key":"1_month::c_recSBPZsb9soMtNVb_recSlH9Co2P4eozgV"}]}],"other_checklist_items":[]},{"id":"recWW5NwfZ6Coenk0","name":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","asset_types":[{"id":"rec3ELONOSXrK8MGc","name":"System changeover under fire condition","checklist":[{"id":"0776fcfa-103d-4273-8f3e-ae067114f147","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.5 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SYSTEM CHANGEOVER UNDER FIRE CONDITION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"System changeover under fire condition","variant":null,"variant_id":"rec3ELONOSXrK8MGc","item_no":"4.3","prompt":"OPERATE the manual switches at the FFCP. Check\nthat fans start and stop and dampers, if applicable,\nopen and close as documented (see Appendices H\nand I).","input":null,"possible_fault":"Fans do not respond or indicator faults","possible_fault_description":"AS1851 TABLE 13.4.2.5 ITEM 4.3 – Fan/damper not responsive at FFCP.","severity_level":"critical","fault_id":"recD5JzdEbAFZGNQn","prompt_id":"recD5JzdEbAFZGNQn_prompt","inspection_id":"c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0"},{"id":"5e05227c-1f54-48d8-9dab-1c11d84adc7e","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.5 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SYSTEM CHANGEOVER UNDER FIRE CONDITION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"System changeover under fire condition","variant":null,"variant_id":"rec3ELONOSXrK8MGc","item_no":"4.2","prompt":"CONDUCT a simulation of a fire/smoke situation\n(for each system or zone where relevant) to effect\nchangeover from normal mode to fire mode or\nshutdown as appropriate.\nCHECK fans, dampers and indicator lamps operate in\nfire mode (see Appendices H and I).\nTests required in Items 4.4, 4.5 and 4.6 are carried\nout during this simulation test (see Notes 1 and 2).","input":null,"possible_fault":"No response from system or zones","possible_fault_description":"AS1851 TABLE 13.4.2.5 ITEM 4.2 – Fire mode not activated from detector.","severity_level":"critical","fault_id":"rec95vDpJQrKhFL1q","prompt_id":"rec95vDpJQrKhFL1q_prompt","inspection_id":"c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0"},{"id":"76e2edfe-a774-42a5-88a4-73bd0f23b827","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.5 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SYSTEM CHANGEOVER UNDER FIRE CONDITION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"System changeover under fire condition","variant":null,"variant_id":"rec3ELONOSXrK8MGc","item_no":"4.6","prompt":"CHECK to ensure that the integrity and leakage\nperformance are not compromised by operation of the\nmechanical systems in fire mode.","input":null,"possible_fault":"Leaks or curtain malfunction","possible_fault_description":"AS1851 TABLE 13.4.2.5 ITEM 4.6 – Curtain fails under fire mode.","severity_level":"non-critical","fault_id":"recsOU9iC9CmX4Uwn","prompt_id":"recsOU9iC9CmX4Uwn_prompt","inspection_id":"c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0"},{"id":"943201e6-9989-404c-8284-659368f80306","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.5 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SYSTEM CHANGEOVER UNDER FIRE CONDITION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"System changeover under fire condition","variant":null,"variant_id":"rec3ELONOSXrK8MGc","item_no":"4.4","prompt":"Where supply air systems are fitted with a smoke\ndetector(s), check system shuts down when the\ndetector is automatically activated as documented\n(see Appendices H and I).\nVerify re-start when smoke clears and verify that the\nFFCP manual override ‘ON’ operates while the fan\nhas shut down due to supply smoke detection.","input":null,"possible_fault":"Fan continues to operate after smoke input","possible_fault_description":"AS1851 TABLE 13.4.2.5 ITEM 4.4 – System fails to shut down on smoke.","severity_level":"critical","fault_id":"rec9q32FzTrOs16B8","prompt_id":"rec9q32FzTrOs16B8_prompt","inspection_id":"c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0"},{"id":"9c1e5440-82b9-443c-9473-446869ba9abc","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.4 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SYSTEM CHANGEOVER UNDER FIRE CONDITION","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"System changeover under fire condition","variant":null,"variant_id":"rec3ELONOSXrK8MGc","item_no":"3.1","prompt":"SIMULATE by activation from FIP, the fire/smoke\nsituation (for each system or zone where relevant),\nrequired to effect changeover from normal mode to\nfire mode or shutdown as appropriate. Check fans,\ndampers and indicator lamps operate in fire mode as\ndocumented (see Appendices H and I).\nNOTES:\n1 The purpose of a simulated testing routine is to\ncheck the functioning of the air-handling\nchangeover system and not the detectors\nthemselves. The recommended practice in this\ncase is to simulate activation of the system by\ninitiating the fire alarm via the switch in the\nFIP.\n2 This changeover test is initiated in the fire panel\nto verify the integrity of the interface between\nfire and mechanical systems.\n3 Verification of fan or damper operation may use\nelementary testing procedures; e.g. hearing fan\nstart, observation of indicator lamp change of\nstatus, feeling of air movement across doorway,\ngrille, duct, etc.","input":null,"possible_fault":"No changeover or no fan/damper response","possible_fault_description":"AS1851 TABLE 13.4.2.4 ITEM 3.1 – Fire mode changeover fails on FIP trigger.","severity_level":"critical","fault_id":"recSPmkp4wc7SD9BY","prompt_id":"recSPmkp4wc7SD9BY_prompt","inspection_id":"c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0"},{"id":"c24f2036-62d5-4976-9cf7-f011693fa66a","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.4 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SYSTEM CHANGEOVER UNDER FIRE CONDITION","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"System changeover under fire condition","variant":null,"variant_id":"rec3ELONOSXrK8MGc","item_no":"3.2","prompt":"SWITCH system back to ‘normal’ and check that all\nequipment and indicator lamps are in the correct\nnon-fire mode (see Appendices H and I).","input":null,"possible_fault":"Non-fire mode not restored","possible_fault_description":"AS1851 TABLE 13.4.2.4 ITEM 3.2 – System fails to revert to normal.","severity_level":"non-critical","fault_id":"recnJb3GSoUizzxb5","prompt_id":"recnJb3GSoUizzxb5_prompt","inspection_id":"c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0"},{"id":"cdcf5416-6768-4d00-9fa7-a31d2446bcc9","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.5 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SYSTEM CHANGEOVER UNDER FIRE CONDITION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"System changeover under fire condition","variant":null,"variant_id":"rec3ELONOSXrK8MGc","item_no":"4.1","prompt":"COMPLETE all three-monthly test activities as listed\nin Table 13.4.2.4.","input":null,"possible_fault":"Items missed in 3-monthly testing","possible_fault_description":"AS1851 TABLE 13.4.2.5 ITEM 4.1 – Not all 3-monthly tests completed.","severity_level":"non-conformance","fault_id":"rec7d5STI05fz0hWC","prompt_id":"rec7d5STI05fz0hWC_prompt","inspection_id":"c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0"},{"id":"f3302af6-2f40-4f49-8d35-43eeed795c0d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.5 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SYSTEM CHANGEOVER UNDER FIRE CONDITION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"System changeover under fire condition","variant":null,"variant_id":"rec3ELONOSXrK8MGc","item_no":"4.5","prompt":"CHECK zone smoke control system performance\ncriteria as documented (see Appendices H and I).","input":"TEXT","possible_fault":"Incorrect pressure or airflow in zone","possible_fault_description":"AS1851 TABLE 13.4.2.5 ITEM 4.5 – Zone smoke control not compliant.","severity_level":"non-critical","fault_id":"recGG2ExAP8S3yQdH","prompt_id":"recGG2ExAP8S3yQdH_prompt","inspection_id":"c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rec3ELONOSXrK8MGc_recWW5NwfZ6Coenk0"}]},{"id":"recBWgH7naCbYbxsO","name":"Motorized relief openings, windows and shutters","checklist":[]},{"id":"recCNF62ZNJDZKWQE","name":"Fire isolated exit pressurization systems","checklist":[{"id":"088659d0-5a0b-4aaa-af81-3f1f1a3f300d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.2","prompt":"(e) When smoke is introduced to the supply smoke\nsensor of any air-pressurization system, the\nassociated pressurization fan is shut down.","input":null,"possible_fault":"Fan fails to stop with smoke","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.2e – Fan does not shut down on smoke.","severity_level":"critical","fault_id":"recU4iiCoKopjQN2a","prompt_id":"recU4iiCoKopjQN2a_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"0a27a62a-a1ba-4844-bb84-9ca1cb3261bb","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.2","prompt":"(c) The noise level at typical doorways and those\nidentified as subject to the highest noise level.","input":null,"possible_fault":"Excessive or high-pitched noise","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.2c – Noise levels exceed limits.","severity_level":"non-critical","fault_id":"recMwAjidtZhEx5pk","prompt_id":"recMwAjidtZhEx5pk_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"0bbfbe97-e87e-4d7f-be7d-d254529ee843","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.2","prompt":"(d) Time taken for door opening force and airflow\nvelocity to be restored, after opening and re-\nclosing two successive doors adjacent to the\ntest door(s) (to be that identified as having the\nlongest restoration time).","input":null,"possible_fault":"Restoration too slow","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.2d – Airflow/door force not restored promptly.","severity_level":"non-critical","fault_id":"recQbtT8wToLzdtQq","prompt_id":"recQbtT8wToLzdtQq_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"0e08ba8f-7e75-4733-b717-34daae7f57ad","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.2 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"1.1","prompt":"(f) Air movement.","input":null,"possible_fault":"Reverse or low air pressure","possible_fault_description":"AS1851 TABLE 13.4.2.2 ITEM 1.1f – Airflow incorrect through opened doors.","severity_level":"critical","fault_id":"rec2qLIKTIwVFGWlE","prompt_id":"rec2qLIKTIwVFGWlE_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"0e4a4cf8-170f-4b29-8d1f-1715ade62042","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.2 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"1.1","prompt":"(a) Fan operation.","input":null,"possible_fault":"Fan fails to operate","possible_fault_description":"AS1851 TABLE 13.4.2.2 ITEM 1.1a – Fan not triggered by FIP activation.","severity_level":"critical","fault_id":"recexHHicXbVqOMyc","prompt_id":"recexHHicXbVqOMyc_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"1fab8c2b-9935-4f03-88d9-14550660d4c0","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.2 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"1.1","prompt":"SIMULATE by activation from FIP, the fire/smoke\nsituation required to effect operation of the pressurization\nsystem. Check fans, dampers and indicator lamps operate in\nfire mode as documented. Check for excessive noise, ease\nof opening doors and correct movement of air from each\npressurized area through a selected open door (see\nAppendices H and I).","input":null,"possible_fault":"Fan or damper not working","possible_fault_description":"AS1851 TABLE 13.4.2.2 ITEM 1.1 – Components fail to operate in fire mode.","severity_level":"critical","fault_id":"reculaZ9dgiX8vVjk","prompt_id":"reculaZ9dgiX8vVjk_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"3f414667-dd68-4627-943d-5bfdfc087108","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.4","prompt":"Switch system to ‘normal’ and check that all\nequipment and indicator lamps are in the correct\nnon-fire mode. (Refer Appendices H and I.)","input":null,"possible_fault":"Still in fire mode or error state","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.4 – System fails to return to normal mode.","severity_level":"non-critical","fault_id":"reckg9H6MLNP4uG7z","prompt_id":"reckg9H6MLNP4uG7z_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"76a71193-9fc0-482f-b659-667032af4a55","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.1","prompt":"COMPLETE all three-monthly test activities, as\nlisted in Table 13.4.2.2.","input":null,"possible_fault":"Items skipped or incomplete","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.1 – 3-monthly tests not fully conducted.","severity_level":"non-conformance","fault_id":"recUga7Xyi4M8HAeX","prompt_id":"recUga7Xyi4M8HAeX_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"aab0b5d3-d1d4-414d-b229-861e0934d40c","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.2 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"1.1","prompt":"(c) Indicator lamps.","input":null,"possible_fault":"Indicator does not light","possible_fault_description":"AS1851 TABLE 13.4.2.2 ITEM 1.1c – Fire mode light not functioning.","severity_level":"non-critical","fault_id":"recfBVLLyInKkswXM","prompt_id":"recfBVLLyInKkswXM_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"b2122f50-deab-43e7-a7b8-2cb7dae11820","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.2","prompt":"CHECK that the following parameters meet the\nperformance requirements (see Appendices H and\nI, and Notes 1 and 2).\n(a) Airflow velocity across all required doorways.","input":null,"possible_fault":"Low/no airflow detected","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.2a – Air velocity insufficient at doorway.","severity_level":"critical","fault_id":"recEClDv2BcT7xd4O","prompt_id":"recEClDv2BcT7xd4O_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"b71a7d9a-18ac-414b-ad3c-29a7aa7b25a9","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.2","prompt":"(b) The force required to open each door.","input":null,"possible_fault":"Door too hard to open","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.2b – Door opening force exceeds limit.","severity_level":"non-critical","fault_id":"recuLHgTUEgZNIY5B","prompt_id":"recuLHgTUEgZNIY5B_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"b7477ac4-f87b-4c09-a75a-8975f8969428","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.2","prompt":"(f) Operation of the manual switch provided for\nfire brigade personnel starts and stops fans\nsupplying air to the pressurized fire-isolated\nescape routes.","input":null,"possible_fault":"Switch does not activate fan","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.2g – Manual fan switch non-functional.","severity_level":"critical","fault_id":"recM4u5jEr9T1E0GZ","prompt_id":"recM4u5jEr9T1E0GZ_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"cb2bfec0-845c-48cf-9816-128a210ff10d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.2","prompt":"Verify re-start when smoke clears and verify\nthat the FFCP manual override ‘ON’ operates\nwhile the fan has shut down due to supply\nsmoke detection.","input":null,"possible_fault":"Fan fails to restart or override fails","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.2f – Restart or FFCP override fails.","severity_level":"critical","fault_id":"recGNqVOI8JPmqrCw","prompt_id":"recGNqVOI8JPmqrCw_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"dc46c025-3a40-4e35-8f39-ff7f05e951a1","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.2 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"1.1","prompt":"(b) Damper operation.","input":null,"possible_fault":"Damper jammed or unresponsive","possible_fault_description":"AS1851 TABLE 13.4.2.2 ITEM 1.1b – Damper fails to open/close as required.","severity_level":"critical","fault_id":"recXsqnSEA2ArPYIs","prompt_id":"recXsqnSEA2ArPYIs_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"deb2c1ee-60d7-43d0-9fc9-9db01c4d1256","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.2 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"1.1","prompt":"(d) Noise.","input":null,"possible_fault":"Excessive fan/damper noise","possible_fault_description":"AS1851 TABLE 13.4.2.2 ITEM 1.1d – Abnormal sound during system activation.","severity_level":"non-critical","fault_id":"recxjulr327WcVsd4","prompt_id":"recxjulr327WcVsd4_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"efd2c98c-fb10-4a67-b9f6-178cd4b14238","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.2","prompt":"SIMULATE a fire/smoke situation from any device\nsuch as a sprinkler, heat of smoke detector, to\neffect operation of the pressurization and all other\nsystems required to operate in fire mode.","input":null,"possible_fault":"No system activation on trigger","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.2 – System fails to activate from detector.","severity_level":"critical","fault_id":"recpjKMwVjXSo9hM1","prompt_id":"recpjKMwVjXSo9hM1_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"f6443d02-948f-4d57-b14d-381c524573f6","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.2 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"1.2","prompt":"SWITCH all systems back to ‘normal’ and check that all\nequipment and indicator lamps are in the correct non-fire\nmode (see Appendices H and I).","input":null,"possible_fault":"Stays in fire mode","possible_fault_description":"AS1851 TABLE 13.4.2.2 ITEM 1.2 – System fails to revert to normal operation.","severity_level":"non-critical","fault_id":"rectBew8NrPchFIRX","prompt_id":"rectBew8NrPchFIRX_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"fa4512f0-912b-4e18-bb86-58749bbc0ccf","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.3","prompt":"(h) With all air-pressurization and other systems\noperating simultaneously, check that any\nspecific air relief is fully operational and\nenables the required airflow from pressurized\nareas to be sustained.","input":null,"possible_fault":"Insufficient pressure relief","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.3 – Air relief fails to maintain airflow.","severity_level":"non-critical","fault_id":"recX4En3NlDznNJnY","prompt_id":"recX4En3NlDznNJnY_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"fb60d678-176c-4460-914e-aa9b8ae6dec5","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.3 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE-ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"2.2","prompt":"(g) Check indicator lamps change status when fan\nstarts or stops.","input":null,"possible_fault":"Lamps fail to change","possible_fault_description":"AS1851 TABLE 13.4.2.3 ITEM 2.2h – Fan status lamps do not update.","severity_level":"non-critical","fault_id":"recEOyABi3p2rggWz","prompt_id":"recEOyABi3p2rggWz_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"},{"id":"fd11bd5e-3c65-4c69-8fb0-80a0fb4d774e","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.2 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE ISOLATED EXIT PRESSURIZATION SYSTEMS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fire isolated exit pressurization systems","variant":null,"variant_id":"recCNF62ZNJDZKWQE","item_no":"1.1","prompt":"(e) Ease of door opening.","input":null,"possible_fault":"Door sticks under pressure","possible_fault_description":"AS1851 TABLE 13.4.2.2 ITEM 1.1e – Door too hard to open under pressure.","severity_level":"non-critical","fault_id":"recbqztjPjnR8dBIH","prompt_id":"recbqztjPjnR8dBIH_prompt","inspection_id":"c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recCNF62ZNJDZKWQE_recWW5NwfZ6Coenk0"}]},{"id":"recF02GvAeiRTzdlR","name":"Smoke reservoirs","checklist":[{"id":"acc39004-742e-4a69-b757-8aaab5de7815","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.3.4 YEARLY SURVEY AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE RESERVOIRS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke reservoirs","variant":null,"variant_id":"recF02GvAeiRTzdlR","item_no":"3.1","prompt":"CHECK to ensure that changes to the smoke\nreservoirs have not been made, such as the addition of\nlight fittings or openings created, which would\notherwise compromise the integrity of the system.","input":null,"possible_fault":"Additional penetrations present","possible_fault_description":"AS1851 TABLE 13.4.3.4 ITEM 3.1 – Smoke reservoir compromised by modifications.","severity_level":"non-conformance","fault_id":"rec7NeSanbJ8ggsqS","prompt_id":"rec7NeSanbJ8ggsqS_prompt","inspection_id":"c_recF02GvAeiRTzdlR_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recF02GvAeiRTzdlR_recWW5NwfZ6Coenk0"}]},{"id":"recGdvqgim8FzHNua","name":"Power supplies—Main switchboards (low voltage)","checklist":[{"id":"01014156-5c06-45e2-bbfc-af426bd1867e","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.9","prompt":"CHECK wiring diagram and report where considered\nto be incorrect.","input":null,"possible_fault":"Outdated or incorrect diagrams","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.9 – Schematics no longer reflect current installation.","severity_level":"non-conformance","fault_id":"recLYlMTHrfD8zaoA","prompt_id":"recLYlMTHrfD8zaoA_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"16ed990f-4acf-48cb-a1e0-d0f3c520bcfd","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.11","prompt":"CHECK current draw on main risers and compare to\nrating.","input":null,"possible_fault":"Overcurrent on mains","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.11 – Current draw exceeds rated capacity.","severity_level":"non-critical","fault_id":"reclzKdkfua8r24Dg","prompt_id":"reclzKdkfua8r24Dg_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"1a9e21fa-4055-4501-a0bb-8534997a7e94","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.3","prompt":"CHECK, clean or replace, as necessary, contacts or\nfaulty relays.","input":null,"possible_fault":"Faulty or corroded relay contacts","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.3 – Contacts or relays require attention.","severity_level":"non-critical","fault_id":"rec4BplO4N1AEaOuv","prompt_id":"rec4BplO4N1AEaOuv_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"29d78a9a-9d3a-4f1b-b22d-bff89f8b8192","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.6","prompt":"CHECK and rectify, where necessary, condition of\nexposed cable insulation.","input":null,"possible_fault":"Deteriorated or cracked insulation","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.6 – Damaged cable insulation observed.","severity_level":"non-critical","fault_id":"recg3hmuoGrwAj9St","prompt_id":"recg3hmuoGrwAj9St_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"38d8f4cc-2442-4884-8706-bbbec28732fb","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.10","prompt":"TEST operation of main breakers (manually) with\npower switched off.","input":null,"possible_fault":"Main breaker fails manual trip test","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.10 – Main breaker doesn’t function when manually tested.","severity_level":"critical","fault_id":"recJMVipj0RDjbboY","prompt_id":"recJMVipj0RDjbboY_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"471ac068-fa9d-485d-a6b6-25f1f30307e4","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.2","prompt":"EXAMINE the general condition of conduits,\nconnectors, switches and wiring.","input":null,"possible_fault":"Degraded or unsafe wiring","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.2 – Components show signs of wear, heat, or damage.","severity_level":"critical","fault_id":"recpzJIeRKxkossBO","prompt_id":"recpzJIeRKxkossBO_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"53edadbf-9e84-473c-ba4e-8df6f9b40d06","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.12","prompt":"CHECK continuity to earth.","input":null,"possible_fault":"Earth bonding not continuous","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.12 – Earthing not present or disconnected.","severity_level":"non-conformance","fault_id":"rec80fvGHzw9txKZ8","prompt_id":"rec80fvGHzw9txKZ8_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"55f03cb1-e068-4633-935b-a25b92c16bd6","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.8","prompt":"CHECK panel seals, and rectify if faulty.","input":null,"possible_fault":"Air or moisture ingress","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.8 – Faulty or perished door/panel seals.","severity_level":"non-critical","fault_id":"recO7KqdNFm8RJtHe","prompt_id":"recO7KqdNFm8RJtHe_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"668794fa-b630-4304-944b-5dd85ffb0a80","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.13","prompt":"CHECK and record neutral current.","input":null,"possible_fault":"Neutral current imbalance","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.13 – Elevated or inconsistent neutral current.","severity_level":"non-critical","fault_id":"recTd998YjzwnXwI4","prompt_id":"recTd998YjzwnXwI4_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"6f2950f1-0a2d-4ebf-ad2e-bdcebcd5f170","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.5","prompt":"CHECK all fuses for correct rating.","input":null,"possible_fault":"Incorrect fuse size or rating","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.5 – Fuse rating does not match system requirements.","severity_level":"non-critical","fault_id":"rec4HW34MFvYGex0y","prompt_id":"rec4HW34MFvYGex0y_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"750e7ce8-859d-4e82-bd85-c32db80a9ff6","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.1","prompt":"CHECK for loose busbar connections and cable\nterminations and retighten any loose connections.","input":null,"possible_fault":"Loose or faulty busbar connections","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.1 – Busbar or cable terminations are loose or insecure.","severity_level":"non-critical","fault_id":"recH0Doh0XhkC689G","prompt_id":"recH0Doh0XhkC689G_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"a076a33b-65b5-4a29-a16b-bea49a5f7777","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.4","prompt":"INSPECT interpole barriers and shrouds.","input":null,"possible_fault":"Missing or damaged barriers","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.4 – Barriers/shrouds are not present or compromised.","severity_level":"critical","fault_id":"recI4rggwIYcRCWSI","prompt_id":"recI4rggwIYcRCWSI_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"},{"id":"b716997c-f101-4736-a413-5eafccb69bfe","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.26 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES POWER SUPPLIES—MAIN SWITCHBOARDS (LOW VOLTAGE)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Power supplies—Main switchboards (low voltage)","variant":null,"variant_id":"recGdvqgim8FzHNua","item_no":"25.7","prompt":"VACUUM clean switchboard interior and remove\nany rubbish.","input":null,"possible_fault":"Internal dust or foreign materials","possible_fault_description":"AS1851 TABLE 13.4.1.26 ITEM 25.7 – Dust buildup or trash inside the board enclosure.","severity_level":"non-critical","fault_id":"recO7bZFivYXUgUja","prompt_id":"recO7bZFivYXUgUja_prompt","inspection_id":"c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recGdvqgim8FzHNua_recWW5NwfZ6Coenk0"}]},{"id":"recHD7M5vlcA8Wep9","name":"Air control dampers—recycle air, relief air, smoke spill and outdoor air","checklist":[]},{"id":"rechlq14W977UYLVb","name":"Automatic smoke and heat vents","checklist":[{"id":"010b0672-829a-4eb4-a105-3a4bec6b24f7","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.2","prompt":"CHECK air supply and control panel for signs of\ndamage.","input":null,"possible_fault":"Panel fault found","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.2 – Control unit or air delivery system damaged","severity_level":"non-critical","fault_id":"recTutqfcrzuh3PFS","prompt_id":"recTutqfcrzuh3PFS_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"145ddff7-86a0-4dad-87a6-ea45f0ca42d6","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.9 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"8.3","prompt":"CHECK air filter and drain fluid.","input":null,"possible_fault":"Clogged filter","possible_fault_description":"AS1851 2012 TABLE 13.4.1.9 ITEM 8.3 – Filter is blocked or fluid not drained","severity_level":"non-critical","fault_id":"recm5nTzzup30AYnA","prompt_id":"recm5nTzzup30AYnA_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"18408795-9190-483a-b2a7-c7ec85029faa","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.12","prompt":"CHECK manual/automatic operation and operating\ntime of system.","input":null,"possible_fault":"No vent movement","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.12 – Activation by switch/manual not functioning","severity_level":"critical","fault_id":"recE5av32hgRL7CWa","prompt_id":"recE5av32hgRL7CWa_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"1d3f59e4-46ab-4bae-b769-6ab7977ecb08","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.6","prompt":"CHECK battery backup supply where power is\nrequired to operate vents.","input":null,"possible_fault":"Battery fails test","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.6 – Emergency power backup not holding charge","severity_level":"critical","fault_id":"rec3DBROL4iusUx9p","prompt_id":"rec3DBROL4iusUx9p_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"2ad27ad7-28ee-4b19-acd2-a663405005cf","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.11","prompt":"CHECK ram dust covers are in place.","input":null,"possible_fault":"Missing cover","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.11 – Dust guard not installed or dislodged","severity_level":"non-critical","fault_id":"recshEoKshqWAvg8T","prompt_id":"recshEoKshqWAvg8T_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"43b03d9c-61ce-4833-8396-990ce771ee0d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.4","prompt":"CHECK air filter and drain fluid.","input":null,"possible_fault":"Blocked filter","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.4 – Drain clogged or airflow restricted by debris","severity_level":"non-critical","fault_id":"rec9XQ9XST1XSNQXB","prompt_id":"rec9XQ9XST1XSNQXB_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"51113c6c-5336-4f53-9c7e-9ee03725255b","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.9 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"8.2","prompt":"CHECK power supply to control panel.","input":null,"possible_fault":"No power input","possible_fault_description":"AS1851 2012 TABLE 13.4.1.9 ITEM 8.2 – Control panel not receiving mains supply","severity_level":"critical","fault_id":"recTSvNQ1rt8CFtmu","prompt_id":"recTSvNQ1rt8CFtmu_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"544a2799-f5d9-48d1-ba09-81d8dabf2d9b","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.3","prompt":"CHECK power supply to control panel.","input":null,"possible_fault":"Loss of supply","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.3 – Power input missing or intermittent at control source","severity_level":"non-critical","fault_id":"reccjHh8WrCqxcnuG","prompt_id":"reccjHh8WrCqxcnuG_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"54cf645a-ccb6-479f-9e0f-508c63d2713b","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.9 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"8.7","prompt":"CHECK and ensure that the vents and all\ncomponents such as pulleys, hinges, latches,\ncables, etc. are free from obstruction and capable\nof operation.","input":null,"possible_fault":"Vent obstruction","possible_fault_description":"AS1851 2012 TABLE 13.4.1.9 ITEM 8.7 – Physical items or component friction prevent vent opening","severity_level":"critical","fault_id":"rec0JxVWm3W64wTz6","prompt_id":"rec0JxVWm3W64wTz6_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"586e2996-d39e-4caa-8dbc-34901c459410","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.5","prompt":"CHECK system air pressure.","input":null,"possible_fault":"Pressure too low","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.5 – System air insufficient to support vent actuation","severity_level":"critical","fault_id":"recf842hTUyVLqoDA","prompt_id":"recf842hTUyVLqoDA_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"5d07775c-c683-4ca2-a7c2-39e0a8d46af7","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.10","prompt":"CHECK drain holes and internal drain channels are\nclear.","input":null,"possible_fault":"Drain blocked","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.10 – Water channels or holes obstructed by debris","severity_level":"non-critical","fault_id":"recH136E1DHypQLrj","prompt_id":"recH136E1DHypQLrj_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"6acaebd0-1f0e-49be-ae12-ad11dcc801f4","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.9 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"8.4","prompt":"CHECK system air pressure.","input":null,"possible_fault":"Low air pressure","possible_fault_description":"AS1851 2012 TABLE 13.4.1.9 ITEM 8.4 – System air supply insufficient or unstable","severity_level":"critical","fault_id":"recsnBf9dUDYDsFgK","prompt_id":"recsnBf9dUDYDsFgK_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"6faaecc1-f08e-4145-9b97-92876c9efa35","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.14","prompt":"REPLACE all fusible links throughout the building\nevery 25 years from the date of manufacture.","input":null,"possible_fault":"Link exceeds age","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.14 – Fusible link >25 years must be replaced","severity_level":"recommendation","fault_id":"recVKYUGbdeCtxvIL","prompt_id":"recVKYUGbdeCtxvIL_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"8ba0f4b1-e23e-4747-beba-f69c3e9dc36d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.9 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"8.1","prompt":"CHECK air supply and control panel for signs of\ndamage.","input":null,"possible_fault":"Damaged controller","possible_fault_description":"AS1851 2012 TABLE 13.4.1.9 ITEM 8.1 – Visible damage or faults on air supply or panel","severity_level":"non-critical","fault_id":"recCStaNe03tOuizL","prompt_id":"recCStaNe03tOuizL_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"9708db9f-1003-44b4-80db-69bb39ff31d1","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.9 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"8.6","prompt":"CHECK operation under mains failure condition.","input":null,"possible_fault":"Fails on mains off","possible_fault_description":"AS1851 2012 TABLE 13.4.1.9 ITEM 8.6 – No response from system under power loss test","severity_level":"critical","fault_id":"rec5ljrVswDIj1HL5","prompt_id":"rec5ljrVswDIj1HL5_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"ace1e763-b9e2-4c35-8360-889547646ab3","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.13","prompt":"REPLACE any fusible release links if coated with\npaint.","input":null,"possible_fault":"Link painted over","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.13 – Painted links affect fire release trigger","severity_level":"recommendation","fault_id":"recNf8M9s7Fs0kBLL","prompt_id":"recNf8M9s7Fs0kBLL_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"ae127063-38a3-4185-b0a7-4f06d101daae","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.1","prompt":"COMPLETE all six-monthly service activities as\nlisted in Table 13.4.1.9.","input":null,"possible_fault":"Missed inspections","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.1 – Prior biannual checks not done or not recorded","severity_level":"non-conformance","fault_id":"rec8rYUwBE2hqX4HO","prompt_id":"rec8rYUwBE2hqX4HO_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"b76c3b3c-d811-4394-bff3-80bffb5560e8","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.9","prompt":"CHECK vents for damage, wear or corrosion.","input":null,"possible_fault":"Corroded/damaged vent","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.9 – Corrosion or wear noted on vent housing","severity_level":"non-critical","fault_id":"rec5SVCtmr9NiP0ra","prompt_id":"rec5SVCtmr9NiP0ra_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"b91b4c0c-6fa4-4ae8-82f9-757b5f9de0cf","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.7","prompt":"CHECK operation under mains failure condition","input":null,"possible_fault":"No action on failover","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.7 – System fails to open vents when mains disconnected","severity_level":"non-critical","fault_id":"recyPIywh3NQUlslg","prompt_id":"recyPIywh3NQUlslg_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"bd4f109f-1351-4bc4-a1c9-c5b47ae53313","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.10 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"9.8","prompt":"CHECK and ensure that the vents and all\ncomponents such as pulleys, hinges, latches,\ncables, etc. are free from obstruction and capable\nof operation.","input":null,"possible_fault":"Component blocked","possible_fault_description":"AS1851 2012 TABLE 13.4.1.10 ITEM 9.8 – Hinges, pulleys, or cables restrict opening","severity_level":"non-critical","fault_id":"reciIZ4VO26Ottwal","prompt_id":"reciIZ4VO26Ottwal_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"},{"id":"cccabffe-d64c-424f-a144-2aaa6a5a8d65","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.9 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AUTOMATIC SMOKE AND HEAT VENTS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Automatic smoke and heat vents","variant":null,"variant_id":"rechlq14W977UYLVb","item_no":"8.5","prompt":"CHECK battery backup supply where power is\nrequired to operate vents.","input":null,"possible_fault":"Backup fault","possible_fault_description":"AS1851 2012 TABLE 13.4.1.9 ITEM 8.5 – Battery backup not available for vent activation","severity_level":"critical","fault_id":"recDjYg1OsUqUUUyw","prompt_id":"recDjYg1OsUqUUUyw_prompt","inspection_id":"c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_rechlq14W977UYLVb_recWW5NwfZ6Coenk0"}]},{"id":"reci5aqsQ2FmJSdcR","name":"Electric heaters—Duct or unit mounted","checklist":[{"id":"018fcce0-4437-4de2-821a-1b4a7cbf92d0","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.15 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES ELECTRIC HEATERS—DUCT OR UNIT MOUNTED","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Electric heaters—Duct or unit mounted","variant":null,"variant_id":"reci5aqsQ2FmJSdcR","item_no":"14.7","prompt":"CHECK operation of over-temperature cut-out by\nsimulating overheating of the heater bank.","input":null,"possible_fault":"Cut-out fails on overheat test","possible_fault_description":"AS1851 2012 TABLE 13.4.1.15 ITEM 14.7 – Over-temp cut-out fails to activate.","severity_level":"critical","fault_id":"rec6YOQ2jwS0FII2M","prompt_id":"rec6YOQ2jwS0FII2M_prompt","inspection_id":"c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0"},{"id":"052ff2e4-dcbd-411a-bbf2-6b35c8ecdedd","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.15 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES ELECTRIC HEATERS—DUCT OR UNIT MOUNTED","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Electric heaters—Duct or unit mounted","variant":null,"variant_id":"reci5aqsQ2FmJSdcR","item_no":"14.2","prompt":"CHECK for loose external connections and fittings.","input":null,"possible_fault":"External fittings loose","possible_fault_description":"AS1851 2012 TABLE 13.4.1.15 ITEM 14.2 – Loose or disconnected wiring/fittings detected.","severity_level":"non-critical","fault_id":"recF1sfuk1Gbbj0t8","prompt_id":"recF1sfuk1Gbbj0t8_prompt","inspection_id":"c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0"},{"id":"3b26cdb2-7969-435d-a159-68761cba2514","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.15 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES ELECTRIC HEATERS—DUCT OR UNIT MOUNTED","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Electric heaters—Duct or unit mounted","variant":null,"variant_id":"reci5aqsQ2FmJSdcR","item_no":"14.5","prompt":"CHECK that the heater switches off upon switching\noff the fan.","input":null,"possible_fault":"Heater remains on after fan","possible_fault_description":"AS1851 2012 TABLE 13.4.1.15 ITEM 14.5 – Heater does not shut off when fan is off.","severity_level":"non-critical","fault_id":"recYo7P3iB2WKa2u4","prompt_id":"recYo7P3iB2WKa2u4_prompt","inspection_id":"c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0"},{"id":"4c3d4e0e-1b10-44a0-9cfc-3a850fbe42ab","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.15 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES ELECTRIC HEATERS—DUCT OR UNIT MOUNTED","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Electric heaters—Duct or unit mounted","variant":null,"variant_id":"reci5aqsQ2FmJSdcR","item_no":"14.6","prompt":"CHECK operation of airflow-sensing device by\nsimulating loss of airflow.","input":null,"possible_fault":"No cut-out on airflow loss","possible_fault_description":"AS1851 2012 TABLE 13.4.1.15 ITEM 14.6 – Airflow sensing device fails under test.","severity_level":"critical","fault_id":"recW2g3GVmRpHhCCj","prompt_id":"recW2g3GVmRpHhCCj_prompt","inspection_id":"c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0"},{"id":"7999f17d-7920-4081-8da9-d1ec065604b5","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.15 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES ELECTRIC HEATERS—DUCT OR UNIT MOUNTED","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Electric heaters—Duct or unit mounted","variant":null,"variant_id":"reci5aqsQ2FmJSdcR","item_no":"14.4","prompt":"CHECK the elements for obstructions and\naccumulation of foreign matter.\nNOTE: A duct access panel may be installed to\npermit convenient inspection.","input":null,"possible_fault":"Elements blocked","possible_fault_description":"AS1851 2012 TABLE 13.4.1.15 ITEM 14.4 – Dust or debris obstructs heater elements.","severity_level":"non-critical","fault_id":"recMlQLH2lRj2ShL0","prompt_id":"recMlQLH2lRj2ShL0_prompt","inspection_id":"c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0"},{"id":"8f7ba78f-87c6-4ee9-ada4-018b070797eb","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.15 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES ELECTRIC HEATERS—DUCT OR UNIT MOUNTED","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Electric heaters—Duct or unit mounted","variant":null,"variant_id":"reci5aqsQ2FmJSdcR","item_no":"14.3","prompt":"CHECK for loose internal thermal insulation.","input":null,"possible_fault":"Internal insulation detached","possible_fault_description":"AS1851 2012 TABLE 13.4.1.15 ITEM 14.3 – Internal thermal insulation is loose or missing.","severity_level":"non-critical","fault_id":"recZqaixKJ4nE9ckb","prompt_id":"recZqaixKJ4nE9ckb_prompt","inspection_id":"c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0"},{"id":"f4ad8b09-12d0-4826-969f-440331e7bbb5","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.15 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES ELECTRIC HEATERS—DUCT OR UNIT MOUNTED","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Electric heaters—Duct or unit mounted","variant":null,"variant_id":"reci5aqsQ2FmJSdcR","item_no":"14.1","prompt":"CHECK the outside surface of the heater casing for\ndiscolouration or any indication of overheating.","input":null,"possible_fault":"Discolouration on casing","possible_fault_description":"AS1851 2012 TABLE 13.4.1.15 ITEM 14.1 – Heater casing shows signs of heat damage.","severity_level":"informational","fault_id":"recEHbVjfsumvwZC5","prompt_id":"recEHbVjfsumvwZC5_prompt","inspection_id":"c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reci5aqsQ2FmJSdcR_recWW5NwfZ6Coenk0"}]},{"id":"reckO73o3q9J2ScAK","name":"Air control dampers—Supply, return and exhaust air","checklist":[]},{"id":"reclY0pYkUEuWixUW","name":"Active fire and smoke control systems","checklist":[{"id":"565460ba-4828-42b4-a1bd-159e762f4713","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.3.2 YEARLY SURVEY AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES ACTIVE FIRE AND SMOKE CONTROL SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Active fire and smoke control systems","variant":null,"variant_id":"reclY0pYkUEuWixUW","item_no":"1.1","prompt":"CHECK for physical impediments that may impair\nsafe operation of smoke control systems comprising\nexit pressurization systems, smoke exhaust systems,\nchangeover systems and system shutdown.","input":null,"possible_fault":"Blockage present","possible_fault_description":"AS1851 TABLE 13.4.3.2 ITEM 1.1 – Obstruction impairs smoke control systems.","severity_level":"non-critical","fault_id":"recVqbEKGFZZUE58a","prompt_id":"recVqbEKGFZZUE58a_prompt","inspection_id":"c_reclY0pYkUEuWixUW_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reclY0pYkUEuWixUW_recWW5NwfZ6Coenk0"},{"id":"f267e01e-8771-4354-973a-83de8fbe6dbe","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.3.2 YEARLY SURVEY AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES ACTIVE FIRE AND SMOKE CONTROL SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Active fire and smoke control systems","variant":null,"variant_id":"reclY0pYkUEuWixUW","item_no":"1.2","prompt":"CHECK to ensure mechanical services additions and\nremovals, building work, or unintentional\nobstructions have not affected the functionality or\nperformance of the original design.","input":null,"possible_fault":"Unapproved alterations","possible_fault_description":"AS1851 TABLE 13.4.3.2 ITEM 1.2 – Alterations affect system performance.","severity_level":"non-conformance","fault_id":"recY29kK4bPmvwrmd","prompt_id":"recY29kK4bPmvwrmd_prompt","inspection_id":"c_reclY0pYkUEuWixUW_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reclY0pYkUEuWixUW_recWW5NwfZ6Coenk0"}]},{"id":"recMHbxO45GpJiWRQ","name":"Outdoor intakes","checklist":[{"id":"0b050630-e136-443a-b74d-572d033c2c52","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.18 MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES OUTDOOR INTAKES","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Outdoor intakes","variant":null,"variant_id":"recMHbxO45GpJiWRQ","item_no":"17.1","prompt":"REMOVE any combustible material from the vicinity of the intakes","input":null,"possible_fault":"Combustible hazards near intake","possible_fault_description":"AS1851 2012 TABLE 13.4.1.18 ITEM 17.1 – Combustible material located near air intakes.","severity_level":"critical","fault_id":"recSzEAkxOwQt8DGV","prompt_id":"recSzEAkxOwQt8DGV_prompt","inspection_id":"c_recMHbxO45GpJiWRQ_recWW5NwfZ6Coenk0","grouping_key":"1_month::c_recMHbxO45GpJiWRQ_recWW5NwfZ6Coenk0"},{"id":"2db88b48-8d7d-4f9f-a4c4-9825f758d3b1","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.19 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES OUTDOOR INTAKES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Outdoor intakes","variant":null,"variant_id":"recMHbxO45GpJiWRQ","item_no":"18.1","prompt":"COMPLETE all monthly service activities as listed\nin Table 13.4.1.18.","input":null,"possible_fault":"Monthly tasks missed","possible_fault_description":"AS1851 2012 TABLE 13.4.1.19 ITEM 18.1 – Monthly checks not completed as required.","severity_level":"non-conformance","fault_id":"recSczOq3R61K0JFW","prompt_id":"recSczOq3R61K0JFW_prompt","inspection_id":"c_recMHbxO45GpJiWRQ_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recMHbxO45GpJiWRQ_recWW5NwfZ6Coenk0"},{"id":"4e9a40d1-0a45-48b5-9d9f-94035bdf7ec0","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.19 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES OUTDOOR INTAKES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Outdoor intakes","variant":null,"variant_id":"recMHbxO45GpJiWRQ","item_no":"18.3","prompt":"CHECK and clean insect screens, replace if\ndamaged.","input":null,"possible_fault":"Screens blocked or damaged","possible_fault_description":"AS1851 2012 TABLE 13.4.1.19 ITEM 18.3 – Insect screens clogged or physically damaged.","severity_level":"non-critical","fault_id":"recL7vkds07bcBFe9","prompt_id":"recL7vkds07bcBFe9_prompt","inspection_id":"c_recMHbxO45GpJiWRQ_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recMHbxO45GpJiWRQ_recWW5NwfZ6Coenk0"},{"id":"c965d2a3-0c4e-4414-86c7-25cabc00b787","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.19 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES OUTDOOR INTAKES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Outdoor intakes","variant":null,"variant_id":"recMHbxO45GpJiWRQ","item_no":"18.4","prompt":"CHECK to ensure that the oil bath or adhesive\ncoating is as specified by the manufacturer.\nNOTE: Oil bath filters are now obsolete in new\ncommercial air-conditioning systems, and\nadhesive coated filters are uncommon; however, if\nsuch devices are still in service, the oil bath fluid\nor adhesive coating should be checked on an\nannual basis to ensure that the material is as\nspecified by the original filter manufacturer and\nhas a flashpoint not less than 160ºC.","input":null,"possible_fault":"Oil/adhesive level incorrect","possible_fault_description":"AS1851 2012 TABLE 13.4.1.19 ITEM 18.4 – Coating not to spec or flashpoint below 160°C.","severity_level":"non-critical","fault_id":"recsMohF5BedI4Mbf","prompt_id":"recsMohF5BedI4Mbf_prompt","inspection_id":"c_recMHbxO45GpJiWRQ_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recMHbxO45GpJiWRQ_recWW5NwfZ6Coenk0"},{"id":"e92259cf-2361-4abd-b206-b22d0c67eefa","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.19 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES OUTDOOR INTAKES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Outdoor intakes","variant":null,"variant_id":"recMHbxO45GpJiWRQ","item_no":"18.2","prompt":"CHECK intake louvres for corrosion and damage.","input":null,"possible_fault":"Louvre corrosion or damage","possible_fault_description":"AS1851 2012 TABLE 13.4.1.19 ITEM 18.2 – Intake louvres show corrosion or structural issues.","severity_level":"non-critical","fault_id":"recUYPFrvE99dZKS2","prompt_id":"recUYPFrvE99dZKS2_prompt","inspection_id":"c_recMHbxO45GpJiWRQ_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recMHbxO45GpJiWRQ_recWW5NwfZ6Coenk0"}]},{"id":"recnO36HiT7wmEPzD","name":"Smoke dampers","checklist":[{"id":"043fd28a-e0ce-4d51-ad73-9c425ec2d034","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke dampers","variant":null,"variant_id":"recnO36HiT7wmEPzD","item_no":"3.10","prompt":"CHECK and ensure that the smoke damper is in place\n free from obstruction and capable of operation (see\n Notes 1 and 2).","input":null,"possible_fault":"Jammed or not operable","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.10 – Blocked unit may fail to contain smoke in fire.","severity_level":"critical","fault_id":"reccwgPgqDjikxVy3","prompt_id":"reccwgPgqDjikxVy3_prompt","inspection_id":"c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0"},{"id":"1bff1f4a-0543-43b7-9045-cf2f4659fa66","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke dampers","variant":null,"variant_id":"recnO36HiT7wmEPzD","item_no":"3.12","prompt":"ENSURE damper moves to its fail-safe position on\n removal of power source.","input":null,"possible_fault":"No fail-safe action","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.12 – Damper must default to safe position on power loss.","severity_level":"critical","fault_id":"rec3L1pfLVcNDSdqq","prompt_id":"rec3L1pfLVcNDSdqq_prompt","inspection_id":"c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0"},{"id":"6b2005c1-3e12-4341-9358-1950d2c347dc","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke dampers","variant":null,"variant_id":"recnO36HiT7wmEPzD","item_no":"3.13","prompt":"CHECK for signs of tampering or modifications. The\n responsible entity shall confirm that modifications\n comply with the manufacturer’s requirements or a\n registered testing authority’s confirmation of\n operation.","input":null,"possible_fault":"Unauthorised mods","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.13 – Any alteration must be certified to ensure safe function.","severity_level":"non-conformance","fault_id":"recOSdRA64ZwgSwZ3","prompt_id":"recOSdRA64ZwgSwZ3_prompt","inspection_id":"c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0"},{"id":"ceb60f7b-171c-401e-8878-2b24e2752691","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke dampers","variant":null,"variant_id":"recnO36HiT7wmEPzD","item_no":"3.9","prompt":"CHECK tip seals for signs of damage that would\n adversely affect smoke leakage performance.","input":null,"possible_fault":"Damaged or worn seals","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.9 – Seal failure can allow smoke to pass through closed damper.","severity_level":"non-critical","fault_id":"recVsf8tLGGlHDoPs","prompt_id":"recVsf8tLGGlHDoPs_prompt","inspection_id":"c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0"},{"id":"d306fa93-836f-488e-abae-7c13d8aa4828","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.9 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke dampers","variant":null,"variant_id":"recnO36HiT7wmEPzD","item_no":"8.1","prompt":"ENSURE all dampers operate open and close in\naccordance with the system requirements (see\nAppendices H and I).\nCHECK all systems required to shut down are not\noperating (see Appendices H and I).","input":null,"possible_fault":"Damper remains open/closed when it shouldn't","possible_fault_description":"AS1851 TABLE 13.4.2.9 ITEM 8.1 – Dampers fail to open/close as designed.","severity_level":"critical","fault_id":"recllkE7byCVzStz9","prompt_id":"recllkE7byCVzStz9_prompt","inspection_id":"c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0"},{"id":"f748844b-6755-4247-ac8b-eada5a94a5c5","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke dampers","variant":null,"variant_id":"recnO36HiT7wmEPzD","item_no":"3.11","prompt":"CHECK smoke dampers and casings for corrosion,\n accumulation of dust, which may prevent future\n operation or affect the overall integrity. The extent of\n corrosion shall not impede damper operation or\n prevent it remaining in place until the next inspection\n (5 years) (see Notes 1, 2 and 5).","input":null,"possible_fault":"Corrosion or dirt","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.11 – Build-up may prevent movement during activation.","severity_level":"non-critical","fault_id":"recDLy8JmmJDkAjaA","prompt_id":"recDLy8JmmJDkAjaA_prompt","inspection_id":"c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0"},{"id":"fe1eb086-e4f1-4cd0-9b1e-762aec6447c5","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke dampers","variant":null,"variant_id":"recnO36HiT7wmEPzD","item_no":"3.8","prompt":"CHECK the damper is free from obstruction and\n capable of operating from fully open to fully closed.","input":null,"possible_fault":"Incomplete operation","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.8 – Damper must travel fully to seal off air pathway.","severity_level":"non-critical","fault_id":"recPTSMKe1Qc50t7c","prompt_id":"recPTSMKe1Qc50t7c_prompt","inspection_id":"c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recnO36HiT7wmEPzD_recWW5NwfZ6Coenk0"}]},{"id":"recns6YC4Kb6ZBFcx","name":"Fire and smoke curtains","checklist":[{"id":"06894c0c-4149-43d7-8c9f-ac8e97f31c84","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.9","prompt":"CHECK that the light warning unit flashes with\nthe correct intensity when required.","input":null,"possible_fault":"Light not flashing","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.9 – Confirm light warning activates correctly.","severity_level":"non-critical","fault_id":"recC0VOp4tMZL5qTi","prompt_id":"recC0VOp4tMZL5qTi_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"19b8d519-227c-4542-80fc-5b687b78928c","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.8","prompt":"(a) CHECK mains power input (where applicable).","input":null,"possible_fault":"No mains input","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.8a – Inspect MCC mains input (if applicable).","severity_level":"critical","fault_id":"rectQTrpIqfyqhKWE","prompt_id":"rectQTrpIqfyqhKWE_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"1ce76781-3c0a-4416-b409-a90f0bedbda5","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.2","prompt":"(a) CHECK bottom bar and capping (where\napplied) positioning in relation to the ceiling.\nAdjust where necessary.","input":null,"possible_fault":"Incorrect top limit","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.2 – Curtain not fully retracted","severity_level":"non-critical","fault_id":"recrehdtL60Qzx5ZZ","prompt_id":"recrehdtL60Qzx5ZZ_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"1d9c4338-55e1-4a6b-974e-d034cef6e1b8","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.3","prompt":"CHECK that the bottom limit position is closing\nto the correct position.","input":null,"possible_fault":"Stops too early/late","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.3 – Curtain bottom not aligned","severity_level":"non-critical","fault_id":"recQNeq0tXBmRJNPq","prompt_id":"recQNeq0tXBmRJNPq_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"203802dc-96dd-4859-8d28-197921512873","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.11 SIX MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"10.1","prompt":"CHECK there are no physical obstructions likely to\nimpede operation. RECORD any changes or\nadditions to the surrounding area.","input":null,"possible_fault":"Obstruction present","possible_fault_description":"AS1851 2012 TABLE 13.4.1.11 ITEM 10.1 – Obstructed path prevents curtain deployment","severity_level":"critical","fault_id":"reckaVE6Zdk8I2wTb","prompt_id":"reckaVE6Zdk8I2wTb_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"26a530b3-506d-48c2-9d9d-ca906687549e","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.8","prompt":"(g) CHECK the motor drive voltage.","input":null,"possible_fault":"Drive voltage fault","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.8g – Confirm correct motor drive voltage.","severity_level":"non-critical","fault_id":"rec9iD7AmMVUYZxVK","prompt_id":"rec9iD7AmMVUYZxVK_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"357ba413-8128-4fbd-b8b0-dc744d283fbf","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.4.B","prompt":"CHECK the ascent and descent speeds. RECORD results and adjust if necessary.","input":null,"possible_fault":"Speed incorrect","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.4 – Drop/raise speed outside spec","severity_level":"non-critical","fault_id":"recDr8keB1g3sNVkK","prompt_id":"recDr8keB1g3sNVkK_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"3ee0b355-3ef2-4d0d-b0cb-976b840c183b","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.6","prompt":"CHECK gravity fail-safe or other fail-safe\ndeployment of curtain by disconnecting all power\nsources to all controls.","input":null,"possible_fault":"Fail-safe not working","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.6 – Confirm curtain deploys safely with all power off.","severity_level":"critical","fault_id":"recIpVAwNsYfnrgsf","prompt_id":"recIpVAwNsYfnrgsf_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"45141630-1c4c-4daa-9317-e85d57264c4f","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.7.A","prompt":"REPLACE batteries that are more than two years old.","input":"DATE","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recuc31tdOSMRq3yT_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"4657e768-3e1f-4cd3-ba35-badd06c1acf8","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.11 SIX MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"10.5","prompt":"(e) CHECK the permanent d.c. power supplied\nfrom the PSU to the MCU (where applicable).","input":null,"possible_fault":"No DC output","possible_fault_description":"AS1851 2012 TABLE 13.4.1.11 ITEM 10.5 – DC not supplied to MCU","severity_level":"critical","fault_id":"rec1cQfAlpr3IGvab","prompt_id":"rec1cQfAlpr3IGvab_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"54d69325-4fd4-4b77-942f-957560a588d1","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.12","prompt":"(b) CHECK the hold time at the half height\nposition.","input":null,"possible_fault":"Hold delay wrong","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.12b – Confirm hold time at half height is accurate.","severity_level":"non-critical","fault_id":"recmNjqftAu3tKMyZ","prompt_id":"recmNjqftAu3tKMyZ_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"55a73db4-b897-459f-97d5-e358032fdb28","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.8","prompt":"(c) CHECK the transformer outputs (where applicable).","input":null,"possible_fault":"No output","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.8c – Test MCC transformer output.","severity_level":"non-critical","fault_id":"recDYnolTLxUh3Wc6","prompt_id":"recDYnolTLxUh3Wc6_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"61f8895d-1ed2-4ff4-8835-f57e2777fb56","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.8","prompt":"(h) CHECK the motor stall-out function\n(where fitted).","input":null,"possible_fault":"No stall protection","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.8h – Check motor stall-out protection (if fitted).","severity_level":"non-critical","fault_id":"recvTz3sK4Z4KP7WU","prompt_id":"recvTz3sK4Z4KP7WU_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"681e9f3d-fbe7-4885-aaea-af3fa4f7bb4d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.11 SIX MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"10.5","prompt":"(b) CONFIRM correct display and LED\nnotification.","input":null,"possible_fault":"LED not displaying","possible_fault_description":"AS1851 2012 TABLE 13.4.1.11 ITEM 10.5 – No status indication on PSU","severity_level":"non-critical","fault_id":"recYwii75TWvVaFT8","prompt_id":"recYwii75TWvVaFT8_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"76ba809d-ec72-4773-9659-b74fabe750f0","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.8","prompt":"(e) CHECK the permanent d.c. power supplied from the PSU to the MCC (where applicable).","input":null,"possible_fault":"No d.c. power","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.8e – Confirm d.c. power is supplied to MCC.","severity_level":"critical","fault_id":"recES5KcW7enerQif","prompt_id":"recES5KcW7enerQif_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"78dc8a15-3d49-40d1-baac-1afe346351ba","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.8","prompt":"(f) CHECK the motor brake voltage.","input":null,"possible_fault":"Brake voltage fault","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.8f – Confirm correct motor brake voltage.","severity_level":"non-critical","fault_id":"recfCXHHDF8xuWtVc","prompt_id":"recfCXHHDF8xuWtVc_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"877d2b45-43e7-4c57-83d4-c0883039c6a8","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.14","prompt":"REPLACE all fusible links throughout the\nbuilding every 25 years from the date of\nmanufacture.","input":null,"possible_fault":"Expired link","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.14 – Replace fusible links every 25 years.","severity_level":"non-critical","fault_id":"recioS0gTno0gGokd","prompt_id":"recioS0gTno0gGokd_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"923fa58c-3d5a-42fb-80cd-249a95e657ae","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.11 SIX MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"10.4","prompt":"CHECK for damage and confirm the integrity of\nside tracks, to ensure correct operation.","input":null,"possible_fault":"Track misaligned","possible_fault_description":"AS1851 2012 TABLE 13.4.1.11 ITEM 10.4 – Damaged or blocked guide track","severity_level":"non-critical","fault_id":"recs64osdBiGlcWEn","prompt_id":"recs64osdBiGlcWEn_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"9fb62f37-6cc7-4f63-b059-df0c0ff4a8fd","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.12","prompt":"(c) CHECK that the curtain closes when\nactivated by the second alarm source (dual\ndrop only).","input":null,"possible_fault":"No second drop","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.12c – Check curtain drops on second alarm.","severity_level":"non-critical","fault_id":"rech1TrezM7ichEV3","prompt_id":"rech1TrezM7ichEV3_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"afd9e122-24cd-46c6-aad5-b75cc394da8d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.11 SIX MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"10.2","prompt":"CHECK manual deployment of curtain via switch at\ncontrol panel.","input":null,"possible_fault":"Manual release fails","possible_fault_description":"AS1851 2012 TABLE 13.4.1.11 ITEM 10.2 – Manual drop fails from panel switch","severity_level":"critical","fault_id":"recHbhGJDjiJO9cZ0","prompt_id":"recHbhGJDjiJO9cZ0_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"b0843304-c8cc-4332-9722-55f40015b04d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.7.B","prompt":"REPLACE batteries that are more than two years old.","input":null,"possible_fault":"Battery expired","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.7 – Replace batteries older than two years.","severity_level":"non-critical","fault_id":"rec1vxSmzCPmHt7Qn","prompt_id":"rec1vxSmzCPmHt7Qn_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"b294d335-3fc1-442e-aaa4-580f9f98dbba","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.4.A","prompt":"CHECK the ascent and descent speeds. RECORD results and adjust if necessary.","input":"NUMBER","possible_fault":null,"possible_fault_description":null,"severity_level":null,"fault_id":null,"prompt_id":"recn8wf9359cQotAY_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"b3db9614-09f9-412f-a4aa-f04e4c5989cf","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.10","prompt":"CHECK that the local audible warning system is\ndistinctly audible in the vicinity of the curtain.","input":null,"possible_fault":"No sound","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.10 – Confirm local audible warning functions.","severity_level":"non-critical","fault_id":"rec6jlL06OkGQXAZh","prompt_id":"rec6jlL06OkGQXAZh_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"b41825fe-65cb-43a2-9339-149dd6944458","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.8","prompt":"(d) CHECK the control voltage being supplied from the PSU to the MCC.","input":null,"possible_fault":"Low control voltage","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.8d – Verify voltage between PSU and MCC.","severity_level":"non-critical","fault_id":"recOOQx0O5LNjpKjy","prompt_id":"recOOQx0O5LNjpKjy_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"b5b088e1-e75a-410b-906e-4500b2c9a7c5","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.11 SIX MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"10.5","prompt":"(c) CHECK the battery charger outputs.","input":null,"possible_fault":"No charger output","possible_fault_description":"AS1851 2012 TABLE 13.4.1.11 ITEM 10.5 – Battery charger not supplying output","severity_level":"critical","fault_id":"recdAuOtwTMhagxv8","prompt_id":"recdAuOtwTMhagxv8_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"c4e95068-34a3-40ee-9752-a8ae4d2d43fb","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.5","prompt":"CHECK automatic deployment of curtain via\nalarm signal activation.","input":null,"possible_fault":"Alarm not linked","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.5 – Curtain fails to respond to alarm","severity_level":"non-conformance","fault_id":"rec7uZlkXGJD8uzWP","prompt_id":"rec7uZlkXGJD8uzWP_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"c6a38cb3-4740-4d2a-91d0-87b47d973392","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.11 SIX MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"10.5","prompt":"(d) CHECK the control voltage being supplied\nfrom the PSU to the MCU.","input":null,"possible_fault":"Control voltage missing","possible_fault_description":"AS1851 2012 TABLE 13.4.1.11 ITEM 10.5 – No voltage reaching control unit","severity_level":"critical","fault_id":"rec488QO0OElSIos4","prompt_id":"rec488QO0OElSIos4_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"c835b148-4aad-478d-828f-d5269d575ca9","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.8","prompt":"(b) CONFIRM correct display and LED notification.","input":null,"possible_fault":"Display fault","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.8b – Check MCC LED display is working correctly.","severity_level":"non-critical","fault_id":"recysXL5c9l60gyV9","prompt_id":"recysXL5c9l60gyV9_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"cbc15ef6-a75e-45cd-a0dd-340707295d53","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.2","prompt":"(b) CONFIRM that the curtain performs the soft\nascent function (where fitted).","input":null,"possible_fault":"No soft ascent","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.2 – Curtain does not ascend softly","severity_level":"non-critical","fault_id":"rec6KnRxT9C8tL8vZ","prompt_id":"rec6KnRxT9C8tL8vZ_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"dc8f6df7-4a42-44b2-9ec8-95e84bdcb1c6","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.12","prompt":"(a) CHECK the half drop height.","input":null,"possible_fault":"Half drop incorrect","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.12a – Check dual-drop half height is correct.","severity_level":"non-critical","fault_id":"recOgGMLoFaIYponI","prompt_id":"recOgGMLoFaIYponI_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"de14b733-8d31-4360-bc41-c844706d7c5f","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.11 SIX MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"10.3","prompt":"CHECK for damage to curtain fabric.","input":null,"possible_fault":"Torn or damaged fabric","possible_fault_description":"AS1851 2012 TABLE 13.4.1.11 ITEM 10.3 – Curtain surface has holes or tears","severity_level":"non-critical","fault_id":"recnPbJ4qStXZ3jlZ","prompt_id":"recnPbJ4qStXZ3jlZ_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"e02cf166-268d-4bf7-a49b-a810756787c3","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.11 SIX MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"10.5","prompt":"(a) CHECK mains power input.","input":null,"possible_fault":"No mains input","possible_fault_description":"AS1851 2012 TABLE 13.4.1.11 ITEM 10.5 – Mains power not reaching PSU","severity_level":"critical","fault_id":"recOQMSr6sDPKOIlZ","prompt_id":"recOQMSr6sDPKOIlZ_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"e8e6a078-909b-40e4-ad93-6cc90b30124d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.11","prompt":"CHECK that the obstruction warning system\nactivates the appropriate warning system when the\ncurtain is obstructed for more than the required\nduration.","input":null,"possible_fault":"No obstruction alarm","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.11 – Test obstruction system activates correctly.","severity_level":"critical","fault_id":"recHN2a4Qu63PCqwV","prompt_id":"recHN2a4Qu63PCqwV_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"ea80d9cf-902b-45af-83ab-c0c8f73c8185","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.13","prompt":"CHECK that the curtain retracts temporarily when\nthe retract button is pressed.","input":null,"possible_fault":"No retract action","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.13 – Confirm retract function activates on command.","severity_level":"non-critical","fault_id":"recIVt3ohiFjpP9kY","prompt_id":"recIVt3ohiFjpP9kY_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"},{"id":"f0698524-77e0-4be1-a4e2-c94f0bcd578e","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.12 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE CURTAINS AND SMOKE CURTAINS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fire and smoke curtains","variant":null,"variant_id":"recns6YC4Kb6ZBFcx","item_no":"11.1","prompt":"COMPLETE all six-monthly service activities, as\nlisted in Table 13.4.1.11.","input":null,"possible_fault":"Service incomplete","possible_fault_description":"AS1851 2012 TABLE 13.4.1.12 ITEM 11.1 – Missing scheduled checks","severity_level":"non-conformance","fault_id":"recOdG7wF0IkTX4DY","prompt_id":"recOdG7wF0IkTX4DY_prompt","inspection_id":"c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recns6YC4Kb6ZBFcx_recWW5NwfZ6Coenk0"}]},{"id":"recPfp5rPgBuqKZrD","name":"Motor control centres","checklist":[{"id":"25f22172-7f39-4b6c-856c-c715a53e096d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.10","prompt":"CHECK panel seals, and rectify if faulty.","input":null,"possible_fault":"Air/dust ingress via panel gaps","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.10 – Panel seal ineffective","severity_level":"non-critical","fault_id":"recXxXWuO5nV8jUkN","prompt_id":"recXxXWuO5nV8jUkN_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"2ad5d9d5-907a-4b39-b980-0af228dffc71","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.4","prompt":"CHECK overload ratings against motor nameplate\nratings.","input":null,"possible_fault":"Incorrect motor protection","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.4 – Overload not aligned with motor rating","severity_level":"non-critical","fault_id":"rec4MS3s4GF4hWLdm","prompt_id":"rec4MS3s4GF4hWLdm_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"2c4be08a-d01d-4950-81b4-6b256056076a","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.9","prompt":"INSPECT each switchboard internally to ensure it is\nclean and free from rubbish.","input":null,"possible_fault":"Dust accumulation or obstructions","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.9 – Switchboard blocked or dirty","severity_level":"non-critical","fault_id":"recHCzLQyGdjzGLYo","prompt_id":"recHCzLQyGdjzGLYo_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"307dcc94-b47f-4a54-a24f-9e95d37b7761","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.5","prompt":"CHECK circuit protectors (fuses and circuit\nbreakers) for correct rating.","input":null,"possible_fault":"Improper circuit protection","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.5 – Fuse rating mismatch","severity_level":"non-conformance","fault_id":"rec1iLTMkPsFbmSva","prompt_id":"rec1iLTMkPsFbmSva_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"3eea77bc-ad35-4b05-8592-62193040441a","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.3","prompt":"CHECK, clean or replace, as necessary, any faulty\ncontacts or relays.","input":null,"possible_fault":"Malfunctioning contactors","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.3 – Relay or contact wear/failure","severity_level":"non-critical","fault_id":"rec8dVtsL9OC7s54s","prompt_id":"rec8dVtsL9OC7s54s_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"61d86375-347d-4cdc-98fb-64d25cc82743","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.8","prompt":"CHECK and rectify any damaged or faulty exposed\ncable insulation.","input":null,"possible_fault":"Cracked or degraded insulation","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.8 – Exposed or degraded insulation","severity_level":"non-critical","fault_id":"rec2XzyrQyM862vqU","prompt_id":"rec2XzyrQyM862vqU_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"7815a54a-97f1-4a21-ad38-38f9f36f9f77","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.7","prompt":"INSPECT interpole barriers and shrouds where\nfitted.","input":null,"possible_fault":"Damaged or missing barriers","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.7 – Missing insulation protection","severity_level":"critical","fault_id":"recnsfWxGgzA7wU1W","prompt_id":"recnsfWxGgzA7wU1W_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"83260835-4624-4c41-a027-6363c639daa5","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.11","prompt":"CHECK and report where wiring diagram(s) are\nconsidered to be incorrect.","input":null,"possible_fault":"Incorrect diagrams","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.11 – Outdated or misleading wiring info","severity_level":"non-conformance","fault_id":"recIIA2AxxkUq4PVa","prompt_id":"recIIA2AxxkUq4PVa_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"9e6f5c4c-1284-415f-9f76-eb02128d2227","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.1","prompt":"CHECK for loose busbar connections and cable\nterminations.","input":null,"possible_fault":"Loose electrical joints","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.1 – Loose connections increase fire risk","severity_level":"non-critical","fault_id":"recOFCsU5DeqXH9F9","prompt_id":"recOFCsU5DeqXH9F9_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"a83199ef-bf27-470d-bd00-8b6937030bcb","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.12","prompt":"CHECK continuity to earth.","input":null,"possible_fault":"Faulty or missing earthing","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.12 – Earth connection not verified","severity_level":"non-critical","fault_id":"reczfxhB1Vnvv9NZj","prompt_id":"reczfxhB1Vnvv9NZj_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"aefdd51a-4482-4461-9fd1-53e8133f3810","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.2","prompt":"CHECK general condition of conduits, connectors,\nswitches and wiring for any condition likely to\nadversely affect their function.","input":null,"possible_fault":"Damaged or aged components","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.2 – Degradation affecting functionality","severity_level":"non-critical","fault_id":"recbh9MNF9zKtw4nB","prompt_id":"recbh9MNF9zKtw4nB_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"cac24ae8-09ef-40a0-bc3b-de294c916ce1","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.6","prompt":"CHECK connections at motors, switchboards and\nequipment subject to vibration. Retighten cable\nterminations as necessary.","input":null,"possible_fault":"Loose cables at motors/switchboards","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.6 – Vibration causes terminal looseness","severity_level":"non-critical","fault_id":"reclsyjrlSfZIyiX5","prompt_id":"reclsyjrlSfZIyiX5_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"},{"id":"fe6ca283-aebb-4582-852d-5fd94e5066c4","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.25 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTOR CONTROL CENTRES","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Motor control centres","variant":null,"variant_id":"recPfp5rPgBuqKZrD","item_no":"24.13","prompt":"CHECK and record neutral current.","input":null,"possible_fault":"Unbalanced or excessive neutral load","possible_fault_description":"AS1851 TABLE 13.4.1.25 ITEM 24.13 – Neutral conductor overloaded","severity_level":"non-critical","fault_id":"rec2JmlHQnJrWScgS","prompt_id":"rec2JmlHQnJrWScgS_prompt","inspection_id":"c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recPfp5rPgBuqKZrD_recWW5NwfZ6Coenk0"}]},{"id":"recSWgdGeR0vfIQso","name":"Variable frequency inverters (VFIs)","checklist":[{"id":"1c88d180-5108-4cd9-90ce-fc657f370be4","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.20 THREE-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES VARIABLE FREQUENCY INVERTERS (VFIs)","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Variable frequency inverters (VFIs)","variant":null,"variant_id":"recSWgdGeR0vfIQso","item_no":"19.2","prompt":"CHECK electrical connections and tighten where\nnecessary.","input":null,"possible_fault":"Loose or corroded connections","possible_fault_description":"AS1851 2012 TABLE 13.4.1.20 ITEM 19.2 – Electrical terminals are loose or need tightening.","severity_level":"non-critical","fault_id":"recZ6SlzgDgqBl2Od","prompt_id":"recZ6SlzgDgqBl2Od_prompt","inspection_id":"c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0"},{"id":"23326db1-86b9-4a69-b6d3-b165f1878817","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.21 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES VARIABLE FREQUENCY INVERTERS (VFIs)","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Variable frequency inverters (VFIs)","variant":null,"variant_id":"recSWgdGeR0vfIQso","item_no":"20.2","prompt":"CHECK for evidence of damage or overheating and\nclean or repair where necessary.","input":null,"possible_fault":"Damaged casing or hot spots","possible_fault_description":"AS1851 2012 TABLE 13.4.1.21 ITEM 20.2 – Signs of heat damage or cracks on VFI body.","severity_level":"non-critical","fault_id":"recFfg0npWOXOMYG4","prompt_id":"recFfg0npWOXOMYG4_prompt","inspection_id":"c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0"},{"id":"5c4c0de1-1e22-4ec6-92fa-17ea1c7f5b4c","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.20 THREE-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES VARIABLE FREQUENCY INVERTERS (VFIs)","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Variable frequency inverters (VFIs)","variant":null,"variant_id":"recSWgdGeR0vfIQso","item_no":"19.1","prompt":"CHECK for dust and accumulated dirt on vents and\ncircuit boards and clean where necessary.\nWhere there is evidence of moisture, inspect on a\nmonthly basis or replace enclosure with one having\nan appropriate IP rating.","input":null,"possible_fault":"Accumulated dust or moisture","possible_fault_description":"AS1851 2012 TABLE 13.4.1.20 ITEM 19.1 – Dust on boards or moisture detected on inspection.","severity_level":"non-critical","fault_id":"recRZsbzKT0XFuzo5","prompt_id":"recRZsbzKT0XFuzo5_prompt","inspection_id":"c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0"},{"id":"a83d572c-da2f-4779-9de5-d0fc0451b52f","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.22 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES VARIABLE FREQUENCY INVERTERS (VFIs)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Variable frequency inverters (VFIs)","variant":null,"variant_id":"recSWgdGeR0vfIQso","item_no":"21.3","prompt":"CHECK operation of fire-mode override functions\nand correct if necessary.","input":null,"possible_fault":"Fire override not operating","possible_fault_description":"AS1851 TABLE 13.4.1.22 ITEM 21.3 – Fire-mode override fails or missing","severity_level":"critical","fault_id":"recFHoUPeBNkM1jue","prompt_id":"recFHoUPeBNkM1jue_prompt","inspection_id":"c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0"},{"id":"acf4c6eb-eab0-4e5f-979b-e73989bbf8d6","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.20 THREE-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES VARIABLE FREQUENCY INVERTERS (VFIs)","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Variable frequency inverters (VFIs)","variant":null,"variant_id":"recSWgdGeR0vfIQso","item_no":"19.3","prompt":"CHECK the operation of all cooling fans.","input":null,"possible_fault":"Fan not spinning or faulty","possible_fault_description":"AS1851 2012 TABLE 13.4.1.20 ITEM 19.3 – Cooling fan not operational or making noise.","severity_level":"critical","fault_id":"recCq2RxvTNg7krWH","prompt_id":"recCq2RxvTNg7krWH_prompt","inspection_id":"c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0"},{"id":"db269010-13c9-48c1-8aa3-89d0614a6182","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.22 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES VARIABLE FREQUENCY INVERTERS (VFIs)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Variable frequency inverters (VFIs)","variant":null,"variant_id":"recSWgdGeR0vfIQso","item_no":"21.1","prompt":"COMPLETE all six-monthly service activities,\n(see Table 13.4.1.21).","input":null,"possible_fault":"Missed six-monthly checks","possible_fault_description":"AS1851 TABLE 13.4.1.22 ITEM 21.1 – Six-monthly tasks not completed","severity_level":"non-conformance","fault_id":"recgthF0H1SDi6gsg","prompt_id":"recgthF0H1SDi6gsg_prompt","inspection_id":"c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0"},{"id":"e91e68ac-a077-4527-941f-9a2746e5937f","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.21 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES VARIABLE FREQUENCY INVERTERS (VFIs)","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"Variable frequency inverters (VFIs)","variant":null,"variant_id":"recSWgdGeR0vfIQso","item_no":"20.1","prompt":"COMPLETE all three-monthly service activities as\nlisted in Table 13.4.1.20.","input":null,"possible_fault":"Missed 3-monthly tasks","possible_fault_description":"AS1851 2012 TABLE 13.4.1.21 ITEM 20.1 – 3-monthly maintenance tasks not done.","severity_level":"non-conformance","fault_id":"reckJwte3qT6xYEDi","prompt_id":"reckJwte3qT6xYEDi_prompt","inspection_id":"c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0"},{"id":"fcacff22-80df-45d2-baac-0e0851d687d3","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.22 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES VARIABLE FREQUENCY INVERTERS (VFIs)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Variable frequency inverters (VFIs)","variant":null,"variant_id":"recSWgdGeR0vfIQso","item_no":"21.2","prompt":"CHECK calibration and set point of all adjustable\ncomponents, including customer settings and correct\nif necessary.","input":null,"possible_fault":"Incorrect calibration or settings","possible_fault_description":"AS1851 TABLE 13.4.1.22 ITEM 21.2 – Settings incorrect or out of spec","severity_level":"non-conformance","fault_id":"rec2q2E0AnwEkM0pr","prompt_id":"rec2q2E0AnwEkM0pr_prompt","inspection_id":"c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recSWgdGeR0vfIQso_recWW5NwfZ6Coenk0"}]},{"id":"recTU27tupBDXTwn8","name":"Pneumatic compressor/receiver station","checklist":[{"id":"15eabec8-bc9c-4068-9487-3d5c21106a52","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.24 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"23.1","prompt":"DRAIN and clean sump and replace sump oil.","input":null,"possible_fault":"Contaminated or low oil","possible_fault_description":"AS1851 TABLE 13.4.1.24 ITEM 23.2 – Sump oil dirty or degraded","severity_level":"non-critical","fault_id":"recR7CZqcDY5H3ZlT","prompt_id":"recR7CZqcDY5H3ZlT_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"2b83cd9e-d144-4f8a-b95b-46d30362816a","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.24 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"23.1","prompt":"COMPLETE all three-monthly service activities\n(see Table 13.4.1.23.)","input":null,"possible_fault":"Missed 3-monthly items","possible_fault_description":"AS1851 TABLE 13.4.1.24 ITEM 23.1 – 3-monthly maintenance not completed","severity_level":"non-conformance","fault_id":"recjv1LZoXd2lING4","prompt_id":"recjv1LZoXd2lING4_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"3fa9fbf0-03b7-4df4-a854-92fc12590441","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.23 THREE-MONTHLY, ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"22.6","prompt":"CHECK air intake filter and crankcase breather.\nClean or replace as necessary.","input":null,"possible_fault":"Clogged filter or breather","possible_fault_description":"AS1851 TABLE 13.4.1.23 ITEM 22.6 – Air filter or breather obstructed","severity_level":"non-critical","fault_id":"recsi62ly3dV5mJC1","prompt_id":"recsi62ly3dV5mJC1_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"43b29329-d984-47af-823a-a5bde57ccea2","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.23 THREE-MONTHLY, ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"22.1","prompt":"CHECK cut-in and cut-out pressures and record.","input":null,"possible_fault":"Incorrect pressure settings","possible_fault_description":"AS1851 TABLE 13.4.1.23 ITEM 22.1 – Pressure cut-in/cut-out settings not within range","severity_level":"non-critical","fault_id":"recmMmkVaOrVi7s3a","prompt_id":"recmMmkVaOrVi7s3a_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"442e4922-8bda-412b-8559-8b94697a6dc0","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.23 THREE-MONTHLY, ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"22.5","prompt":"CHECK and clean auto condensate drain or\nactuate manual drain.","input":null,"possible_fault":"Blocked or faulty drain","possible_fault_description":"AS1851 TABLE 13.4.1.23 ITEM 22.5 – Condensate not draining correctly","severity_level":"non-critical","fault_id":"recJIq4LijVTwfDJ0","prompt_id":"recJIq4LijVTwfDJ0_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"4e4f77e5-3f45-41d3-a682-ccfc6c63789b","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.24 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"23.3","prompt":"CHECK compressor holding-down bolts are secure.","input":null,"possible_fault":"Loose compressor base","possible_fault_description":"AS1851 TABLE 13.4.1.24 ITEM 23.3 – Compressor mounting bolts are loose or missing","severity_level":"non-critical","fault_id":"rec7whxIzAoEzQ5Sa","prompt_id":"rec7whxIzAoEzQ5Sa_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"6992f2b0-c31e-4966-96eb-207808937c01","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.23 THREE-MONTHLY, ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"22.2","prompt":"CHECK unit for overheating, undue noise and\nexcessive vibration.","input":null,"possible_fault":"Overheating or excessive noise","possible_fault_description":"AS1851 TABLE 13.4.1.23 ITEM 22.2 – Unit noisy or vibrating excessively","severity_level":"non-critical","fault_id":"rec2r6LQyL6khFomd","prompt_id":"rec2r6LQyL6khFomd_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"72fe7889-e0a2-4f25-80ec-87e987e3a4e7","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.24 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"23.8","prompt":"CHECK electrical connections, isolators and\nterminal box.","input":null,"possible_fault":"Loose terminals or unsafe wiring","possible_fault_description":"AS1851 TABLE 13.4.1.24 ITEM 23.8 – Unsafe or faulty electrical installation","severity_level":"non-critical","fault_id":"rec8YqQgZf3tH1NqB","prompt_id":"rec8YqQgZf3tH1NqB_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"86077362-168d-4311-bdcb-7495acc55817","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.23 THREE-MONTHLY, ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"22.7","prompt":"CHECK belts for wear (if belt drive); adjust\ntension or replace as required.","input":null,"possible_fault":"Worn or loose belt","possible_fault_description":"AS1851 TABLE 13.4.1.23 ITEM 22.7 – Belts require tensioning or change","severity_level":"non-critical","fault_id":"rec4koAolx8YB92ed","prompt_id":"rec4koAolx8YB92ed_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"88453e5e-31a3-4adb-9152-2a2e4aacdf45","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.24 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"23.5","prompt":"CHECK unit for any sign of corrosion or\ndeterioration. Treat corrosion with rust inhibitor.","input":null,"possible_fault":"Corrosion or deterioration","possible_fault_description":"AS1851 TABLE 13.4.1.24 ITEM 23.5 – External/internal rust not treated","severity_level":"non-critical","fault_id":"reccyZMQdPLiqty5E","prompt_id":"reccyZMQdPLiqty5E_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"b11682a2-835a-4c10-86c7-9dba1f93d19b","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.24 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"23.2","prompt":"CHECK pulley alignment (if belt drive). Ensure\npulleys are secure on shaft.","input":null,"possible_fault":"Misaligned or loose pulleys","possible_fault_description":"AS1851 TABLE 13.4.1.24 ITEM 23.3 – Pulley misalignment affects performance","severity_level":"non-critical","fault_id":"recZpLnuhOdz27IxU","prompt_id":"recZpLnuhOdz27IxU_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"cb3ca1fc-e4c6-44b5-b373-c13fe3d7397b","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.23 THREE-MONTHLY, ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"22.4","prompt":"CHECK if pressure-relief valves are operating by\nmanually bleeding.","input":null,"possible_fault":"Relief valve not operating","possible_fault_description":"AS1851 TABLE 13.4.1.23 ITEM 22.4 – Relief valve stuck or inoperative","severity_level":"critical","fault_id":"reck1uGEOXs9lWJwm","prompt_id":"reck1uGEOXs9lWJwm_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"d67655f4-bc20-4080-b1d9-50752c36fc67","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.24 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"23.4","prompt":"CHECK and open pressure vessel; clean and operate\nreceiver drain valves.","input":null,"possible_fault":"Pressure build-up or drain failure","possible_fault_description":"AS1851 TABLE 13.4.1.24 ITEM 23.4 – Pressure vessel unclean or blocked drains","severity_level":"critical","fault_id":"rec4bZDdPvvhAeIiK","prompt_id":"rec4bZDdPvvhAeIiK_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"e3a96fee-d7a5-49fb-8541-da68f03b0514","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.24 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"23.7","prompt":"Test run the unit and CHECK for satisfactory\noperation. Observe the frequency of compressor\noperation for possible unloader malfunction.","input":null,"possible_fault":"Poor performance or overcycling","possible_fault_description":"AS1851 TABLE 13.4.1.24 ITEM 23.7 – Operation irregularities or short cycling","severity_level":"non-critical","fault_id":"recRzJ2f4pqb615SO","prompt_id":"recRzJ2f4pqb615SO_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"e476c38b-7782-4698-a9e8-1b5fe3c07dd6","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.24 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"23.6","prompt":"CHECK pressure-relief valve operation and setting,\nwhere appropriate.","input":null,"possible_fault":"PRV stuck or incorrectly set","possible_fault_description":"AS1851 TABLE 13.4.1.24 ITEM 23.6 – Valve doesn't activate under pressure","severity_level":"non-critical","fault_id":"recd4AxMxmXSbqSQe","prompt_id":"recd4AxMxmXSbqSQe_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"},{"id":"ebdebba9-d681-4b5b-b73d-33f83b8774e2","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.23 THREE-MONTHLY, ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES PNEUMATIC COMPRESSOR/RECEIVER STATION","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Pneumatic compressor/receiver station","variant":null,"variant_id":"recTU27tupBDXTwn8","item_no":"22.3","prompt":"CHECK crankcase oil level and top up as\nnecessary.","input":null,"possible_fault":"Low or dirty oil","possible_fault_description":"AS1851 TABLE 13.4.1.23 ITEM 22.3 – Oil level too low or requires change","severity_level":"non-critical","fault_id":"rechr7eE3Gn3JhBxB","prompt_id":"rechr7eE3Gn3JhBxB_prompt","inspection_id":"c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recTU27tupBDXTwn8_recWW5NwfZ6Coenk0"}]},{"id":"recXsIA8l4pxQp2Bb","name":"Fans and motors","checklist":[{"id":"4630c597-4c8d-4fc5-b2bc-d543d2e358c8","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.3 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"2.3","prompt":"CHECK casing, guards and impeller for corrosion.","input":null,"possible_fault":"Corrosion on casing/guards/impeller","possible_fault_description":"AS1851 TABLE 13.4.1.3 ITEM 2.3 - Corrosion on casing/guards/impeller","severity_level":"non-critical","fault_id":"recmqFI9ZpVUEhCBQ","prompt_id":"recmqFI9ZpVUEhCBQ_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"},{"id":"528f6e88-afa3-440f-8b77-586481911d35","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.2 THREE-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"1.7","prompt":"CHECK for correct tension.","input":null,"possible_fault":"Incorrect belt tension","possible_fault_description":"AS1851 TABLE 13.4.1.2 ITEM 1.7 - Incorrect fan belt tension","severity_level":"non-critical","fault_id":"rec354Zdi867xDK65","prompt_id":"rec354Zdi867xDK65_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"},{"id":"5bc019b0-a28d-4fdf-b842-3cb58804c8af","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.2 THREE-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"1.1","prompt":"CHECK there are no physical obstructions likely to\n impede performance.","input":null,"possible_fault":"Obstructions impeding fan performance","possible_fault_description":"AS1851 TABLE 13.4.1.2 ITEM 1.1 - Physical obstructions impeding performance","severity_level":"non-critical","fault_id":"recgTO7hDCfkuDdpQ","prompt_id":"recgTO7hDCfkuDdpQ_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"},{"id":"9931d86e-59ff-448f-8b45-c199f9d7166c","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.2 THREE-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"1.4","prompt":"CHECK fan belts for wear.","input":null,"possible_fault":"Fan belts worn/damaged","possible_fault_description":"AS1851 TABLE 13.4.1.2 ITEM 1.4 - Fan belts worn/damaged condition","severity_level":"non-critical","fault_id":"recDdeyo8uPMATmtQ","prompt_id":"recDdeyo8uPMATmtQ_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"},{"id":"9fc51f1b-6ca0-4a3d-81e1-19bebd16ed16","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.2 THREE-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"1.5","prompt":"CHECK for satisfactory condition.","input":null,"possible_fault":"Guards/safety features unsatisfactory","possible_fault_description":"AS1851 TABLE 13.4.1.2 ITEM 1.5 - Guards/safety features unsatisfactory condition","severity_level":"non-critical","fault_id":"recb5KyznDNAMlsb0","prompt_id":"recb5KyznDNAMlsb0_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"},{"id":"acf57653-a70d-40b4-a679-19c169a51faa","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.2 THREE-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"1.3","prompt":"CHECK flexible connections, where fitted, for\n leaks, tearing or fraying.","input":null,"possible_fault":"Leaks/tearing/fraying in connections","possible_fault_description":"AS1851 TABLE 13.4.1.2 ITEM 1.3 - Flexible connections leaking/torn/frayed","severity_level":"non-critical","fault_id":"rec3yJ26UbBX77mlG","prompt_id":"rec3yJ26UbBX77mlG_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"},{"id":"ba1dfb36-488c-400d-9a7e-d3316771ef75","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.3 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"2.4","prompt":"CHECK electrical connections, isolators and terminal\n box.","input":null,"possible_fault":"Poor electrical connections/terminals","possible_fault_description":"AS1851 TABLE 13.4.1.3 ITEM 2.4 - Poor electrical connections/isolators/terminals","severity_level":"non-critical","fault_id":"recrpFlhGsjV39bmt","prompt_id":"recrpFlhGsjV39bmt_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"},{"id":"bce47a73-ced2-4f47-8199-acd8708555d5","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.3 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"2.1","prompt":"COMPLETE all three-monthly service activities\n (see Table 13.4.1.2.)","input":null,"possible_fault":"Three-monthly items not completed","possible_fault_description":"AS1851 TABLE 13.4.1.3 ITEM 2.1 - Three-monthly service activities not completed","severity_level":"non-conformance","fault_id":"recOVfuZn4kAT03LL","prompt_id":"recOVfuZn4kAT03LL_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"},{"id":"e78ff161-6e91-42a5-b2d0-570695b50d88","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.2 THREE-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"1.2","prompt":"CHECK motor and all bearings for noise,\n overheating and excessive vibration.","input":null,"possible_fault":"Noise/overheating/excessive vibration","possible_fault_description":"AS1851 TABLE 13.4.1.2 ITEM 1.2 - Motor/bearings noise/overheating/vibration","severity_level":"non-critical","fault_id":"rec8RdW9M7BTu8yuc","prompt_id":"rec8RdW9M7BTu8yuc_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"},{"id":"f2387c82-7554-4fbe-9088-909837dbeabf","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.2 THREE-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"1.6","prompt":"CHECK lubrication of bearings.","input":null,"possible_fault":"Inadequate bearing lubrication","possible_fault_description":"AS1851 TABLE 13.4.1.2 ITEM 1.6 - Inadequate bearing lubrication","severity_level":"recommendation","fault_id":"rec0jFuNMceIpGF2W","prompt_id":"rec0jFuNMceIpGF2W_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"},{"id":"ffab85a2-8d9a-43db-88d2-52816a2d0a9a","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.3 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES—FANS AND MOTORS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Fans and motors","variant":null,"variant_id":"recXsIA8l4pxQp2Bb","item_no":"2.2","prompt":"CHECK pulley wheels for alignment and couplings for\n alignment and tightness.","input":null,"possible_fault":"Misaligned pulleys/loose couplings","possible_fault_description":"AS1851 TABLE 13.4.1.3 ITEM 2.2 - Pulleys misaligned/couplings loose","severity_level":"non-critical","fault_id":"recEob6HT3t7xoFUH","prompt_id":"recEob6HT3t7xoFUH_prompt","inspection_id":"c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recXsIA8l4pxQp2Bb_recWW5NwfZ6Coenk0"}]},{"id":"recXTAXJ6j6LIBS3z","name":"Kitchen exhaust systems","checklist":[{"id":"095ac7dd-04ee-4d21-9546-e53cda6861c0","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.16 MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES KITCHEN EXHAUST SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Kitchen exhaust systems","variant":null,"variant_id":"recXTAXJ6j6LIBS3z","item_no":"15.1","prompt":"CHECK grease-arresting filters for excessive grease\naccumulation.","input":null,"possible_fault":"Excessive grease on filters","possible_fault_description":"AS1851 2012 TABLE 13.4.1.16 ITEM 15.1 – Filters clogged with grease beyond safe limit.","severity_level":"non-critical","fault_id":"recGuem5OfLyXBHpw","prompt_id":"recGuem5OfLyXBHpw_prompt","inspection_id":"c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0","grouping_key":"1_month::c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0"},{"id":"0f13b98c-f456-4d39-aaa5-3573784736bc","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.17 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES KITCHEN EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Kitchen exhaust systems","variant":null,"variant_id":"recXTAXJ6j6LIBS3z","item_no":"16.4","prompt":"CHECK duct for accumulated grease and\nCLEAN.","input":null,"possible_fault":"Grease buildup in ducting","possible_fault_description":"AS1851 2012 TABLE 13.4.1.17 ITEM 16.4 – Ductwork contains grease deposits, needs cleaning.","severity_level":"non-critical","fault_id":"recDQfenvLg87bWgO","prompt_id":"recDQfenvLg87bWgO_prompt","inspection_id":"c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0"},{"id":"646aa1a1-2c20-414c-b614-16376ff3574f","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.16 MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES KITCHEN EXHAUST SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Kitchen exhaust systems","variant":null,"variant_id":"recXTAXJ6j6LIBS3z","item_no":"15.3","prompt":"CHECK grease gutters for excessive grease\naccumulation.","input":null,"possible_fault":"Gutters blocked with grease","possible_fault_description":"AS1851 2012 TABLE 13.4.1.16 ITEM 15.3 – Grease gutters are heavily clogged or blocked.","severity_level":"non-critical","fault_id":"recEodISJZ7np9YTd","prompt_id":"recEodISJZ7np9YTd_prompt","inspection_id":"c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0","grouping_key":"1_month::c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0"},{"id":"90ac5dd6-6762-4b3b-bea8-4dc7d6a2b64d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.16 MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES KITCHEN EXHAUST SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Kitchen exhaust systems","variant":null,"variant_id":"recXTAXJ6j6LIBS3z","item_no":"15.4","prompt":"CHECK that grease-arresting filters are secured in\nthe correct position and undamaged.","input":null,"possible_fault":"Filter loose or damaged","possible_fault_description":"AS1851 2012 TABLE 13.4.1.16 ITEM 15.4 – Filters unsecured or visibly damaged.","severity_level":"non-critical","fault_id":"recgyPoeFpvpin21k","prompt_id":"recgyPoeFpvpin21k_prompt","inspection_id":"c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0","grouping_key":"1_month::c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0"},{"id":"9b0bdb7e-021e-4514-8f0a-c81d2825fd2f","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.16 MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES KITCHEN EXHAUST SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Kitchen exhaust systems","variant":null,"variant_id":"recXTAXJ6j6LIBS3z","item_no":"15.2","prompt":"CHECK hood and its exhaust plenum for excessive\ngrease accumulation.","input":null,"possible_fault":"Heavy grease buildup","possible_fault_description":"AS1851 2012 TABLE 13.4.1.16 ITEM 15.2 – Hood or plenum shows excess grease accumulation.","severity_level":"non-critical","fault_id":"recOjHSyBl1JP5otW","prompt_id":"recOjHSyBl1JP5otW_prompt","inspection_id":"c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0","grouping_key":"1_month::c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0"},{"id":"a8d1751a-a523-4ff9-8c76-082c501c1793","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.17 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES KITCHEN EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Kitchen exhaust systems","variant":null,"variant_id":"recXTAXJ6j6LIBS3z","item_no":"16.2","prompt":"CLEAN hood and its exhaust plenum.","input":null,"possible_fault":"Plenum not cleaned","possible_fault_description":"AS1851 2012 TABLE 13.4.1.17 ITEM 16.2 – Hood or plenum not properly cleaned during service.","severity_level":"recommendation","fault_id":"recjtTGDfbGp8Geiq","prompt_id":"recjtTGDfbGp8Geiq_prompt","inspection_id":"c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0"},{"id":"acc95a3b-8f24-4fbc-895b-ef47def5bba7","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.16 MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES KITCHEN EXHAUST SYSTEMS","inspection_period":"1_month","inspection_period_frequency":1,"inspection_period_interval":"month","inspection_period_in_days":30,"asset_type":"Kitchen exhaust systems","variant":null,"variant_id":"recXTAXJ6j6LIBS3z","item_no":"15.5","prompt":"CLEAN grease-arresting filters as required\n(monthly, see Note).\nNOTE: Owing to wide variations in usage, frequency of cleaning is subject to the assessment of the inspector or \nthe requirements of the regulatory authority. In some cases, cleaning may need to be more frequent than monthly","input":null,"possible_fault":"Dirty filters not cleaned","possible_fault_description":"AS1851 2012 TABLE 13.4.1.16 ITEM 15.5 – Filters left uncleaned as required.","severity_level":"non-critical","fault_id":"recbmuynALVGsJkD8","prompt_id":"recbmuynALVGsJkD8_prompt","inspection_id":"c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0","grouping_key":"1_month::c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0"},{"id":"e73f664f-473e-42f6-8095-0c1675f2d876","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.17 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES KITCHEN EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Kitchen exhaust systems","variant":null,"variant_id":"recXTAXJ6j6LIBS3z","item_no":"16.1","prompt":"COMPLETE all monthly service activities as\nlisted in Table 13.4.1.16.","input":null,"possible_fault":"Monthly checks missed","possible_fault_description":"AS1851 2012 TABLE 13.4.1.17 ITEM 16.1 – Monthly checks from Table 13.4.1.16 not completed.","severity_level":"non-conformance","fault_id":"recriJiSUnlfTzpj0","prompt_id":"recriJiSUnlfTzpj0_prompt","inspection_id":"c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0"},{"id":"f4adefe4-c143-4a38-a392-06fce4ce9ca8","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.17 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES KITCHEN EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Kitchen exhaust systems","variant":null,"variant_id":"recXTAXJ6j6LIBS3z","item_no":"16.3","prompt":"CHECK for excessive leaks or damage to\ngrease-arresting filters, and REPLACE as\nnecessary.\nNOTE: Non-metallic grease filters and other\nspecial types have to be replaced at specific\ntime intervals whether damaged or not. In\nthese cases, follow manufacturer’s\ninstructions.","input":null,"possible_fault":"Leaking or expired filters","possible_fault_description":"AS1851 2012 TABLE 13.4.1.17 ITEM 16.3 – Grease filters leaking or past service life.","severity_level":"non-critical","fault_id":"recYJqUcXrzvZQtee","prompt_id":"recYJqUcXrzvZQtee_prompt","inspection_id":"c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recXTAXJ6j6LIBS3z_recWW5NwfZ6Coenk0"}]},{"id":"recZ1U9gFhSsdvLVo","name":"System shutdown","checklist":[{"id":"7bc7bc23-8630-44b2-a3d9-48d4c74f4521","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.8 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SYSTEM SHUTDOWN","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"System shutdown","variant":null,"variant_id":"recZ1U9gFhSsdvLVo","item_no":"7.1","prompt":"SIMULATE a fire/smoke situation from any device\nsuch as a sprinkler, heat or smoke detector, to effect\nshutdown of all mechanical ventilation systems not\nrequired to operate in fire mode.\nCHECK all systems required to shut down are not\noperating (see Appendices H and I).","input":null,"possible_fault":"System continues running in fire mode","possible_fault_description":"AS1851 TABLE 13.4.2.8 ITEM 7.1 – Non-fire mode ventilation fails to shut down.","severity_level":"non-critical","fault_id":"recpd2GGSDl8mgCEn","prompt_id":"recpd2GGSDl8mgCEn_prompt","inspection_id":"c_recZ1U9gFhSsdvLVo_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recZ1U9gFhSsdvLVo_recWW5NwfZ6Coenk0"}]},{"id":"reczmXK0WrIpxuI0s","name":"Mechanical and intumescent fire dampers","checklist":[{"id":"298a408a-73b1-49ca-ac75-49132c72fd40","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Mechanical and intumescent fire dampers","variant":null,"variant_id":"reczmXK0WrIpxuI0s","item_no":"3.7","prompt":"REPLACE all fusible links throughout the building\n every 25 years from the date of manufacture.\n Commencing after 25 years, replace 20% per year\n over the 5 year routine service cycle.","input":null,"possible_fault":"Link > 25 years old","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.7 – Old links may degrade and fail during an emergency.","severity_level":"recommendation","fault_id":"recMkVHsHAJHVifAD","prompt_id":"recMkVHsHAJHVifAD_prompt","inspection_id":"c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0"},{"id":"311c3a36-91e5-4aa1-befd-6cb3219f74bf","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Mechanical and intumescent fire dampers","variant":null,"variant_id":"reczmXK0WrIpxuI0s","item_no":"3.1","prompt":"CHECK and ensure that the fire damper is in place,\n open and free from obstruction (see Notes 1 and 2).","input":null,"possible_fault":"Obstructed damper","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.1 – Blockage may prevent proper closure in fire conditions.","severity_level":"critical","fault_id":"rec0juULspaBb6GNo","prompt_id":"rec0juULspaBb6GNo_prompt","inspection_id":"c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0"},{"id":"3aa56f9f-86dc-4006-bbdf-0e8bc8419e8e","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Mechanical and intumescent fire dampers","variant":null,"variant_id":"reczmXK0WrIpxuI0s","item_no":"3.6","prompt":"CHECK the integrity of the surrounding structure\n within the immediate proximity of the fire damper\n (see Notes 1 and 2).","input":null,"possible_fault":"Wall/floor compromised","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.6 – Surrounding damage may let fire/smoke bypass the damper.","severity_level":"critical","fault_id":"recES93l283u2G8mk","prompt_id":"recES93l283u2G8mk_prompt","inspection_id":"c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0"},{"id":"57854027-0970-4e92-811a-938f0326fab7","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Mechanical and intumescent fire dampers","variant":null,"variant_id":"reczmXK0WrIpxuI0s","item_no":"3.5","prompt":"CHECK for signs of tampering or modifications. The\n responsible entity shall confirm that modifications\n comply with the manufacturer’s requirements or a\n registered testing authority’s confirmation of\n operation (see Notes 1 and 2).","input":null,"possible_fault":"Tampering or changes","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.5 – Unverified changes may void compliance or cause failure.","severity_level":"non-conformance","fault_id":"recxRF3eKZb9Dg8lI","prompt_id":"recxRF3eKZb9Dg8lI_prompt","inspection_id":"c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0"},{"id":"594c9c8b-64ad-4f36-8eac-27c54f5aab14","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Mechanical and intumescent fire dampers","variant":null,"variant_id":"reczmXK0WrIpxuI0s","item_no":"3.2","prompt":"For mechanical fire dampers, remove or release the\n fusible link to ensure closure (and latching) (see\n Notes 1 and 2).","input":null,"possible_fault":"Fails to close or latch","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.2 – Non-operational link may prevent fire isolation.","severity_level":"critical","fault_id":"rec6dmZVB42bFQ91l","prompt_id":"rec6dmZVB42bFQ91l_prompt","inspection_id":"c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0"},{"id":"8772ba28-1472-4222-a025-6ebd7d51f1af","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Mechanical and intumescent fire dampers","variant":null,"variant_id":"reczmXK0WrIpxuI0s","item_no":"3.3","prompt":"CHECK and ensure that the fire damper is in place,\n free from obstruction and is capable of operation (see\n Notes 1, 2, 3 and 4).","input":null,"possible_fault":"Jammed or blocked","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.3 – Blocked blades may prevent expansion during fire.","severity_level":"critical","fault_id":"reclk8eoFH7X6Qpm2","prompt_id":"reclk8eoFH7X6Qpm2_prompt","inspection_id":"c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0"},{"id":"ddcd6562-b870-476b-8d19-4c60be51b273","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.4 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES FIRE DAMPERS AND SMOKE DAMPERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Mechanical and intumescent fire dampers","variant":null,"variant_id":"reczmXK0WrIpxuI0s","item_no":"3.4","prompt":"CHECK fire dampers, including casing, retaining\n flanges and fusible links, for corrosion. The extent of\n corrosion shall not impede damper operation or\n prevent it remaining in place until the next inspection\n (5 years) (see Notes 1, 2, 3 and 5).","input":null,"possible_fault":"Rust or surface corrosion","possible_fault_description":"AS1851 2012 TABLE 13.4.1.4 ITEM 3.4 – Corrosion may impair movement or cause part failure.","severity_level":"non-critical","fault_id":"rec7N5jiPYwilR6HR","prompt_id":"rec7N5jiPYwilR6HR_prompt","inspection_id":"c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczmXK0WrIpxuI0s_recWW5NwfZ6Coenk0"}]},{"id":"reczwjpBSwKxfPEyW","name":"Smoke exhaust systems","checklist":[{"id":"00829f73-749c-4142-babe-5f594a7edad0","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.6 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE EXHAUST SYSTEMS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Smoke exhaust systems","variant":null,"variant_id":"reczwjpBSwKxfPEyW","item_no":"5.2","prompt":"SWITCH all systems back to ‘normal’ and check that\nall equipment and indicator lamps are in the correct\nnon-fire mode (see Appendices H and I).","input":null,"possible_fault":"System remains in fire mode","possible_fault_description":"AS1851 TABLE 13.4.2.6 ITEM 5.2 – System fails to revert to non-fire mode.","severity_level":"non-critical","fault_id":"recxDLe7ZT3yLiJVl","prompt_id":"recxDLe7ZT3yLiJVl_prompt","inspection_id":"c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0"},{"id":"2ecbed2b-0e74-4eb2-9721-99b2c9b55d5b","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.7 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke exhaust systems","variant":null,"variant_id":"reczwjpBSwKxfPEyW","item_no":"6.1","prompt":"COMPLETE all three-monthly test activities as\nlisted in Table 13.4.2.6.","input":null,"possible_fault":"Partial or incomplete test execution","possible_fault_description":"AS1851 TABLE 13.4.2.7 ITEM 6.1 – Not all 3-monthly tests completed.","severity_level":"non-conformance","fault_id":"recHmKdS8JW1QgpuZ","prompt_id":"recHmKdS8JW1QgpuZ_prompt","inspection_id":"c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0"},{"id":"3515c458-2e44-4f80-b2cf-f9f42d5716cb","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.7 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke exhaust systems","variant":null,"variant_id":"reczwjpBSwKxfPEyW","item_no":"6.2","prompt":"(b) Indicator lamps change status when fan starts\nor stops.","input":null,"possible_fault":"Lamps do not indicate status change","possible_fault_description":"AS1851 TABLE 13.4.2.7 ITEM 6.2b – Fan status indicators not working.","severity_level":"non-critical","fault_id":"rec9hlWW4nw6VkES3","prompt_id":"rec9hlWW4nw6VkES3_prompt","inspection_id":"c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0"},{"id":"36738c96-e2c2-4f1e-b3e6-a78992dcdd91","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.7 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke exhaust systems","variant":null,"variant_id":"reczwjpBSwKxfPEyW","item_no":"6.2","prompt":"CHECK:\n(a) Exhaust airflow rate from the space.","input":null,"possible_fault":"Low or no airflow rate","possible_fault_description":"AS1851 TABLE 13.4.2.7 ITEM 6.2a – Insufficient airflow in fire mode.","severity_level":"critical","fault_id":"recva32nFVqZ5Sz6k","prompt_id":"recva32nFVqZ5Sz6k_prompt","inspection_id":"c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0"},{"id":"429379ae-fa9e-4791-94e9-0f24abab54f8","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.7 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke exhaust systems","variant":null,"variant_id":"reczwjpBSwKxfPEyW","item_no":"6.2","prompt":"d) The maximum noise level in the space.\nNOTE: In some installations maximum noise\ncriteria may not be specified.","input":null,"possible_fault":"Exceeds acceptable noise level","possible_fault_description":"AS1851 TABLE 13.4.2.7 ITEM 6.2d – Noise exceeds design threshold.","severity_level":"non-critical","fault_id":"rec260oR4lwzYYXMK","prompt_id":"rec260oR4lwzYYXMK_prompt","inspection_id":"c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0"},{"id":"cb71ef6a-bf1d-4dd6-a2a5-90dba8f9f260","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.7 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke exhaust systems","variant":null,"variant_id":"reczwjpBSwKxfPEyW","item_no":"6.2","prompt":"(c) That operation of the manual switch provided\nfor fire brigade personnel starts and stops\nsmoke exhaust fans.","input":null,"possible_fault":"Switch fails to operate fan","possible_fault_description":"AS1851 TABLE 13.4.2.7 ITEM 6.2c – Manual switch for fan non-functional.","severity_level":"non-critical","fault_id":"recwnsDescMaLLoDW","prompt_id":"recwnsDescMaLLoDW_prompt","inspection_id":"c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0"},{"id":"ed7982be-a706-4a41-a436-ea649efe19e6","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.6 THREE-MONTHLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE EXHAUST SYSTEMS","inspection_period":"3_month","inspection_period_frequency":3,"inspection_period_interval":"month","inspection_period_in_days":90,"asset_type":"Smoke exhaust systems","variant":null,"variant_id":"reczwjpBSwKxfPEyW","item_no":"5.1","prompt":"SIMULATE a fire/smoke situation by activation from\nthe FIP, to effect operation of the smoke exhaust\nsystem and all other systems required to operate in fire\nmode. Check fans, dampers, automatic doors and\nindicator lamps operate in fire mode as documented\n(see Appendices H and I). Check for excessive noise\nand correct movement of air.","input":null,"possible_fault":"No airflow or excessive noise","possible_fault_description":"AS1851 TABLE 13.4.2.6 ITEM 5.1 – Smoke exhaust not operating correctly.","severity_level":"non-critical","fault_id":"recGMaifL7XVASlcT","prompt_id":"recGMaifL7XVASlcT_prompt","inspection_id":"c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0","grouping_key":"3_month::c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0"},{"id":"f62a8aa1-9691-4c48-9453-f87f89e90f58","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.7 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke exhaust systems","variant":null,"variant_id":"reczwjpBSwKxfPEyW","item_no":"6.3","prompt":"SWITCH all systems back to ‘normal’ and check\nthat all equipment and indicator lamps are in the\ncorrect non-fire mode (see Appendices H and I).","input":null,"possible_fault":"System still operates in fire mode","possible_fault_description":"AS1851 TABLE 13.4.2.7 ITEM 6.3 – Normal mode not restored.","severity_level":"informational","fault_id":"recNwGWZHiChhHAPE","prompt_id":"recNwGWZHiChhHAPE_prompt","inspection_id":"c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0"},{"id":"fb93159b-bc05-49b7-b899-f3321cb6578e","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.2.7 YEARLY TEST AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES SMOKE EXHAUST SYSTEMS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"Smoke exhaust systems","variant":null,"variant_id":"reczwjpBSwKxfPEyW","item_no":"6.2","prompt":"CONDUCT a simulation of a fire/smoke situation\nfrom any device such as a sprinkler, heat or smoke\ndetector, to effect operation of the smoke exhaust\nsystem and all other systems required to operate in\nfire mode. Check fans, dampers, automatic doors\nand indicator lamps operate in fire mode as\ndocumented (see Appendices H and I).","input":null,"possible_fault":"Smoke exhaust not triggered; doors or fans fail to operate","possible_fault_description":"AS1851 TABLE 13.4.2.7 ITEM 6.2 – Simulation fails to activate exhaust systems.","severity_level":"critical","fault_id":"recrNQDmvZPQbIobn","prompt_id":"recrNQDmvZPQbIobn_prompt","inspection_id":"c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reczwjpBSwKxfPEyW_recWW5NwfZ6Coenk0"}]}],"other_checklist_items":[{"id":"09d39546-b3e0-42a4-b270-83cddc9d487a","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.7","prompt":"(a) REMOVE any foreign matter from the blades.","input":null,"possible_fault":"Blades obstructed","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.7 – Foreign matter restricts vent blade movement.","severity_level":"non-critical","fault_id":"recelxacjGn5A8kDt","prompt_id":"recelxacjGn5A8kDt_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"15f9a7b7-bf5c-4a64-a049-93724e2f52b8","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.6 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—RECYCLE AIR, RELIEF AIR, SMOKE SPILL AND OUTDOOR AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—recycle air, relief air, smoke spill and outdoor air\"","variant":null,"variant_id":"recHD7M5vlcA8Wep9","item_no":"5.2","prompt":"ENSURE damper(s) moves to its fire mode position\nupon removal of power source.","input":null,"possible_fault":"Damper fails fire mode","possible_fault_description":"AS1851 2012 TABLE 13.4.1.6 ITEM 5.2 – Damper does not reach fire-safe position upon power loss","severity_level":"critical","fault_id":"rec1VcZmwJ0FHGzX6","prompt_id":"rec1VcZmwJ0FHGzX6_prompt","inspection_id":"c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0"},{"id":"19b43d56-4936-4323-8437-b3ad387e818d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.14 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"13.4","prompt":"CHECK all control centres and supply lines for\ndamage or deterioration.","input":null,"possible_fault":"Cracked or deteriorated supply lines","possible_fault_description":"AS1851 2012 TABLE 13.4.1.14 ITEM 13.4 – Control centres or lines are damaged or degraded.","severity_level":"critical","fault_id":"rec2Fqv4XLOjwU14h","prompt_id":"rec2Fqv4XLOjwU14h_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"2066ba82-7d67-4ab2-aff8-76cbf3519f0f","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.14 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"13.1","prompt":"COMPLETE all six-monthly service activities as\nlisted in Table 13.4.1.12.","input":null,"possible_fault":"Missed 6-monthly checks","possible_fault_description":"AS1851 2012 TABLE 13.4.1.14 ITEM 13.1 – Six-monthly tests missed or not properly completed.","severity_level":"non-conformance","fault_id":"recHnHx9JsZZ4A7mM","prompt_id":"recHnHx9JsZZ4A7mM_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"22edfc26-15c6-4148-8967-a157b6eb6b40","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.1","prompt":"CHECK the control centre (and in the case of\npneumatic actuators, the air supply) for signs of\ndamage.","input":null,"possible_fault":"Control centre damaged","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.1 – Control centre or air supply visibly damaged or tampered.","severity_level":"critical","fault_id":"rec2CU0QjzkWRCUWO","prompt_id":"rec2CU0QjzkWRCUWO_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"250ffef5-cbf5-44d8-bfb6-c3bf7976e21f","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.3.3 YEARLY SURVEY AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS (WINDOWS AND SHUTTERS)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"2.2","prompt":"CHECK inlet openings to ensure there have not been\nany major structural alterations that could inhibit their\nfunction.","input":null,"possible_fault":"Opening obstructed or altered","possible_fault_description":"AS1851 TABLE 13.4.3.3 ITEM 2.2 – Inlet openings obstructed or altered.","severity_level":"non-critical","fault_id":"rec8NVjZ7xlSc5D2l","prompt_id":"rec8NVjZ7xlSc5D2l_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"2b042c29-8303-4a6f-9d58-4e41e96e3ef5","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.8 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—SUPPLY, RETURN AND EXHAUST AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—Supply, return and exhaust air\"","variant":null,"variant_id":"reckO73o3q9J2ScAK","item_no":"7.5","prompt":"CHECK dampers for corrosion.\nNOTE: Corrosion may adversely affect the\noperation of the damper.","input":null,"possible_fault":"Corroded damper","possible_fault_description":"AS1851 2012 TABLE 13.4.1.8 ITEM 7.5 – Metal rust compromises structure or inhibits function","severity_level":"non-critical","fault_id":"recdv365E8psARefA","prompt_id":"recdv365E8psARefA_prompt","inspection_id":"c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0"},{"id":"2b44b2a0-2d89-4872-903d-2e8a9ad2425d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.14 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"13.7","prompt":"REPLACE all fusible links throughout the building\nevery 25 years from the date of manufacture.","input":null,"possible_fault":"Expired fusible links","possible_fault_description":"AS1851 2012 TABLE 13.4.1.14 ITEM 13.7 – Fusible links are over 25 years old.","severity_level":"recommendation","fault_id":"recWIVsPV9Gd3IJim","prompt_id":"recWIVsPV9Gd3IJim_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"2c7dfb83-2dfe-4b60-af94-ac786ae05957","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.5","prompt":"CHECK battery backup supply where power is\nrequired to operate system.","input":null,"possible_fault":"Backup supply faulty","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.5 – Battery does not supply backup power or fails to hold charge.","severity_level":"critical","fault_id":"recNH66tb3uu4l5wH","prompt_id":"recNH66tb3uu4l5wH_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"30771dc7-daa0-46b1-80f5-52847da430a9","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.7 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—SUPPLY, RETURN AND EXHAUST AIR","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Air control dampers—Supply, return and exhaust air\"","variant":null,"variant_id":"reckO73o3q9J2ScAK","item_no":"6.1","prompt":"CHECK that the damper is capable of operating from \nfully open to fully closed, and is clear of obstructions. \nWhere the damper is not required to fully open or \nclose, check that it is capable of operating between \nmaximum and minimum positions. \n \n NOTE: Increase frequency to three-monthly if \ndampers are dedicated to fire mode duty only and \nare exposed to the corrosive effects of exterior air","input":null,"possible_fault":"Incomplete movement","possible_fault_description":"AS1851 2012 TABLE 13.4.1.7 ITEM 6.1 – Damper fails to reach designated open/close positions","severity_level":"non-critical","fault_id":"rec5458PHsMnZLIFG","prompt_id":"rec5458PHsMnZLIFG_prompt","inspection_id":"c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0"},{"id":"32147957-360c-4b90-b54b-b52969d77173","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.14 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"13.2","prompt":"CHECK all vents and connecting air lines to\nascertain unauthorized alterations, damage or\ncorrosion.","input":null,"possible_fault":"Lines damaged or corroded","possible_fault_description":"AS1851 2012 TABLE 13.4.1.14 ITEM 13.2 – Vents or air lines show signs of corrosion or damage.","severity_level":"non-critical","fault_id":"recyf0gw1MkgKXO7F","prompt_id":"recyf0gw1MkgKXO7F_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"3405489a-c7ca-4363-b62d-bc7293423bf8","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.7","prompt":"(b) REMOVE any debris from the internal rain\nchannel.","input":null,"possible_fault":"Blocked channel","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.7 – Internal rainwater channel clogged by debris.","severity_level":"non-critical","fault_id":"recw2rZrNkHRqgyzk","prompt_id":"recw2rZrNkHRqgyzk_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"43a6932e-53fb-406c-b0d4-691be10200dd","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.8","prompt":"CHECK the manual function by operating the\nopen/close manual switch.\nNOTE: Closing times in excess of 20 s should be\ninvestigated.","input":null,"possible_fault":"Manual switch not functioning","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.8 – Open/close manual switch fails to respond or delays action.","severity_level":"non-critical","fault_id":"recmlRfJahGBt8PXs","prompt_id":"recmlRfJahGBt8PXs_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"4c0d57cb-7ad6-42dc-861b-2f5355685c88","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.6","prompt":"CHECK operation under mains failure condition.","input":null,"possible_fault":"No function on power failure","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.6 – Unit fails to operate under simulated mains failure condition.","severity_level":"critical","fault_id":"reccg1a8LFdU3R7IG","prompt_id":"reccg1a8LFdU3R7IG_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"4e204b1f-f932-4b31-b431-297e62eb6ab7","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.8 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—SUPPLY, RETURN AND EXHAUST AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—Supply, return and exhaust air\"","variant":null,"variant_id":"reckO73o3q9J2ScAK","item_no":"7.1","prompt":"COMPLETE all six-monthly service activities as\nlisted in Table 13.4.1.7.","input":null,"possible_fault":"Missed routine tasks","possible_fault_description":"AS1851 2012 TABLE 13.4.1.8 ITEM 7.1 – Six-month service items not verified prior to annual check","severity_level":"non-conformance","fault_id":"rec4YAyMgBPKWyszI","prompt_id":"rec4YAyMgBPKWyszI_prompt","inspection_id":"c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0"},{"id":"4e84444c-aa91-4bfe-9668-25d25f26c588","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.6 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—RECYCLE AIR, RELIEF AIR, SMOKE SPILL AND OUTDOOR AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—recycle air, relief air, smoke spill and outdoor air\"","variant":null,"variant_id":"recHD7M5vlcA8Wep9","item_no":"5.1","prompt":"COMPLETE all six-monthly service activities as\nlisted in Table 13.4.1.5.","input":null,"possible_fault":"Service tasks missed","possible_fault_description":"AS1851 2012 TABLE 13.4.1.6 ITEM 5.1 – Failure to perform required half-yearly checks affects annual compliance","severity_level":"non-conformance","fault_id":"rec9oiksMKDKcRoB8","prompt_id":"rec9oiksMKDKcRoB8_prompt","inspection_id":"c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0"},{"id":"5218d9a9-0dac-4cff-98f2-cec94075991e","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.4","prompt":"CHECK system pressure against manufacturer’s\nrequirements, and RECORD.\nNOTE: The frequency of filter inspection and\nservice could vary depending on usage and the\nquantity of supplied air. Fluid should be drained\nfrom the filter bowl before fluid reaches the filter\nelement.","input":null,"possible_fault":"Incorrect pressure","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.4 – System pressure is outside manufacturer-specified range.","severity_level":"non-critical","fault_id":"recwhYr56J4dPH4VN","prompt_id":"recwhYr56J4dPH4VN_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"52716b2f-8c95-4b52-83b0-56ed94edd4b4","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.7","prompt":"(c) CHECK that the drain holes are clear.","input":null,"possible_fault":"Drain holes blocked","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.7 – Drain holes obstructed causing water to pool inside vents.","severity_level":"non-critical","fault_id":"rec4Hv6oOPLkkSGD1","prompt_id":"rec4Hv6oOPLkkSGD1_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"58cae728-6629-4f98-8369-d83ac0ae013a","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.3.3 YEARLY SURVEY AND RECORDS SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS (WINDOWS AND SHUTTERS)","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"2.1","prompt":"CHECK draught curtain areas to ensure there have not\nbeen any major alterations or additions that could\ninhibit their function.\nCHECK inlet openings to ensure there have not been\nany major structural alterations that could inhibit their\nfunction.","input":null,"possible_fault":"Curtain modified or inlet blocked","possible_fault_description":"AS1851 TABLE 13.4.3.3 ITEM 2.1 – Draught curtain/inlet functionality impaired.","severity_level":"non-critical","fault_id":"recryVCeE9Q7kyXUs","prompt_id":"recryVCeE9Q7kyXUs_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"5a1bd6ec-4840-4679-be30-eb383737fca4","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.6 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—RECYCLE AIR, RELIEF AIR, SMOKE SPILL AND OUTDOOR AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—recycle air, relief air, smoke spill and outdoor air\"","variant":null,"variant_id":"recHD7M5vlcA8Wep9","item_no":"5.4","prompt":"CHECK linkage and damper bearings.","input":null,"possible_fault":"Bearing issues found","possible_fault_description":"AS1851 2012 TABLE 13.4.1.6 ITEM 5.4 – Bearings/linkages damaged or worn, reducing movement reliability","severity_level":"non-critical","fault_id":"recsFj82YZcEB6zCj","prompt_id":"recsFj82YZcEB6zCj_prompt","inspection_id":"c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0"},{"id":"5ace59d7-3a26-485c-a22a-e1e2c1de447f","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.6 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—RECYCLE AIR, RELIEF AIR, SMOKE SPILL AND OUTDOOR AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—recycle air, relief air, smoke spill and outdoor air\"","variant":null,"variant_id":"recHD7M5vlcA8Wep9","item_no":"5.3","prompt":"CHECK that there is no excessive leakage past\ndampers when in the closed position (only where\ndampers are required to close fully).","input":null,"possible_fault":"Excessive leakage","possible_fault_description":"AS1851 2012 TABLE 13.4.1.6 ITEM 5.3 – Excess air leaks through damper when in closed position","severity_level":"non-critical","fault_id":"rec5dOA7ZHXKW9jjw","prompt_id":"rec5dOA7ZHXKW9jjw_prompt","inspection_id":"c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0"},{"id":"62235cf7-3778-464a-9bcd-2da5b8e3cadd","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.2","prompt":"CHECK the power supply indicator is functioning.","input":null,"possible_fault":"Power indicator not working","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.2 – Power indicator light is off or not showing status.","severity_level":"non-critical","fault_id":"recbMIazrNqSYdHqq","prompt_id":"recbMIazrNqSYdHqq_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"6e41299b-8333-42a6-8cad-d54059b5690f","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.9","prompt":"CLEAN or REPLACE the filter element. If any\ndamage or fault is discovered, correct immediately.","input":null,"possible_fault":"Filter dirty or damaged","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.9 – Air filter element dirty, damaged or overdue for replacement.","severity_level":"non-critical","fault_id":"recfBuC9b4BDyHaDm","prompt_id":"recfBuC9b4BDyHaDm_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"760ee792-74af-4315-a05f-41e5baab8367","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.14 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"13.6","prompt":"ENSURE installation plans include current\ninformation.","input":null,"possible_fault":"Plans outdated","possible_fault_description":"AS1851 2012 TABLE 13.4.1.14 ITEM 13.6 – Installation plans are outdated or incorrect.","severity_level":"non-conformance","fault_id":"recwPecqcMMBjfqWL","prompt_id":"recwPecqcMMBjfqWL_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"9cb09e36-4274-4146-b5b4-465d3db29580","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.7","prompt":"(d) CHECK the vents for signs of damage, wear\nand tear or corrosion.","input":null,"possible_fault":"Damage or corrosion found","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.7 – Vents show signs of wear, corrosion or structural defects.","severity_level":"non-critical","fault_id":"recFZ7ZApaWPhrbjq","prompt_id":"recFZ7ZApaWPhrbjq_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"a9b236f0-82f4-4f26-816d-366cd87a592d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.5 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—RECYCLE AIR, RELIEF AIR, SMOKE SPILL AND OUTDOOR AIR","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Air control dampers—recycle air, relief air, smoke spill and outdoor air\"","variant":null,"variant_id":"recHD7M5vlcA8Wep9","item_no":"4.1","prompt":"CHECK that the damper is capable of operating from\n fully open to fully closed, and is clear of obstructions.\n Where the damper is not required to fully open or close,\n check that it is capable of operating between maximum\n and minimum positions.\n NOTE: Increase frequency to three-monthly if dampers\n are dedicated to fire mode duty only and are exposed\n to the corrosive effects of exterior air.","input":null,"possible_fault":"Damper fails full range","possible_fault_description":"AS1851 2012 TABLE 13.4.1.5 ITEM 4.1 – Damper cannot open/close as required due to obstruction or jamming","severity_level":"critical","fault_id":"recCM2p0SfA3eDT7K","prompt_id":"recCM2p0SfA3eDT7K_prompt","inspection_id":"c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0"},{"id":"ae56ccd4-c9b8-4396-a42e-327b597a18ff","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.8 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—SUPPLY, RETURN AND EXHAUST AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—Supply, return and exhaust air\"","variant":null,"variant_id":"reckO73o3q9J2ScAK","item_no":"7.3","prompt":"CHECK that there is no excessive leakage past\ndampers when in the closed position (only where\ndampers are required to close fully).","input":null,"possible_fault":"Leak under closure","possible_fault_description":"AS1851 2012 TABLE 13.4.1.8 ITEM 7.3 – Damper leaks air despite being in full close position","severity_level":"non-critical","fault_id":"recx5O7ZTEmDyUfJl","prompt_id":"recx5O7ZTEmDyUfJl_prompt","inspection_id":"c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0"},{"id":"b40ba359-9904-4198-8ca4-54ab883a82bf","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.6 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—RECYCLE AIR, RELIEF AIR, SMOKE SPILL AND OUTDOOR AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—recycle air, relief air, smoke spill and outdoor air\"","variant":null,"variant_id":"recHD7M5vlcA8Wep9","item_no":"5.5","prompt":"CHECK dampers for corrosion.\nNOTE: Corrosion may adversely affect the\noperation of the damper.","input":null,"possible_fault":"Corrosion evident","possible_fault_description":"AS1851 2012 TABLE 13.4.1.6 ITEM 5.5 – Rusting present on damper surfaces, may impact operation","severity_level":"non-critical","fault_id":"recseWvmZiRyTmUt6","prompt_id":"recseWvmZiRyTmUt6_prompt","inspection_id":"c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0"},{"id":"c798db10-e157-49a4-8b72-edbfdb3234f7","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.8 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—SUPPLY, RETURN AND EXHAUST AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—Supply, return and exhaust air\"","variant":null,"variant_id":"reckO73o3q9J2ScAK","item_no":"7.2","prompt":"ENSURE damper(s) moves to its required failure\nmode position upon removal of power source.","input":null,"possible_fault":"Fails safe position","possible_fault_description":"AS1851 2012 TABLE 13.4.1.8 ITEM 7.2 – Damper does not shift to fail-safe mode when power removed","severity_level":"critical","fault_id":"rec5KHjkjTzgwjji4","prompt_id":"rec5KHjkjTzgwjji4_prompt","inspection_id":"c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0"},{"id":"d08842d4-ecc9-4c6f-acd1-05fca5db4f6d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.14 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"13.3","prompt":"If equipped, CHECK the fusible release links for\ntype and temperature rating and replace release links\nthat have been coated with paint or similar coatings.","input":null,"possible_fault":"Links painted or wrong spec","possible_fault_description":"AS1851 2012 TABLE 13.4.1.14 ITEM 13.3 – Painted or incorrect type/temp rating fusible links.","severity_level":"non-conformance","fault_id":"recSEFNGtmvTmJOOA","prompt_id":"recSEFNGtmvTmJOOA_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"d450cfef-b637-48cb-bbe7-5af726bbdc18","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.7","prompt":"(e) ENSURE cylinder ram dust covers are in place.","input":null,"possible_fault":"Dust covers missing","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.7 – Cylinder dust covers are not present or improperly fitted.","severity_level":"non-critical","fault_id":"rectcE8V2fuc26G30","prompt_id":"rectcE8V2fuc26G30_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"d77050d2-220c-4adc-a991-0c088dd3f2c6","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.13 SIX-MONTHLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"6_month","inspection_period_frequency":6,"inspection_period_interval":"month","inspection_period_in_days":180,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"12.3","prompt":"DRAIN any fluid that has accumulated in the air\nfilter.\nNOTE: Solvents should not be used.","input":null,"possible_fault":"Fluid in filter bowl","possible_fault_description":"AS1851 2012 TABLE 13.4.1.13 ITEM 12.3 – Fluid buildup in filter bowl could block air or damage unit.","severity_level":"non-critical","fault_id":"recpdZPBJZk3m51x5","prompt_id":"recpdZPBJZk3m51x5_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"6_month::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"e1511385-3b37-4055-ba09-1b9c1466627d","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.6 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—RECYCLE AIR, RELIEF AIR, SMOKE SPILL AND OUTDOOR AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—recycle air, relief air, smoke spill and outdoor air\"","variant":null,"variant_id":"recHD7M5vlcA8Wep9","item_no":"5.6","prompt":"If motors are pneumatic, CHECK for air leaks in\nthe air lines and connections.","input":null,"possible_fault":"Air line leakage","possible_fault_description":"AS1851 2012 TABLE 13.4.1.6 ITEM 5.6 – Pneumatic supply has visible air leaks at joints or valves","severity_level":"non-critical","fault_id":"recO5VBN9Gtm4xaJp","prompt_id":"recO5VBN9Gtm4xaJp_prompt","inspection_id":"c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recHD7M5vlcA8Wep9_recWW5NwfZ6Coenk0"},{"id":"e8eeaa87-2d0c-4164-b723-1a9f7b7afd87","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.14 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES MOTORIZED RELIEF OPENINGS, WINDOWS AND SHUTTERS","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Motorized relief openings, windows and shutters\"","variant":null,"variant_id":"recBWgH7naCbYbxsO","item_no":"13.5","prompt":"ENSURE all relief openings, windows and shutters\noperate open and close in accordance with the\nsystem requirements. (Refer Appendix I.)","input":null,"possible_fault":"Shutters not operating properly","possible_fault_description":"AS1851 2012 TABLE 13.4.1.14 ITEM 13.5 – Opening/closing fails or not per system specs.","severity_level":"critical","fault_id":"recLWzsZrJhlKulVa","prompt_id":"recLWzsZrJhlKulVa_prompt","inspection_id":"c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_recBWgH7naCbYbxsO_recWW5NwfZ6Coenk0"},{"id":"eaef6fac-baad-4b5f-9c74-4bebe04b092b","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.8 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—SUPPLY, RETURN AND EXHAUST AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—Supply, return and exhaust air\"","variant":null,"variant_id":"reckO73o3q9J2ScAK","item_no":"7.6","prompt":"If motors are pneumatic, CHECK for air leaks in the\nair lines and connections.","input":null,"possible_fault":"Pneumatic leak detected","possible_fault_description":"AS1851 2012 TABLE 13.4.1.8 ITEM 7.6 – Compressed air system has leaks causing inconsistent damper control","severity_level":"non-critical","fault_id":"recZdBwgNlnGLaY4e","prompt_id":"recZdBwgNlnGLaY4e_prompt","inspection_id":"c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0"},{"id":"eaf83bd8-bcb5-4907-aa32-1b5301adb281","standard_code":"au_as_1851_2012","version":"full","category":"Fire and Smoke Control Features of Mechanical Services (Smoke Hazard Management System)","category_id":"recWW5NwfZ6Coenk0","group_header":"TABLE 13.4.1.8 YEARLY ROUTINE SERVICE SCHEDULE FIRE AND SMOKE CONTROL FEATURES OF MECHANICAL SERVICES AIR CONTROL DAMPERS—SUPPLY, RETURN AND EXHAUST AIR","inspection_period":"1_year","inspection_period_frequency":1,"inspection_period_interval":"year","inspection_period_in_days":365,"asset_type":"\"Air control dampers—Supply, return and exhaust air\"","variant":null,"variant_id":"reckO73o3q9J2ScAK","item_no":"7.4","prompt":"CHECK linkage and damper bearings.","input":null,"possible_fault":"Worn linkages/bearings","possible_fault_description":"AS1851 2012 TABLE 13.4.1.8 ITEM 7.4 – Mechanical wear affects performance of damper movement","severity_level":"non-critical","fault_id":"recRYgPkzghawAu8f","prompt_id":"recRYgPkzghawAu8f_prompt","inspection_id":"c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0","grouping_key":"1_year::c_reckO73o3q9J2ScAK_recWW5NwfZ6Coenk0"}]}],"uncategorised_checklist_items":[],"prompt_sets":[{"name":"2012: Emergency Plans and Training","prompts":[{"id":1131,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 14.4.2 (Six-monthly)","help_text":"AS1851-2012 Table 14.4.2 (Six-monthly)","sort_order":1,"ref":"1","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1132,"active":true,"required":false,"type":"REMARK","label":"Emergency control organization (ECO) - Inspect plan","help_text":"INSPECT the ECO list and check for compliance with the emergency plan.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1133,"active":true,"required":false,"type":"REMARK","label":"Emergency evacuation equipment","help_text":"INSPECT the emergency evacuation equipment and check for compliance with the emergency plan.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1134,"active":true,"required":false,"type":"REMARK","label":"Training","help_text":"INSPECT training records and check for compliance with the emergency plan.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1135,"active":true,"required":false,"type":"REMARK","label":"Emergency control organization (ECO ) - Test procedures","help_text":"TEST the ECO for relevance to the facility by initiating an alarm and checking the response for compliance with the emergency procedures.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1136,"active":true,"required":false,"type":"REMARK","label":"Evacuation diagrams","help_text":"INSPECT the emergency response diagrams for relevancy and check for compliance with the emergency plan.","sort_order":6,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1137,"active":true,"required":false,"type":"REMARK","label":"Assembly areas","help_text":"INSPECT the nominated assembly area(s) and test for relevance to the facility and compliance with the emergency plan.","sort_order":7,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1138,"active":true,"required":false,"type":"REMARK","label":"Emergency response procedures","help_text":"INSPECT the emergency procedures testing for relevancy to the facility or to a nominated incident covered by the emergency procedures by conducting an evacuation exercise.","sort_order":8,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1139,"active":true,"required":false,"type":"REMARK","label":"AS1851-2012 Table 14.4.214.4.3 (Annual)","help_text":"AS1851-2012 Table 14.4.214.4.3 (Annual)","sort_order":9,"ref":"2","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1140,"active":true,"required":false,"type":"REMARK","label":"Emergency plan","help_text":"INSPECT the emergency plan and check for relevancy to the facility.","sort_order":10,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1141,"active":true,"required":false,"type":"REMARK","label":"Evacuation exercise","help_text":"INSPECT evacuation exercise records and check for compliance with the emergency plan.","sort_order":11,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Emergency Plans and Training","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","prompts":[{"id":1181,"active":true,"required":false,"type":"HEADER","label":"13.4.3.2 Active fire and smoke control systems—Yearly","help_text":"13.4.3.2 Active fire and smoke control systems—Yearly","sort_order":1,"ref":"1.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1182,"active":true,"required":false,"type":"REMARK","label":"CHECK - System","help_text":"CHECK for physical impediments that may impair safe operation of smoke control systems comprising exit pressurization systems, smoke exhaust systems, changeover systems and system shutdown.","sort_order":2,"ref":"1.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1183,"active":true,"required":false,"type":"REMARK","label":"CHECK - Alterations","help_text":"CHECK to ensure mechanical services additions and removals, building work, or unintentional obstructions have not affected the functionality or performance of the original design.","sort_order":3,"ref":"1.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1184,"active":true,"required":false,"type":"HEADER","label":"6.4.1.4 -  Additional Activities (Smoke Hazard Management Systems) - Yearly Service","help_text":"6.4.1.4 -  Additional Activities (Smoke Hazard Management Systems) - Yearly Service","sort_order":4,"ref":"3.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1185,"active":true,"required":false,"type":"REMARK","label":"CHECK - FFCP latching and reset","help_text":"CHECK that after initiation by a signal from the FIP, the FFCP remains operating in the fire mode until reset by the reset switch on the FFCP.","sort_order":5,"ref":"3.19","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1186,"active":true,"required":false,"type":"REMARK","label":"CHECK - Manual override controls","help_text":"CHECK that manual override ON-AUTO-OFF control operates.\n\n ** NOTE: ** Manual override should function in normal mode and fire mode.","sort_order":6,"ref":"3.20","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1187,"active":true,"required":false,"type":"REMARK","label":"CHECK - Airflow fault indicator","help_text":"CHECK the operation of the airflow fault indicator","sort_order":7,"ref":"3.21","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1188,"active":true,"required":false,"type":"REMARK","label":"CHECK - Open-circuit fault indicator","help_text":"CHECK the operation of the air-handling equipment interconnecting cable open-circuit fault indicator.","sort_order":8,"ref":"3.22","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1189,"active":true,"required":false,"type":"REMARK","label":"CHECK - Closed-circuit fault indicator","help_text":"CHECK the operation of the air-handling equipment interconnecting cable closed-circuit fault indicator.","sort_order":9,"ref":"3.23","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1190,"active":true,"required":false,"type":"REMARK","label":"CHECK - Electrical","help_text":"CHECK the operation of the electricity phasefail fault indicator.","sort_order":10,"ref":"3.24","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1191,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fan-running indicator","help_text":"CHECK the operation of the fan-running indicator.","sort_order":11,"ref":"3.25","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1192,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fan-stopped indicator","help_text":"CHECK the operation of the fan-stopped indicator.","sort_order":12,"ref":"3.26","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1193,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fan fault indicator","help_text":"CHECK the operation of the fan-fault indicator.","sort_order":13,"ref":"3.27","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Active Fire and Smoke Control System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","prompts":[{"id":1414,"active":true,"required":false,"type":"HEADER","label":"13.4.1.5 Air control dampers—Recycle air, relief air, smoke spill and outdoor air—Six-monthly","help_text":"13.4.1.5 Air control dampers—Recycle air, relief air, smoke spill and outdoor air—Six-monthly","sort_order":1,"ref":"4.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1416,"active":true,"required":false,"type":"HEADER","label":"13.4.1.6 Air control dampers—Recycle air, relief air, smoke spill and outdoor air—Yearly","help_text":"13.4.1.6 Air control dampers—Recycle air, relief air, smoke spill and outdoor air—Yearly","sort_order":1,"ref":"5.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1430,"active":true,"required":false,"type":"HEADER","label":"13.4.1.5 Air control dampers—Recycle air, relief air, smoke spill and outdoor air—Six-monthly","help_text":"13.4.1.5 Air control dampers—Recycle air, relief air, smoke spill and outdoor air—Six-monthly","sort_order":1,"ref":"4.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1415,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operation","help_text":"CHECK that the damper is capable of operating from fully open to fully closed, and is clear of obstructions.\nWhere the damper is not required to fully open or close, check that it is capable of operating between maximum\nand minimum positions.\n\nNOTE: Increase frequency to three-monthly if dampers are dedicated to fire mode duty only and are exposed to the corrosive effects of exterior air.","sort_order":2,"ref":"4.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1417,"active":true,"required":false,"type":"REMARK","label":"COMPLETE all six-monthly service activities, (see Table 13.4.1.5).","help_text":"COMPLETE all six-monthly service activities, (see Table 13.4.1.21).","sort_order":2,"ref":"5.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1431,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operation","help_text":"CHECK that the damper is capable of operating from fully open to fully closed, and is clear of obstructions.\nWhere the damper is not required to fully open or close, check that it is capable of operating between maximum\nand minimum positions.\n\nNOTE: Increase frequency to three-monthly if dampers are dedicated to fire mode duty only and are exposed to the corrosive effects of exterior air.","sort_order":2,"ref":"4.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1418,"active":true,"required":false,"type":"REMARK","label":"ENSURE - Fire mode\nposition","help_text":"ENSURE damper(s) moves to its fire mode position\nupon removal of power source.","sort_order":3,"ref":"5.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1432,"active":true,"required":false,"type":"HEADER","label":"13.4.1.6 Air control dampers—Recycle air, relief air, smoke spill and outdoor air—Yearly","help_text":"13.4.1.6 Air control dampers—Recycle air, relief air, smoke spill and outdoor air—Yearly","sort_order":3,"ref":"5.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1419,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leakage","help_text":"CHECK that there is no excessive leakage past\ndampers when in the closed position (only where\ndampers are required to close fully).","sort_order":4,"ref":"5.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1433,"active":true,"required":false,"type":"REMARK","label":"COMPLETE all six-monthly service activities, (see Table 13.4.1.5).","help_text":"COMPLETE all six-monthly service activities, (see Table 13.4.1.21).","sort_order":4,"ref":"5.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1420,"active":true,"required":false,"type":"REMARK","label":"CHECK - Bearings","help_text":"CHECK linkage and damper bearings.","sort_order":5,"ref":"5.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1434,"active":true,"required":false,"type":"REMARK","label":"ENSURE - Fire mode\nposition","help_text":"ENSURE damper(s) moves to its fire mode position\nupon removal of power source.","sort_order":5,"ref":"5.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1421,"active":true,"required":false,"type":"REMARK","label":"CHECK - Corrosion","help_text":"CHECK dampers for corrosion.\n\nNOTE: Corrosion may adversely affect the\noperation of the damper.","sort_order":6,"ref":"5.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1435,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leakage","help_text":"CHECK that there is no excessive leakage past\ndampers when in the closed position (only where\ndampers are required to close fully).","sort_order":6,"ref":"5.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1422,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air leaks","help_text":"If motors are pneumatic, CHECK for air leaks in\nthe air lines and connections.","sort_order":7,"ref":"5.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1436,"active":true,"required":false,"type":"REMARK","label":"CHECK - Bearings","help_text":"CHECK linkage and damper bearings.","sort_order":7,"ref":"5.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1437,"active":true,"required":false,"type":"REMARK","label":"CHECK - Corrosion","help_text":"CHECK dampers for corrosion.\n\nNOTE: Corrosion may adversely affect the\noperation of the damper.","sort_order":8,"ref":"5.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1438,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air leaks","help_text":"If motors are pneumatic, CHECK for air leaks in\nthe air lines and connections.","sort_order":9,"ref":"5.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Recycle Air, Relief Air, Smoke Spill and Outdoor Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Air Control Dampers (Supply, Return and Exhaust Air)","prompts":[{"id":1423,"active":true,"required":false,"type":"HEADER","label":"13.4.1.7 Air control dampers—Supply, return and exhaust air—Six-monthly","help_text":"13.4.1.7 Air control dampers—Supply, return and exhaust air—Six-monthly","sort_order":1,"ref":"6.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Supply, Return and Exhaust Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1439,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operation","help_text":"CHECK that the damper is capable of operating from fully open to fully closed, and is clear of obstructions. Where the damper is not required to fully open or\nclose, check that it is capable of operating between maximum and minimum positions.\n\nNOTE: Increase frequency to three-monthly if dampers are dedicated to fire mode duty only and are exposed to the corrosive effects of exterior air.","sort_order":2,"ref":"6.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Supply, Return and Exhaust Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1424,"active":true,"required":false,"type":"HEADER","label":"13.4.1.8 Air control dampers—Supply, return and exhaust air—Yearly","help_text":"13.4.1.8 Air control dampers—Supply, return and exhaust air—Yearly","sort_order":3,"ref":"7.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Supply, Return and Exhaust Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1425,"active":true,"required":false,"type":"REMARK","label":"COMPLETE all six-monthly service activities, (see Table 13.4.1.7).","help_text":"COMPLETE all six-monthly service activities, (see Table 13.4.1.7).","sort_order":4,"ref":"7.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Supply, Return and Exhaust Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1426,"active":true,"required":false,"type":"REMARK","label":"ENSURE - Power failure\nposition","help_text":"ENSURE damper(s) moves to its required failure mode position upon removal of power source.","sort_order":5,"ref":"7.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Supply, Return and Exhaust Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1427,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leakage","help_text":"CHECK that there is no excessive leakage past dampers when in the closed position (only where\ndampers are required to close fully).","sort_order":6,"ref":"7.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Supply, Return and Exhaust Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1428,"active":true,"required":false,"type":"REMARK","label":"CHECK - Bearings","help_text":"CHECK linkage and damper bearings.","sort_order":7,"ref":"7.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Supply, Return and Exhaust Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1429,"active":true,"required":false,"type":"REMARK","label":"CHECK - Corrosion","help_text":"CHECK dampers for corrosion.\n\nNOTE: Corrosion may adversely affect the\noperation of the damper.","sort_order":8,"ref":"7.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Supply, Return and Exhaust Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1440,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air leaks","help_text":"If motors are pneumatic, CHECK for air leaks in the\nair lines and connections.","sort_order":9,"ref":"7.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Air Control Dampers (Supply, Return and Exhaust Air)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","prompts":[{"id":1194,"active":true,"required":false,"type":"HEADER","label":"13.4.1.9 Automatic smoke and heat vents—Six monthly","help_text":"13.4.1.9 Automatic smoke and heat vents—Six monthly","sort_order":1,"ref":"8.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1195,"active":true,"required":false,"type":"REMARK","label":"CHECK - Control panel","help_text":"CHECK air supply and control panel for signs of damage.","sort_order":2,"ref":"8.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1196,"active":true,"required":false,"type":"REMARK","label":"CHECK - Power supply","help_text":"CHECK power supply to control panel.","sort_order":3,"ref":"8.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1197,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air filter","help_text":"CHECK air filter and drain fluid.","sort_order":4,"ref":"8.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1198,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air pressure","help_text":"CHECK system air pressure.","sort_order":5,"ref":"8.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1199,"active":true,"required":false,"type":"REMARK","label":"CHECK - Battery - backup supply","help_text":"CHECK battery backup supply where power is required to operate vents.","sort_order":6,"ref":"8.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1200,"active":true,"required":false,"type":"REMARK","label":"CHECK - Battery function","help_text":"CHECK operation under mains failure condition.","sort_order":7,"ref":"8.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1201,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstruction - Vents and all components","help_text":"CHECK and ensure that the vents and all components such as pulleys, hinges, latches, cables, etc. are free from obstruction and capable of operation.","sort_order":8,"ref":"8.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1202,"active":true,"required":false,"type":"HEADER","label":"13.4.1.10 Automatic smoke and heat vents—Yearly","help_text":"13.4.1.10 Automatic smoke and heat vents—Yearly","sort_order":9,"ref":"9.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1203,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly service","help_text":"COMPLETE all six-monthly service activities as listed in Table 13.4.1.9.","sort_order":10,"ref":"9.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1204,"active":true,"required":false,"type":"REMARK","label":"CHECK - Control panel","help_text":"CHECK air supply and control panel for signs of damage.","sort_order":11,"ref":"9.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1205,"active":true,"required":false,"type":"REMARK","label":"CHECK - Power supply","help_text":"CHECK power supply to control panel.","sort_order":12,"ref":"9.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1206,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air filter","help_text":"CHECK air filter and drain fluid.","sort_order":13,"ref":"9.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1207,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air pressure","help_text":"CHECK system air pressure.","sort_order":14,"ref":"9.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1208,"active":true,"required":false,"type":"REMARK","label":"CHECK - Battery","help_text":"CHECK battery backup supply where power is required to operate vents.","sort_order":15,"ref":"9.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1209,"active":true,"required":false,"type":"REMARK","label":"CHECK - Battery function","help_text":"CHECK operation under mains failure condition","sort_order":16,"ref":"9.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1210,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstruction","help_text":"CHECK and ensure that the vents and all components such as pulleys, hinges, latches, cables, etc. are free from obstruction and capable of operation.","sort_order":17,"ref":"9.08","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1211,"active":true,"required":false,"type":"REMARK","label":"CHECK - Vents","help_text":"CHECK vents for damage, wear or corrosion.","sort_order":18,"ref":"9.09","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1212,"active":true,"required":false,"type":"REMARK","label":"CHECK - Drain holes and channels","help_text":"CHECK drain holes and internal drain channels are clear.","sort_order":19,"ref":"9.10","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1213,"active":true,"required":false,"type":"REMARK","label":"CHECK - Dust covers","help_text":"CHECK ram dust covers are in place.","sort_order":20,"ref":"9.11","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1214,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operation","help_text":"CHECK manual/automatic operation and operating time of system.","sort_order":21,"ref":"9.12","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1215,"active":true,"required":false,"type":"REMARK","label":"REPLACE - Fusible links","help_text":"REPLACE any fusible release links if coated with paint.","sort_order":22,"ref":"9.13","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1216,"active":true,"required":false,"type":"REMARK","label":"REPLACE - Fusible links","help_text":"REPLACE all fusible links throughout the building every 25 years from the date of manufacture.","sort_order":23,"ref":"9.14","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Automatic Smoke and Heat Vent","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Electric Heaters (Duct or Unit Monitored)","prompts":[{"id":1217,"active":true,"required":false,"type":"HEADER","label":"13.4.1.15 Electric heaters—Duct or unit mounted—Yearly","help_text":"13.4.1.15 Electric heaters—Duct or unit mounted—Yearly","sort_order":1,"ref":"14","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Electric Heaters (Duct or Unit Monitored)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1218,"active":true,"required":false,"type":"REMARK","label":"CHECK - Overheating","help_text":"CHECK the outside surface of the heater casing for discolouration or any indication of overheating.","sort_order":2,"ref":"14.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Electric Heaters (Duct or Unit Monitored)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1219,"active":true,"required":false,"type":"REMARK","label":"CHECK - Loose connections","help_text":"CHECK for loose external connections and fittings.","sort_order":3,"ref":"14.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Electric Heaters (Duct or Unit Monitored)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1220,"active":true,"required":false,"type":"REMARK","label":"CHECK - Loose insulation","help_text":"CHECK for loose internal thermal insulation.","sort_order":4,"ref":"14.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Electric Heaters (Duct or Unit Monitored)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1221,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstructions","help_text":"CHECK the elements for obstructions and accumulation of foreign matter.\n\n NOTE: A duct access panel may be installed to permit convenient inspection.","sort_order":5,"ref":"14.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Electric Heaters (Duct or Unit Monitored)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1222,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fan interlock","help_text":"CHECK that the heater switches off upon switching off the fan.","sort_order":6,"ref":"14.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Electric Heaters (Duct or Unit Monitored)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1223,"active":true,"required":false,"type":"REMARK","label":"CHECK - Airflow failure switch","help_text":"CHECK operation of airflow-sensing device by simulating loss of airflow.","sort_order":7,"ref":"14.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Electric Heaters (Duct or Unit Monitored)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1224,"active":true,"required":false,"type":"REMARK","label":"CHECK - Overtemperature cut-out","help_text":"CHECK operation of over-temperature cut-out by simulating overheating of the heater bank.","sort_order":8,"ref":"14.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Electric Heaters (Duct or Unit Monitored)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Fans and Motor","prompts":[{"id":1413,"active":true,"required":false,"type":"HEADER","label":"13.4.1.2 Fans and motors—Three-monthly","help_text":"13.4.1.2 Fans and motors—Three-monthly","sort_order":1,"ref":"1.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1225,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstructions","help_text":"CHECK there are no physical obstructions likely to impede performance.","sort_order":2,"ref":"1.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1226,"active":true,"required":false,"type":"REMARK","label":"CHECK - Noise, overheating and vibration","help_text":"CHECK motor and all bearings for noise, overheating and excessive vibration.","sort_order":3,"ref":"1.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1227,"active":true,"required":false,"type":"REMARK","label":"CHECK - Flexible connections","help_text":"CHECK flexible connections, where fitted, for leaks, tearing or fraying.","sort_order":4,"ref":"1.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1228,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fan belts (wear)","help_text":"CHECK fan belts for wear.","sort_order":5,"ref":"1.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1229,"active":true,"required":false,"type":"REMARK","label":"CHECK - Guards and other safety features","help_text":"CHECK for satisfactory condition.","sort_order":6,"ref":"1.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1230,"active":true,"required":false,"type":"REMARK","label":"CHECK - Bearings","help_text":"CHECK lubrication of bearings.","sort_order":7,"ref":"1.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1231,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fan belts (tension)","help_text":"CHECK for correct tension.","sort_order":8,"ref":"1.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1232,"active":true,"required":false,"type":"HEADER","label":"13.4.1.3 Fans and motors—Yearly","help_text":"13.4.1.3 Fans and motors—Yearly","sort_order":9,"ref":"2.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1233,"active":true,"required":false,"type":"HEADER","label":"CHECK - Three-monthly service","help_text":"COMPLETE all three-monthly service activities (see Table 13.4.1.2.)","sort_order":10,"ref":"2.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1234,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pulley wheels and couplings","help_text":"CHECK pulley wheels for alignment and couplings for alignment and tightness.","sort_order":11,"ref":"2.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1235,"active":true,"required":false,"type":"REMARK","label":"CHECK - Casing guards and impeller","help_text":"CHECK casing, guards and impeller for corrosion.","sort_order":12,"ref":"2.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1236,"active":true,"required":false,"type":"REMARK","label":"CHECK - Electrical","help_text":"CHECK electrical connections, isolators and terminal box.","sort_order":13,"ref":"2.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fans and Motor","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Fire and Smoke Curtain","prompts":[{"id":1237,"active":true,"required":false,"type":"HEADER","label":"13.4.1.11 Fire and smoke curtains—Six-monthly","help_text":"13.4.1.11 Fire and smoke curtains—Six-monthly","sort_order":1,"ref":"10.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1238,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operation","help_text":"CHECK there are no physical obstructions likely to impede operation. RECORD any changes or additions to the surrounding area.","sort_order":2,"ref":"10.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1239,"active":true,"required":false,"type":"REMARK","label":"CHECK - Manual operation","help_text":"CHECK manual deployment of curtain via switch at control panel.","sort_order":3,"ref":"10.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1240,"active":true,"required":false,"type":"REMARK","label":"CHECK - Curtain fabric","help_text":"CHECK for damage to curtain fabric.","sort_order":4,"ref":"10.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1241,"active":true,"required":false,"type":"REMARK","label":"CHECK - Guide tracks (where fitted)","help_text":"CHECK for damage and confirm the integrity of side tracks, to ensure correct operation.","sort_order":5,"ref":"10.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1242,"active":true,"required":false,"type":"REMARK","label":"CHECK - Electrical tests‚ÄîPower supply unit (PSU)","help_text":"(a) CHECK mains power input.\n\n (b) CONFIRM correct display and LED notification.\n\n (c) CHECK the battery charger outputs.\n\n (d) CHECK the control voltage being supplied from the PSU to the MCU.\n\n (e) CHECK the permanent d.c. power supplied from the PSU to the MCU (where applicable).","sort_order":6,"ref":"10.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1243,"active":true,"required":false,"type":"HEADER","label":"13.4.1.12 Fire curtains and smoke curtains—Yearly","help_text":"13.4.1.12 Fire curtains and smoke curtains—Yearly","sort_order":7,"ref":"11.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1244,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly service","help_text":"COMPLETE all six-monthly service activities, as listed in Table 13.4.1.11.","sort_order":8,"ref":"11.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1250,"active":true,"required":false,"type":"REMARK","label":"CHECK - Top limit","help_text":"(a) CHECK bottom bar and capping (where applied) positioning in relation to the ceiling. Adjust where necessary.\n\n (b) CONFIRM that the curtain performs the soft ascent function (where fitted).","sort_order":9,"ref":"11.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1251,"active":true,"required":false,"type":"REMARK","label":"CHECK - Bottom limit","help_text":"CHECK that the bottom limit position is closing to the correct position.","sort_order":10,"ref":"11.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1252,"active":true,"required":false,"type":"TEXT","label":"RECORD - Operating ascent speed","help_text":"CHECK the ascent speeds. RECORD results and adjust if necessary.","sort_order":11,"ref":"11.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1253,"active":true,"required":false,"type":"TEXT","label":"RECORD - Operating descent speed","help_text":"CHECK the descent speeds. RECORD results and adjust if necessary.","sort_order":11,"ref":"11.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1254,"active":true,"required":false,"type":"REMARK","label":"CHECK - Automatic operation","help_text":"CHECK automatic deployment of curtain via alarm signal activation.","sort_order":12,"ref":"11.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1255,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fail-safe operation","help_text":"CHECK gravity fail-safe or other fail-safe deployment of curtain by disconnecting all power sources to all controls.","sort_order":13,"ref":"11.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1256,"active":true,"required":false,"type":"DATE","label":"CHECK - Battery function (Last replaced)","help_text":"REPLACE batteries that are more than two years old.","sort_order":14,"ref":"11.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1257,"active":true,"required":false,"type":"REMARK","label":"CHECK - Electrical tests‚ Motor control card (MCC)","help_text":"(a) CHECK mains power input (where applicable).\n\n (b) CONFIRM correct display and LED notification.\n\n (c) CHECK the transformer outputs (where applicable).\n\n (d) CHECK the control voltage being supplied from the PSU to the MCC.\n\n (e) CHECK the permanent d.c. power supplied from the PSU to the MCC (where applicable).\n\n (f) CHECK the motor brake voltage.\n\n (g) CHECK the motor drive voltage.\n\n (h) CHECK the motor stall-out function (where fitted).","sort_order":15,"ref":"11.08","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1258,"active":true,"required":false,"type":"REMARK","label":"CHECK - Light warning (where fitted)","help_text":"CHECK that the light warning unit flashes with the correct intensity when required.","sort_order":16,"ref":"11.09","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1245,"active":true,"required":false,"type":"REMARK","label":"CHECK - Audible warning (where fitted)","help_text":"CHECK that the local audible warning system is distinctly audible in the vicinity of the curtain.","sort_order":17,"ref":"11.10","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1246,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstruction warning (where fitted)","help_text":"CHECK that the obstruction warning system activates the appropriate warning system when the curtain is obstructed for more than the required duration.","sort_order":18,"ref":"11.11","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1247,"active":true,"required":false,"type":"REMARK","label":"CHECK - Split/dual drop delay (where fitted)","help_text":"(a) CHECK the half drop height.\n\n (b) CHECK the hold time at the half height position.\n\n (c) CHECK that the curtain closes when activated by the second alarm source (dual drop only).","sort_order":19,"ref":"11.12","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1248,"active":true,"required":false,"type":"REMARK","label":"CHECK - Emergency retract (where fitted)","help_text":"CHECK that the curtain retracts temporarily when the retract button is pressed.","sort_order":20,"ref":"11.13","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1249,"active":true,"required":false,"type":"REMARK","label":"REPLACE - Fusible link (where fitted)","help_text":"REPLACE all fusible links throughout the building every 25 years from the date of manufacture.","sort_order":21,"ref":"11.14","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Curtain","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Fire and Smoke Damper","prompts":[{"id":1259,"active":true,"required":false,"type":"HEADER","label":"13.4.1.4 Fire dampers—Yearly","help_text":"13.4.1.4 Fire dampers—Yearly","sort_order":1,"ref":"3.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1260,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstruction","help_text":"CHECK and ensure that the smoke damper is in place free from obstruction and capable of operation (see Notes 1 and 2).","sort_order":2,"ref":"3.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1261,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operation","help_text":"CHECK the damper is free from obstruction and capable of operating from fully open to fully closed.","sort_order":3,"ref":"3.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1262,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstruction‚ Intumescent dampers","help_text":"CHECK and ensure that the fire damper is in place, free from obstruction and is capable of operation (see Notes 1, 2, 3 and 4).","sort_order":4,"ref":"3.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1263,"active":true,"required":false,"type":"REMARK","label":"CHECK - Corrosion‚ Mechanical and intumescent dampers","help_text":"CHECK fire dampers, including casing, retaining flanges and fusible links, for corrosion. The extent of corrosion shall not impede damper operation or prevent it remaining in place until the next inspection (5 years) (see Notes 1, 2, 3 and 5).","sort_order":5,"ref":"3.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1264,"active":true,"required":false,"type":"REMARK","label":"CHECK - Tampering and modifications‚ Mechanical and intumescent dampers","help_text":"CHECK for signs of tampering or modifications. The responsible entity shall confirm that modifications comply with the manufacturer‚  requirements or a registered testing authority‚  confirmation of operation (see Notes 1 and 2).","sort_order":6,"ref":"3.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1265,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire-resisting construction‚ Mechanical and intumescent dampers","help_text":"CHECK the integrity of the surrounding structure within the immediate proximity of the fire damper (see Notes 1 and 2).","sort_order":7,"ref":"3.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1266,"active":true,"required":false,"type":"REMARK","label":"REPLACE - Fusible ink","help_text":"REPLACE all fusible links throughout the building every 25 years from the date of manufacture. Commencing after 25 years, replace 20% per year over the 5 year routine service cycle.","sort_order":8,"ref":"3.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1267,"active":true,"required":false,"type":"HEADER","label":"13.4.1.4 Smoke dampers—Yearly","help_text":"13.4.1.4 Smoke dampers—Yearly","sort_order":9,"ref":"3.08","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1268,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operation","help_text":"CHECK the damper is free from obstruction and capable of operating from fully open to fully closed.","sort_order":10,"ref":"3.08","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1269,"active":true,"required":false,"type":"REMARK","label":"CHECK - Tip seals","help_text":"CHECK tip seals for signs of damage that would adversely affect smoke leakage performance.","sort_order":11,"ref":"3.09","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1270,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstruction‚ Mechanical dampers","help_text":"CHECK and ensure that the fire damper is in place, open and free from obstruction (see Notes 1 and 2).\n\n ** NOTE ** - For mechanical fire dampers, remove or release the fusible link to ensure closure (and latching) (see Notes 1 and 2).","sort_order":12,"ref":"3.10","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1271,"active":true,"required":false,"type":"REMARK","label":"CHECK - Corrosion","help_text":"CHECK smoke dampers and casings for corrosion, accumulation of dust, which may prevent future operation or affect the overall integrity. The extent of corrosion shall not impede damper operation or prevent it remaining in place until the next inspection (5 years) (see Notes 1, 2 and 5).","sort_order":13,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1272,"active":true,"required":false,"type":"REMARK","label":"ENSURE - Fail-safe operation","help_text":"ENSURE damper moves to its fail-safe position on removal of power source.","sort_order":14,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1273,"active":true,"required":false,"type":"REMARK","label":"CHECK - Tampering and modifications","help_text":"CHECK for signs of tampering or modifications. The responsible entity shall confirm that modifications comply with the manufacturer‚  requirements or a registered testing authority‚  confirmation of operation.","sort_order":15,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1274,"active":true,"required":false,"type":"HEADER","label":"13.4.2.9 Smoke dampers—Yearly","help_text":"13.4.2.9 Smoke dampers—Yearly","sort_order":16,"ref":"8.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1275,"active":true,"required":false,"type":"REMARK","label":"ENSURE - Normal operation","help_text":"ENSURE all dampers operate open and close in accordance with the system requirements (see Appendices H and I).","sort_order":17,"ref":"8.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1276,"active":true,"required":false,"type":"REMARK","label":"CHECK - Normal operation","help_text":"CHECK all systems required to shut down are not operating (see Appendices H and I).","sort_order":18,"ref":"8.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire and Smoke Damper","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","prompts":[{"id":1277,"active":true,"required":false,"type":"HEADER","label":"13.4.2.2 Fire isolated exit pressurization systems—Three-monthly","help_text":"13.4.2.2 Fire isolated exit pressurization systems—Three-monthly","sort_order":1,"ref":"1.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1278,"active":true,"required":false,"type":"REMARK","label":"CHECK - Simulation (from FIP)","help_text":"SIMULATE by activation from FIP, the fire/smoke situation required to effect operation of the pressurization system. Check fans, dampers and indicator lamps operate in fire mode as documented. Check for excessive noise, ease of opening doors and correct movement of air from each pressurized area through a selected open door (see Appendices H and I).\n\n (a) Fan operation.\n\n (b) Damper operation.\n\n (c) Indicator lamps.\n\n (d) Noise.\n\n (e) Ease of door opening.\n\n (f) Air movement.\n\n ** See Notes ** 1 to 5.\n\n SWITCH all systems back to ‚Äònormal‚Äô and check that all equipment and indicator lamps are in the correct non-fire mode (see Appendices H and I).","sort_order":2,"ref":"1.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1279,"active":true,"required":false,"type":"REMARK","label":"CHECK - Non-fire\nmode","help_text":"SWITCH all systems back to ‘normal’ and check that all\nequipment and indicator lamps are in the correct non-fire\nmode (see Appendices H and I).","sort_order":3,"ref":"1.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1280,"active":true,"required":false,"type":"HEADER","label":"13.4.2.3 Fire-isolated exit pressurization systems—Yearly","help_text":"13.4.2.3 Fire-isolated exit pressurization systems—Yearly","sort_order":4,"ref":"2.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1281,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Three-monthly tests","help_text":"COMPLETE all three-monthly test activities, as listed in Table 13.4.2.2.","sort_order":5,"ref":"2.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1282,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Simulation (from Detector)","help_text":"SIMULATE a fire/smoke situation from any device such as a sprinkler, heat of smoke detector, to effect operation of the pressurization and all other systems required to operate in fire mode.","sort_order":6,"ref":"2.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1283,"active":true,"required":false,"type":"REMARK","label":"CHECK - Simulation (from Detector)","help_text":"CHECK that the following parameters meet the performance requirements (see Appendices H and I, and Notes 1 and 2).\n\n (a) Airflow velocity across all required doorways.\n\n (b) The force required to open each door.\n\n (c) The noise level at typical doorways and those identified as subject to the highest noise level.\n\n (d) Time taken for door opening force and airflow velocity to be restored, after opening and reclosing two successive doors adjacent to the test door(s) (to be that identified as having the longest restoration time).\n\n (e) When smoke is introduced to the supply smoke sensor of any air-pressurization system, the associated pressurization fan is shut down.\n Verify re-start when smoke clears and verify that the FFCP manual override 'ON' operates while the fan has shut down due to supply smoke detection.\n\n (f) Operation of the manual switch provided for fire brigade personnel starts and stops fans supplying air to the pressurized fire-isolated escape routes.\n\n (g) Check indicator lamps change status when fan starts or stops.","sort_order":7,"ref":"2.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1284,"active":true,"required":false,"type":"REMARK","label":"CHECK - Simulation","help_text":"(h) With all air-pressurization and other systems operating simultaneously, check that any specific air relief is fully operational and enables the required airflow from pressurized areas to be sustained.","sort_order":8,"ref":"2.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1285,"active":true,"required":false,"type":"REMARK","label":"CHECK - Revert system to normal","help_text":"Switch system to normal and check that all equipment and indicator lamps are in the correct non-fire mode. (Refer Appendices H and I.)","sort_order":9,"ref":"2.40","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1286,"active":true,"required":false,"type":"REMARK","label":"CHECK - FFCP latching and reset","help_text":"CHECK that after initiation by a signal from the FIP, the FFCP remains operating in the fire mode until reset by the reset switch on the FFCP.","sort_order":10,"ref":"3.19","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1287,"active":true,"required":false,"type":"REMARK","label":"CHECK - Manual override controls","help_text":"CHECK that manual override ON-AUTO-OFF control operates.\n\n ** NOTE: ** Manual override should function in normal mode and fire mode.","sort_order":11,"ref":"3.20","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1288,"active":true,"required":false,"type":"REMARK","label":"CHECK - Airflow fault indicator","help_text":"CHECK the operation of the airflow fault indicator","sort_order":12,"ref":"3.21","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1289,"active":true,"required":false,"type":"REMARK","label":"CHECK - Open-circuit fault indicator","help_text":"CHECK the operation of the air-handling equipment interconnecting cable open-circuit fault indicator.","sort_order":13,"ref":"3.22","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1290,"active":true,"required":false,"type":"REMARK","label":"CHECK - Closed-circuit fault indicator","help_text":"CHECK the operation of the air-handling equipment interconnecting cable closed-circuit fault indicator.","sort_order":14,"ref":"3.23","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1291,"active":true,"required":false,"type":"REMARK","label":"CHECK - Electrical","help_text":"CHECK the operation of the electricity phasefail fault indicator.","sort_order":15,"ref":"3.24","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1292,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fan-running indicator","help_text":"CHECK the operation of the fan-running indicator.","sort_order":16,"ref":"3.25","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1293,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fan-stopped indicator","help_text":"CHECK the operation of the fan-stopped indicator.","sort_order":17,"ref":"3.26","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1294,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fan fault indicator","help_text":"CHECK the operation of the fan-fault indicator.","sort_order":18,"ref":"3.27","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Fire Isolated Exit Pressurisation System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Kitchen Exhaust System","prompts":[{"id":1295,"active":true,"required":false,"type":"HEADER","label":"13.4.1.16 Kitchen exhaust systems—Monthly","help_text":"13.4.1.16 Kitchen exhaust systems—Monthly","sort_order":1,"ref":"15.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1296,"active":true,"required":false,"type":"REMARK","label":"CHECK - Filters","help_text":"CHECK grease-arresting filters for excessive grease accumulation.","sort_order":2,"ref":"15.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1297,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hood and plenum","help_text":"CHECK hood and its exhaust plenum for excessive grease accumulation.","sort_order":3,"ref":"15.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1298,"active":true,"required":false,"type":"REMARK","label":"CHECK - Gutters","help_text":"CHECK grease gutters for excessive grease accumulation.","sort_order":4,"ref":"15.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1299,"active":true,"required":false,"type":"REMARK","label":"CHECK - Filter (condition)","help_text":"CHECK that grease-arresting filters are secured in the correct position and undamaged.","sort_order":5,"ref":"15.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1300,"active":true,"required":false,"type":"REMARK","label":"CHECK - Filter (clean)","help_text":"CLEAN grease-arresting filters as required (monthly, see Note).","sort_order":6,"ref":"15.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1301,"active":true,"required":false,"type":"HEADER","label":"13.4.1.17 Kitchen exhaust systems—Yearly","help_text":"13.4.1.17 Kitchen exhaust systems—Yearly","sort_order":7,"ref":"16.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1302,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service","help_text":"COMPLETE all monthly service activities as listed in Table 13.4.1.16.","sort_order":8,"ref":"16.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1303,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hood and plenum","help_text":"CLEAN hood and its exhaust plenum.","sort_order":9,"ref":"16.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1304,"active":true,"required":false,"type":"REMARK","label":"CHECK AND REPLACE - Filter (replace)","help_text":"CHECK for excessive leaks or damage to grease-arresting filters, and REPLACE as necessary.\n\n ** NOTE: ** Non-metallic grease filters and other special types have to be replaced at specific time intervals whether damaged or not. In these cases, follow manufacturer‚  instructions.","sort_order":10,"ref":"16.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1305,"active":true,"required":false,"type":"REMARK","label":"CHECK - Duct","help_text":"CHECK duct for accumulated grease and CLEAN.","sort_order":11,"ref":"16.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Kitchen Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Motor Control Centre","prompts":[{"id":1306,"active":true,"required":false,"type":"HEADER","label":"13.4.1.25 Motor control centres—Yearly","help_text":"13.4.1.25 Motor control centres—Yearly","sort_order":1,"ref":"24.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1307,"active":true,"required":false,"type":"REMARK","label":"Motor control centres shall be inspected","help_text":"Motor control centres shall be inspected","sort_order":2,"ref":"24.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1308,"active":true,"required":false,"type":"REMARK","label":"CHECK - Wiring and switches","help_text":"CHECK general condition of conduits, connectors, switches and wiring for any condition likely to adversely affect their function.","sort_order":3,"ref":"24.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1309,"active":true,"required":false,"type":"REMARK","label":"CHECK - Contacts and relays","help_text":"CHECK, clean or replace, as necessary, any faulty contacts or relays.","sort_order":4,"ref":"24.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1310,"active":true,"required":false,"type":"REMARK","label":"CHECK - Overload ratings","help_text":"CHECK overload ratings against motor nameplate ratings.","sort_order":5,"ref":"24.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1311,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fuses","help_text":"CHECK circuit protectors (fuses and circuit breakers) for correct rating.","sort_order":6,"ref":"24.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1312,"active":true,"required":false,"type":"REMARK","label":"CHECK - Electrical connections","help_text":"CHECK connections at motors, switchboards and equipment subject to vibration. Retighten cable terminations as necessary.","sort_order":7,"ref":"24.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1313,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Interpole barriers","help_text":"INSPECT interpole barriers and shrouds where fitted.","sort_order":8,"ref":"24.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1314,"active":true,"required":false,"type":"REMARK","label":"CHECK - Cable insulation","help_text":"CHECK and rectify any damaged or faulty exposed cable insulation.","sort_order":9,"ref":"24.08","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1315,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Switchboard","help_text":"INSPECT each switchboard internally to ensure it is clean and free from rubbish.","sort_order":10,"ref":"24.09","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1316,"active":true,"required":false,"type":"REMARK","label":"CHECK - Panel seals","help_text":"CHECK panel seals, and rectify if faulty.","sort_order":11,"ref":"24.10","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1317,"active":true,"required":false,"type":"REMARK","label":"CHECK - Wiring diagrams","help_text":"CHECK and report where wiring diagram(s) are considered to be incorrect.","sort_order":12,"ref":"24.11","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1318,"active":true,"required":false,"type":"REMARK","label":"CHECK - Earthing","help_text":"CHECK continuity to earth.","sort_order":13,"ref":"24.12","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1319,"active":true,"required":false,"type":"REMARK","label":"CHECK - Neutral current","help_text":"CHECK and record neutral current.","sort_order":14,"ref":"24.13","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motor Control Centre","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","prompts":[{"id":1320,"active":true,"required":false,"type":"HEADER","label":"13.4.1.13 Motorized relief openings, windows and shutters—Six monthly","help_text":"13.4.1.13 Motorized relief openings, windows and shutters—Six monthly","sort_order":1,"ref":"12.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1321,"active":true,"required":false,"type":"REMARK","label":"CHECK - Visual inspection","help_text":"CHECK the control centre (and in the case of pneumatic actuators, the air supply) for signs of damage.","sort_order":2,"ref":"12.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1322,"active":true,"required":false,"type":"REMARK","label":"CHECK - Power supply","help_text":"CHECK the power supply indicator is functioning.","sort_order":3,"ref":"12.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1323,"active":true,"required":false,"type":"REMARK","label":"DRAIN - Air filter‚ Pneumatic systems","help_text":"DRAIN any fluid that has accumulated in the air filter.\n\n ** NOTE: ** Solvents should not be used.","sort_order":4,"ref":"12.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1324,"active":true,"required":false,"type":"REMARK","label":"CHECK - System pressure‚ Pneumatic systems","help_text":"CHECK system pressure against manufacturer‚  requirements, and RECORD.\n\n NOTE: The frequency of filter inspection and service could vary depending on usage and the quantity of supplied air. Fluid should be drained from the filter bowl before fluid reaches the filter element.","sort_order":5,"ref":"12.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1325,"active":true,"required":false,"type":"REMARK","label":"CHECK - Battery","help_text":"CHECK battery backup supply where power is required to operate system.","sort_order":6,"ref":"12.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1326,"active":true,"required":false,"type":"REMARK","label":"CHECK - Battery function","help_text":"CHECK operation under mains failure condition.","sort_order":7,"ref":"12.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1327,"active":true,"required":false,"type":"REMARK","label":"CHECK - Vents","help_text":"(a) REMOVE any foreign matter from the blades.\n\n (b) REMOVE any debris from the internal rain channel.\n\n (c) CHECK that the drain holes are clear.\n\n (d) CHECK the vents for signs of damage, wear and tear or corrosion.\n\n (e) ENSURE cylinder ram dust covers are in place.","sort_order":8,"ref":"12.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1328,"active":true,"required":false,"type":"REMARK","label":"CHECK - Open/close switch","help_text":"CHECK the manual function by operating the open/close manual switch.\n\n ** NOTE: ** Closing times in excess of 20 s should be investigated.","sort_order":9,"ref":"12.08","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1329,"active":true,"required":false,"type":"REMARK","label":"CLEAN or REPLACE - Air filter‚ Pneumatic systems","help_text":"CLEAN or REPLACE the filter element. If any damage or fault is discovered, correct immediately.","sort_order":10,"ref":"12.09","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1330,"active":true,"required":false,"type":"HEADER","label":"13.4.1.14 Motorized relief openings, windows and shutters—Yearly","help_text":"13.4.1.14 Motorized relief openings, windows and shutters—Yearly","sort_order":11,"ref":"13.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1331,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly service","help_text":"COMPLETE all six-monthly service activities as listed in Table 13.4.1.12.","sort_order":12,"ref":"13.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1332,"active":true,"required":false,"type":"REMARK","label":"CHECK - Vents and air lines‚ Pneumatic systems","help_text":"CHECK all vents and connecting air lines to ascertain unauthorized alterations, damage or corrosion.","sort_order":13,"ref":"13.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1333,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fusible release links","help_text":"If equipped, CHECK the fusible release links for type and temperature rating and replace release links that have been coated with paint or similar coatings.","sort_order":14,"ref":"13.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1334,"active":true,"required":false,"type":"REMARK","label":"CHECK - Control centres and supply lines","help_text":"CHECK all control centres and supply lines for damage or deterioration.","sort_order":15,"ref":"13.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1335,"active":true,"required":false,"type":"REMARK","label":"ENSURE - Operation","help_text":"ENSURE all relief openings, windows and shutters operate open and close in accordance with the system requirements. (Refer Appendix I.)","sort_order":16,"ref":"13.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1336,"active":true,"required":false,"type":"REMARK","label":"ENSURE - Plans","help_text":"ENSURE installation plans include current information.","sort_order":17,"ref":"13.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1337,"active":true,"required":false,"type":"REMARK","label":"REPLACE - Fusible release link (where fitted)","help_text":"REPLACE all fusible links throughout the building every 25 years from the date of manufacture.","sort_order":18,"ref":"13.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1338,"active":true,"required":false,"type":"HEADER","label":"13.4.3.3 Motorized relief openings (windows and shutters)—Yearly","help_text":"13.4.3.3 Motorized relief openings (windows and shutters)—Yearly","sort_order":19,"ref":"2.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1339,"active":true,"required":false,"type":"REMARK","label":"CHECK - Draught curtains‚ Frames forming roof compartments","help_text":"CHECK draught curtain areas to ensure there have not been any major alterations or additions that could inhibit their function.","sort_order":20,"ref":"2.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1340,"active":true,"required":false,"type":"REMARK","label":"CHECK - Inlet openings","help_text":"CHECK inlet openings to ensure there have not been any major structural alterations that could inhibit their function.","sort_order":22,"ref":"2.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Motorized Relief Openings (Windows and Shutter)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Outdoor Intake","prompts":[{"id":1341,"active":true,"required":false,"type":"HEADER","label":"13.4.1.18 Outdoor intakes—Monthly","help_text":"13.4.1.18 Outdoor intakes—Monthly","sort_order":1,"ref":"17.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Outdoor Intake","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1342,"active":true,"required":false,"type":"REMARK","label":"REMOVE - Fire hazards","help_text":"REMOVE any combustible material from the vicinity of the intakes.","sort_order":2,"ref":"17.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Outdoor Intake","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1343,"active":true,"required":false,"type":"HEADER","label":"13.4.1.19 Outdoor intakes—Yearly","help_text":"13.4.1.19 Outdoor intakes—Yearly","sort_order":3,"ref":"18.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Outdoor Intake","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1344,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service","help_text":"COMPLETE all monthly service activities as listed in Table 13.4.1.18.","sort_order":4,"ref":"18.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Outdoor Intake","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1345,"active":true,"required":false,"type":"REMARK","label":"CHECK - Corrosion","help_text":"CHECK intake louvres for corrosion and damage.","sort_order":5,"ref":"18.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Outdoor Intake","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1346,"active":true,"required":false,"type":"REMARK","label":"CHECK - Insect screens","help_text":"CHECK and clean insect screens, replace if damaged.","sort_order":6,"ref":"18.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Outdoor Intake","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","prompts":[{"id":1347,"active":true,"required":false,"type":"REMARK","label":"13.4.1.23 Pneumatic compressor/receiver station—Three-monthly","help_text":"13.4.1.23 Pneumatic compressor/receiver station—Three-monthly","sort_order":1,"ref":"22.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1348,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressures","help_text":"CHECK cut-in and cut-out pressures and record.","sort_order":2,"ref":"22.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1349,"active":true,"required":false,"type":"REMARK","label":"CHECK - Overheating, noise and vibration","help_text":"CHECK unit for overheating, undue noise and excessive vibration.","sort_order":3,"ref":"22.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1350,"active":true,"required":false,"type":"REMARK","label":"CHECK - Crankcase oil","help_text":"CHECK crankcase oil level and top up as necessary.","sort_order":4,"ref":"22.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1351,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure-relief valves","help_text":"CHECK if pressure-relief valves are operating by manually bleeding.","sort_order":5,"ref":"22.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1352,"active":true,"required":false,"type":"REMARK","label":"CHECK - Condensate drain","help_text":"CHECK and clean auto condensate drain or actuate manual drain.","sort_order":6,"ref":"22.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1353,"active":true,"required":false,"type":"REMARK","label":"CHECK - Filter and breather","help_text":"CHECK air intake filter and crankcase breather. Clean or replace as necessary.","sort_order":7,"ref":"22.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1354,"active":true,"required":false,"type":"REMARK","label":"CHECK - Belts","help_text":"CHECK belts for wear (if belt drive); adjust tension or replace as required.","sort_order":8,"ref":"22.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1355,"active":true,"required":false,"type":"HEADER","label":"13.4.1.24 Pneumatic compressor/receiver station—Yearly","help_text":"13.4.1.24 Pneumatic compressor/receiver station—Yearly","sort_order":9,"ref":"23.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1356,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Three-monthly service","help_text":"COMPLETE all three-monthly service activities (see Table 13.4.1.23.)","sort_order":10,"ref":"23.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1357,"active":true,"required":false,"type":"REMARK","label":"DRAIN - Sump and oil","help_text":"DRAIN and clean sump and replace sump oil.","sort_order":11,"ref":"23.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1358,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pulley alignment","help_text":"CHECK pulley alignment (if belt drive). Ensure pulleys are secure on shaft.","sort_order":12,"ref":"23.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1359,"active":true,"required":false,"type":"REMARK","label":"CHECK - Compressor bolts","help_text":"CHECK compressor holding-down bolts are secure.","sort_order":13,"ref":"23.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1360,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure vessel","help_text":"CHECK and open pressure vessel; clean and operate receiver drain valves.","sort_order":14,"ref":"23.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1361,"active":true,"required":false,"type":"REMARK","label":"CHECK - Corrosion","help_text":"CHECK unit for any sign of corrosion or deterioration. Treat corrosion with rust inhibitor.","sort_order":15,"ref":"23.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1362,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure-relief valve","help_text":"CHECK pressure-relief valve operation and setting, where appropriate.","sort_order":16,"ref":"23.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1363,"active":true,"required":false,"type":"REMARK","label":"RUN & CHECK - Operation","help_text":"Test run the unit and CHECK for satisfactory operation. Observe the frequency of compressor operation for possible unloader malfunction.","sort_order":17,"ref":"23.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1364,"active":true,"required":false,"type":"REMARK","label":"CHECK - Electrical","help_text":"CHECK electrical connections, isolators and terminal box.","sort_order":18,"ref":"23.08","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Pneumatic Compressor/Receiver Station","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","prompts":[{"id":1365,"active":true,"required":false,"type":"HEADER","label":"13.4.1.26 Power supplies—Main switchboards (low voltage)—Yearly","help_text":"13.4.1.26 Power supplies—Main switchboards (low voltage)—Yearly","sort_order":1,"ref":"25.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1366,"active":true,"required":false,"type":"REMARK","label":"CHECK - Busbar connections","help_text":"CHECK for loose busbar connections and cable terminations and retighten any loose connections.","sort_order":2,"ref":"25.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1371,"active":true,"required":false,"type":"REMARK","label":"EXAMINE - Wiring and switches","help_text":"EXAMINE the general condition of conduits, connectors, switches and wiring.","sort_order":3,"ref":"25.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1372,"active":true,"required":false,"type":"REMARK","label":"CHECK - Contacts and relays","help_text":"CHECK, clean or replace, as necessary, contacts or faulty relays.","sort_order":4,"ref":"25.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1373,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Interpole barriers","help_text":"INSPECT interpole barriers and shrouds.","sort_order":5,"ref":"25.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1374,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fuses","help_text":"CHECK all fuses for correct rating.","sort_order":6,"ref":"25.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1375,"active":true,"required":false,"type":"REMARK","label":"CHECK - Cable insulation","help_text":"CHECK and rectify, where necessary, condition of exposed cable insulation.","sort_order":7,"ref":"25.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1376,"active":true,"required":false,"type":"REMARK","label":"VACUUM - Switchboard","help_text":"VACUUM clean switchboard interior and remove any rubbish.","sort_order":8,"ref":"25.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1377,"active":true,"required":false,"type":"REMARK","label":"CHECK - Panel seals","help_text":"CHECK panel seals, and rectify if faulty.","sort_order":9,"ref":"25.08","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1378,"active":true,"required":false,"type":"REMARK","label":"CHECK - Wiring diagrams","help_text":"CHECK wiring diagram and report where considered to be incorrect.","sort_order":10,"ref":"25.09","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1367,"active":true,"required":false,"type":"REMARK","label":"TEST - Breakers","help_text":"TEST operation of main breakers (manually) with power switched off.","sort_order":11,"ref":"25.10","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1368,"active":true,"required":false,"type":"REMARK","label":"CHECK - Current draw","help_text":"CHECK current draw on main risers and compare to rating.","sort_order":12,"ref":"25.11","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1369,"active":true,"required":false,"type":"REMARK","label":"CHECK - Earthing","help_text":"CHECK continuity to earth.","sort_order":13,"ref":"25.12","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1370,"active":true,"required":false,"type":"REMARK","label":"CHECK - Neutral current","help_text":"CHECK and record neutral current.","sort_order":14,"ref":"25.13","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Power Supplies, Main Switchboards (Low Voltage)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Smoke Exhaust System","prompts":[{"id":1379,"active":true,"required":false,"type":"HEADER","label":"13.4.2.6 Smoke exhaust systems—Three-monthly","help_text":"13.4.2.6 Smoke exhaust systems—Three-monthly","sort_order":1,"ref":"5.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Smoke Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1380,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Simulation (from the FIP)","help_text":"SIMULATE a fire/smoke situation by activation from the FIP, to effect operation of the smoke exhaust system and all other systems required to operate in fire mode. Check fans, dampers, automatic doors and indicator lamps operate in fire mode as documented (see Appendices H and I). Check for excessive noise and correct movement of air.","sort_order":2,"ref":"5.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Smoke Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1381,"active":true,"required":false,"type":"REMARK","label":"SWITCH - Revert to normal","help_text":"SWITCH all systems back to 'normal' and check that all equipment and indicator lamps are in the correct non-fire mode (see Appendices H and I).","sort_order":3,"ref":"5.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Smoke Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1382,"active":true,"required":false,"type":"HEADER","label":"13.4.2.7 Smoke exhaust systems—Yearly","help_text":"13.4.2.7 Smoke exhaust systems—Yearly","sort_order":4,"ref":"6.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Smoke Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1383,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Three-monthly tests","help_text":"COMPLETE all three-monthly test activities as listed in Table 13.4.2.6.","sort_order":5,"ref":"6.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Smoke Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1384,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Partial simulation","help_text":"CONDUCT a simulation of a fire/smoke situation from any device such as a sprinkler, heat or smoke detector, to effect operation of the smoke exhaust system and all other systems required to operate in fire mode. Check fans, dampers, automatic doors and indicator lamps operate in fire mode as documented (see Appendices H and I).\n\n CHECK:\n (a) Exhaust airflow rate from the space.\n\n (b) Indicator lamps change status when fan starts or stops.\n\n (c) That operation of the manual switch provided for fire brigade personnel starts and stops smoke exhaust fans.\n\n (d) The maximum noise level in the space.\n\n NOTE: In some installations maximum noise criteria may not be specified.","sort_order":6,"ref":"6.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Smoke Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1385,"active":true,"required":false,"type":"REMARK","label":"SWITCH - Revert to normal","help_text":"SWITCH all systems back to 'normal' and check that all equipment and indicator lamps are in the correct non-fire mode (see Appendices H and I).","sort_order":7,"ref":"6.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Smoke Exhaust System","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Smoke Reservoir","prompts":[{"id":1386,"active":true,"required":false,"type":"HEADER","label":"13.4.3.4 Smoke reservoirs—Yearly","help_text":"13.4.3.4 Smoke reservoirs—Yearly","sort_order":1,"ref":"3.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Smoke Reservoir","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1387,"active":true,"required":false,"type":"REMARK","label":"CHECK - Changes","help_text":"CHECK to ensure that changes to the smoke reservoirs have not been made, such as the addition of light fittings or openings created, which would otherwise compromise the integrity of the system.","sort_order":2,"ref":"3.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Smoke Reservoir","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","prompts":[{"id":1388,"active":true,"required":false,"type":"HEADER","label":"13.4.2.4 System changeover under fire condition—Three-monthly","help_text":"13.4.2.4 System changeover under fire condition—Three-monthly","sort_order":1,"ref":"3.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1389,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Simulation (from FIP)","help_text":"SIMULATE by activation from FIP, the fire/smoke situation (for each system or zone where relevant), required to effect changeover from normal mode to fire mode or shutdown as appropriate. Check fans, dampers and indicator lamps operate in fire mode as documented (see Appendices H and I).\n\n NOTES:\n 1 The purpose of a simulated testing routine is to check the functioning of the air-handling changeover system and not the detectors themselves. The recommended practice in this case is to simulate activation of the system by initiating the fire alarm via the switch in the FIP.\n\n 2 This changeover test is initiated in the fire panel to verify the integrity of the interface between fire and mechanical systems.\n\n 3 Verification of fan or damper operation may use elementary testing procedures; e.g. hearing fan start, observation of indicator lamp change of status, feeling of air movement across doorway, grille, duct, etc.","sort_order":2,"ref":"3.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1390,"active":true,"required":false,"type":"REMARK","label":"SWITCH - Revert to normal","help_text":"SWITCH system back to ‚Äònormal‚Äô and check that all equipment and indicator lamps are in the correct non-fire mode (see Appendices H and I).","sort_order":3,"ref":"3.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1391,"active":true,"required":false,"type":"HEADER","label":"13.4.2.5 System changeover under fire condition—Yearly","help_text":"13.4.2.5 System changeover under fire condition—Yearly","sort_order":4,"ref":"4.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1392,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Three-monthly tests","help_text":"COMPLETE all three-monthly test activities as listed in Table 13.4.2.4.","sort_order":5,"ref":"4.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1393,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Simulation (from Detector)","help_text":"CONDUCT a simulation of a fire/smoke situation (for each system or zone where relevant) to effect changeover from normal mode to fire mode or shutdown as appropriate.","sort_order":6,"ref":"4.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1394,"active":true,"required":false,"type":"REMARK","label":"CHECK - Simulation (from Detector)","help_text":"CHECK fans, dampers and indicator lamps operate in fire mode (see Appendices H and I).\n\n Tests required in Items 4.4, 4.5 and 4.6 are carried out during this simulation test (see Notes 1 and 2).","sort_order":7,"ref":"4.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1395,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Fans start and stop at Fire fan control panel (FFCP)","help_text":"OPERATE the manual switches at the FFCP. Check that fans start and stop and dampers, if applicable, open and close as documented (see Appendices H and I).","sort_order":8,"ref":"4.04","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1396,"active":true,"required":false,"type":"REMARK","label":"CHECK - System shutdown","help_text":"Where supply air systems are fitted with a smoke detector(s), check system shuts down when the detector is automatically activated as documented (see Appendices H and I).\n\n Verify re-start when smoke clears and verify that the FFCP manual override ‚ÄòON‚Äô operates while the fan has shut down due to supply smoke detection.","sort_order":9,"ref":"4.05","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1397,"active":true,"required":false,"type":"REMARK","label":"CHECK - Zone smoke control","help_text":"CHECK zone smoke control system performance criteria as documented (see Appendices H and I).","sort_order":10,"ref":"4.06","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1398,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire curtains and smoke curtains","help_text":"CHECK to ensure that the integrity and leakage performance are not compromised by operation of the mechanical systems in fire mode.","sort_order":11,"ref":"4.07","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Changeover Under Fire Condition","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: System Shutdown","prompts":[{"id":1399,"active":true,"required":false,"type":"HEADER","label":"13.4.2.8 System shutdown—Yearly","help_text":"13.4.2.8 System shutdown—Yearly","sort_order":1,"ref":"7.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Shutdown","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1400,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Simulation (from detector)","help_text":"SIMULATE a fire/smoke situation from any device such as a sprinkler, heat or smoke detector, to effect shutdown of all mechanical ventilation systems not required to operate in fire mode.","sort_order":2,"ref":"7.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Shutdown","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1401,"active":true,"required":false,"type":"REMARK","label":"CHECK - Simulation (from detector)","help_text":"CHECK all systems required to shut down are not operating (see Appendices H and I).","sort_order":3,"ref":"7.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: System Shutdown","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","prompts":[{"id":1402,"active":true,"required":false,"type":"HEADER","label":"13.4.1.20 Variable frequency inverters (VFIs)—Three-monthly","help_text":"13.4.1.20 Variable frequency inverters (VFIs)—Three-monthly","sort_order":1,"ref":"19.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1403,"active":true,"required":false,"type":"REMARK","label":"CHECK - Dust and dirt","help_text":"CHECK for dust and accumulated dirt on vents and circuit boards and clean where necessary.\n\n Where there is evidence of moisture, inspect on a monthly basis or replace enclosure with one having an appropriate IP rating.","sort_order":2,"ref":"19.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1404,"active":true,"required":false,"type":"REMARK","label":"CHECK - Electrical","help_text":"CHECK electrical connections and tighten where necessary.","sort_order":3,"ref":"19.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1405,"active":true,"required":false,"type":"REMARK","label":"CHECK - Cooling fans","help_text":"CHECK the operation of all cooling fans.","sort_order":4,"ref":"19.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1406,"active":true,"required":false,"type":"HEADER","label":"13.4.1.21 Variable frequency inverters (VFIs)—Six-monthly","help_text":"13.4.1.21 Variable frequency inverters (VFIs)—Six-monthly","sort_order":5,"ref":"20.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1407,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Three-monthly service","help_text":"COMPLETE all three-monthly service activities as listed in Table 13.4.1.20.","sort_order":6,"ref":"20.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1408,"active":true,"required":false,"type":"REMARK","label":"CHECK - Damage and overheating","help_text":"CHECK for evidence of damage or overheating and clean or repair where necessary.","sort_order":7,"ref":"20.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1409,"active":true,"required":false,"type":"HEADER","label":"13.4.1.22 Variable frequency inverters (VFIs)—Yearly","help_text":"13.4.1.22 Variable frequency inverters (VFIs)—Yearly","sort_order":8,"ref":"21.00","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1410,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly service","help_text":"COMPLETE all six-monthly service activities, (see Table 13.4.1.21).","sort_order":9,"ref":"21.01","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1411,"active":true,"required":false,"type":"REMARK","label":"CHECK - Calibration","help_text":"CHECK calibration and set point of all adjustable components, including customer settings and correct if necessary.","sort_order":10,"ref":"21.02","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1412,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire mode override","help_text":"CHECK operation of fire-mode override functions and correct if necessary.","sort_order":11,"ref":"21.03","estimated_duration":null,"prompt_set":"2012: Fire & Smoke Control: Variable Frequency Inverters (VFIs)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Blanket","prompts":[{"id":1043,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 11.4 (Six-monthly)","help_text":"AS1851-2012 Table 11.4 (Six-monthly)","sort_order":1,"ref":"1","estimated_duration":null,"prompt_set":"2012: Fire Blanket","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1152,"active":true,"required":false,"type":"REMARK","label":"CHECK - Accessibility","help_text":"CHECK that the fire blanket is:\n\n(a) Conspicuous.\n\n(b) In its assigned location.\n\n(c) Readily accessible.\n\n(d) Installed in accordance with AS 2444.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Blanket","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1153,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage","help_text":"CHECK that the location sign is visible and correct.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Blanket","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1154,"active":true,"required":false,"type":"REMARK","label":"CHECK - Blanket container","help_text":"CHECK that the fire blanket container:\n\n(a) Is securely and correctly supported.\n\n(b) Is clean and free from damage.\n\n(c) Has clear and legible instructions thereon.\n\n(d) Has a service record tag/label attached.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Blanket","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1155,"active":true,"required":false,"type":"REMARK","label":"REMOVE - Fire blanket","help_text":"REMOVE the fire blanket from the container and check:\n\n(a) For any damage or contamination to the fire blanket (refer also Clause 11.2.4).\n\n(b) For unsecured or damaged hand-holding devices.\n\n(c) That the fire blanket is correctly folded.\n\nWhere the fire blanket conforms to the above, REPLACE the blanket into the container as recommended by the manufacturer.\n\n** NOTE: ** It is important that fire blankets are always folded in the manner prescribed by the manufacturer in order that they can be removed from the container quickly (see AS/NZS 3504).","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Blanket","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","prompts":[{"id":805,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.1.2 (Monthly service)","help_text":"AS1851-2012 Table 6.4.1.2 (Monthly service)","sort_order":1,"ref":"1","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":806,"active":true,"required":false,"type":"REMARK","label":"INSPECT - External alarm","help_text":"INSPECT the external alarm (bell or strobe light) to ensure it clearly indicates the designated building entry point.\n\nInspect to ensure the external alarm label is legible with the word ‘FIRE’ in characters not less than 25 mm in height.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":807,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Control and indicating equipment (CIE)","help_text":"INSPECT the following as applicable:\n\nFire indicator panel (FIP), sub-indicator panel (SIP), repeater panel, fire brigade panel (FBP), mimic panel, fire fan control panel (FFCP) and—\n\n(a) ensure that they are clearly visible, readily accessible and free from dust and contaminants;\n\n(b) where a panel is obscured by a door, check that the door is correctly labelled.\n\nWhere manual call points use replaceable frangible elements, ENSURE that at least one replacement element and tool are available","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":808,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Battery enclosure","help_text":"Where vented batteries are used, INSPECT the battery enclosure for evidence of corrosion.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":809,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Fire alarm","help_text":"SIMULATE an alarm condition and confirm that all required common or general visual and audible indications operate and the external alarm is activated. Where the system is monitored ensure the alarm has activated the alarm signalling equipment. Where CIE is a subindicator panel, confirm that the alarm condition is indicated at the FIP.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":810,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Occupant warning system","help_text":"SIMULATE an alarm and confirm the alarm initiates the occupant warning system including any visual warning devices (VWD).","sort_order":6,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":811,"active":true,"required":false,"type":"REMARK","label":"INITIATE - Isolate/Disable","help_text":"INITIATE an isolate/disable condition at the fire indicator panel and confirm that all required common or general visual and audible indications operate. Where the system is monitored, ensure the isolate is received by the monitoring service provider alarm signalling equipment. Where the panel is an SIP, confirm that the isolate/disable condition is indicated at the FIP as either a fault or isolate/disable.","sort_order":7,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":812,"active":true,"required":false,"type":"REMARK","label":"TEST - Filament visual indicators","help_text":"TEST the operation of each filament type visual indicators.","sort_order":8,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":813,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Zone block plan","help_text":"INSPECT zone block plans to ensure that they are securely mounted and legible and supplementary zone drawings, where required, are available and legible.","sort_order":9,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":814,"active":true,"required":false,"type":"REMARK","label":"‘Text deleted’","help_text":"‘Text deleted’","sort_order":10,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":815,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.1.3 (Six-monthly service)","help_text":"AS1851-2012 Table 6.4.1.3 (Six-monthly service)","sort_order":11,"ref":"2","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":816,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service","help_text":"Complete all monthly service activities, as listed in Table 6.4.1.2.","sort_order":12,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":817,"active":true,"required":false,"type":"REMARK","label":"CHECK - Local control station (LCS)","help_text":"(a) Ensure that they are clearly visible readily accessible and free from dust and contaminants.\n\n(b) Check that the door is correctly labelled.","sort_order":13,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":818,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Visual warning devices","help_text":"INSPECT all visual warning devices, including:\n\n• DO NOT ENTER\n• EVACUATE\n• FIRE ALARM\n• SYSTEM INOPERATIVE\n\nfor any condition or damage that is likely to adversely affect their function.","sort_order":14,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":819,"active":true,"required":false,"type":"REMARK","label":"TEST - Local control station (LCS) discharge inhibit switch","help_text":"TEST the operation of each inhibit or auto/manual switch and confirm that:\n\n(a) It prevents the automatic discharge of suppression system.\n\n(b) Stops and resets the normal system discharge sequence.\n\n(c) Causes the illumination of a visual indicator at the LCS and the system FIP.\n\n(d) Causes an audible indication.\n\n(e) Does not override the operation of the manual discharge switch.","sort_order":15,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":820,"active":true,"required":false,"type":"REMARK","label":"TEST - Local control station (LCS) manual initiate switch","help_text":"TEST the operation of the manual initiate switch and confirm normal system discharge sequence, including fire and evacuation alarms, time delays equipment shutdowns, and that it overrides the LCS discharge inhibit switch.","sort_order":16,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":821,"active":true,"required":false,"type":"REMARK","label":"CONFIRM - System inoperative visual warning device (VWD)","help_text":"CONFIRM the system inoperative VWD operates for:\n\n(a) Operation of a service switch (discharge initiating circuit electrical isolation).\n\n(b) Fault in the discharge actuator circuit.\n\n(c) Operation of a lock-off valve (where fitted).\n\n(d) Operation of a manual inhibit switch (where fitted).\n\n(e) Isolation or fault in any part of the fire detection or control system that prevents the automatic or electrical manual discharge of the suppression system.","sort_order":17,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":822,"active":true,"required":false,"type":"REMARK","label":"TEST - System operation and logic","help_text":"TEST the system logic (e.g. dual detector operation or dependency on more than one alarm) and confirm the operation of—\n\n• VWDs\n• audible alarms\n• directional valve signal/output\n• equipment fire mode signal/output\n• HVAC fire mode signal/output\n• system discharge actuator\n• door and damper release and\n• ancillary controls\n\n** ‘Text deleted’ **","sort_order":18,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":823,"active":true,"required":false,"type":"REMARK","label":"TEST - Actuator circuit faults","help_text":"TEST each supervised actuator circuit to ensure a fault is registered at the FIP.","sort_order":19,"ref":"2.8","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":824,"active":true,"required":false,"type":"REMARK","label":"TEST & CONFIRM - Actuator","help_text":"TEST the function of each actuator and ensure that each actuator operates correctly.\n\nEnsure that each actuator has been mechanically isolated or temporarily removed from the suppressant supply to prevent unintended discharge.\n\nFor non-resettable actuators (e.g. pyrotechnic types) substitute the actuator with a load of equivalent value and CONFIRM the operating current is as required.","sort_order":20,"ref":"2.9","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":825,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.1.4 (Annual service)","help_text":"AS1851-2012 Table 6.4.1.4 (Annual service)","sort_order":21,"ref":"3","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":826,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and sixmonthly service","help_text":"COMPLETE all monthly and six-monthly service activities, as listed in Table 6.4.1.2 and 6.4.1.3.","sort_order":22,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":827,"active":true,"required":false,"type":"REMARK","label":"CHECK - Manual call points","help_text":"CHECK all manual call points are free of conditions likely to adversely affect their function.","sort_order":23,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":828,"active":true,"required":false,"type":"REMARK","label":"TEST - Manual call points","help_text":"TEST the operation of each manual call point.","sort_order":24,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":829,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Other warning devices","help_text":"Where other warning devices are used as the alarm-indicating devices, INSPECT all devices to ensure that they are in place.","sort_order":25,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":830,"active":true,"required":false,"type":"REMARK","label":"TEST - Panel switches and keypads","help_text":"TEST the operation of each control.","sort_order":26,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":831,"active":true,"required":false,"type":"REMARK","label":"TEST - Visual indicators","help_text":"TEST the operation of each visual indicator and alphanumeric displays.","sort_order":27,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":832,"active":true,"required":false,"type":"REMARK","label":"MEASURE & CHECK - Battery","help_text":"MEASURE system quiescent and maximum alarm currents in accordance with Appendix F. Calculate the required battery capacity and CHECK the nominal capacity of the installed batteries is not less than the calculated capacity.\n\n** ‘Text deleted’ **","sort_order":28,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":833,"active":true,"required":false,"type":"REMARK","label":"TEST - Fire Detectors","help_text":"TEST detectors as specified in Appendix G and confirm correct alarm zone indication. Where the detectors are used as part of special hazards systems 100% of the detectors shall be functionally tested Annual.","sort_order":29,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":834,"active":true,"required":false,"type":"REMARK","label":"TEST - Audibility","help_text":"TEST the occupant warning system and check the signals are distinctly audible in all areas of the building.\n\n** NOTE: ** In order to reduce the disturbance to occupants an acceptable means of conducting this test is to provide an audio signal other than the warning signal at a reduced sound pressure level. Where the FIP is connected to a sound systems and intercom systems for emergency purposes (AS 1670.4) or EWIS (AS 2220.2) test in accordance with Table 6.4.3.2.","sort_order":30,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":835,"active":true,"required":false,"type":"REMARK","label":"MEASURE - Occupant warning system sound pressure level","help_text":"MEASURE and record the sound pressure level from at least one reference point for each amplifier used and ensure at each reference point the measured value is consistent with the required sound pressure level at each reference point.","sort_order":31,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":836,"active":true,"required":false,"type":"REMARK","label":"TEST - Alarm acknowledgement facility","help_text":"TEST not less than 20% of installed alarm acknowledgement facilities in such a manner that over a 5-year period, all facilities are tested. CHECK the alarm acknowledgement facility functions as required.","sort_order":32,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":837,"active":true,"required":false,"type":"REMARK","label":"TEST - Alarm investigation facility","help_text":"TEST the alarm investigation facility if enabled and check it functions as required.","sort_order":33,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":838,"active":true,"required":false,"type":"REMARK","label":"TEST - Batteries condition","help_text":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","sort_order":34,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":839,"active":true,"required":false,"type":"REMARK","label":"Smoke alarms and heat alarms","help_text":"Refer to Clause 6.4.2.","sort_order":35,"ref":"3.14","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":840,"active":true,"required":false,"type":"REMARK","label":"INSPECT & REPORT - Service life","help_text":"Inspect detectors, equipment or other items having a defined service life and report where the service life is exceeded or will be exceeded before the next scheduled service.","sort_order":36,"ref":"3.15","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":841,"active":true,"required":false,"type":"REMARK","label":"SURVEY - Protected areas survey","help_text":"SURVEY all areas of the building from floor level and check—\n\n(a) that the fire detection and alarm system has not been altered, damaged or compromised;\n\n(b) detection device and remote indicators are appropriate for the current use;\n\n(c) for any condition that may cause a nuisance alarm or the unintentional operation of a suppression system;\n\n(d) all exposed cabling, conduits, junction boxes and the like for any condition that may impact on the performance of the system and are labelled correctly; and\n\n(e) all CIE to ensure all components are appropriately mounted and secure.","sort_order":37,"ref":"3.17","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":842,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Interfaced system initiation","help_text":"Simulate alarm(s) to verify that each interface transmission path initiates the corresponding interfaced system(s) as required.","sort_order":38,"ref":"3.18","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":843,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table6.4.1.5 (Five Annual service)","help_text":"AS1851-2012 Table6.4.1.5 (Five Annual service)","sort_order":39,"ref":"4","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":844,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly, sixmonthly and Annual service","help_text":"Complete all monthly, six-monthly and Annual service activities, as listed in Tables 6.4.1.2, 6.4.1.3 and 6.4.1.4.","sort_order":40,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":845,"active":true,"required":false,"type":"REMARK","label":"TEST - Supervised circuits","help_text":"TEST each input and output supervised circuit for any condition that prevents the transmission of the required signal and ensure a fault is registered at the FIP.","sort_order":41,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":846,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Fault","help_text":"SIMULATE a circuit fault condition at the FIP and confirm that all required common or general visual and audible indications operate. Where such faults are monitored, ensure the fault has activated the alarm signalling equipment. Where the panel is an SIP confirm that the fault condition is indicated at the FIP.","sort_order":42,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":847,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Addressable short circuit isolators","help_text":"Apply short circuits as required to verify that the short circuit isolation functions as required.","sort_order":43,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":848,"active":true,"required":false,"type":"REMARK","label":"REDUCE & CONFIRM - Power supply supervision","help_text":"Where the system is monitored, REDUCE the CIE operating voltage to trigger a power supply supervision fault and CONFIRM that it is received by the monitoring service provider. Where the panel is an SIP or a distributed power supply, confirm that the power supply supervision fault condition is indicated at least as a fault at the FIP.","sort_order":44,"ref":"4.5","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":849,"active":true,"required":false,"type":"REMARK","label":"REMOVE - Collective detection circuits","help_text":"For each collective fire detection circuit,\n\nREMOVE the last detector or device on the circuit and confirm that a fault signal is registered at the CIE.","sort_order":45,"ref":"4.6","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":850,"active":true,"required":false,"type":"REMARK","label":"CONDUCT & VERIFY - Interface and control test","help_text":"CONDUCT a functional test with each system’s interface and VERIFY that each interfaced system responds to the signal as required (see Appendix D).","sort_order":46,"ref":"4.7","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":851,"active":true,"required":false,"type":"INTEGER","label":"MEASURE & RECORD - Occupant warning system speaker circuits","help_text":"MEASURE and record the impedance of each loud speaker circuit and check that it has not changed by more than 15% from the last test nor exceeded the rated output as required for the amplifier.","sort_order":47,"ref":"4.8","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":852,"active":true,"required":false,"type":"REMARK","label":"TEST - Monitoring connection","help_text":"Where the system is monitored, TEST that the loss of each of the monitoring links is indicated at the monitored site.","sort_order":48,"ref":"4.9","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":853,"active":true,"required":false,"type":"REMARK","label":"TEST - Alarm verification facility","help_text":"TEST one detector of each type per circuit with alarm verification facility enabled to check that it functions as required.","sort_order":49,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Fire Detection: Fire Indicator Panel (FDCIE)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Detection: Smoke and Heat Alarms","prompts":[{"id":789,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.2.2 (Six-monthly service)","help_text":"AS1851-2012 Table 6.4.2.2 (Six-monthly service)","sort_order":1,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":790,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Smoke alarms and heat alarms","help_text":"INSPECT all alarms for any condition that is likely to adversely affect their operation, such as excessive deposition of dust or coating of paint.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":791,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Battery missing indication","help_text":"INSPECT all alarms to ensure that any required ‘battery missing indicator’ has not operated.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":792,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Mains power on indicator","help_text":"INSPECT that the mains power on indicator is illuminated.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":793,"active":true,"required":false,"type":"REMARK","label":"ACTIVATE & CHECK - Alarm test","help_text":"ACTIVATE the alarm test function and check correct activation of the audible indication.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":794,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Other warning devices","help_text":"Where other sensory warning devices are used as alarm-indicating devices, INSPECT all devices to ensure that they are in place.","sort_order":6,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":795,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.2.3 (Annual service)","help_text":"AS1851-2012 Table 6.4.2.3 (Annual service)","sort_order":7,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":796,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly service","help_text":"COMPLETE all six-monthly service activities, as listed in Table 6.4.2.2.","sort_order":8,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":797,"active":true,"required":false,"type":"REMARK","label":"TEST - Interconnecting alarms","help_text":"Where alarms are interconnected, TEST that the activation of each alarm operates the audible alarm indication in other alarms.","sort_order":9,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":798,"active":true,"required":false,"type":"REMARK","label":"TEST - Smoke alarms","help_text":"TEST 100% of smoke alarms in accordance with the manufacturer’s instructions.","sort_order":10,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":799,"active":true,"required":false,"type":"REMARK","label":"TEST - Heat alarms","help_text":"TEST 100% of heat alarms in accordance with the manufacturer’s instructions.","sort_order":11,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":800,"active":true,"required":false,"type":"REMARK","label":"TEST - Other warning devices","help_text":"Where other sensory warning devices are used as alarm-indicating devices, TEST all devices to ensure that they are functioning correctly.","sort_order":12,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":801,"active":true,"required":false,"type":"REMARK","label":"CLEAN - Smoke alarms and heat alarms","help_text":"CLEAN each alarm in accordance with the manufacturer’s instructions.","sort_order":13,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":802,"active":true,"required":false,"type":"REMARK","label":"CHECK - Batteries","help_text":"CHECK the manufacturer’s requirements for battery replacement and replace the battery if required.","sort_order":14,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":803,"active":true,"required":false,"type":"REMARK","label":"REPLACE - Service life","help_text":"REPLACE smoke alarms and heat alarms where the service life date is exceeded.","sort_order":15,"ref":"2.8","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":804,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Survey—Spacing and location","help_text":"INSPECT each alarm to ensure spacing and location requirements are as required.","sort_order":16,"ref":"2.9","estimated_duration":null,"prompt_set":"2012: Fire Detection: Smoke and Heat Alarms","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","prompts":[{"id":970,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 10.4.1 (Six-monthly)","help_text":"AS1851-2012 Table 10.4.1 (Six-monthly)","sort_order":0,"ref":"1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":971,"active":true,"required":false,"type":"REMARK","label":"CHECK - Accessibility","help_text":"CHECK the extinguisher is conspicuous, readily accessible and in its assigned location.\n\n- All extinguishers types","sort_order":1,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":972,"active":true,"required":false,"type":"REMARK","label":"CHECK - Anti-tamper device","help_text":"CHECK that the anti-tamper device is intact.\n\n- All extinguishers types","sort_order":2,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":973,"active":true,"required":false,"type":"REMARK","label":"CHECK - Exterior and operating instructions","help_text":"CHECK that the extinguisher is clean and the operating instructions are legible.","sort_order":3,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":974,"active":true,"required":false,"type":"REMARK","label":"CHECK - Service tag or label","help_text":"CHECK that the service tag or label is firmly attached to the extinguisher.\n\n- All extinguishers types","sort_order":4,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":975,"active":true,"required":false,"type":"REMARK","label":"CHECK - External damage","help_text":"CHECK that the extinguisher, including any attachments, is not damaged (see AS 2337.1).\n\n- All extinguishers types","sort_order":5,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":976,"active":true,"required":false,"type":"REMARK","label":"CHECK - External corrosion","help_text":"CHECK that the exterior of the extinguisher is not pitted or otherwise damaged by corrosion (see Clause 10.2.5 and AS 2337.1).\n\n- All extinguishers types","sort_order":6,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":977,"active":true,"required":false,"type":"REMARK","label":"CHECK - Outlet hose assembly","help_text":"CHECK that the hose is securely fitted, the nozzle is securely attached, the assembly is free from obstruction, and the hose shows no cracking or other signs of damage or deterioration.\n\n- All extinguishers types","sort_order":7,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":978,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure indicator","help_text":"Where fitted, CHECK that the pressure indicator is legible, and registering within the operable range.\n\n- All extinguishers types","sort_order":8,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":979,"active":true,"required":false,"type":"REMARK","label":"WEIGH - Contents","help_text":"WEIGH the extinguisher to determine that it is fully charged.\n\n- All extinguisher types","sort_order":9,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":980,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage","help_text":"CHECK that the location sign is visible.\n\n- All extinguishers types","sort_order":10,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":981,"active":true,"required":false,"type":"REMARK","label":"CHECK - Support bracket","help_text":"CHECK that the appropriate support bracket is securely attached to wall or other suitable feature.\n\n- All extinguishers types","sort_order":11,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":982,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discharge nozzle","help_text":"CHECK that the appropriate discharge nozzle is fitted and is not blocked or damaged.\n\n- All extinguishers types","sort_order":12,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":983,"active":true,"required":false,"type":"REMARK","label":"INVERT - Powder— Portable extinguishers","help_text":"INVERT the extinguisher and ensure that the powder remains free flowing.\n\n- Powder (stored pressure), powder (gas container)","sort_order":13,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":984,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Compressed gas container","help_text":"DETERMINE that the compressed gas container is the correct size and type, in good condition, fully charged, and subjected to service as per AS 2030.5.\n\n-  All gas container extinguishers","sort_order":14,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":985,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Actuating device","help_text":"DETERMINE, where possible and without discharging any contents, that the actuating device is free of corrosion, moves freely and is undamaged.\n\n- Water (stored pressure), wet chemical, foam\n- (stored pressure), powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":15,"ref":"1.17","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1168,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Internal components","help_text":"DETERMINE that the internal discharge tube and strainer (where fitted) provide clear passage and are securely attached.\n\n- Water (gas container), foam (gas container)","sort_order":16,"ref":"1.18","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":986,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 10.4.2 (Annual service)","help_text":"AS1851-2012 Table 10.4.2 (Annual service)","sort_order":17,"ref":"2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":987,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly service","help_text":"COMPLETE all six-monthly service activities, as listed in Table 10.4.1.","sort_order":18,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1169,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operating head or cap","help_text":"CHECK that the threads on operating head or cap are not damaged, vent(s) is (are) not blocked, and any strainer or expansion device is unobstructed. For heads with no screw thread, determine that security locking device is undamaged and operational.\n\n- Water (gas container), foam (gas container), water with additive (stored pressure), foam (stored pressure), powder (gas container)","sort_order":19,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":988,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discharge","help_text":"CHECK that the extinguisher functions in accordance with the operating instructions and that the discharge is satisfactory. Recharge in accordance with Item 2.8.\n\n(a) Water with additive (stored pressure), foam (stored pressure)\n\n(b) Water with corrosion inhibitors or freezing point depressants (stored pressure)*\n\n* To be discharged on a three-Annual frequency.","sort_order":20,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":989,"active":true,"required":false,"type":"REMARK","label":"CHECK - Actuating device","help_text":"CHECK that the actuating device is free of corrosion, moves freely, and is undamaged; any cutting edge is sharp; and all sealing gaskets are in good condition.\n\n- Water (gas container), foam (gas container), foam (stored pressure) powder (gas container)","sort_order":21,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1170,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components - Water with additive, foam","help_text":"(a) CHECK that the internal discharge tube, strainer and anti-overfill tube (where fitted) provide clear passage and are securely attached, and that the anti-overfill device is undamaged.\n\n- Water with additive (stored pressure), foam (stored pressure)","sort_order":22,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":990,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components - Powder (gas container)","help_text":"(b) CHECK that the internal discharge tube, or the gas inlet tube or ports, provide clear passage and are correctly installed, and that the powder is free flowing.\n\n- Powder (gas container)","sort_order":23,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":991,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal condition— Portable extinguishers","help_text":"CHECK that the interior of cylinder is clean, is not pitted by corrosion (see AS 2337.1), and any internal lining is in good condition.\n\n- Water (gas container), water with additive (stored pressure), foam (gas container), foam (stored pressure), powder (gas container)","sort_order":24,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":992,"active":true,"required":false,"type":"REMARK","label":"RECHARGE - Extinguishing agent replacement","help_text":"RECHARGE the extinguisher with fresh extinguishing agent in accordance with the manufacturer’s instructions.\n\n- Water with additive (stored pressure), foam (gas container), foam (stored pressure)\n\nUpon the completion of recharging stored pressure type extinguishers, perform a leak test as per Item 2.10.","sort_order":25,"ref":"2.8","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":993,"active":true,"required":false,"type":"REMARK","label":"CHECK - Seals","help_text":"CHECK that the operating head or cap seal is in good condition.\n\n- Water (gas container), water with additive (stored pressure), foam (gas container), foam (stored pressure), powder (gas container)","sort_order":26,"ref":"2.9","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":994,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leak detection","help_text":"CHECK if there are any leaks at the joints and seals that were renewed or disturbed during recharging.\n\nWater with additive (stored pressure), foam (stored pressure)","sort_order":27,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":995,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire hazard","help_text":"CHECK that the fire hazard/risk to be protected has not changed.\n\n- All extinguisher types","sort_order":28,"ref":"2.11","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":996,"active":true,"required":false,"type":"REMARK","label":"CHECK - Suitability","help_text":"CHECK that the extinguisher is the correct type, class, size and/or rating for the hazard to be protected.\n\n- All extinguisher types","sort_order":29,"ref":"2.12","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":997,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstructions","help_text":"(a) CHECK that no alterations have been made to the building that may impede access to the extinguisher or increase the travel distances to more than those required.\n\n- All portable extinguishers","sort_order":30,"ref":"2.13","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1143,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 10.4.3 (Five-yearly service)","help_text":"AS1851-2012 Table 10.4.3 (Five-Annual service)","sort_order":31,"ref":"3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1144,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly and Annual service","help_text":"COMPLETE all six-monthly and Annual service activities, as listed in Table 10.4.1 and 10.4.2.","sort_order":32,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1145,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discharge","help_text":"CHECK that the extinguisher functions in accordance with the operating instructions and that the discharge is satisfactory. Recharge in accordance with Item 3.9.\n\n- Water (gas container), water (stored pressure), wet chemical, foam (gas container), powder\n\n- (gas container), powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":33,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1171,"active":true,"required":false,"type":"REMARK","label":"CHECK - Actuating device","help_text":"CHECK that the actuating device is free of corrosion, moves freely, and is undamaged; any cutting edge is sharp; and all sealing gaskets are in good condition.\n\n- Water (stored pressure), wet chemical, powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":34,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1172,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components","help_text":"(a) CHECK that the internal discharge tube, strainer and anti-overfill tube (where fitted) provide clear passage and are securely attached, and that the anti overfill device is undamaged.\n\n- Water (stored pressure), wet chemical","sort_order":35,"ref":"3.4(a)","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1146,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components","help_text":"(b) CHECK that the internal discharge tube provides clear passage, is securely attached, and there is no evidence of moisture or foreign matter in the cylinder.\n\n- Powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":36,"ref":"3.4(b)","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1173,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal condition— Portable extinguishers","help_text":"CHECK that the interior of the cylinder is clean, is not pitted by corrosion (see AS 2337.1), and any internal lining is in good condition.\n\n- Where the lining cannot be removed to inspect the interior of the cylinder, the cylinder shall be accepted or rejected as per AS 2337.1.\n\n- Water (stored pressure), wet chemical, powder (stored pressure), vaporizing liquid.\n\n- For carbon dioxide extinguishers, this examination shall be in accordance with AS 2030.5, and shall be performed at a gas cylinder test station certified by a registered certifying body (see AS 2337.1).","sort_order":37,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1147,"active":true,"required":false,"type":"REMARK","label":"CHECK - Seals","help_text":"CHECK that the operating head or cap seal is in good condition.\n\nWater (stored pressure), wet chemical, powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":38,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1148,"active":true,"required":false,"type":"REMARK","label":"SUBJECT - Pressure test: Portable extinguishers","help_text":"(a) SUBJECT the extinguisher body to a hydrostatic pressure test of 1.5 times the working pressure, the marked periodic test pressure, or 2 MPa, whichever is the greatest.\n\n- Water (gas container), water (stored pressure), wet chemical, foam (gas container), foam (stored pressure), powder (gas container), powder (stored pressure), vaporizing liquid\n\n(b) SUBJECT the extinguisher body to a hydrostatic pressure test, in accordance with the requirements of AS 2030.5, at a Gas Cylinder Test Station certified by a Registered Certifying body (see AS 2337.1).\n\n - Carbon dioxide","sort_order":39,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1149,"active":true,"required":false,"type":"REMARK","label":"RECHARGE - Extinguishing agent replacement","help_text":"At the frequency specified by the extinguishing manufacturer, RECHARGE the extinguisher with fresh extinguishing agent, as specified on the extinguisher label, in accordance with the manufacturer’s instructions.\n\nWet chemical, foam (gas container with sealed foam liquid container), powder (gas container), powder (stored pressure), carbon dioxide, vaporizing liquid\n\nUpon the completion of recharging stored pressure type extinguishers, perform a leak test as per Item 3.12.","sort_order":40,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1150,"active":true,"required":false,"type":"REMARK","label":"RENEW - Seals and gaskets","help_text":"RENEW all seals and gaskets fitted to the actuating device, operating head, or cap.\n\n - All extinguisher types","sort_order":41,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1151,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leak detection","help_text":"CHECK if there are any leaks at the joints and seals that were renewed or disturbed during recharging.\n\n- Water (stored pressure), wet chemical, foam (stored pressure), powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":42,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Adverse Enviroment (Portable)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Extinguisher: Portable","prompts":[{"id":934,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 10.4.1 (Six-monthly)","help_text":"AS1851-2012 Table 10.4.1 (Six-monthly)","sort_order":0,"ref":"1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":935,"active":true,"required":false,"type":"REMARK","label":"CHECK - Accessibility","help_text":"CHECK the extinguisher is conspicuous, readily accessible and in its assigned location.\n\n- All extinguishers types","sort_order":1,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":936,"active":true,"required":false,"type":"REMARK","label":"CHECK - Anti-tamper device","help_text":"CHECK that the anti-tamper device is intact.\n\n- All extinguishers types","sort_order":2,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":937,"active":true,"required":false,"type":"REMARK","label":"CHECK - Exterior and operating instructions","help_text":"CHECK that the extinguisher is clean and the operating instructions are legible.","sort_order":3,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":938,"active":true,"required":false,"type":"REMARK","label":"CHECK - Service tag or label","help_text":"CHECK that the service tag or label is firmly attached to the extinguisher.\n\n- All extinguishers types","sort_order":4,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":939,"active":true,"required":false,"type":"REMARK","label":"CHECK - External damage","help_text":"CHECK that the extinguisher, including any attachments, is not damaged (see AS 2337.1).\n\n- All extinguishers types","sort_order":5,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":940,"active":true,"required":false,"type":"REMARK","label":"CHECK - External corrosion","help_text":"CHECK that the exterior of the extinguisher is not pitted or otherwise damaged by corrosion (see Clause 10.2.5 and AS 2337.1).\n\n- All extinguishers types","sort_order":6,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":941,"active":true,"required":false,"type":"REMARK","label":"CHECK - Outlet hose assembly","help_text":"CHECK that the hose is securely fitted, the nozzle is securely attached, the assembly is free from obstruction, and the hose shows no cracking or other signs of damage or deterioration.\n\n- All extinguishers types","sort_order":7,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":942,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure indicator","help_text":"Where fitted, CHECK that the pressure indicator is legible, and registering within the operable range.\n\n- All extinguishers types","sort_order":8,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":943,"active":true,"required":false,"type":"REMARK","label":"WEIGH - Contents","help_text":"WEIGH the extinguisher to determine that it is fully charged.\n\n- All extinguisher types","sort_order":9,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":944,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage","help_text":"CHECK that the location sign is visible.\n\n- All extinguishers types","sort_order":10,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":945,"active":true,"required":false,"type":"REMARK","label":"CHECK - Support bracket","help_text":"CHECK that the appropriate support bracket is securely attached to wall or other suitable feature.\n\n- All extinguishers types","sort_order":11,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":946,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discharge nozzle","help_text":"CHECK that the appropriate discharge nozzle is fitted and is not blocked or damaged.\n\n- All extinguishers types","sort_order":12,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":947,"active":true,"required":false,"type":"REMARK","label":"INVERT - Powder— Portable extinguishers","help_text":"INVERT the extinguisher and ensure that the powder remains free flowing.\n\n- Powder (stored pressure), powder (gas container)","sort_order":13,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":948,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Compressed gas container","help_text":"DETERMINE that the compressed gas container is the correct size and type, in good condition, fully charged, and subjected to service as per AS 2030.5.\n\n-  All gas container extinguishers","sort_order":14,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":949,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Actuating device","help_text":"DETERMINE, where possible and without discharging any contents, that the actuating device is free of corrosion, moves freely and is undamaged.\n\n- Water (stored pressure), wet chemical, foam\n- (stored pressure), powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":15,"ref":"1.17","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1142,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Internal components","help_text":"DETERMINE that the internal discharge tube and strainer (where fitted) provide clear passage and are securely attached.\n\n- Water (gas container), foam (gas container)","sort_order":16,"ref":"1.18","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":950,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 10.4.2 (Annual service)","help_text":"AS1851-2012 Table 10.4.2 (Annual service)","sort_order":17,"ref":"2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":951,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly service","help_text":"COMPLETE all six-monthly service activities, as listed in Table 10.4.1.","sort_order":18,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1162,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operating head or cap","help_text":"CHECK that the threads on operating head or cap are not damaged, vent(s) is (are) not blocked, and any strainer or expansion device is unobstructed. For heads with no screw thread, determine that security locking device is undamaged and operational.\n\n- Water (gas container), foam (gas container), water with additive (stored pressure), foam (stored pressure), powder (gas container)","sort_order":19,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":952,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discharge","help_text":"CHECK that the extinguisher functions in accordance with the operating instructions and that the discharge is satisfactory. Recharge in accordance with Item 2.8.\n\n(a) Water with additive (stored pressure), foam (stored pressure)\n\n(b) Water with corrosion inhibitors or freezing point depressants (stored pressure)*\n\n* To be discharged on a three-Annual frequency.","sort_order":20,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":953,"active":true,"required":false,"type":"REMARK","label":"CHECK - Actuating device","help_text":"CHECK that the actuating device is free of corrosion, moves freely, and is undamaged; any cutting edge is sharp; and all sealing gaskets are in good condition.\n\n- Water (gas container), foam (gas container), foam (stored pressure) powder (gas container)","sort_order":21,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1163,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components - Water with additive, foam","help_text":"(a) CHECK that the internal discharge tube, strainer and anti-overfill tube (where fitted) provide clear passage and are securely attached, and that the anti-overfill device is undamaged.\n\n- Water with additive (stored pressure), foam (stored pressure)","sort_order":22,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":954,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components - Powder (gas container)","help_text":"(b) CHECK that the internal discharge tube, or the gas inlet tube or ports, provide clear passage and are correctly installed, and that the powder is free flowing.\n\n- Powder (gas container)","sort_order":23,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":955,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal condition— Portable extinguishers","help_text":"CHECK that the interior of cylinder is clean, is not pitted by corrosion (see AS 2337.1), and any internal lining is in good condition.\n\n- Water (gas container), water with additive (stored pressure), foam (gas container), foam (stored pressure), powder (gas container)","sort_order":24,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":956,"active":true,"required":false,"type":"REMARK","label":"RECHARGE - Extinguishing agent replacement","help_text":"RECHARGE the extinguisher with fresh extinguishing agent in accordance with the manufacturer’s instructions.\n\n- Water with additive (stored pressure), foam (gas container), foam (stored pressure)\n\nUpon the completion of recharging stored pressure type extinguishers, perform a leak test as per Item 2.10.","sort_order":25,"ref":"2.8","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":957,"active":true,"required":false,"type":"REMARK","label":"CHECK - Seals","help_text":"CHECK that the operating head or cap seal is in good condition.\n\n- Water (gas container), water with additive (stored pressure), foam (gas container), foam (stored pressure), powder (gas container)","sort_order":26,"ref":"2.9","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":958,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leak detection","help_text":"CHECK if there are any leaks at the joints and seals that were renewed or disturbed during recharging.\n\nWater with additive (stored pressure), foam (stored pressure)","sort_order":27,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":959,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire hazard","help_text":"CHECK that the fire hazard/risk to be protected has not changed.\n\n- All extinguisher types","sort_order":28,"ref":"2.11","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":960,"active":true,"required":false,"type":"REMARK","label":"CHECK - Suitability","help_text":"CHECK that the extinguisher is the correct type, class, size and/or rating for the hazard to be protected.\n\n- All extinguisher types","sort_order":29,"ref":"2.12","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":961,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstructions","help_text":"(a) CHECK that no alterations have been made to the building that may impede access to the extinguisher or increase the travel distances to more than those required.\n\n- All portable extinguishers","sort_order":30,"ref":"2.13","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":962,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 10.4.3 (Five-yearly service)","help_text":"AS1851-2012 Table 10.4.3 (Five-Annual service)","sort_order":31,"ref":"3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":963,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly and Annual service","help_text":"COMPLETE all six-monthly and Annual service activities, as listed in Table 10.4.1 and 10.4.2.","sort_order":32,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":964,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discharge","help_text":"CHECK that the extinguisher functions in accordance with the operating instructions and that the discharge is satisfactory. Recharge in accordance with Item 3.9.\n\n- Water (gas container), water (stored pressure), wet chemical, foam (gas container), powder\n\n- (gas container), powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":33,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1164,"active":true,"required":false,"type":"REMARK","label":"CHECK - Actuating device","help_text":"CHECK that the actuating device is free of corrosion, moves freely, and is undamaged; any cutting edge is sharp; and all sealing gaskets are in good condition.\n\n- Water (stored pressure), wet chemical, powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":34,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1165,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components","help_text":"(a) CHECK that the internal discharge tube, strainer and anti-overfill tube (where fitted) provide clear passage and are securely attached, and that the anti overfill device is undamaged.\n\n- Water (stored pressure), wet chemical","sort_order":35,"ref":"3.4(a)","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":965,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components","help_text":"(b) CHECK that the internal discharge tube provides clear passage, is securely attached, and there is no evidence of moisture or foreign matter in the cylinder.\n\n- Powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":36,"ref":"3.4(b)","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1166,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal condition— Portable extinguishers","help_text":"CHECK that the interior of the cylinder is clean, is not pitted by corrosion (see AS 2337.1), and any internal lining is in good condition.\n\n- Where the lining cannot be removed to inspect the interior of the cylinder, the cylinder shall be accepted or rejected as per AS 2337.1.\n\n- Water (stored pressure), wet chemical, powder (stored pressure), vaporizing liquid.\n\n- For carbon dioxide extinguishers, this examination shall be in accordance with AS 2030.5, and shall be performed at a gas cylinder test station certified by a registered certifying body (see AS 2337.1).","sort_order":37,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":966,"active":true,"required":false,"type":"REMARK","label":"CHECK - Seals","help_text":"CHECK that the operating head or cap seal is in good condition.\n\nWater (stored pressure), wet chemical, powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":38,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":967,"active":true,"required":false,"type":"REMARK","label":"SUBJECT - Pressure test: Portable extinguishers","help_text":"(a) SUBJECT the extinguisher body to a hydrostatic pressure test of 1.5 times the working pressure, the marked periodic test pressure, or 2 MPa, whichever is the greatest.\n\n- Water (gas container), water (stored pressure), wet chemical, foam (gas container), foam (stored pressure), powder (gas container), powder (stored pressure), vaporizing liquid\n\n(b) SUBJECT the extinguisher body to a hydrostatic pressure test, in accordance with the requirements of AS 2030.5, at a Gas Cylinder Test Station certified by a Registered Certifying body (see AS 2337.1).\n\n - Carbon dioxide","sort_order":39,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":968,"active":true,"required":false,"type":"REMARK","label":"RECHARGE - Extinguishing agent replacement","help_text":"At the frequency specified by the extinguishing manufacturer, RECHARGE the extinguisher with fresh extinguishing agent, as specified on the extinguisher label, in accordance with the manufacturer’s instructions.\n\nWet chemical, foam (gas container with sealed foam liquid container), powder (gas container), powder (stored pressure), carbon dioxide, vaporizing liquid\n\nUpon the completion of recharging stored pressure type extinguishers, perform a leak test as per Item 3.12.","sort_order":40,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":969,"active":true,"required":false,"type":"REMARK","label":"RENEW - Seals and gaskets","help_text":"RENEW all seals and gaskets fitted to the actuating device, operating head, or cap.\n\n - All extinguisher types","sort_order":41,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1167,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leak detection","help_text":"CHECK if there are any leaks at the joints and seals that were renewed or disturbed during recharging.\n\n- Water (stored pressure), wet chemical, foam (stored pressure), powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":42,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Portable","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Extinguisher: Wheeled","prompts":[{"id":998,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 10.4.1 (Six-monthly)","help_text":"AS1851-2012 Table 10.4.1 (Six-monthly)","sort_order":0,"ref":"1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":999,"active":true,"required":false,"type":"REMARK","label":"CHECK - Accessibility","help_text":"CHECK the extinguisher is conspicuous, readily accessible and in its assigned location.\n\n- All extinguishers types","sort_order":1,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1000,"active":true,"required":false,"type":"REMARK","label":"CHECK - Anti-tamper device","help_text":"CHECK that the anti-tamper device is intact.\n\n- All extinguishers types","sort_order":2,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1001,"active":true,"required":false,"type":"REMARK","label":"CHECK - Exterior and operating instructions","help_text":"CHECK that the extinguisher is clean and the operating instructions are legible.","sort_order":3,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1002,"active":true,"required":false,"type":"REMARK","label":"CHECK - Service tag or label","help_text":"CHECK that the service tag or label is firmly attached to the extinguisher.\n\n- All extinguishers types","sort_order":4,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1003,"active":true,"required":false,"type":"REMARK","label":"CHECK - External damage","help_text":"CHECK that the extinguisher, including any attachments, is not damaged (see AS 2337.1).\n\n- All extinguishers types","sort_order":5,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1004,"active":true,"required":false,"type":"REMARK","label":"CHECK - External corrosion","help_text":"CHECK that the exterior of the extinguisher is not pitted or otherwise damaged by corrosion (see Clause 10.2.5 and AS 2337.1).\n\n- All extinguishers types","sort_order":6,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1005,"active":true,"required":false,"type":"REMARK","label":"CHECK - Outlet hose assembly","help_text":"CHECK that the hose is securely fitted, the nozzle is securely attached, the assembly is free from obstruction, and the hose shows no cracking or other signs of damage or deterioration.\n\n- All extinguishers types","sort_order":7,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1006,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure indicator","help_text":"Where fitted, CHECK that the pressure indicator is legible, and registering within the operable range.\n\n- All extinguishers types","sort_order":8,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1007,"active":true,"required":false,"type":"REMARK","label":"WEIGH - Contents","help_text":"WEIGH the extinguisher to determine that it is fully charged.\n\n- All extinguisher types","sort_order":9,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1008,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage","help_text":"CHECK that the location sign is visible.\n\n- All extinguishers types","sort_order":10,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1009,"active":true,"required":false,"type":"REMARK","label":"CHECK - Support bracket","help_text":"CHECK that the appropriate support bracket is securely attached to wall or other suitable feature.\n\n- All extinguishers types","sort_order":11,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1010,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discharge nozzle","help_text":"CHECK that the appropriate discharge nozzle is fitted and is not blocked or damaged.\n\n- All extinguishers types","sort_order":12,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1011,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discharge nozzle and control valve","help_text":"CHECK that the discharge nozzle is not blocked and that the control valve is functional.\n\n- All wheeled extinguishers","sort_order":13,"ref":"1.13","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1012,"active":true,"required":false,"type":"REMARK","label":"CHECK - Carriage assembly","help_text":"CHECK that the carriage assembly is functional and free from corrosion.\n\n- All wheeled extinguishers","sort_order":14,"ref":"1.14","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1013,"active":true,"required":false,"type":"REMARK","label":"INVERT - Powder— Portable extinguishers","help_text":"INVERT the extinguisher and ensure that the powder remains free flowing.\n\n- Powder (stored pressure), powder (gas container)","sort_order":15,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1014,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Compressed gas container","help_text":"DETERMINE that the compressed gas container is the correct size and type, in good condition, fully charged, and subjected to service as per AS 2030.5.\n\n-  All gas container extinguishers","sort_order":16,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1015,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Actuating device","help_text":"DETERMINE, where possible and without discharging any contents, that the actuating device is free of corrosion, moves freely and is undamaged.\n\n- Water (stored pressure), wet chemical, foam\n- (stored pressure), powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":17,"ref":"1.17","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1180,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Internal components","help_text":"DETERMINE that the internal discharge tube and strainer (where fitted) provide clear passage and are securely attached.\n\n- Water (gas container), foam (gas container)","sort_order":18,"ref":"1.18","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1016,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Tyres","help_text":"DETERMINE that pneumatic tyres, where fitted, are pressurized to the recommended pressure.\n\n- All wheeled extinguishers","sort_order":19,"ref":"1.19","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1017,"active":true,"required":false,"type":"REMARK","label":"LUBRICATE - Wheels","help_text":"LUBRICATE wheel bearings (where applicable).\n\n- All wheeled extinguishers","sort_order":20,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1018,"active":true,"required":false,"type":"REMARK","label":"CHECK - Mobility","help_text":"CHECK that the extinguisher moves readily on its wheels by rolling it for a distance of at least 5 m.\n\n- All wheeled extinguishers","sort_order":21,"ref":"1.21","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1019,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 10.4.2 (Annual service)","help_text":"AS1851-2012 Table 10.4.2 (Annual service)","sort_order":22,"ref":"2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1020,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly service","help_text":"COMPLETE all six-monthly service activities, as listed in Table 10.4.1.","sort_order":23,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1174,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operating head or cap","help_text":"CHECK that the threads on operating head or cap are not damaged, vent(s) is (are) not blocked, and any strainer or expansion device is unobstructed. For heads with no screw thread, determine that security locking device is undamaged and operational.\n\n- Water (gas container), foam (gas container), water with additive (stored pressure), foam (stored pressure), powder (gas container)","sort_order":24,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1021,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discharge","help_text":"CHECK that the extinguisher functions in accordance with the operating instructions and that the discharge is satisfactory. Recharge in accordance with Item 2.8.\n\n(a) Water with additive (stored pressure), foam (stored pressure)\n\n(b) Water with corrosion inhibitors or freezing point depressants (stored pressure)*\n\n* To be discharged on a three-Annual frequency.","sort_order":25,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1022,"active":true,"required":false,"type":"REMARK","label":"CHECK - Actuating device","help_text":"CHECK that the actuating device is free of corrosion, moves freely, and is undamaged; any cutting edge is sharp; and all sealing gaskets are in good condition.\n\n- Water (gas container), foam (gas container), foam (stored pressure) powder (gas container)","sort_order":26,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1175,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components - Water with additive, foam","help_text":"(a) CHECK that the internal discharge tube, strainer and anti-overfill tube (where fitted) provide clear passage and are securely attached, and that the anti-overfill device is undamaged.\n\n- Water with additive (stored pressure), foam (stored pressure)","sort_order":27,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1176,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components - Powder (gas container)","help_text":"(b) CHECK that the internal discharge tube, or the gas inlet tube or ports, provide clear passage and are correctly installed, and that the powder is free flowing.\n\n- Powder (gas container)","sort_order":28,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1023,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal condition— Portable extinguishers","help_text":"CHECK that the interior of cylinder is clean, is not pitted by corrosion (see AS 2337.1), and any internal lining is in good condition.\n\n- Water (gas container), water with additive (stored pressure), foam (gas container), foam (stored pressure), powder (gas container)","sort_order":29,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1024,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal condition— Wheeled extinguishers","help_text":"CHECK that the interior of cylinder is clean.\n\n- Water (gas container), foam (gas container), foam (stored pressure)","sort_order":30,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1025,"active":true,"required":false,"type":"REMARK","label":"RECHARGE - Extinguishing agent replacement","help_text":"RECHARGE the extinguisher with fresh extinguishing agent in accordance with the manufacturer’s instructions.\n\n- Water with additive (stored pressure), foam (gas container), foam (stored pressure)\n\nUpon the completion of recharging stored pressure type extinguishers, perform a leak test as per Item 2.10.","sort_order":31,"ref":"2.8","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1026,"active":true,"required":false,"type":"REMARK","label":"CHECK - Seals","help_text":"CHECK that the operating head or cap seal is in good condition.\n\n- Water (gas container), water with additive (stored pressure), foam (gas container), foam (stored pressure), powder (gas container)","sort_order":32,"ref":"2.9","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1027,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leak detection","help_text":"CHECK if there are any leaks at the joints and seals that were renewed or disturbed during recharging.\n\nWater with additive (stored pressure), foam (stored pressure)","sort_order":33,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1028,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire hazard","help_text":"CHECK that the fire hazard/risk to be protected has not changed.\n\n- All extinguisher types","sort_order":34,"ref":"2.11","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1029,"active":true,"required":false,"type":"REMARK","label":"CHECK - Suitability","help_text":"CHECK that the extinguisher is the correct type, class, size and/or rating for the hazard to be protected.\n\n- All extinguisher types","sort_order":35,"ref":"2.12","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1030,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstructions","help_text":"(a) CHECK that no alterations have been made to the building that may impede access to the extinguisher or increase the travel distances to more than those required.\n\n- All portable extinguishers\n\nb) CHECK that no alterations have been made to the building that may impede access to, or restrict the movement of, the extinguisher.\n\n- All wheeled extinguishers","sort_order":36,"ref":"2.13","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1031,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 10.4.3 (Five-yearly service)","help_text":"AS1851-2012 Table 10.4.3 (Five-Annual service)","sort_order":37,"ref":"3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1032,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six-monthly and Annual service","help_text":"COMPLETE all six-monthly and Annual service activities, as listed in Table 10.4.1 and 10.4.2.","sort_order":38,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1033,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discharge","help_text":"CHECK that the extinguisher functions in accordance with the operating instructions and that the discharge is satisfactory. Recharge in accordance with Item 3.9.\n\n- Water (gas container), water (stored pressure), wet chemical, foam (gas container), powder\n\n- (gas container), powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":39,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1177,"active":true,"required":false,"type":"REMARK","label":"CHECK - Actuating device","help_text":"CHECK that the actuating device is free of corrosion, moves freely, and is undamaged; any cutting edge is sharp; and all sealing gaskets are in good condition.\n\n- Water (stored pressure), wet chemical, powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":40,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1178,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components","help_text":"(a) CHECK that the internal discharge tube, strainer and anti-overfill tube (where fitted) provide clear passage and are securely attached, and that the anti overfill device is undamaged.\n\n- Water (stored pressure), wet chemical","sort_order":41,"ref":"3.4(a)","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1179,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal components","help_text":"(b) CHECK that the internal discharge tube provides clear passage, is securely attached, and there is no evidence of moisture or foreign matter in the cylinder.\n\n- Powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":42,"ref":"3.4(b)","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1034,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal condition— Portable extinguishers","help_text":"CHECK that the interior of the cylinder is clean, is not pitted by corrosion (see AS 2337.1), and any internal lining is in good condition.\n\n- Where the lining cannot be removed to inspect the interior of the cylinder, the cylinder shall be accepted or rejected as per AS 2337.1.\n\n- Water (stored pressure), wet chemical, powder (stored pressure), vaporizing liquid.\n\n- For carbon dioxide extinguishers, this examination shall be in accordance with AS 2030.5, and shall be performed at a gas cylinder test station certified by a registered certifying body (see AS 2337.1).","sort_order":43,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1035,"active":true,"required":false,"type":"REMARK","label":"CHECK - Internal condition— Wheeled extinguishers","help_text":"CHECK the interior of the cylinder in accordance with the internal examination requirements of AS 2030.5 at a Gas Cylinder Test Station certified by a Registered Certifying Body (see AS 2337.1).\n\n- All wheeled extinguishers","sort_order":44,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1036,"active":true,"required":false,"type":"REMARK","label":"CHECK - Seals","help_text":"CHECK that the operating head or cap seal is in good condition.\n\nWater (stored pressure), wet chemical, powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":45,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1037,"active":true,"required":false,"type":"REMARK","label":"SUBJECT - Pressure test: Portable extinguishers","help_text":"(a) SUBJECT the extinguisher body to a hydrostatic pressure test of 1.5 times the working pressure, the marked periodic test pressure, or 2 MPa, whichever is the greatest.\n\n- Water (gas container), water (stored pressure), wet chemical, foam (gas container), foam (stored pressure), powder (gas container), powder (stored pressure), vaporizing liquid\n\n(b) SUBJECT the extinguisher body to a hydrostatic pressure test, in accordance with the requirements of AS 2030.5, at a Gas Cylinder Test Station certified by a Registered Certifying body (see AS 2337.1).\n\n - Carbon dioxide","sort_order":46,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1038,"active":true,"required":false,"type":"REMARK","label":"SUBJECT - Pressure test: Wheeled extinguishers","help_text":"SUBJECT the extinguisher body to a hydrostatic pressure test, in accordance with the requirements of AS 2030.5, at a Gas Cylinder Test Station certified by a Registered Certifying Body (see AS 2337.1).\n\n - All wheeled extinguishers","sort_order":47,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1039,"active":true,"required":false,"type":"REMARK","label":"RECHARGE - Extinguishing agent replacement","help_text":"At the frequency specified by the extinguishing manufacturer, RECHARGE the extinguisher with fresh extinguishing agent, as specified on the extinguisher label, in accordance with the manufacturer’s instructions.\n\nWet chemical, foam (gas container with sealed foam liquid container), powder (gas container), powder (stored pressure), carbon dioxide, vaporizing liquid\n\nUpon the completion of recharging stored pressure type extinguishers, perform a leak test as per Item 3.12.","sort_order":48,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1040,"active":true,"required":false,"type":"REMARK","label":"RENEW - Seals and gaskets","help_text":"RENEW all seals and gaskets fitted to the actuating device, operating head, or cap.\n\n - All extinguisher types","sort_order":49,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1041,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leak detection","help_text":"CHECK if there are any leaks at the joints and seals that were renewed or disturbed during recharging.\n\n- Water (stored pressure), wet chemical, foam (stored pressure), powder (stored pressure), carbon dioxide, vaporizing liquid","sort_order":50,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1042,"active":true,"required":false,"type":"REMARK","label":"SUBJECT - Hose Assembly","help_text":"(a) SUBJECT the hose assembly to a hydrostatic pressure test of 10 MPa.\n\n- All CO2 type wheeled extinguishers\n\n(b) SUBJECT the hose assembly to a hydrostatic pressure test of 1.5 times the extinguisher working pressure, or 2 MPa, whichever is the greater.\n\n- All wheeled extinguishers (other than CO2)","sort_order":51,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Fire Extinguisher: Wheeled","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Hose Reel","prompts":[{"id":910,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 9.4.1 (Six-monthly)","help_text":"AS1851-2012 Table 9.4.1 (Six-monthly)","sort_order":0,"ref":"1","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":911,"active":true,"required":false,"type":"REMARK","label":"CHECK - Accessibility","help_text":"CHECK that the hose reel is readily accessible with no obstacles restricting its access. Where a hose reel is installed in a recess or cabinet, CHECK that the clearances around the hose reel comply with the requirements of AS 2441.","sort_order":1,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":912,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage","help_text":"Where a location sign is required by AS 2441, CHECK that it is correctly located and visible.","sort_order":2,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":913,"active":true,"required":false,"type":"REMARK","label":"CHECK - Operating instructions","help_text":"CHECK that the operating instructions are legible.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":914,"active":true,"required":false,"type":"REMARK","label":"CHECK - Damage","help_text":"CHECK for any damage or corrosion of components that could adversely affect the operation of the hose reel.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":915,"active":true,"required":false,"type":"REMARK","label":"CHECK - Cabinet","help_text":"CHECK that any hose reel cabinet is accessible, clear of extraneous materials, clearly and correctly marked and in good repair.","sort_order":6,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":916,"active":true,"required":false,"type":"REMARK","label":"CHECK - Nozzle interlock","help_text":"CHECK that the nozzle is retained in the nozzle interlock.","sort_order":7,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":917,"active":true,"required":false,"type":"REMARK","label":"TEST - Swing arm","help_text":"Where fitted, TEST the swing arm to ensure it operates correctly and allows the hose to be run off in its intended direction.","sort_order":8,"ref":"1.7*","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":918,"active":true,"required":false,"type":"REMARK","label":"TEST - Unwind","help_text":"With the nozzle closed and stop valve open, TEST that the hose reel can be unwound freely in its intended direction by unwinding at least 5 m of hose.","sort_order":9,"ref":"1.8*","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":919,"active":true,"required":false,"type":"REMARK","label":"DETERMINE - Leakage","help_text":"With the nozzle closed, pressurize the reel by opening the stop valve. DETERMINE if there are any leaks from the reels waterway, including glands, nozzle, stop valve, hose or any fittings.\n\n** NOTE: ** In order to check that there is no leakage of water from any part of the reel waterway, it is recommended that the hose be completely unwound off the reel, so that all parts of the waterway can be examined.","sort_order":10,"ref":"1.9*","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":920,"active":true,"required":false,"type":"REMARK","label":"TEST - Flow","help_text":"TEST water to ensure it is able to flow through the reel by opening and closing the nozzle.","sort_order":11,"ref":"1.10*","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":921,"active":true,"required":false,"type":"REMARK","label":"CHECK - Service tag or label","help_text":"CHECK that the service tag or label is firmly attached to the hose reel.","sort_order":12,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":922,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 9.4.2 (Annual service)","help_text":"AS1851-2012 Table 9.4.2 (Annual service)","sort_order":13,"ref":"2","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":923,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Six monthly service","help_text":"COMPLETE all six-monthly service activities, as listed in Table 9.4.1.","sort_order":14,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":933,"active":true,"required":false,"type":"REMARK","label":"CHECK - Obstructions","help_text":"CHECK that no alterations have been made to the building, which impede access to the hose reel or restrict the running out of the hose, and that the hose can reach the fire hazard/risk in accordance with AS 2441.","sort_order":15,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":924,"active":true,"required":false,"type":"REMARK","label":"CHECK - Anchor points","help_text":"CHECK that the hose reel is securely mounted and that the anchor points are tight.","sort_order":16,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":925,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hose guide","help_text":"CHECK that any hose guide fixed to the hose reel supply pipe is not able to move upwards and cause the hose to jamb.","sort_order":17,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":926,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hose fittings","help_text":"CHECK that all hose fittings and connections are tight.","sort_order":18,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":927,"active":true,"required":false,"type":"REMARK","label":"CHECK - Bearings","help_text":"CHECK that the hose reel bearings are not damaged or excessively worn.","sort_order":19,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":928,"active":true,"required":false,"type":"HEADER","label":"Most disadvantaged hose reel flow test","help_text":"Most disadvantaged hose reel flow test","sort_order":20,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":929,"active":true,"required":false,"type":"INTEGER","label":"MEASURE - Flow rate","help_text":"With the stop valve and nozzle fully opened, MEASURE the water flow rate from the most disadvantaged hose reel.\n\nMinimum acceptable flow rates:\n\n(a) 0.33 L/s for reels with 19 mm hose.\n\n(b) 0.41 L/s for reels with 25 mm hose.","sort_order":21,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":930,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hose","help_text":"CHECK hose for kinking, excessive damage or wear, or collapse.","sort_order":22,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":931,"active":true,"required":false,"type":"REMARK","label":"CHECK - Ancillary equipment","help_text":"CHECK that any foam branch pipe or other equipment is in good repair and maintained in accordance with the manufacturer’s instructions.","sort_order":23,"ref":"2.8","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":932,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire hazard","help_text":"CHECK that the hose reel is appropriate protection for the fire hazard/risk.","sort_order":24,"ref":"2.9","estimated_duration":null,"prompt_set":"2012: Fire Hose Reel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Hydrant: System (Landing Valve)","prompts":[{"id":636,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 4.4.1 (Monthly service)","help_text":"AS1851-2012 Table 4.4.1 (Monthly service)","sort_order":1,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":637,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service","help_text":"Where pumpsets are fitted complete all pumpset monthly service activities, as listed in Table 3.4.1.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":638,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump-starting devices","help_text":"(a) CHECK that all isolating valves to pumpstarting pressure devices are secured in the open position.\n\n(b) CHECK that pressure switches are securely mounted and are protected against the ingress of water, dust and insects.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":639,"active":true,"required":false,"type":"REMARK","label":"START & RESTART - Pump-starting devices function test— Compression ignition engine (diesel)","help_text":"(a) START each pumpset by reducing the applied water pressure to the pump-starting device and run engine, in accordance with Section 3.\n\n(b) RESTART the pumpset using the manual starting device and again run the compression ignition engine in accordance with Section 3.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":640,"active":true,"required":false,"type":"INTEGER","label":"RECORD & VERIFY - Pump-starting devices function test— Compression ignition engine (diesel)","help_text":"(c) RECORD the pump cut-in pressures and verify that they are within the ranges required.","sort_order":5,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":641,"active":true,"required":false,"type":"REMARK","label":"START & RESTART - Pump-starting devices function test— Electric motor drivers","help_text":"(a) START each pumpset by reducing the applied water pressure to the starting device and run motor in accordance with Section 3.\n\n(b)RESTART the pumpset using the manual starting device and again run the motor in accordance with Section 3.","sort_order":6,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":642,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 4.4.2 (Six-monthly service)","help_text":"AS1851-2012 Table 4.4.2 (Six-monthly service)","sort_order":7,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":643,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service","help_text":"COMPLETE all monthly service activities, as listed in Table 4.4.1.","sort_order":8,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":644,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Water supply stop valves and isolating valves","help_text":"OPERATE (two full turns) all water supply stop valves (including backflow prevention stop valves and underground key-operated valves except where owned by the water supply authority) and verify they are fully open, secure in the open position (relaxed ¼ turn if appropriate) and are correctly labelled.\n\n** NOTES: ** ‘Text deleted’","sort_order":9,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":645,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hydrant valves (above ground)","help_text":"CHECK all hydrant valves:\n\n(a) Are accessible.\n\n(b) Hand-wheels are securely fitted.\n\n(c) Blanking caps, where fitted, are in good condition.","sort_order":10,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":646,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hydrant valves (below ground)","help_text":"CHECK all hydrant valves:\n\n(a) Are accessible.\n\n(b) Blanking caps, where fitted, are in good condition.\n\n(c) Check cover plate for ease of opening.\n\n(d) Not leaking.","sort_order":11,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":647,"active":true,"required":false,"type":"REMARK","label":"CHECK - Booster assembly (where fitted)","help_text":"CHECK all booster assemblies:\n\n(a) Are accessible.\n\n(b) Hand-wheels are securely fitted.\n\n(c) Pressure gauges and blanking caps, where fitted, are in good condition.\n\n(d) For condition of washers on booster assembly connection inlets.\n\n(e) For legible labelling indicating maximum system working pressure.\n\n(f) For legibility of hydrant system block plan where fitted.","sort_order":12,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":648,"active":true,"required":false,"type":"REMARK","label":"DEPRESSURIZE & CHECK - Remote pump starting","help_text":"DEPRESSURIZE the hydrant system(s) at the most hydraulically disadvantaged hydrant and CHECK that the pump starts.","sort_order":13,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":649,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hydrant and booster connections— Compatibility","help_text":"CHECK that all hydrant and booster connection points are compatible with local brigade requirements.","sort_order":14,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":650,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hydrant hose (where fitted)","help_text":"CHECK all branch pipes, nozzles and hose couplings are in good condition, compatible with the hydrant valves and properly stowed.","sort_order":15,"ref":"2.8","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":651,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foam concentrate and loose equipment (where provided)","help_text":"CHECK:\n\n(a) Equipment provided in the cabinet is in accordance with the cabinet contents list.\n\n(b) Equipment items are compatible and in good condition.\n\n(c) Foam concentrate containers are in good condition, seals are intact and the labels are legible.\n\n** NOTE: ** Storage of foam concentrate in aggressive environments may require testing or replacement of the concentrate.\n\n(d) Signage for legibility.","sort_order":16,"ref":"2.9","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":652,"active":true,"required":false,"type":"REMARK","label":"CHECK - Cabinets","help_text":"CHECK that all hydrant and booster cabinets or enclosures are accessible, clear of extraneous materials, clearly and correctly marked and in good condition.","sort_order":17,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":653,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure-reducing/ pressure-limiting valves","help_text":"CHECK pressure readings on the low side of pressure-reducing and pressure-limiting valves for deviations from designed operating pressure.\n\n** NOTE: ** Gauges or facilities for gauges should be installed immediately upstream and downstream of the valve(s).","sort_order":18,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":654,"active":true,"required":false,"type":"REMARK","label":"CHECK - Block plan (where required)","help_text":"CHECK for legibility and appropriate location.","sort_order":19,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":655,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 4.4.3 (Annual service)","help_text":"AS1851-2012 Table 4.4.3 (Annual service)","sort_order":20,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":656,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and sixmonthly service","help_text":"COMPLETE all monthly and six-monthly service activities, as listed in Tables 4.4.1 and 4.4.2.","sort_order":21,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":657,"active":true,"required":false,"type":"REMARK","label":"OPEN - Hydrant valves (above and below ground)","help_text":"OPEN partially all hydrant valves in the system and prove the presence of water at each point.\n\n** NOTE: ** To prevent water damage, it is recommended that a suitable adapter to limit water flow be used for this test on internal hydrants. Each hydrant in the system should be opened separately.","sort_order":22,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":658,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Water supply valves","help_text":"(a) OPERATE (two full turns) all water supply valves—above ground, underground keyoperated valves (except where owned by the water supply authority) and subsidiary stop valves (e.g., floor isolation valves). Ensure they are fully open and, where applicable, secured in the open position (relaxed ¼ turn where applicable) and are correctly labelled.","sort_order":23,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":659,"active":true,"required":false,"type":"REMARK","label":"VERIFY & TEST - water supply valves","help_text":"(b) VERIFY that the valve position indicators are securely mounted and indicate correctly.\n\n(c) TEST each valve monitor (where fitted) by closing and re-opening the valve. Verify correct indication at the CIE.","sort_order":24,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":660,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Non-return valves","help_text":"VERIFY that all non-return valves are operating freely and are seating correctly.","sort_order":25,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":661,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Hydrant hose (where fitted)","help_text":"VERIFY all branch pipe, nozzles and hose couplings waterways are unobstructed and in good condition.","sort_order":26,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":662,"active":true,"required":false,"type":"REMARK","label":"OPERATE & VERIFY - Pressure-reducing station test - Operation","help_text":"(a) OPERATE all pressure-reducing valves and verify correct operation under flow conditions.\n\n(b) VERIFY that pressure readings on the low pressure side of the valves are within the range stated at the pressure-reducing valve station.","sort_order":27,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":663,"active":true,"required":false,"type":"DECIMAL","label":"Record - Pressure-reducing station test......kPa","help_text":"(c) OPERATE pressure-relief valve and record operating pressure. If necessary, adjust the setting to relieve at 50 kPa above the operating pressure of the pressure-reducing valve. Replace the tamper seal if necessary.\n\n** NOTE: ** The pressure-relief valve test may be carried out using a portable test apparatus.","sort_order":28,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":664,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Water supply proving test","help_text":"CONDUCT a water supply proving test for each water supply verifying that the system flow and pressure requirements meet the design criteria, using either—\n\n(a) a fixed flow meter test facility; or\n\n(b) a portable test apparatus at the most hydraulically disadvantaged hydrant valve(s).","sort_order":29,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":665,"active":true,"required":false,"type":"REMARK","label":"CONDUCT & VERIFY - Hydrant system interface control test (fire trips)","help_text":"(a) CONDUCT a functional system test via the pressure switch or flow switch with other interfaced fire systems.\n\n(b) VERIFY that the interface functions as required.\n\nNOTE: It is recommended that the responsible entity coordinate testing the interfaced fire protection systems.","sort_order":30,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":666,"active":true,"required":false,"type":"REMARK","label":"CHECK & CLEAN - Water supply (river, lake, etc.) Strainers/screens","help_text":"(a) CHECK suction inlet strainer(s) or screen(s).\n\n(b) Following water supply proving test\n\n(Table 4.4.2 Item 2.6), CLEAN suction inlet strainer(s). Lower raised screen and raise and clean ‘in-use’ screen.","sort_order":31,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":667,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey—Installation","help_text":"(a) Pipework—CHECK that exposed water distribution system, including pipework, pipe supports and valve, appears free from corrosion and damage, not subject to external loads and pipework is properly supported.\n\n(b) Hydrant obstructions—CHECK for obstructions likely to impede hydrant valve access.","sort_order":32,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":668,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey—Design","help_text":"(a) Occupancy—CHECK that hydrant design remains applicable for current building arrangement or use.\n\n(b) Site documentation—CHECK that block plans, emergency instructions and pressure schedules contain the details required in accordance with AS 2419.1.","sort_order":33,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":669,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 4.4.4 (Five-Annual service)","help_text":"AS1851-2012 Table 4.4.4 (Five-Annual service)","sort_order":34,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":670,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly, six-monthly and Annual service","help_text":"COMPLETE all monthly, six monthly and Annual service activities, as listed in Tables 4.4.1, 4.4.2 and 4.4.3.","sort_order":35,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":671,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Booster connection flow test (where fitted)","help_text":"CONDUCT a flow test through booster connection in accordance with AS 2419.1 or to approved design Standard.\n\n** NOTE: ** Conduct the flow test after a satisfactory (pass) hydrostatic test.","sort_order":36,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":672,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Hydrostatic test","help_text":"Where a booster is fitted CONDUCT a hydrostatic pressure test on the entire system at 1.5 times the system working pressure of the required design Standard.","sort_order":37,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":673,"active":true,"required":false,"type":"REMARK","label":"CHANGE & LUBRICATE - Booster assembly","help_text":"(a) CHANGE all washers on booster assembly connection inlets.\n\n(b) LUBRICATE internal non-return spring check valves on a 10-Annual basis.","sort_order":38,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":674,"active":true,"required":false,"type":"REMARK","label":"EXAMINE & FIT - Drain and test valve washers","help_text":"For screw-down style valves, EXAMINE seating and fit new washers. For packed gland variants, FIT new gland packing.","sort_order":39,"ref":"4.5","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":675,"active":true,"required":false,"type":"REMARK","label":"FIT - Stop valves","help_text":"FIT new gland packing and lubricate spindle.","sort_order":40,"ref":"4.6","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":676,"active":true,"required":false,"type":"REMARK","label":"FIT - Hydrant valves","help_text":"FIT new seatings to all hydrant valves and lubricate spindles. (Perishable items only.)\n\nNOTE: This activity should be completed prior to conducting the hydrostatic pressure test.","sort_order":41,"ref":"4.7","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":677,"active":true,"required":false,"type":"REMARK","label":"RENEW - Water supply nonreturn valves","help_text":"RENEW water supply non-return valve seatings and gaskets.","sort_order":42,"ref":"4.8","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":678,"active":true,"required":false,"type":"REMARK","label":"CHECK - Gauges","help_text":"CHECK all pressure gauges against calibrated gauge.","sort_order":43,"ref":"4.9","estimated_duration":null,"prompt_set":"2012: Fire Hydrant: System (Landing Valve)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Protected Air Duct","prompts":[{"id":1156,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.7 (Annual SERVICE)","help_text":"AS1851-2012 Table 12.4.7 (Annual SERVICE)","sort_order":1,"ref":"7","estimated_duration":null,"prompt_set":"2012: Fire Protected Air Duct","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1157,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Location","help_text":"INSPECT against drawings and all schedules (see Clause 12.2.5) that no air duct has been added, removed or modified.","sort_order":2,"ref":"7.1","estimated_duration":null,"prompt_set":"2012: Fire Protected Air Duct","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1158,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Fire-protected duct","help_text":"(a) INSPECT fire-resistant ducts from drawings, plans and schedule for condition of fire protection system or coating, including supports.\n\n(b) CHECK for mechanical damage.","sort_order":3,"ref":"7.2","estimated_duration":null,"prompt_set":"2012: Fire Protected Air Duct","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1159,"active":true,"required":false,"type":"REMARK","label":"INSPECT & CHECK - Fire protection system or coating","help_text":"(a) INSPECT visually for areas of deterioration, vermiculite, cement, mineral fibre and plaster (or combinations thereof) spray’s loss of adhesion.\n\n(b) CHECK fire protective boards and cladding for missing material or loss of adhesion.","sort_order":4,"ref":"7.3","estimated_duration":null,"prompt_set":"2012: Fire Protected Air Duct","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1160,"active":true,"required":false,"type":"REMARK","label":"Damper","help_text":"For damper operation refer to Section 13 of this Standard.","sort_order":5,"ref":"7.4","estimated_duration":null,"prompt_set":"2012: Fire Protected Air Duct","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1161,"active":true,"required":false,"type":"REMARK","label":"Ducting","help_text":"(a) Report to the owner or owner’s representative or occupier where any deficiency is identified.\n\n(b) Amend schedule as required to maintain accuracy.","sort_order":6,"ref":"7.5","estimated_duration":null,"prompt_set":"2012: Fire Protected Air Duct","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Protected Structural Member","prompts":[{"id":1120,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.2 (Annual service)","help_text":"AS1851-2012 Table 12.4.2 (Annual service)","sort_order":1,"ref":"2","estimated_duration":null,"prompt_set":"2012: Fire Protected Structural Member","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1121,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Structural members","help_text":"INSPECT against drawings (see Clause 12.2.5) that no structural steel members have been added, removed or modified.","sort_order":2,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Protected Structural Member","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1122,"active":true,"required":false,"type":"REMARK","label":"CHECK - Inspection","help_text":"(a) CHECK condition of fire protection system or coating.\n\n(b) CHECK for mechanical damage.","sort_order":3,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Protected Structural Member","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1123,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Fire-protection system or coating","help_text":"(a) INSPECT visually for areas of deterioration against vermiculite, cement, mineral fibre and plaster (or combinations of) spray’s loss of adhesion.\n\n(b) CHECK for intumescent coating visual damage to the surface (e.g. bubbling, peeling, flaking and scratches).\n\n(c) CHECK fire-protective boards and cladding for missing boards or loss of adhesion.","sort_order":4,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Protected Structural Member","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire pumpset: Diesel Pump","prompts":[{"id":491,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump areas","help_text":"(a) CHECK that pump areas are unobstructed, not used for storage and lighting is adequate.\n\n (b) Where pump pressure-relief valves are fitted, CHECK that discharge will not cause flooding or water damage.","sort_order":1,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":490,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 3.4.1 (Monthly service)","help_text":"AS1851-2012 Table 3.4.1 (Monthly service)","sort_order":2,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":492,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage and ID plates per AS 2941 (where applicable)","help_text":"(a) CHECK that each pumpset has a clearly visible warning sign stating â€˜Danger this Pump Starts Automaticallyâ€™.\n\n (b) CHECK that there are readily seen and clearly legible ID plates on each controller, driver (diesel and electric), pumpset (on base plate) and pump (on the pump).\n\n (c) CHECK each pump controller is labelled â€˜Fire Pump Controllerâ€™, has clear operating instructions posted, has all operating components clearly identified, and has all indicating lights clearly labelled.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":493,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump water supply valves","help_text":"CHECK that all valves are in the open position or the closed position, as labelled, and secured, where applicable.\n\n ** NOTES: ** â€˜Text deletedâ€™","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":494,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure gauges","help_text":"CHECK that all pressure gauges are reading within the ranges required and record pressure.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":495,"active":true,"required":false,"type":"REMARK","label":"PERFORM - Water supply tank (if installed)","help_text":"Perform routine service in accordance with Section 5.","sort_order":6,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":496,"active":true,"required":false,"type":"REMARK","label":"CHECK - General inspection","help_text":"CHECK for any obvious signs of physical damage or deterioration.","sort_order":7,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":497,"active":true,"required":false,"type":"REMARK","label":"CHECK - Compression ignition (diesel) driven pumpset(s)","help_text":"Monitor and engine start batteries.\n\n (a) CHECK monitor and engine start batteries and enclosures for corrosion, physical damage and secure mounting.\n\n (b) REMOVE any corrosion from battery terminals as required.\n\n (c) TEST the float charge voltage of both the monitor and engine start batteries and record result.\n\n (d) CHECK electrolyte levels and top up with distilled water as necessary.\n\n (e) CHECK warning signage and rating (battery capacity) signage (where required).\n\n (f) CHECK battery capacity or cold cranking amperage is appropriate.","sort_order":8,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1441,"active":true,"required":false,"type":"DECIMAL","label":"Monitor battery float charge voltage (V)","help_text":"Monitor battery float charge voltage (V)","sort_order":9,"ref":"1.7(c)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1442,"active":true,"required":false,"type":"DECIMAL","label":"Engine Start battery float charge voltage (V)","help_text":"Engine Start battery float charge voltage (V)","sort_order":10,"ref":"1.7(c)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":498,"active":true,"required":false,"type":"REMARK","label":"CHECK - Engine warming devices","help_text":"Where fitted, check engine warming device is working appropriately.","sort_order":11,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":499,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fuel tank(s)","help_text":"CHECK that the fuel tank is full.","sort_order":12,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":500,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump controller","help_text":"(a) CHECK enclosure for corrosion and ingress of water, dust or insects.\n\n (b) CHECK operation of all visual indicators, switches and sounders.","sort_order":13,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":501,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump controller status","help_text":"(a) CHECK the main isolating switch is in the â€˜ONâ€™ position and secured in position where facilities are provided and, where fitted, the green power supply indicators are illuminated and that no red warning lamps are on.\n\n (b) CHECK all lights are functional by pressing the indicator test button, where fitted.","sort_order":14,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":502,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pre-test checks","help_text":"Prior to commencing any test function:\n\n (a) CHECK all safety guards are in place and secure.\n\n (b) CHECK the water supply availabilityâ€”town main pressure adequate or suction tank is full.\n\n (c) Where compression ignition engine driven pumpsets are installed, CHECK that water, oil, belt drives and exhaust condensate drains and cooling water valves are in the correct position. Check fuel water-trap/filter for water contamination. Rectify where required.","sort_order":15,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":503,"active":true,"required":false,"type":"REMARK","label":"START & RECORD - Pump starting devicesâ€” Compression ignition engine","help_text":"(a) START each pumpset by reducing the applied water pressure to the starting device and for compression ignition engines run engine continuously for not less than 10 min on the first automatic start and check that the driver achieves full speed within 15 s of starting.\n\n (b) RESTART the pumpset using the manual starting device.\n\n (c) RECORD the starting pressures, test run time and the hour meter reading at completion of the test.","sort_order":16,"ref":"1.13","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1445,"active":true,"required":false,"type":"INTEGER","label":"Record the Starting Pressures (kPa)","help_text":"Record the Starting Pressures (kPa)","sort_order":17,"ref":"1.13(c)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1446,"active":true,"required":false,"type":"INTEGER","label":"Record the Run Time (min)","help_text":"Record the Run Time (min)","sort_order":18,"ref":"1.13(c)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1443,"active":true,"required":false,"type":"DECIMAL","label":"Record the Hour Meter Reading (h)","help_text":"Record the Hour Meter Reading (h)","sort_order":19,"ref":"1.13(c)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":504,"active":true,"required":false,"type":"REMARK","label":"CHECK - Run test checks","help_text":"During and after the running period CHECK:\n\n (a) Pump operates at the correct discharge pressure. Record suction and discharge pressure.\n\n ** NOTE: ** The discharge pressures may vary with varied suction static pressure. An excessive negative suction pressure may indicate a suction partial blockage or partially closed valve.\n\n (b) Pump gland and drain (where applicable) operates efficiently.\n\n (c) Out-of-balance condition or abnormal noises are not evident.\n\n (d) All local and remote â€˜pump runningâ€™ alarms operate.\n\n (e) Running speed is correct, and record the result.\n\n (f) Water, oil and fuel leaks are not evident and fittings on ancillary equipment are secure.\n\n (g) Battery charger or alternator/generator is operating at required value within tolerances.\n\n (h) Engine stop mechanism returns to start position automatically.\n\n (i) Belt drives are in good condition.\n\n (j) Battery charger power failure alarm operates correctly.\n\n (k) Engine instrumentation is operating. Record the results.\n\n (l) Flow is evident from the circulation relief valve when the pump is operating at shut-off head and ceases at the appropriate pressure.\n\n (m) Exhaust system is leak free.\n\n (n) Cooling water (heat exchanger cooled engines only) is discharging.","sort_order":20,"ref":"1.14","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1447,"active":true,"required":false,"type":"INTEGER","label":"Record suction pressure (kPa)","help_text":"Record suction pressure (kPa)","sort_order":21,"ref":"1.14(a)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1448,"active":true,"required":false,"type":"INTEGER","label":"Record discharge pressure (kPa)","help_text":"Record discharge pressure (kPa)","sort_order":22,"ref":"1.14(a)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1459,"active":true,"required":false,"type":"DECIMAL","label":"Record battery charger voltage (V)","help_text":"Record battery charger voltage (V)","sort_order":23,"ref":"1.14(g)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1460,"active":true,"required":false,"type":"INTEGER","label":"Record oil pressure (kPa)","help_text":"Record oil pressure (kPa)","sort_order":24,"ref":"1.14(k)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1461,"active":true,"required":false,"type":"INTEGER","label":"Record engine temp (deg C)","help_text":"Record engine temp (deg C)","sort_order":25,"ref":"1.14(k)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":505,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump controller status","help_text":"CHECK that the main isolating switch is in the ON position and secured in position where facilities are provided and, where fitted, the green power supply lamps are illuminated and that no red warning lamps are on. Ensure all lights are functional by pressing the lamp test button, where fitted.","sort_order":26,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":506,"active":true,"required":false,"type":"REMARK","label":"START & RECORD - Pump starting devices","help_text":"(a) START each pumpset by reducing the applied water pressure to the starting device and run motor continuously for at least 3 minutes.\n\n (b) RESTART each pumpset using the manual starting device and run motor continuously for at least 3 minutes.\n\n (c) RECORD the starting pressures and the run time at the completion of the test.","sort_order":27,"ref":"1.17","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1449,"active":true,"required":false,"type":"INTEGER","label":"Record the Starting Pressures (kPa)","help_text":"Record the Starting Pressures (kPa)","sort_order":28,"ref":"1.17(c)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1450,"active":true,"required":false,"type":"INTEGER","label":"Record the Run Time (min)","help_text":"Record the Run Time (min)","sort_order":29,"ref":"1.17(c)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":507,"active":true,"required":false,"type":"INTEGER","label":"CHECK & RECORD - Run test checks","help_text":"During and after the running period CHECK:\n\n (a) Pump operates at the correct discharge pressures allowing for varying suction conditions. Record suction and discharge pressure.\n\n (b) Pump glands and drain or mechanical seal(s) operate efficiently.\n\n (c) Out-of-balance condition or abnormal noises are not evident.\n\n (d) Both local and remote â€˜pump runningâ€™ alarms and lights operate.","sort_order":30,"ref":"1.18","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1451,"active":true,"required":false,"type":"INTEGER","label":"Record suction pressure (kPa)","help_text":"Record suction pressure (kPa)","sort_order":31,"ref":"1.18(a)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1452,"active":true,"required":false,"type":"INTEGER","label":"Record discharge pressure (kPa)","help_text":"Record discharge pressure (kPa)","sort_order":32,"ref":"1.18(a)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":508,"active":true,"required":false,"type":"REMARK","label":"CHECK - Controller batteries","help_text":"(a) CHECK battery complies with details on identification plate fitted to the enclosure.\n\n (b) CHECK battery for corrosion, physical damage and security.\n\n (c) CHECK battery enclosure for corrosion, and the ingress of water, dust and insects.\n\n (d) CHECK float voltage of the battery and record.","sort_order":33,"ref":"1.19","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1444,"active":true,"required":false,"type":"DECIMAL","label":"Record batter float voltage (V)","help_text":"Record batter float voltage (V)","sort_order":34,"ref":"1.19)d)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":509,"active":true,"required":false,"type":"REMARK","label":"RETURN - Restoration to operational condition all pumpsets","help_text":"After completion of testing procedures, RETURN all equipment to the operational condition.","sort_order":35,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":510,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 3.4.2 (Six-monthly service)","help_text":"AS1851-2012 Table 3.4.2 (Six-monthly service)","sort_order":36,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":511,"active":true,"required":false,"type":"REMARK","label":"Monthly service","help_text":"Complete all monthly service activities, as listed in Table 3.4.1.","sort_order":37,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":512,"active":true,"required":false,"type":"REMARK","label":"Hydro-pneumatic accumulator (where fitted)","help_text":"CHECK accumulator air pressure.","sort_order":38,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":513,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 3.4.3 (Annual service)","help_text":"AS1851-2012 Table 3.4.3 (Annual service)","sort_order":39,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":514,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and six-monthly service","help_text":"Complete all monthly and six-monthly service activities as listed in Tables 3.4.1 and 3.4.2.","sort_order":40,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":515,"active":true,"required":false,"type":"REMARK","label":"RUN - Annual full flow test - shut-off (zero flow) for 10 min","help_text":"(a) With the pump room door(s) closed, and the pump testing technician present:\n\n ** NOTE: ** If the pump room temperature rises more than 10Â°C above ambient temperature, this could indicate inadequate ventilation and possible reduction in engine power.\n\n (i) RUN the pumpset at shut-off (zero flow) for 10 min to allow all equipment to attain normal operating temperature.","sort_order":41,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":516,"active":true,"required":false,"type":"HEADER","label":"(ii) RUN the pumpset at 130% of duty flow (sprinklers, hydrants or combined as applicable) for 10 min and record the result.","help_text":"(ii) RUN the pumpset at 130% of duty flow (sprinklers, hydrants or combined as applicable) for 10 min and record the result.","sort_order":42,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":517,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (A) Suction pressures. .....kPa","help_text":"(A) Suction pressures.","sort_order":43,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":518,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (B) Discharge pressure. .....kPa","help_text":"(B) Discharge pressure.","sort_order":44,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":519,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (C) Engine running temperature. ......Â°C","help_text":"(C) Engine running temperature.","sort_order":45,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":520,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (D) Engine oil pressure. .....kPa","help_text":"(D) Engine oil pressure.","sort_order":46,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":521,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (E) Air temperature at the engine intake manifold.","help_text":"(E) Air temperature at the engine intake manifold.","sort_order":47,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":522,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (F) Engine RPM","help_text":"(F) Engine RPM, using both installed tachometer and calibrated tachometer. Record variations.","sort_order":48,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":523,"active":true,"required":false,"type":"HEADER","label":"(iii) Reduce the flow to the duty flow (sprinklers, hydrants or combined) for sufficient time to record the water supply proving test results.","help_text":"(iii) Reduce the flow to the duty flow (sprinklers, hydrants or combined) for sufficient time to record the water supply proving test results.","sort_order":49,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":524,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (A) Suction pressures. .....kPa","help_text":"(A) Suction pressures.","sort_order":50,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":525,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (B) Discharge pressure. .....kPa","help_text":"(B) Discharge pressure.","sort_order":51,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":526,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (C) Engine running temperature. ......Â°C","help_text":"(C) Engine running temperature.","sort_order":52,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":527,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (D) Engine oil pressure. .....kPa","help_text":"(D) Engine oil pressure.","sort_order":53,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":528,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (E) Air temperature at the engine intake manifold.","help_text":"(E) Air temperature at the engine intake manifold.","sort_order":54,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":529,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (F) Engine RPM","help_text":"(F) Engine RPM, using both installed tachometer and calibrated tachometer. Record variations.","sort_order":55,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":530,"active":true,"required":false,"type":"HEADER","label":"(iv) Further reduce the flow until shut-off (zero flow) is achieved and continue to run the pumpset until total run time has reached 30 min.","help_text":"(iv) Further reduce the flow until shut-off (zero flow) is achieved and continue to run the pumpset until total run time has reached 30 min.","sort_order":56,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":531,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (A) Suction pressures. .....kPa","help_text":"(A) Suction pressures.","sort_order":57,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":532,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (B) Discharge pressure. .....kPa","help_text":"(B) Discharge pressure.","sort_order":58,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":533,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (C) Engine running temperature. ......Â°C","help_text":"(C) Engine running temperature.","sort_order":59,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":534,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (D) Engine oil pressure. .....kPa","help_text":"(D) Engine oil pressure.","sort_order":60,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":535,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (E) Air temperature at the engine intake manifold.","help_text":"(E) Air temperature at the engine intake manifold.","sort_order":61,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":536,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Annual full flow test - (F) Engine RPM","help_text":"(F) Engine RPM, using both installed tachometer and calibrated tachometer. Record variations.","sort_order":62,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":537,"active":true,"required":false,"type":"REMARK","label":"CHECK, SIMULATE & TEST - Annual full flow testâ€” Compression ignition (diesel) driven pumpsetâ€”Sprinklers and hydrants load test. This test may be combined with tests required by Table 2.4.2.3, Item 3.5 if applicable","help_text":"(vi) While carrying out the above procedures, CHECK temperature of bearings and stuffing box leakage and note and report any abnormality.\n\n (b) SIMULATE an engine fail to start and ensure that engine-start cycling requirements and alarm activations are satisfied.\n\n (c) TEST correct operation of pump priming tanks and associated equipment, where fitted.","sort_order":63,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":538,"active":true,"required":false,"type":"REMARK","label":"CHECK - All batteries","help_text":"(a) CHECK each battery for any condition likely to indicate an adverse effect on its function.\n\n (b) Where batteries are replaced they shall comply with batteries manufactured in accordance with AS 4029 (series).","sort_order":64,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":539,"active":true,"required":false,"type":"REMARK","label":"REPLACE - Engine start batteries","help_text":"REPLACE all engine-starting batteries after a maximum of 2 years service, irrespective of condition. Record date of replacement on the new battery and the date the batteries were replaced in the service record.","sort_order":65,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":540,"active":true,"required":false,"type":"REMARK","label":"CHECK - Control batteries","help_text":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","sort_order":66,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":541,"active":true,"required":false,"type":"INTEGER","label":"TEST & RECORD - Battery charger","help_text":"Test and record battery charger voltage output.","sort_order":67,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":542,"active":true,"required":false,"type":"REMARK","label":"REPLACE - Compressionignition (diesel) driven pumpset","help_text":"(a) REPLACE engine oil with new oil that meets the engine manufacturerâ€™s specification. More frequent oil changes shall be carried out if recommended by the engine manufacturer.\n\n (b) REPLACE engine oil filter and fuel filters and, if required, air filters.\n\n (c) CHECK the condition of the fuel.\n\n ** NOTE: ** Visually check a sample of the fuel for foreign particles, contamination, fungal growth, appropriate smell and colour, etc. If suspect, report, replace or send the sample to an independent testing agent.","sort_order":68,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":543,"active":true,"required":false,"type":"REMARK","label":"INSPECT & FLUSH - Compressionignition (diesel) driven pumpset","help_text":"(d) INSPECT engine cooling hoses and replace where necessary.\n\n (e) FLUSH engine cooling system and refill using manufacturerâ€™s approved corrosion inhibitor (water-cooled engines only).","sort_order":69,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":544,"active":true,"required":false,"type":"REMARK","label":"PRESSURE TEST - Compressionignition (diesel) driven pumpset","help_text":"(f) PRESSURE TEST engine cooling system in accordance with the manufacturerâ€™s recommendations (radiator and heat exchanger cooled engines only).","sort_order":70,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":545,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Compressionignition (diesel) driven pumpset","help_text":"(g) CHECK correct operation of the engine cooling system pressure-reducing valves, where fitted.\n\n (h) REMOVE and CLEAN or REPLACE heat exchanger strainer(s).\n\n (i) CARRY out any other routine service procedures in accordance with the engine manufacturerâ€™s requirements.\n\n (j) INSPECT pump/driver coupling for wear and alignment. Replace worn or damaged components.\n\n (k) GREASE jump bearings to the manufacturerâ€™s specifications where greased nipples are provided.\n\n (l) Where the pump bearings are of the oillubricated type, REPLACE the bearing oil with new oil that meets the pump manufacturerâ€™s specification (does not apply to turbine type vertical shaft centrifugal pumps).\n\n (m) REPLACE the oil in right-angle gearboxes with new oil that meets the manufacturerâ€™s specification.","sort_order":71,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":546,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Electric motordriven pumpset","help_text":"With all electrical equipment isolated from all power supplies:\n\n (a) INSPECT the condition of all exposed heavy current-carrying contacts. Report any item showing any signs of wear or corrosion.\n\n (b) INSPECT pump/driver coupling for wear and alignment. Report worn or damaged components.\n\n (c) Where grease nipples are provided, GREASE pump and motor bearings to the manufacturerâ€™s specifications.\n\n (d) Where the pump bearings are of the oillubricated type, REPLACE the bearing oil with new oil that meets the pump manufacturerâ€™s specification (does not apply to turbine type vertical shaft centrifugal pumps).","sort_order":72,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":547,"active":true,"required":false,"type":"REMARK","label":"ENSURE - Non-return valves","help_text":"ENSURE all non-return valves are operating freely and are seating correctly.","sort_order":73,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":548,"active":true,"required":false,"type":"REMARK","label":"SURVEY - Pipework corrosion","help_text":"SURVEY the system and equipment to identify external corrosion, and detail extent and location accordingly.","sort_order":74,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":549,"active":true,"required":false,"type":"REMARK","label":"CHECK - System pressure-relief valve","help_text":"CHECK that the system pressure relief valve opens and closes at the pressure required.\n\n ** NOTE: ** Inappropriate settings for pressure-relief valves can result in very large quantities of water flowing to waste. Ensure settings are maintained to have pressures as identified and not higher than allowed by system component rated working pressures.","sort_order":75,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":550,"active":true,"required":false,"type":"REMARK","label":"RETURN - Restoration to operational condition","help_text":"After completion of testing procedures, RETURN all equipment to the operational condition.","sort_order":76,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":551,"active":true,"required":false,"type":"REMARK","label":"RETURN - Overspeed shutdown device","help_text":"Operate engine overspeed test switch. Ensure the engine shuts down and engine, overspeed light illuminates on the controller.","sort_order":77,"ref":"3.14","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":552,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Variable speed control","help_text":"Operate the pump at 50% of duty flow and 100% of duty flow, and ensure duty head is not exceeded by more than 10%.","sort_order":78,"ref":"3.15","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":553,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Remote pump start/stop function","help_text":"Operate the pump start/stop functions from the remote location, and ensure the appropriate indications are received at the FIP/remote stop/start panel.","sort_order":79,"ref":"3.16","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":554,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 3.4.4 (Five-Annual service)","help_text":"AS1851-2012 Table 3.4.4 (Five-Annual service)","sort_order":80,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":555,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly, sixmonthly and Annual service","help_text":"COMPLETE all monthly, six-monthly and Annual activities, as listed in Tables 3.4.1, 3.4.2 and 3.4.3.","sort_order":81,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":556,"active":true,"required":false,"type":"REMARK","label":"REPACK - Pump","help_text":"REPACK pump glands.","sort_order":82,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":557,"active":true,"required":false,"type":"REMARK","label":"OVERHAUL - Relief, engine cooling and pressure regulating valves","help_text":"OVERHAUL the following valves in accordance with supplierâ€™s specifications:\n\n (a) Circulation-relief valves.\n\n (b) Pressure-relief valves.\n\n (c) Engine cooling valve.\n\n (d) Pressure regulating valve.","sort_order":83,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":558,"active":true,"required":false,"type":"REMARK","label":"FIT & CHECK - Stop valves","help_text":"(a) FIT new gland packing and lubricate spindles.\n\n (b) For ball and butterfly valves, CHECK for leakage and replace if necessary.","sort_order":84,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":559,"active":true,"required":false,"type":"REMARK","label":"REPLACE - Compression ignition engine","help_text":"Replace engine air filters.\n\n ** NOTE: ** The air filter should be marked with install date.","sort_order":85,"ref":"4.5","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":560,"active":true,"required":false,"type":"REMARK","label":"RETURN - Restoration to operational condition","help_text":"After completion of testing procedures, RETURN all equipment to the operational condition.","sort_order":86,"ref":"4.6","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Diesel Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire pumpset: Electric Pump","prompts":[{"id":561,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 3.4.1 (Monthly service)","help_text":"AS1851-2012 Table 3.4.1 (Monthly service)","sort_order":1,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":562,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump areas","help_text":"(a) CHECK that pump areas are unobstructed, not used for storage and lighting is adequate.\n\n (b) Where pump pressure-relief valves are fitted, CHECK that discharge will not cause flooding or water damage.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":563,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage and ID plates per AS 2941 (where applicable)","help_text":"(a) CHECK that each pumpset has a clearly visible warning sign stating â€˜Danger this Pump Starts Automaticallyâ€™.\n\n (b) CHECK that there are readily seen and clearly legible ID plates on each controller, driver (diesel and electric), pumpset (on base plate) and pump (on the pump).\n\n (c) CHECK each pump controller is labelled â€˜Fire Pump Controllerâ€™, has clear operating instructions posted, has all operating components clearly identified, and has all indicating lights clearly labelled.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":564,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump water supply valves","help_text":"CHECK that all valves are in the open position or the closed position, as labelled, and secured, where applicable.\n\n ** NOTES: ** â€˜Text deletedâ€™","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":565,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure gauges","help_text":"CHECK that all pressure gauges are reading within the ranges required and record pressure.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":566,"active":true,"required":false,"type":"REMARK","label":"PERFORM - Water supply tank (if installed)","help_text":"Perform routine service in accordance with Section 5.","sort_order":6,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":567,"active":true,"required":false,"type":"REMARK","label":"CHECK - General inspection","help_text":"CHECK for any obvious signs of physical damage or deterioration.","sort_order":7,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":568,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump controller","help_text":"(a) CHECK enclosure for corrosion and ingress of water, dust or insects.\n\n (b) CHECK operation of all visual indicators, switches and sounders.","sort_order":8,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":569,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump controller status","help_text":"(a) CHECK the main isolating switch is in the â€˜ONâ€™ position and secured in position where facilities are provided and, where fitted, the green power supply indicators are illuminated and that no red warning lamps are on.\n\n (b) CHECK all lights are functional by pressing the indicator test button, where fitted.","sort_order":9,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":570,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pre-test checks","help_text":"Prior to commencing any test function:\n\n (a) CHECK all safety guards are in place and secure.\n\n (b) CHECK the water supply availabilityâ€”town main pressure adequate or suction tank is full.\n\n (c) Where compression ignition engine driven pumpsets are installed, CHECK that water, oil, belt drives and exhaust condensate drains and cooling water valves are in the correct position. Check fuel water-trap/filter for water contamination. Rectify where required.","sort_order":10,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":571,"active":true,"required":false,"type":"REMARK","label":"CHECK - Run test checks","help_text":"During and after the running period CHECK:\n\n (a) Pump operates at the correct discharge pressure. Record suction and discharge pressure.\n\n ** NOTE: ** The discharge pressures may vary with varied suction static pressure. An excessive negative suction pressure may indicate a suction partial blockage or partially closed valve.\n\n (b) Pump gland and drain (where applicable) operates efficiently.\n\n (c) Out-of-balance condition or abnormal noises are not evident.\n\n (d) All local and remote â€˜pump runningâ€™ alarms operate.\n\n (e) Running speed is correct, and record the result.\n\n (f) Water, oil and fuel leaks are not evident and fittings on ancillary equipment are secure.\n\n (g) Battery charger or alternator/generator is operating at required value within tolerances.\n\n (h) Engine stop mechanism returns to start position automatically.\n\n (i) Belt drives are in good condition.\n\n (j) Battery charger power failure alarm operates correctly.\n\n (k) Engine instrumentation is operating. Record the results.\n\n (l) Flow is evident from the circulation relief valve when the pump is operating at shut-off head and ceases at the appropriate pressure.\n\n (m) Exhaust system is leak free.\n\n (n) Cooling water (heat exchanger cooled engines only) is discharging.","sort_order":11,"ref":"1.14","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1462,"active":true,"required":false,"type":"DECIMAL","label":"Record battery charger voltage (V)","help_text":"Record battery charger voltage (V)","sort_order":12,"ref":"1.14(g)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1463,"active":true,"required":false,"type":"INTEGER","label":"Record oil pressure (kPa)","help_text":"Record oil pressure (kPa)","sort_order":13,"ref":"1.14(k)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1464,"active":true,"required":false,"type":"INTEGER","label":"Record engine temp (deg C)","help_text":"Record engine temp (deg C)","sort_order":14,"ref":"1.14(k)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1453,"active":true,"required":false,"type":"INTEGER","label":"Record suction pressure (kPa)","help_text":"Record suction pressure (kPa)","sort_order":15,"ref":"1.14(a)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1454,"active":true,"required":false,"type":"INTEGER","label":"Record discharge pressure (kPa)","help_text":"Record discharge pressure (kPa)","sort_order":16,"ref":"1.14(a)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":572,"active":true,"required":false,"type":"REMARK","label":"CHECK - Electric motor driven pumpsetâ€”Precautions","help_text":"Prior to commencing any test function:\n\n (a) CHECK all safety guards are in place and secure.\n\n (b) CHECK enclosure for corrosion and ingress of water, dust or insects.","sort_order":17,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":573,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump controller status","help_text":"CHECK that the main isolating switch is in the ON position and secured in position where facilities are provided and, where fitted, the green power supply lamps are illuminated and that no red warning lamps are on. Ensure all lights are functional by pressing the lamp test button, where fitted.","sort_order":18,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":574,"active":true,"required":false,"type":"REMARK","label":"START & RECORD - Pump starting devices","help_text":"(a) START each pumpset by reducing the applied water pressure to the starting device and run motor continuously for at least 3 minutes.\n\n (b) RESTART each pumpset using the manual starting device and run motor continuously for at least 3 minutes.\n\n (c) RECORD the starting pressures and the run time at the completion of the test.","sort_order":19,"ref":"1.17","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1455,"active":true,"required":false,"type":"INTEGER","label":"Record the Starting Pressures (kPa)","help_text":"Record the Starting Pressures (kPa)","sort_order":20,"ref":"1.17(c)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1456,"active":true,"required":false,"type":"INTEGER","label":"Record the Run Time (min)","help_text":"Record the Run Time (min)","sort_order":21,"ref":"1.17(c)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":575,"active":true,"required":false,"type":"REMARK","label":"CHECK & RECORD - Run test checks","help_text":"During and after the running period CHECK:\n\n (a) Pump operates at the correct discharge pressures allowing for varying suction conditions. Record suction and discharge pressure.\n\n (b) Pump glands and drain or mechanical seal(s) operate efficiently.\n\n (c) Out-of-balance condition or abnormal noises are not evident.\n\n (d) Both local and remote â€˜pump runningâ€™ alarms and lights operate.","sort_order":22,"ref":"1.18","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1457,"active":true,"required":false,"type":"INTEGER","label":"Record suction pressure (kPa)","help_text":"Record suction pressure (kPa)","sort_order":23,"ref":"1.18(a)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1458,"active":true,"required":false,"type":"INTEGER","label":"Record discharge pressure (kPa)","help_text":"Record discharge pressure (kPa)","sort_order":24,"ref":"1.18(a)","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":576,"active":true,"required":false,"type":"REMARK","label":"RETURN - Restoration to operational condition all pumpsets","help_text":"After completion of testing procedures, RETURN all equipment to the operational condition.","sort_order":25,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":577,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 3.4.2 (Six-monthly service)","help_text":"AS1851-2012 Table 3.4.2 (Six-monthly service)","sort_order":26,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":578,"active":true,"required":false,"type":"REMARK","label":"Monthly service","help_text":"Complete all monthly service activities, as listed in Table 3.4.1.","sort_order":27,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":579,"active":true,"required":false,"type":"REMARK","label":"Alternative power-suppliesâ€” Electric motordriven pumpset","help_text":"In addition to the requirement of Item 1.17 of Table 3.4.1, where alternative power supplies are provided, RUN the pump(s) continuously for not less than 3 minutes off the alternative supply.","sort_order":28,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":580,"active":true,"required":false,"type":"REMARK","label":"Hydro-pneumatic accumulator (where fitted)","help_text":"CHECK accumulator air pressure.","sort_order":29,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":581,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 3.4.3 (Annual service)","help_text":"AS1851-2012 Table 3.4.3 (Annual service)","sort_order":30,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":582,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and six-monthly service","help_text":"Complete all monthly and six-monthly service activities as listed in Tables 3.4.1 and 3.4.2.","sort_order":31,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":583,"active":true,"required":false,"type":"HEADER","label":"(a) With the pump room door(s) closed and the pump testing technician present:\n (i) RUN the pumpset at shut-off (zero flow) for 3 min.","help_text":"(a) With the pump room door(s) closed and the pump testing technician present:\n\n (i) RUN the pumpset at shut-off (zero flow) for 3 min.","sort_order":32,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":584,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (A) Suction pressure .......kPa","help_text":"(A) Suction pressure.","sort_order":33,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":585,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (B) Discharge pressure .....kPa","help_text":"(B) Discharge pressure.","sort_order":34,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":586,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (C) Air temperature at the electric motor .......Â°C","help_text":"(C) Air temperature at the electric motor.","sort_order":35,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":587,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (D) Motor RPM.","help_text":"(D) Motor RPM.","sort_order":36,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":588,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (E) Amps (all three phases).","help_text":"(E) Amps (all three phases).","sort_order":37,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":589,"active":true,"required":false,"type":"HEADER","label":"(ii) RUN the pumpset at 130% of duty flow (sprinklers, hydrants or combined as applicable) for 4 min and record the result.","help_text":"(ii) RUN the pumpset at 130% of duty flow (sprinklers, hydrants or combined as applicable) for 4 min and record the result.","sort_order":38,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":590,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (A) Suction pressure .......kPa","help_text":"(A) Suction pressure.","sort_order":39,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":591,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (B) Discharge pressure .....kPa","help_text":"(B) Discharge pressure.","sort_order":40,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":592,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (C) Air temperature at the electric motor .......Â°C","help_text":"(C) Air temperature at the electric motor.","sort_order":41,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":593,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (D) Motor RPM.","help_text":"(D) Motor RPM.","sort_order":42,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":594,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (E) Amps (all three phases).","help_text":"(E) Amps (all three phases).","sort_order":43,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":595,"active":true,"required":false,"type":"HEADER","label":"(iii) Reduce the flow to the duty flow (sprinklers, hydrants or combined) for sufficient time to record the water supply proving test results.","help_text":"(iii) Reduce the flow to the duty flow (sprinklers, hydrants or combined) for sufficient time to record the water supply proving test results.","sort_order":44,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":596,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (A) Suction pressure .......kPa","help_text":"(A) Suction pressure.","sort_order":45,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":597,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (B) Discharge pressure .....kPa","help_text":"(B) Discharge pressure.","sort_order":46,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":598,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (C) Air temperature at the electric motor .......Â°C","help_text":"(C) Air temperature at the electric motor.","sort_order":47,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":599,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (D) Motor RPM.","help_text":"(D) Motor RPM.","sort_order":48,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":600,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (E) Amps (all three phases).","help_text":"(E) Amps (all three phases).","sort_order":49,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":601,"active":true,"required":false,"type":"HEADER","label":"(iv) Further reduce the flow until shut-off (zero flow) is achieved and continue to run the pumpset until total run time has reached 10 min.","help_text":"(iv) Further reduce the flow until shut-off (zero flow) is achieved and continue to run the pumpset until total run time has reached 10 min.","sort_order":50,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":602,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (A) Suction pressure .......kPa","help_text":"(A) Suction pressure.","sort_order":51,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":603,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (B) Discharge pressure .....kPa","help_text":"(B) Discharge pressure.","sort_order":52,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":604,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (C) Air temperature at the electric motor .......Â°C","help_text":"(C) Air temperature at the electric motor.","sort_order":53,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":605,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (D) Motor RPM.","help_text":"(D) Motor RPM.","sort_order":54,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":606,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (E) Amps (all three phases).","help_text":"(E) Amps (all three phases).","sort_order":55,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":607,"active":true,"required":false,"type":"HEADER","label":"RUN - Annual full flow testâ€” Electric motordriven pumpsetâ€”Sprinklers and hydrants load test","help_text":"During this period RECORD the following for Items (ii), (iii) and (iv) above:","sort_order":56,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":608,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (A) Suction pressure .......kPa","help_text":"(A) Suction pressure.","sort_order":57,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":609,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (B) Discharge pressure .....kPa","help_text":"(B) Discharge pressure.","sort_order":58,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":610,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (C) Air temperature at the electric motor .......Â°C","help_text":"(C) Air temperature at the electric motor.","sort_order":59,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":611,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (D) Motor RPM.","help_text":"(D) Motor RPM.","sort_order":60,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":612,"active":true,"required":false,"type":"INTEGER","label":"RUN - Annual full flow test - (E) Amps (all three phases).","help_text":"(E) Amps (all three phases).","sort_order":61,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":613,"active":true,"required":false,"type":"REMARK","label":"CHECK & TEST - Annual full flow testâ€” Equipment","help_text":"** NOTE ** Ensure current does not exceed full load current of the electric motor.\n\n While carrying out the above procedure, CHECK temperature of bearings and stuffing box leakage and note and report any abnormality.\n\n (b) TEST correct operation of pump priming tanks and associated equipment, were fitted.","sort_order":62,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":614,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Electric motordriven pumpset","help_text":"With all electrical equipment isolated from all power supplies:\n\n (a) INSPECT the condition of all exposed heavy current-carrying contacts. Report any item showing any signs of wear or corrosion.\n\n (b) INSPECT pump/driver coupling for wear and alignment. Report worn or damaged components.\n\n (c) Where grease nipples are provided, GREASE pump and motor bearings to the manufacturerâ€™s specifications.\n\n (d) Where the pump bearings are of the oillubricated type, REPLACE the bearing oil with new oil that meets the pump manufacturerâ€™s specification (does not apply to turbine type vertical shaft centrifugal pumps).","sort_order":63,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":615,"active":true,"required":false,"type":"REMARK","label":"ENSURE - Non-return valves","help_text":"ENSURE all non-return valves are operating freely and are seating correctly.","sort_order":64,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":616,"active":true,"required":false,"type":"REMARK","label":"SURVEY - Pipework corrosion","help_text":"SURVEY the system and equipment to identify external corrosion, and detail extent and location accordingly.","sort_order":65,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":617,"active":true,"required":false,"type":"REMARK","label":"CHECK - System pressure-relief valve","help_text":"CHECK that the system pressure relief valve opens and closes at the pressure required.\n\n ** NOTE: ** Inappropriate settings for pressure-relief valves can result in very large quantities of water flowing to waste. Ensure settings are maintained to have pressures as identified and not higher than allowed by system component rated working pressures.","sort_order":66,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":618,"active":true,"required":false,"type":"REMARK","label":"RETURN - Restoration to operational condition","help_text":"After completion of testing procedures, RETURN all equipment to the operational condition.","sort_order":67,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":619,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Variable speed control","help_text":"Operate the pump at 50% of duty flow and 100% of duty flow, and ensure duty head is not exceeded by more than 10%.","sort_order":68,"ref":"3.15","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":620,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Remote pump start/stop function","help_text":"Operate the pump start/stop functions from the remote location, and ensure the appropriate indications are received at the FIP/remote stop/start panel.","sort_order":69,"ref":"3.16","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":621,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 3.4.4 (Five-Annual service)","help_text":"AS1851-2012 Table 3.4.4 (Five-Annual service)","sort_order":70,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":622,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly, sixmonthly and Annual service","help_text":"COMPLETE all monthly, six-monthly and Annual activities, as listed in Tables 3.4.1, 3.4.2 and 3.4.3.","sort_order":71,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":623,"active":true,"required":false,"type":"REMARK","label":"REPACK - Pump","help_text":"REPACK pump glands.","sort_order":72,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":624,"active":true,"required":false,"type":"REMARK","label":"OVERHAUL - Relief, engine cooling and pressure regulating valves","help_text":"OVERHAUL the following valves in accordance with supplierâ€™s specifications:\n\n (a) Circulation-relief valves.\n\n (b) Pressure-relief valves.\n\n (c) Engine cooling valve.\n\n (d) Pressure regulating valve.","sort_order":73,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":625,"active":true,"required":false,"type":"REMARK","label":"FIT & CHECK - Stop valves","help_text":"(a) FIT new gland packing and lubricate spindles.\n\n (b) For ball and butterfly valves, CHECK for leakage and replace if necessary.","sort_order":74,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":626,"active":true,"required":false,"type":"REMARK","label":"RETURN - Restoration to operational condition","help_text":"After completion of testing procedures, RETURN all equipment to the operational condition.","sort_order":75,"ref":"4.6","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Electric Pump","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire pumpset: Pressure Maintenance (Jacking)","prompts":[{"id":627,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 3.4.5.1 (Monthly service)","help_text":"AS1851-2012 Table 3.4.5.1 (Monthly service)","sort_order":1,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire pumpset: Pressure Maintenance (Jacking)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":633,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 3.4.5.2 (Six-monthly service)","help_text":"AS1851-2012 Table 3.4.5.2 (Six-monthly service)","sort_order":1,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire pumpset: Pressure Maintenance (Jacking)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":628,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump areas","help_text":"(a) CHECK that pump areas are unobstructed, not used for storage and lighting is adequate.\n\n(b) Where pump pressure-relief valves are fitted, CHECK that the discharge will not cause flooding or water damage.\n\n(c) CHECK for any obvious signs of physical damage or deterioration and that all safety guards are in place and secure.","sort_order":2,"ref":"5.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Pressure Maintenance (Jacking)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":634,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service","help_text":"COMPLETE all monthly service activities, as listed in Table 3.4.5.1.","sort_order":2,"ref":"6.1","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Pressure Maintenance (Jacking)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":629,"active":true,"required":false,"type":"REMARK","label":"ENSURE - Valves","help_text":"ENSURE that all valves are in the open position or the closed position, as labelled, and secured where applicable.","sort_order":3,"ref":"5.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Pressure Maintenance (Jacking)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":635,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Hydropneumatic accumulator","help_text":"VERIFY that the air pressure is correct.","sort_order":3,"ref":"6.2","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Pressure Maintenance (Jacking)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":630,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water supply tank (where fitted)","help_text":"CHECK that the water supply tank is full.","sort_order":4,"ref":"5.3","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Pressure Maintenance (Jacking)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":631,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump controller status","help_text":"CHECK that the main isolating switch is in the on position and secured (where facilities are provided), the green power supply lamps are illuminated and that no red warning lamps are on. Ensure all lights are functional by pressing the lamp test button, where fitted.","sort_order":5,"ref":"5.4","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Pressure Maintenance (Jacking)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":632,"active":true,"required":false,"type":"INTEGER","label":"VERIFY & RECORD - Pump","help_text":"(a) VERIFY operation (manual and automatic).\n\n(b) RECORD cut-in and cut-out pressures.","sort_order":6,"ref":"5.5","estimated_duration":null,"prompt_set":"2012: Fire pumpset: Pressure Maintenance (Jacking)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Rated Access Panel","prompts":[{"id":1124,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.1.4 (Annual service)","help_text":"AS1851-2012 Table 12.4.1.4 (Annual service)","sort_order":1,"ref":"4","estimated_duration":null,"prompt_set":"2012: Fire Rated Access Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1125,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Access panel","help_text":"INSPECT against drawings (see Clause 12.2.5) that access panels or hatches, including resistance to incipient spread of fire, have been added, removed or modified.","sort_order":2,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Fire Rated Access Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1126,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Access panel or leaf","help_text":"(a) INSPECT panel to ensure it is free of any visible delamination, and other damage.\n\n(b) INSPECT that the any perimeter seal is in good condition and not damaged.","sort_order":3,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Fire Rated Access Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1127,"active":true,"required":false,"type":"REMARK","label":"INSPECT & VERIFY - Frame","help_text":"(a) INSPECT access panel frame is adequately anchored to surrounding structure.\n\n(b) VERIFY that doorframe is free from excessive distortion at any point along frame sections.","sort_order":4,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire Rated Access Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1128,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Screw-fixed panels (where applicable)","help_text":"INSPECT to ensure screw fixings are all present and engaged in the frame securely.","sort_order":5,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Fire Rated Access Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1129,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Hinged and/or latched panels (where applicable)","help_text":"(a) INSPECT to ensure hinges are in good working order and any latches are operational.\n\n(b) INSPECT no visible through-gap is created around lock/latch, and that the correct number of hinges and locks are present.","sort_order":6,"ref":"4.5","estimated_duration":null,"prompt_set":"2012: Fire Rated Access Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1130,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Additions","help_text":"INSPECT that any added laminates and/or hardware do not interfere with the function of the access panel.","sort_order":7,"ref":"4.6","estimated_duration":null,"prompt_set":"2012: Fire Rated Access Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Rated Glazing (Window)","prompts":[{"id":1048,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.6 (Annual SERVICE)","help_text":"AS1851-2012 Table 12.4.6 (Annual SERVICE)","sort_order":1,"ref":"6","estimated_duration":null,"prompt_set":"2012: Fire Rated Glazing (Window)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1049,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Location","help_text":"INSPECT against drawings (see Clause 12.2.5) that no fire-rated glazing has been added, removed or modified.","sort_order":2,"ref":"6.1","estimated_duration":null,"prompt_set":"2012: Fire Rated Glazing (Window)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1050,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Glass","help_text":"(a) INSPECT for any crazing or cracking around perimeter of glass.\n\n(b) INSPECT for impact crazing or cracking over entire surface area of glass.","sort_order":3,"ref":"6.2","estimated_duration":null,"prompt_set":"2012: Fire Rated Glazing (Window)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1051,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Frame","help_text":"(a) VERIFY that frame is free from distortion at any point along the frame section.\n\n(b) INSPECT frame is securely anchored and free from any visible defects or corrosion.\n\n(c) INSPECT perimeter to ensure no through-gaps are visible and the frame has been fire stopped where it meets bounding construction.","sort_order":4,"ref":"6.3","estimated_duration":null,"prompt_set":"2012: Fire Rated Glazing (Window)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1052,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Seals","help_text":"INSPECT glazing seals are present and have not deteriorated.","sort_order":5,"ref":"6.4","estimated_duration":null,"prompt_set":"2012: Fire Rated Glazing (Window)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Rated Horizontal Sliding Door","prompts":[{"id":1069,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.3.2 (THREE-MONTHLY)","help_text":"AS1851-2012 Table 12.4.3.2 (THREE-MONTHLY)","sort_order":0,"ref":"2","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1070,"active":true,"required":false,"type":"REMARK","label":"SIMULATE & CHECK - Frictional forces, operation and self-closing ability","help_text":"SIMULATE a full operational test (mechanically and electronically) as appropriate to ensure correct automatic closing of the door is achieved.\n\nCHECK operation to ensure the door fully closes from the fully open position and from one intermediary position.","sort_order":1,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1071,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.3.2 (SIX-MONTHLY SERVICE)","help_text":"AS1851-2012 Table 12.4.3.2 (SIX-MONTHLY SERVICE)","sort_order":2,"ref":"2","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1072,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Location","help_text":"INSPECT against drawings and all schedules (see Clause 12.2.5) to ensure that no fire doors has been added, removed or modified.","sort_order":3,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1073,"active":true,"required":false,"type":"REMARK","label":"INSEPCT - Marking-Tags and signage","help_text":"(a) INSPECT door leaves and door frames (where applicable) are tagged in accordance with AS 1905.1.\n\n(b) INSPECT to ensure relevant statutory signage has been applied and that the location of the signage is in accordance with regulatory requirements.","sort_order":4,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1074,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Clearances and overlaps in the closed position","help_text":"INSPECT clearances and overlaps of door panel(s) are in accordance with AS 1905.1.","sort_order":5,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1075,"active":true,"required":false,"type":"REMARK","label":"CHECK - Frictional forces, operation and self-closing ability","help_text":"CHECK forces to open and close door leaves do not exceed maximum 110 N for a door in the path of travel to an exit and 180 N from the closed position and 135 N through its full travel in other places.","sort_order":6,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1076,"active":true,"required":false,"type":"REMARK","label":"INSPCT - Restraint brackets and interlocking steel sections (flame guards)","help_text":"INSPECT restraint brackets and/or interlocking steel sections are as per manufacturer’s specifications, fixed adequately and functional.","sort_order":7,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1077,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Hardware","help_text":"(a) INSPECT hardware required for suspension and operation is fitted and is as per manufacturer’s specifications.\n\n(b) INSPECT hardware is securely attached with the correct fittings in accordance with the requirements of AS 1905.1.","sort_order":8,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1078,"active":true,"required":false,"type":"REMARK","label":"CHECK - Automatic operations","help_text":"(a) CHECK fusible links, where fitted, are intact and unpainted.\n\n(b) CHECK pulley cables are free from fraying, kinks, excessive stretching and corrosion.\n\n(c) CHECK pulleys are free to rotate.\n\n(d) REPLACE all fusible links every 25 years from the date of manufacture.\n\n** NOTE: ** In lieu of replacing all fusible links, a representative sample may be tested as per Section 2.\n\n(e) PERFORM a full operational test (mechanically and electrically) as appropriate to ensure correct automatic closing of the door is achieved.\n\n(f) CHECK operation to ensure the door fully closes from one intermediary position.\n\n(g) TEST operation of illuminated sliding doors, warning signs, sounders and release delays, as appropriate.","sort_order":9,"ref":"2.8","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1079,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Door guides, stops and restraints","help_text":"INSPECT floor and/or track and/or wall-mounted guides and stops and all travel-limiting devices at door open and close locations are adequate and soundly mounted.","sort_order":10,"ref":"2.9","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1080,"active":true,"required":false,"type":"REMARK","label":"CHECK - Other fittings and accessories","help_text":"(a) CHECK arrows indicating opening direction are fixed to each side of the door leaves.\n\n(b) CHECK flush pulls, handles or grips are securely fixed.","sort_order":11,"ref":"2.10","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1081,"active":true,"required":false,"type":"REMARK","label":"INSPECT & CHECK - Door leaf","help_text":"(a) INSPECT door leaf or leaves are free from any delamination, any other damage and all perimeter edge capping is complete and sound.\n\n(b) CHECK door leaf or leaves is/are free from any non-approved fittings, fixings and attachments.","sort_order":12,"ref":"2.11","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1082,"active":true,"required":false,"type":"REMARK","label":"CHECK - Door frame (where applicable)","help_text":"CHECK door frame is adequately anchored to the opening.","sort_order":13,"ref":"2.12","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1083,"active":true,"required":false,"type":"REMARK","label":"CHECK - Other features","help_text":"(a) CHECK service access panels for cavity sliders are suitable and accessible.\n\n(b) CHECK the sill under the door leaf is free from the addition of any combustible covering since installation or previous inspection.","sort_order":14,"ref":"2.13","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1084,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Multiple-leaf doors","help_text":"In addition to the above, INSPECT overlaps or jointing of individual door leaf panels at meeting stiles are in proper alignment and comply with manufacturer’s specifications.","sort_order":15,"ref":"2.14","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1085,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Wicket doors or personnel access doors","help_text":"INSPECT wicket or personnel access doors operate satisfactorily in accordance with the hinged door leaf requirements, and in accordance with the manufacturer’s test approval.\n\n** NOTE: ** These doors are usually found integrated within the sliding door leaf or leaves and are typically side-hung doors.","sort_order":16,"ref":"2.15","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1086,"active":true,"required":false,"type":"REMARK","label":"SERVICE - Power-assisted sliding doors","help_text":"Power-assisted sliding doors are to be serviced in accordance with the manufacturer’s maintenance procedures.","sort_order":17,"ref":"2.16","estimated_duration":null,"prompt_set":"2012: Fire Rated Horizontal Sliding Door","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Rated Shutter","prompts":[{"id":1053,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.5 (Annual SERVICE)","help_text":"AS1851-2012 Table 12.4.5 (Annual SERVICE)","sort_order":1,"ref":"5","estimated_duration":null,"prompt_set":"2012: Fire Rated Shutter","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1054,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Location","help_text":"INSPECT against drawings and all schedules (see Clause 12.2.5) that no fire shutters have been added, removed or modified.","sort_order":2,"ref":"5.1","estimated_duration":null,"prompt_set":"2012: Fire Rated Shutter","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1055,"active":true,"required":false,"type":"REMARK","label":"CHECK - Marking - Tags and signage","help_text":"CHECK fire shutters and frames are tagged in accordance with AS 1905.2.","sort_order":3,"ref":"5.2","estimated_duration":null,"prompt_set":"2012: Fire Rated Shutter","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1056,"active":true,"required":false,"type":"REMARK","label":"CHECK - Bracket fixings and barrel assembly","help_text":"(a) CHECK brackets are securely fixed to the walls.\n\n(b) CHECK barrel assembly is mounted so that the rolled-up curtain on the barrel sits higher than the top level of the guide tracks.","sort_order":4,"ref":"5.3","estimated_duration":null,"prompt_set":"2012: Fire Rated Shutter","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1057,"active":true,"required":false,"type":"REMARK","label":"CHECK - Guide track fixings","help_text":"(a) CHECK guide tracks are securely fixed to the walls.\n\n(b) CHECK guide tracks are mounted such that the curtain overlaps equally the jamb on each side of the opening.\n\n(c) CHECK the gap between the end of the slats, including end clips and the guide track, is no more that 10 mm.\n\n(d) CHECK that the shutter moves freely in the guide tracks without jamming under normal operation.","sort_order":5,"ref":"5.4","estimated_duration":null,"prompt_set":"2012: Fire Rated Shutter","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1058,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Threshold","help_text":"INSPECT that the threshold is of concrete or similar approved material deemed non-combustible.","sort_order":6,"ref":"5.5","estimated_duration":null,"prompt_set":"2012: Fire Rated Shutter","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1059,"active":true,"required":false,"type":"REMARK","label":"INSPECT & REPLACE - Fusible link","help_text":"(a) INSPECT that the fire shutter is fitted with a fusible link (if applicable) of not greater than 80ºC (57ºC in the case of a drenched fire shutter) and the fusible link is in good and operational condition.\n\n(b) REPLACE all fusible links every 25 years from the date of manufacture.\n\n** NOTE: ** In lieu of replacing all fusible links, a representative sample may be tested as per Section 2.","sort_order":7,"ref":"5.6","estimated_duration":null,"prompt_set":"2012: Fire Rated Shutter","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1060,"active":true,"required":false,"type":"REMARK","label":"TEST - Operation test","help_text":"(a) TEST that under simulated automatic operation the fire shutter curtain descends to the threshold at an average speed of between 0.15 m/s and 0.3 m/s.\n\n(b) TEST that under simulated automatic operation the curtain does not rebound creating a gap greater than 25 mm between the bottom rail and the threshold.\n\n(c) CHECK shutter slats, bottom rail and brake release mechanism, illuminated warning signs, sounders and release delays (where fitted) are free from damage and the slats are not binding on each other when opening and closing.","sort_order":8,"ref":"5.7","estimated_duration":null,"prompt_set":"2012: Fire Rated Shutter","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Sprinkler System: Deluge and Water Spray","prompts":[{"id":298,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.1 (Monthly Inspection)","help_text":"AS1851-2012 Table 2.4.2.1 (Monthly Wet Pipe Inspection)","sort_order":1,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":299,"active":true,"required":false,"type":"REMARK","label":"CHECK - Control valve assembly","help_text":"CHECK that control valve assembly area is unobstructed and free of any condition that may adversely affect the operation or access.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":300,"active":true,"required":false,"type":"REMARK","label":"CHECK - Sprinkler spares, sprinklers and sprinkler spanner","help_text":"CHECK that there are spare sprinklers of appropriate quantity and type including a matching sprinkler spanner for each type of sprinkler fitted, available.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":301,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage","help_text":"CHECK for damage, legibility and appropriate location of required signage.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":302,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire brigade booster connection - Obstruction","help_text":"CHECK that the booster connection or enclosure is unobstructed and for any condition that may adversely affect the operation or access.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":303,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire brigade booster connection - Couplings","help_text":"CHECK that the booster connection coupling type is as per the local fire brigade requirements.","sort_order":6,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":304,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Main stop valves and alarm cocks","help_text":"INSPECT each main stop valve and alarm cock for each control assembly is secured in the open position and the main stop valve is correctly labelled.","sort_order":7,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":305,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Main stop valves and alarm cocks","help_text":"CHECK that each isolating valve to each automatic pump start device is locked in the open position.","sort_order":8,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":306,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure switches","help_text":"CHECK each pressure switch and ensure that the cover is in place, correctly labelled, securely mounted and free from any condition likely to adversely affect its function.","sort_order":9,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":307,"active":true,"required":false,"type":"REMARK","label":"CHECK - Alarm signalling equipment (ASE) (stand-alone)","help_text":"CHECK the alarm signalling equipment to ensure that it is securely mounted, free from any condition likely to adversely affect its function and is not indicating alarm, fault, loss of connection, or isolated.","sort_order":10,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":308,"active":true,"required":false,"type":"REMARK","label":"CHECK - Sprinkler system interface to other systems","help_text":"CHECK the sprinkler system alarm interface with other systems is not isolated, inhibited or disabled.","sort_order":11,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":309,"active":true,"required":false,"type":"REMARK","label":"NOTE - Water supply stop valves","help_text":"1 - Where more than 12 water supply stop valves are distributed throughout a high-rise building, forming part of a combined sprinkler/hydrant system, the actions under actions (a) and (b) may be conducted on a rotating basis.\n2 - The period between testing of all water supply stop valves should not exceed 3 months.","sort_order":12,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":310,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Water supply stop valves","help_text":"(a) OPERATE (two full turns) all water supply stop valves (including backflow prevention stop valves but excluding underground keyoperated valves) and verify they are fully open, secure in the open position (relaxed Â¼ turn if appropriate) and are correctly labelled.","sort_order":13,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":311,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Water supply stop valves","help_text":"(b) VERIFY that the valve position indicators are securely mounted and indicate correctly.","sort_order":14,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":312,"active":true,"required":false,"type":"INTEGER","label":"RECORD - System pressure gauge readings before alarm function test, kPa.......","help_text":"(a) RECORD reading from each pressure gauge.","sort_order":15,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":313,"active":true,"required":false,"type":"REMARK","label":"VERIFY - System pressure gauge readings before alarm function test","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":16,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":314,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(a) OPERATE each alarm valve by opening each 15 mm test valve or 10 mm for residential sprinkler systems serving buildings up to 4 storeys in height. Where more than 12 control assemblies are distributed throughout a high-rise building forming part of a combined sprinkler/hydrant system, and initiate the fire brigade alarm, testing may be conducted on a rotating basis. The period between testing of all control assemblies shall not exceed 3 months.","sort_order":17,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":315,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(b) RECORD time(s) to operation of alarm gong(s) and verify that time does not exceed 180 s for general systems or 90 s for residential sprinkler systems.","sort_order":18,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":316,"active":true,"required":false,"type":"REMARK","label":"RESET - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(c) RESET the alarm test valve on completion of each test.","sort_order":19,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":317,"active":true,"required":false,"type":"REMARK","label":"TEST - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(d) Where multiple control valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.","sort_order":20,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":318,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Alarm signal","help_text":"VERIFY the correct operation of each alarm signal. Where the system is monitored ensure the alarm has activated the alarm signalling equipment.","sort_order":21,"ref":"1.13","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":319,"active":true,"required":false,"type":"REMARK","label":"INSPECT - DSEP/DBEP strobe indicator","help_text":"INSPECT for the correct operation of each DSEP/DBEP strobe indicator, where fitted.","sort_order":22,"ref":"1.14","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":320,"active":true,"required":false,"type":"INTEGER","label":"RECORD - System pressure gauge readings after alarm valve test","help_text":"(a) RECORD reading from each pressure gauge.","sort_order":23,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":321,"active":true,"required":false,"type":"REMARK","label":"VERIFY - System pressure gauge readings after alarm valve test","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":24,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":322,"active":true,"required":false,"type":"REMARK","label":"TEST - Pump starting devices function test - Compression ignition drivers (diesel) and electric motor drivers","help_text":"(a) TEST each automatic pump starting device and pump operation by reducing the applied water pressure to the starting device and run pump, in accordance with Section 3. Where more than one starting device is installed, including the manual starting device, the test may be carried out on a rotating basis. The period between the exercising of each starting device is not to exceed 3 months. Where this would require the pump to start more than 5 times in succession, the period may be extended to 6 months.","sort_order":25,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":323,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pump starting devices function test - CUT IN PRESSURE","help_text":"(b) RECORD the pump cut-in pressures and verify that they are within the ranges required.","sort_order":26,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":324,"active":true,"required":false,"type":"REMARK","label":"TEST - Manual pump start device, function test","help_text":"TEST each manual pump starting device and pump operation in accordance with Section 3.","sort_order":27,"ref":"1.17","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":325,"active":true,"required":false,"type":"REMARK","label":"PERFORM - Water supply tanks - Atmospheric or pressure","help_text":"Perform routine service in accordance with Section 5.","sort_order":28,"ref":"1.18","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":326,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foam water sprinkler systems - foam concentrate","help_text":"CHECK that the concentrate level is correct and level indicator reads correctly.","sort_order":29,"ref":"1.19","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":278,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.4.1 (Monthly Inspection)","help_text":"AS1851-2012 Table 2.4.4.1 (Monthly Deluge & Water Spray Inspection)","sort_order":30,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":279,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service activities","help_text":"COMPLETE all monthly wet pipe service activities listed in Table 2.4.2.1 that are applicable to a deluge and water spray system.","sort_order":31,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":280,"active":true,"required":false,"type":"DECIMAL","label":"CHECK - Pressure gauge readings........kPa","help_text":"CHECK that all pressure gauge readings are within the ranges required and RECORD reading from each pressure gauge.","sort_order":32,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":281,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air compressor oil level (where fitted)","help_text":"(a) CHECK oil level is correct and visually assess condition of oil.\n(b) CHECK regulator is locked and set in the correct position.","sort_order":33,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":282,"active":true,"required":false,"type":"REMARK","label":"INSPECT & TEST - Electrical detection (where fitted)","help_text":"INSPECT and TEST in accordance with Section 6.","sort_order":34,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":283,"active":true,"required":false,"type":"REMARK","label":"CHECK - Detector sprinkler line (where fitted)","help_text":"CHECK detector sprinkler line valves are in the correct operating position.","sort_order":35,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":284,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Air compressor (where fitted)","help_text":"VERIFY that air compressor operates at specified cut-in and cut-out pressures.","sort_order":36,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":285,"active":true,"required":false,"type":"REMARK","label":"TEST - Solenoid valve(s)","help_text":"TEST solenoid valves for correct operations.","sort_order":37,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":286,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Low air pressure alarm(s)","help_text":"VERIFY:\n(a) Low air pressure alarm operates at predetermined levels.\n(b) Low pressure alarm(s) visual indicator and sounders are optional.","sort_order":38,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":287,"active":true,"required":false,"type":"REMARK","label":"GENERATE & OBSERVE - Local alarm and fire brigade test simulation in lieu of Item 1.12 in Table 2.4.2.1","help_text":"(a) GENERATE a test of the alarm signalling equipment and local alarm in accordance with the manufacturer's operating manual.\n** NOTE: ** Where fitted, bypass valve may be used for this test.\n(b) OBSERVE correct operation of the fire brigade alarm from each deluge and water spray valve or group of deluge and water spray valves. Where the system is monitored, ensure the alarm has activated the alarm signalling equipment.\n** NOTE: Where multiple deluge and water spray valve assemblies are separately identified at the FIP, only one transmission from the FIP to the monitoring station is required.\"","sort_order":39,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1465,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.2 (Six-monthly Inspection)","help_text":"AS1851-2012 Table 2.4.2.2 (Six-monthly Wet Pipe Inspection)","sort_order":40,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1466,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Floor/zone indication test (where fitted)","help_text":"COMPLETE all monthly service activities, as listed in Table 2.4.2.1.","sort_order":41,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1467,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Floor/zone indication test (where fitted)","help_text":"(a) OPERATE each flow switch test arrangement (automatic or manual).","sort_order":42,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1468,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Floor/zone indication test (where fitted)","help_text":"(b) VERIFY correct flow switch indication at the CIE.","sort_order":43,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1469,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Underground keyoperated and subsidiary valves","help_text":"(a) Except where owned by the water supply authority, OPERATE (two full turns) all underground key-operated valves and verify they are fully open, secure in the open position (relaxed Â¼ turn if appropriate) and are correctly labelled.\n** NOTE: ** Where underground key-operated valves are owned by the water supply authority, the owner should arrange for the water supply authority to test the valve(s) to confirm the valve(s) is operational and in the correct position.\n(b) OPERATE all subsidiary stop valves (floor isolation valves, tail-end valves).Ensure that they are fully open and, where applicable, secured in the open position and are correctly labelled.","sort_order":44,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1510,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Number valves checked","help_text":"RECORD number underground keyoperated and subsidiary valves checked.","sort_order":45,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1470,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Valve-monitoring device test","help_text":"Test each valve monitor by operating the valve and VERIFY the correct indication at the CIE.","sort_order":46,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1511,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Number monitors checked","help_text":"RECORD number valve monitors checked.","sort_order":47,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1512,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pressure gauge readings before main drain test","help_text":"RECORD reading from each pressure gauge.","sort_order":48,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1471,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Pressure gauge readings before main drain test","help_text":"VERIFY pressure gauge readings are within the ranges required.","sort_order":49,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1472,"active":true,"required":false,"type":"REMARK","label":"OPEN - Main drain valve water supply test - Town main supply only","help_text":"(a) OPEN the sprinkler control assembly main drain valve without pump(s) running. In the case of grouped valve sets, open one only.","sort_order":50,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1473,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Main drain valve water supply test - Town main supply only","help_text":"(b) VERIFY that residual water supply pressure, with drain valve open, is within 10% of the original value recorded.","sort_order":51,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1513,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Stabilize flow water supply pressure","help_text":"RECORD stabilize flow water supply pressure (kPa)","sort_order":52,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1474,"active":true,"required":false,"type":"REMARK","label":"CLOSE - Main drain valve water supply test - Town main supply only","help_text":"(c) CLOSE main drain valve and record time for pressure recovery.","sort_order":53,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1514,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Time for pressure recovery","help_text":"RECORD time for pressure recovery (sec)","sort_order":54,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1475,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Main drain valve water supply test - Town main supply only","help_text":"(d) VERIFY that the time for pressure recovery aligns with previously recorded value.\n** NOTE: ** Where the building exceeds four storeys in height, care should be taken to ensure that the static head of the installation does not excessively elevate the residual pressure reading.","sort_order":55,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1476,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water supply (river, lake, etc.) strainers/screens","help_text":"CHECK suction inlet strainer(s) or screen(s) for any condition likely to affect its function. Where blocked, CLEAN the suction inlet strainers or screens.","sort_order":56,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":106,"active":false,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.4.2 (Six-monthly Inspection)","help_text":"AS1851-2012 Table 2.4.4.2 (Six-monthly Deluge & Water Spray Inspection)","sort_order":57,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":288,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service activities","help_text":"COMPLETE all monthly service activities listed in Table 2.4.4.1 and all six-monthly wet pipe service activities listed in Table 2.4.2.2 that are applicable to a deluge and water spray system.","sort_order":58,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":289,"active":true,"required":false,"type":"REMARK","label":"OPERATE, CHECK & VERIFY Deluge valve and auxiliaries, local alarm and fire brigade alarm test","help_text":"(a) Where fitted, CLOSE isolation valve located above deluge valve (prevents entry of water into system piping).\n(b) OPERATE each deluge valve by releasing the system via each installed means.\n(c) CHECK for correct operation of alarm.\n(e) VERIFY correct operation of the fire brigade alarms from each deluge valve or group of deluge assemblies. Where the system is monitored, ensure the alarm has activated the alarm signalling equipment.\n** NOTE: ** Where multiple deluge valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.\n(f) Where an isolation valve has not been fitted above the alarm valve, the main stop valve should be closed, enabling a partial test of the alarm valve.\n** NOTE: ** Consider full testing at the first opportunity (at which time the isolation test valve should be installed).","sort_order":59,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":290,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Deluge valve and auxiliaries, local alarm and fire brigade alarm test - ........s","help_text":"(d) RECORD times to operation of alarm(s) and verify that these do not exceed 30 s.","sort_order":60,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":291,"active":true,"required":false,"type":"REMARK","label":"CLOSE - Deluge valve resetting","help_text":"CLOSE main stop valve. CLOSE drain and RESET manual operating valve.","sort_order":61,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":292,"active":true,"required":false,"type":"REMARK","label":"RESET & OPEN - Detector sprinkler line pressure (where fitted)","help_text":"RESET deluge valve and RESTORE detector sprinkler line pressure. OPEN and SECURE main stop valve.\nOPEN and secure test-isolating valve (where fitted) in an open position.","sort_order":62,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":293,"active":true,"required":false,"type":"REMARK","label":"OPEN - Detector sprinkler line pressure (where fitted)","help_text":"OPEN and secure test-isolating valve (where fitted) in an open position.","sort_order":63,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":294,"active":true,"required":false,"type":"REMARK","label":"RESTORE - Electrical control unit (and FIP/ASE) (where fitted)","help_text":"RESTORE units to operational status.","sort_order":64,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":295,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Pressure gauge readings........kPa","help_text":"(a) RECORD readings from each pressure gauge.","sort_order":65,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":296,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Pressure gauge readings range","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":66,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":297,"active":true,"required":false,"type":"REMARK","label":"SECURE - Valve and cocks","help_text":"SECURE all valves and alarm cocks in the open position or the closed position as labelled.","sort_order":67,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":336,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.3 (Annual Inspection)","help_text":"AS1851-2012 Table 2.4.2.3 (Annual Wet Pipe Inspection)","sort_order":68,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":337,"active":true,"required":false,"type":"REMARK","label":"OPERATE & VERIFY- Pressure reducing valve test","help_text":"(a) OPERATE all pressure-reducing valves and verify correct operation under flow conditions.\n(b) VERIFY that pressure readings on the low pressure side of the valves are within the range stated at the pressure-reducing valve station.","sort_order":69,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1515,"active":true,"required":false,"type":"INTEGER","label":"RECORD - High pressure gauge","help_text":"RECORD high pressure gauge (kPa)","sort_order":70,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1516,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Low pressure gauge","help_text":"RECORD low pressure gauge (kPa)","sort_order":71,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":338,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Pressure-relief valve test","help_text":"OPERATE pressure-relief valve and note operating pressure is within the range stated on the nameplate provided at the reducing valve station.\n**NOTES: **\n1 This test of the pressure-relief valve may be carried out using a portable test apparatus.\n2 Inappropriate settings for pressure-relief valves can result in very large quantities of water flowing to waste. Ensure settings are maintained to have pressures as identified and not higher than allowed by system component rated working pressures.","sort_order":72,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1517,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Operating pressure","help_text":"RECORD operating pressure (kPa)","sort_order":73,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":339,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water supply tanks - Atmospheric or pressure","help_text":"Perform routine service in accordance with Section 5.","sort_order":74,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":340,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Water supply proving test","help_text":"(a) CONDUCT a water supply test, subject to limitations imposed by the water agency controlling the supply source. The test may be a combination of physical testing and calculation as necessary.","sort_order":75,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":341,"active":true,"required":false,"type":"DECIMAL","label":"DISCHARGE - Water supply proving test - Favourable Flow Pressure kPa...","help_text":"(i) Discharge water through the flowmeasuring device at the flow corresponding to the hydraulically most favourable duty flow. Record the flowing pressure.","sort_order":76,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":342,"active":true,"required":false,"type":"DECIMAL","label":"REDUCE - Water supply proving test - Unfavourable Flow Pressure kPa...","help_text":"(ii) Reduce the water flow through the flow measuring device to that corresponding to the most unfavourable duty point. Record the flowing pressure.","sort_order":77,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":343,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Water supply proving test - Satic pressure kPa...","help_text":"(iii) Shut off water flow to flow-measuring device. Record static pressure.","sort_order":78,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":344,"active":true,"required":false,"type":"REMARK","label":"VERIFY & COMPLETE - Water supply proving test","help_text":"(b) VERIFY that the system flow and pressure requirements are satisfied.\n(c) COMPLETE a water supply test report in accordance with AS 2118.1.\n** NOTE: ** This test should be conducted by substituting the installation and below stop valve pressure gauges with calibrated gauges of known accuracy.\nWhere pumpsets are fitted, the water supply flow test should be performed combined with the pumpset load test requirements in Section 3.","sort_order":79,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":345,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Alarm valve - Remote test valve","help_text":"(a) OPERATE the alarm valve by opening each remote test valve.","sort_order":80,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":346,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Alarm valve - Remote test valve - Gong time........s","help_text":"(b) RECORD time(s) to operation of alarm gong(s)","sort_order":81,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":347,"active":true,"required":false,"type":"HEADER","label":"VERIFY - Alarm valve - Remote test valve time","help_text":"(b) Verify that time does not exceed 360 s for AS 2118.1 and 180 s for AS 2118.4 systems.","sort_order":82,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":348,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.1 system time does not exceed 360 s","help_text":"(b) Verify that time does not exceed 360 s for AS 2118.1 systems","sort_order":83,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":349,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.1 system time exceed 360 s","help_text":"(b) Verify that time does not exceed 360 s for AS 2118.1 systems","sort_order":84,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":350,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.4 system time does not exceed 180 s","help_text":"(b) Verify that time does not exceed 180 s for AS 2118.4 systems.","sort_order":85,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":351,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.4 system time exceed 180 s","help_text":"(b) Verify that time does not exceed 180 s for AS 2118.4 systems.","sort_order":86,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":352,"active":true,"required":false,"type":"REMARK","label":"CHECK - Alarm valve - Remote test valve","help_text":"c) CLOSE remote test valve(s) and verify that alarm valve has reseated.","sort_order":87,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":353,"active":true,"required":false,"type":"REMARK","label":"DRAW & VERIFY - Anti-freeze solution test (where applicable)","help_text":"(a) DRAW a sample of anti-freeze solution.\n(b) VERIFY correct specific gravity and top up to correct solution level.","sort_order":88,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":354,"active":true,"required":false,"type":"REMARK","label":"DRAW & VERIFY - Sprinkler system interface control test (fire trips)","help_text":"(a) CONDUCT a functional system test via the pressure switch or flow switch with each interfaced system.\n(b) VERIFY that the interface functions as required.","sort_order":89,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":355,"active":true,"required":false,"type":"REMARK","label":"CLEAN - Water motor alarm gong","help_text":"CLEAN the strainer and lubricate the external gong mechanism.","sort_order":90,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":356,"active":true,"required":false,"type":"REMARK","label":"CLEAN - Water motor direct brigade alarm","help_text":"CLEAN the strainer.","sort_order":91,"ref":"3.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":357,"active":true,"required":false,"type":"REMARK","label":"CHECK & VERIFY - Alarm signalling equipment (ASE) (Standalone)","help_text":"Where an ASE is standalone and is connected to a power supply unit and batteries:\n(a) CHECK the batteries for any condition likely to adversely affects its function and\n(b) Where the battery has not been replaced in the previous two years, VERIFY the battery condition by carrying out a battery discharge test in accordance with Appendix F.","sort_order":92,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1477,"active":true,"required":false,"type":"DATE","label":"RECORD - Date last replaced","help_text":"RECORD date last replaced","sort_order":93,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":358,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Tank quick fill (reduced capacity or break tank)","help_text":"CONDUCT a water supply test through a flowmeasuring device or other appropriate methods that the flow corresponds to the required quick fill-rate.","sort_order":94,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1518,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Flow","help_text":"RECORD flow (L/min)","sort_order":95,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1519,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pressure","help_text":"RECORD pressure (kPa)","sort_order":96,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":359,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Spray booths and ducts","help_text":"INSPECT accumulated spray residue on sprinklers and reapply protective medium (petroleum jelly/paper bags).\nNOTE: The required frequency of inspection depends upon the amount of spraying being done and could be accomplished at the same time as the cleaning of booth.","sort_order":97,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":360,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Kitchen hoods and ducts","help_text":"INSPECT all sprinklers inside kitchen hoods and ducts and CLEAN if necessary to remove accumulated grease and any other foreign matter and verify that the sprinkler head is appropriate for this application.","sort_order":98,"ref":"3.14","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":361,"active":true,"required":false,"type":"REMARK","label":"DRAW - Foam water sprinkler systems - Foam concentrate","help_text":"DRAW a sample and verify condition in accordance with NFPA 11 (pH, specific gravity, sediment, expansion ratio, 25% drain time).","sort_order":99,"ref":"3.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":362,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foam concentrate strainer (where fitted)","help_text":"CHECK and clean foam concentrate strainer (fitted upstream of proportioning device).","sort_order":100,"ref":"3.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":363,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Pipes and hangers","help_text":"CHECK that exposed water distribution system, including pipework, pipe supports and valves, appear free from corrosion and damage, not subject to external loads and pipework is properly supported.","sort_order":101,"ref":"3.17","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":364,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler condition","help_text":"CHECK sprinklers for any condition, including physical damage, contamination, and paint on operating elements or cover plates, likely to adversely affect their function.\nNOTE: Sprinkler frames may be painted as part of the manufacturing process; however, the heat response elements should not be painted as this will delay or prevent operation and paint accumulated at the seat of the sprinkler may affect operation. Minor spatter on the fusible elements may be acceptable but operation should be checked if doubt exists.","sort_order":102,"ref":"3.18","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":365,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Escutcheons, cover plates or guards","help_text":"CHECK for poorly fitting or missing escutcheons or cover plates, damaged guards, and attachment of foreign material.","sort_order":103,"ref":"3.19","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":366,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler obstructions","help_text":"CHECK for obstructions likely to impede sprinkler discharge and for adequate clear space below sprinklers.","sort_order":104,"ref":"3.20","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":367,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Unprotected areas","help_text":"(a) CHECK for presence of unprotected areas such as mezzanines, platforms and building extensions.\n(b) CHECK for sprinkler spacing and location relative to wall, bulkhead and partition alterations and the introduction of fixtures and fittings shielding sprinkler discharge.\n(c) CHECK for the need to install sprinkler guards.","sort_order":105,"ref":"3.21","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":368,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler compatibility","help_text":"CHECK that sprinklers within a compartment are of similar operating characteristics (e.g. area coverage, RTI and temperature rating).","sort_order":106,"ref":"3.22","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":369,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler ambient conditions","help_text":"CHECK for localized changes in ambient temperatures, which may require different sprinkler temperature ratings (e.g. exposure to freezing or high temperature conditions).","sort_order":107,"ref":"3.23","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":370,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - External sprinklers","help_text":"CHECK for new building structures, yard storage or the like, exposing unprotected openings, non-fire resistant walls that may require the provision for external sprinklers.","sort_order":108,"ref":"3.24","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":371,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Occupancy","help_text":"CHECK that sprinkler design remains applicable for the occupancy hazard classification and the category of storage involved.","sort_order":109,"ref":"3.25","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":372,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Storage heights, encapsulation","help_text":"(a) CHECK that sprinkler design remains applicable for storage heights.\nIf height limits are exceeded, check for in-rack (intermediate) sprinklers.\n(b) CHECK for shrink wrapping (encapsulation) where not employed previously.","sort_order":110,"ref":"3.26","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":373,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Site documentation (where required)","help_text":"(a) CHECK that block plans and emergency instructions contain the required details.\n(b) CHECK that up-to-date sprinkler plans are available on site.","sort_order":111,"ref":"3.27","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":327,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.4.3 (Annual Inspection)","help_text":"AS1851-2012 Table 2.4.4.3 (Annual Deluge & Water Spray Inspection)","sort_order":113,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":328,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and sixmonthly service","help_text":"COMPLETE all monthly and six-monthly service activities, listed in Tables 2.4.4.1 and 2.4.4.2.","sort_order":114,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":329,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Full discharge operation test","help_text":"Where practicable, CONDUCT full discharge test to check all open sprinklers and nozzles are unobstructed and provide appropriate coverage.","sort_order":115,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":330,"active":true,"required":false,"type":"REMARK","label":"DRAW - Foam concentrate or premix solution (where applicable)","help_text":"DRAW a sample and verify condition in accordance with NFPA 11 (pH, specific gravity, sediment, expansion ratio, 25% drain time).","sort_order":116,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":331,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foam concentrate strainer (where fitted)","help_text":"CHECK and clean foam concentrate strainer (fitted upstream of proportioning device).","sort_order":117,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":332,"active":true,"required":false,"type":"REMARK","label":"REMOVE & CLEAN - Pilot line strainers","help_text":"REMOVE and CLEAN strainer.","sort_order":118,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":333,"active":true,"required":false,"type":"REMARK","label":"CHECK - Electrical detection (where fitted)","help_text":"INSPECT and test in accordance with Annual requirements in Section 6.","sort_order":119,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":334,"active":true,"required":false,"type":"REMARK","label":"CHECK - Installation","help_text":"To the extent practicable, CHECK that pipe hangers are secure and open sprinklers and spray nozzles are unobstructed. Where applicable, check for missing nozzle dust plugs/caps.","sort_order":120,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":335,"active":true,"required":false,"type":"REMARK","label":"CHECK - System configuration","help_text":"CHECK that system layout remains appropriate for protected hazard. Check for possible misalignment of spray nozzles.","sort_order":121,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":374,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.4.4 (Five-yearly Inspection)","help_text":"AS1851-2012 Table 2.4.4.4 (Five-yearly Deluge & Water Spray Inspection)","sort_order":122,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":375,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly, six-monthly and yearlyl service","help_text":"COMPLETE all monthly, six-monthly and yearly service activities, listed in Tables 2.4.4.1, 2.4.4.2 and 2.4.4.3.","sort_order":123,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":376,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Five-Annual service","help_text":"COMPLETE all five-Annual wet pipe service activities listed in Table 2.4.2.4 that are applicable to a deluge and water spray system.","sort_order":124,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":377,"active":true,"required":false,"type":"REMARK","label":"FIT - Deluge valves","help_text":"FIT new deluge valve seats and seals. Check and clean operating mechanism. Fit new faceplate gasket.","sort_order":125,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":378,"active":true,"required":false,"type":"REMARK","label":"FIT - Diaphragm valve","help_text":"FIT a new diaphragm, unless otherwise specified by the manufacturer.","sort_order":126,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":379,"active":true,"required":false,"type":"REMARK","label":"GENERATE - Foam quality","help_text":"GENERATE foam through delivery device (nozzle, monitor) or test foam maker and check:\n(a) Proportioning ratio (using conductivity meter or refractometer).\n(b) 25% drainage time.\n(c) Expansion ratio.","sort_order":127,"ref":"4.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Deluge and Water Spray","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Sprinkler System: Dry Pipe","prompts":[{"id":191,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.1 (Monthly Inspection)","help_text":"AS1851-2012 Table 2.4.2.1 (Monthly Wet Pipe Inspection)","sort_order":1,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":192,"active":true,"required":false,"type":"REMARK","label":"CHECK - Control valve assembly","help_text":"CHECK that control valve assembly area is unobstructed and free of any condition that may adversely affect the operation or access.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":193,"active":true,"required":false,"type":"REMARK","label":"CHECK - Sprinkler spares, sprinklers and sprinkler spanner","help_text":"CHECK that there are spare sprinklers of appropriate quantity and type including a matching sprinkler spanner for each type of sprinkler fitted, available.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":194,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage","help_text":"CHECK for damage, legibility and appropriate location of required signage.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":195,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire brigade booster connection - Obstruction","help_text":"CHECK that the booster connection or enclosure is unobstructed and for any condition that may adversely affect the operation or access.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":196,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire brigade booster connection - Couplings","help_text":"CHECK that the booster connection coupling type is as per the local fire brigade requirements.","sort_order":6,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":197,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Main stop valves and alarm cocks","help_text":"INSPECT each main stop valve and alarm cock for each control assembly is secured in the open position and the main stop valve is correctly labelled.","sort_order":7,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":198,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump starting devices isolating valve","help_text":"CHECK that each isolating valve to each automatic pump start device is locked in the open position.","sort_order":8,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":199,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure switches","help_text":"CHECK each pressure switch and ensure that the cover is in place, correctly labelled, securely mounted and free from any condition likely to adversely affect its function.","sort_order":9,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":200,"active":true,"required":false,"type":"REMARK","label":"CHECK - Alarm signalling equipment (ASE) (stand-alone)","help_text":"CHECK the alarm signalling equipment to ensure that it is securely mounted, free from any condition likely to adversely affect its function and is not indicating alarm, fault, loss of connection, or isolated.","sort_order":10,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":201,"active":true,"required":false,"type":"REMARK","label":"CHECK - Sprinkler system interface to other systems","help_text":"CHECK the sprinkler system alarm interface with other systems is not isolated, inhibited or disabled.","sort_order":11,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":202,"active":true,"required":false,"type":"REMARK","label":"NOTE - Water supply stop valves","help_text":"1 - Where more than 12 water supply stop valves are distributed throughout a high-rise building, forming part of a combined sprinkler/hydrant system, the actions under actions (a) and (b) may be conducted on a rotating basis.\n2 - The period between testing of all water supply stop valves should not exceed 3 months.","sort_order":12,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":203,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Water supply stop valves","help_text":"(a) OPERATE (two full turns) all water supply stop valves (including backflow prevention stop valves but excluding underground keyoperated valves) and verify they are fully open, secure in the open position (relaxed Â¼ turn if appropriate) and are correctly labelled.","sort_order":13,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":204,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Water supply stop valves","help_text":"(b) VERIFY that the valve position indicators are securely mounted and indicate correctly.","sort_order":14,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":205,"active":true,"required":false,"type":"INTEGER","label":"RECORD - System pressure gauge readings before alarm function test, kPa.......","help_text":"(a) RECORD reading from each pressure gauge.","sort_order":15,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":206,"active":true,"required":false,"type":"REMARK","label":"VERIFY - System pressure gauge readings before alarm function test","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":16,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":207,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(a) OPERATE each alarm valve by opening each 15 mm test valve or 10 mm for residential sprinkler systems serving buildings up to 4 storeys in height. Where more than 12 control assemblies are distributed throughout a high-rise building forming part of a combined sprinkler/hydrant system, and initiate the fire brigade alarm, testing may be conducted on a rotating basis. The period between testing of all control assemblies shall not exceed 3 months.","sort_order":17,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":208,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(b) RECORD time(s) to operation of alarm gong(s) and verify that time does not exceed 180 s for general systems or 90 s for residential sprinkler systems.","sort_order":18,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":209,"active":true,"required":false,"type":"REMARK","label":"RESET - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(c) RESET the alarm test valve on completion of each test.","sort_order":19,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":210,"active":true,"required":false,"type":"REMARK","label":"TEST - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(d) Where multiple control valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.","sort_order":20,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":211,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Alarm signal","help_text":"VERIFY the correct operation of each alarm signal. Where the system is monitored ensure the alarm has activated the alarm signalling equipment.","sort_order":21,"ref":"1.13","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":212,"active":true,"required":false,"type":"REMARK","label":"INSPECT - DSEP/DBEP strobe indicator","help_text":"INSPECT for the correct operation of each DSEP/DBEP strobe indicator, where fitted.","sort_order":22,"ref":"1.14","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":213,"active":true,"required":false,"type":"INTEGER","label":"RECORD - System pressure gauge readings after alarm valve test","help_text":"(a) RECORD reading from each pressure gauge.","sort_order":23,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":214,"active":true,"required":false,"type":"REMARK","label":"VERIFY - System pressure gauge readings after alarm valve test","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":24,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":215,"active":true,"required":false,"type":"REMARK","label":"TEST - Pump starting devices function test - Compression ignition drivers (diesel) and electric motor drivers","help_text":"(a) TEST each automatic pump starting device and pump operation by reducing the applied water pressure to the starting device and run pump, in accordance with Section 3. Where more than one starting device is installed, including the manual starting device, the test may be carried out on a rotating basis. The period between the exercising of each starting device is not to exceed 3 months. Where this would require the pump to start more than 5 times in succession, the period may be extended to 6 months.","sort_order":25,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":216,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pump starting devices function test - CUT IN PRESSURE","help_text":"(b) RECORD the pump cut-in pressures and verify that they are within the ranges required.","sort_order":26,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":217,"active":true,"required":false,"type":"REMARK","label":"TEST - Manual pump start device, function test","help_text":"TEST each manual pump starting device and pump operation in accordance with Section 3.","sort_order":27,"ref":"1.17","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":218,"active":true,"required":false,"type":"REMARK","label":"PERFORM - Water supply tanks - Atmospheric or pressure","help_text":"Perform routine service in accordance with Section 5.","sort_order":28,"ref":"1.18","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":219,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foam water sprinkler systems - foam concentrate","help_text":"CHECK that the concentrate level is correct and level indicator reads correctly.","sort_order":29,"ref":"1.19","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":182,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.3.1 (Monthly Inspection)","help_text":"AS1851-2012 Table 2.4.3.1 (Monthly Dry Pipe Inspection)","sort_order":30,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":183,"active":true,"required":false,"type":"REMARK","label":"CHECK - Monthly service","help_text":"COMPLETE all monthly wet pipe service activities listed in Table 2.4.2.1 that are applicable to a dry pipe system.","sort_order":31,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":184,"active":true,"required":false,"type":"REMARK","label":"CHECK - System air pressure","help_text":"CHECK system air pressure is reading within the range required.","sort_order":32,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":185,"active":true,"required":false,"type":"REMARK","label":"CHECK - System air desiccator or dryer","help_text":"CHECK desiccant condition and replace if necessary.","sort_order":33,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":186,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air compressor oil level","help_text":"CHECK oil level and visually assess condition of oil.","sort_order":34,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":187,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air compressor","help_text":"VERIFY that air compressor operates at specified cut-in and cut-out pressures.","sort_order":35,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":188,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Low air pressure alarms(s)","help_text":"VERIFY:\n(a) Low air pressure alarm operates at predetermined levels.\n(b) Low air pressure alarm(s) visual indicator and sounders are operational.","sort_order":36,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":189,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Local alarm and fire brigade test simulation","help_text":"SIMULATE operation of dry pipe alarm valve and OPERATE local and fire brigade alarms through the bypass valve(s). Where the system is monitored, ensure the alarm has activated the alarm signalling equipment. (Refer to manufacturer's operating manual.)\n** NOTE: ** Where multiple control valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.","sort_order":37,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":190,"active":true,"required":false,"type":"REMARK","label":"DRAIN - Air receiver condensate","help_text":"DRAIN condensate from condensate trap.","sort_order":38,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1478,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.2 (Six-monthly Inspection)","help_text":"AS1851-2012 Table 2.4.2.2 (Six-monthly Wet Pipe Inspection)","sort_order":39,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1479,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Floor/zone indication test (where fitted)","help_text":"COMPLETE all monthly service activities, as listed in Table 2.4.2.1.","sort_order":40,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1480,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Floor/zone indication test (where fitted)","help_text":"(a) OPERATE each flow switch test arrangement (automatic or manual).","sort_order":41,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1481,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Floor/zone indication test (where fitted)","help_text":"(b) VERIFY correct flow switch indication at the CIE.","sort_order":42,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1482,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Underground keyoperated and subsidiary valves","help_text":"(a) Except where owned by the water supply authority, OPERATE (two full turns) all underground key-operated valves and verify they are fully open, secure in the open position (relaxed Â¼ turn if appropriate) and are correctly labelled.\n** NOTE: ** Where underground key-operated valves are owned by the water supply authority, the owner should arrange for the water supply authority to test the valve(s) to confirm the valve(s) is operational and in the correct position.\n(b) OPERATE all subsidiary stop valves (floor isolation valves, tail-end valves).Ensure that they are fully open and, where applicable, secured in the open position and are correctly labelled.","sort_order":43,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1520,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Number valves checked","help_text":"RECORD number underground keyoperated and subsidiary valves checked.","sort_order":44,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1483,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Valve-monitoring device test","help_text":"Test each valve monitor by operating the valve and VERIFY the correct indication at the CIE.","sort_order":45,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1521,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Number monitors checked","help_text":"RECORD number valve monitors checked.","sort_order":46,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1522,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pressure gauge readings before main drain test","help_text":"RECORD reading from each pressure gauge.","sort_order":47,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1484,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Pressure gauge readings before main drain test","help_text":"VERIFY pressure gauge readings are within the ranges required.","sort_order":48,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1485,"active":true,"required":false,"type":"REMARK","label":"OPEN - Main drain valve water supply test - Town main supply only","help_text":"(a) OPEN the sprinkler control assembly main drain valve without pump(s) running. In the case of grouped valve sets, open one only.","sort_order":49,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1486,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Main drain valve water supply test - Town main supply only","help_text":"(b) VERIFY that residual water supply pressure, with drain valve open, is within 10% of the original value recorded.","sort_order":50,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1523,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Stabilize flow water supply pressure","help_text":"RECORD stabilize flow water supply pressure (kPa)","sort_order":51,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1487,"active":true,"required":false,"type":"REMARK","label":"CLOSE - Main drain valve water supply test - Town main supply only","help_text":"(c) CLOSE main drain valve and record time for pressure recovery.","sort_order":52,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1524,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Time for pressure recovery","help_text":"RECORD time for pressure recovery (sec)","sort_order":53,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1488,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Main drain valve water supply test - Town main supply only","help_text":"(d) VERIFY that the time for pressure recovery aligns with previously recorded value.\n** NOTE: ** Where the building exceeds four storeys in height, care should be taken to ensure that the static head of the installation does not excessively elevate the residual pressure reading.","sort_order":54,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1489,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water supply (river, lake, etc.) strainers/screens","help_text":"CHECK suction inlet strainer(s) or screen(s) for any condition likely to affect its function. Where blocked, CLEAN the suction inlet strainers or screens.","sort_order":55,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":220,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.3.2 (Six-monthly Inspection)","help_text":"AS1851-2012 Table 2.4.3.2 (Six-monthly Dry Pipe Inspection)","sort_order":56,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":221,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and sixmonthly service","help_text":"COMPLETE all monthly service activities listed in Table 2.4.3.1 and all six-monthly wet pipe service activities listed in Table 2.4.2.2 that are applicable to a dry pipe system.","sort_order":57,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":222,"active":true,"required":false,"type":"REMARK","label":"OPERATE, CHECK & VERIFY - Alarm valve and auxiliaries, local alarm and fire brigade alarm test","help_text":"(a) Where fitted, CLOSE isolation valve located above alarm valve (to prevent entry of water into system piping).\n(b) OPERATE each alarm valve by releasing air from system.\n(c) CHECK for correct operation of alarms and accelerator or exhauster.\n(e) VERIFY correct operation of the fire brigade alarms from each control assembly or group of control assemblies. Where the system is monitored, ensure the alarm has activated the alarm signalling equipment.\n** NOTE: ** Where multiple control valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.\n(f) Where an isolation valve has not been fitted above the alarm valve, the main stop valve should be mostly closed, enabling a partial test of the alarm valve.\n** NOTE: ** Consider full testing at the first opportunity (at which time the isolation test valve should be installed).","sort_order":58,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":223,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Alarm valve and auxiliaries, local alarm and fire brigade alarm test - Gong Times......s","help_text":"(d) RECORD time(s) to operation of alarms gong(s) and verify that these do not exceed 180 s.","sort_order":59,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":224,"active":true,"required":false,"type":"CHOICE","label":"CONFIRM - (d) Operation of alarms gong(s) exceed 180 s.","help_text":"(d) RECORD time(s) to operation of alarms gong(s) and verify that these do not exceed 180 s.","sort_order":60,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":225,"active":true,"required":false,"type":"CHOICE","label":"CONFIRM - (d) Operation of alarms gong(s) do not exceed 180 s.","help_text":"(d) RECORD time(s) to operation of alarms gong(s) and verify that these do not exceed 180 s.","sort_order":61,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":226,"active":true,"required":false,"type":"REMARK","label":"CONFIRM- Installation pressure","help_text":"RESTORE system air pressure and verify the alarm has reseated.","sort_order":62,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":227,"active":true,"required":false,"type":"REMARK","label":"RESTORE - FIP/ASE","help_text":"RESTORE FIP/ASE to operational status.","sort_order":63,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":228,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Pressure gauge readings......kPa","help_text":"(a) RECORD reading from each pressure gauge.","sort_order":64,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":229,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Pressure gauge readings","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":65,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":230,"active":true,"required":false,"type":"REMARK","label":"RESET & SECURE - Control assemblies resetting","help_text":"RESET and SECURE all valve and alarms cocks in the open position or the closed position, as labelled.","sort_order":66,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":240,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.2 (Annual Inspection)","help_text":"AS1851-2012 Table 2.4.2.2 (Annual Wet Pipe Inspection)","sort_order":67,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":241,"active":true,"required":false,"type":"REMARK","label":"OPERATE- Pressure reducing valve test","help_text":"(a) OPERATE all pressure-reducing valves and verify correct operation under flow conditions.\n(b) VERIFY that pressure readings on the low pressure side of the valves are within the range stated at the pressure-reducing valve station.","sort_order":68,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1525,"active":true,"required":false,"type":"INTEGER","label":"RECORD - High pressure gauge","help_text":"RECORD high pressure gauge (kPa)","sort_order":69,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1526,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Low pressure gauge","help_text":"RECORD low pressure gauge (kPa)","sort_order":70,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":242,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Pressure-relief valve test","help_text":"OPERATE pressure-relief valve and note operating pressure is within the range stated on the nameplate provided at the reducing valve station.\n**NOTES: **\n1 This test of the pressure-relief valve may be carried out using a portable test apparatus.\n2 Inappropriate settings for pressure-relief valves can result in very large quantities of water flowing to waste. Ensure settings are maintained to have pressures as identified and not higher than allowed by system component rated working pressures.","sort_order":71,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1527,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Operating pressure","help_text":"RECORD operating pressure (kPa)","sort_order":72,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":243,"active":true,"required":false,"type":"REMARK","label":"PERFORM - Water supply tanks - Atmospheric or pressure","help_text":"Perform routine service in accordance with Section 5.","sort_order":73,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":244,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Water supply proving test","help_text":"(a) CONDUCT a water supply test, subject to limitations imposed by the water agency controlling the supply source. The test may be a combination of physical testing and calculation as necessary.","sort_order":74,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":245,"active":true,"required":false,"type":"DECIMAL","label":"DISCHARGE - Water supply proving test - Favourable Flow Pressure kPa...","help_text":"(i) Discharge water through the flowmeasuring device at the flow corresponding to the hydraulically most favourable duty flow. Record the flowing pressure.","sort_order":75,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":246,"active":true,"required":false,"type":"DECIMAL","label":"REDUCE - Water supply proving test - Unfavourable Flow Pressure kPa...","help_text":"(ii) Reduce the water flow through the flow measuring device to that corresponding to the most unfavourable duty point. Record the flowing pressure.","sort_order":76,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":247,"active":true,"required":false,"type":"DECIMAL","label":"RECORD- Water supply proving test - Satic pressure kPa...","help_text":"(iii) Shut off water flow to flow-measuring device. Record static pressure.","sort_order":77,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":248,"active":true,"required":false,"type":"REMARK","label":"VERIFY & COMPLETE - Water supply proving test","help_text":"(b) VERIFY that the system flow and pressure requirements are satisfied.\n(c) COMPLETE a water supply test report in accordance with AS 2118.1.\n** NOTE: ** This test should be conducted by substituting the installation and below stop valve pressure gauges with calibrated gauges of known accuracy.\nWhere pumpsets are fitted, the water supply flow test should be performed combined with the pumpset load test requirements in Section 3.","sort_order":78,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":249,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Alarm valve - Remote test valve","help_text":"(a) OPERATE the alarm valve by opening each remote test valve.","sort_order":79,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":250,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Alarm valve - Remote test valve - Gong time........s","help_text":"(b) RECORD time(s) to operation of alarm gong(s)","sort_order":80,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":251,"active":true,"required":false,"type":"HEADER","label":"VERIFY - Alarm valve - Remote test valve time","help_text":"(b) verify that time does not exceed 360 s for AS 2118.1 and 180 s for AS 2118.4 systems.","sort_order":81,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":252,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.1 system time does not exceed 360 s","help_text":"(b) verify that time does not exceed 360 s for AS 2118.1 systems","sort_order":82,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":253,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.1 system time exceed 360 s","help_text":"(b) verify that time does not exceed 360 s for AS 2118.1 systems","sort_order":83,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":254,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.4 system time does not exceed 180 s","help_text":"(b) verify that time does not exceed 180 s for AS 2118.4 systems.","sort_order":84,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":255,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.4 system time exceed 180 s","help_text":"(b) verify that time does not exceed 180 s for AS 2118.4 systems.","sort_order":85,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":256,"active":true,"required":false,"type":"REMARK","label":"CCLOSE - Alarm valve - Remote test valve","help_text":"c) CLOSE remote test valve(s) and verify that alarm valve has reseated.","sort_order":86,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":257,"active":true,"required":false,"type":"REMARK","label":"DRAW & VERIFY - Anti-freeze solution test (where applicable)","help_text":"(a) DRAW a sample of anti-freeze solution.\n(b) VERIFY correct specific gravity and top up to correct solution level.","sort_order":87,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":258,"active":true,"required":false,"type":"REMARK","label":"CONDUCT- Sprinkler system interface control test (fire trips)","help_text":"(a) CONDUCT a functional system test via the pressure switch or flow switch with each interfaced system.\n(b) VERIFY that the interface functions as required.","sort_order":88,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":259,"active":true,"required":false,"type":"REMARK","label":"CLEAN - Water motor alarm gong","help_text":"CLEAN the strainer and lubricate the external gong mechanism.","sort_order":89,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":260,"active":true,"required":false,"type":"REMARK","label":"CLEAN- Water motor direct brigade alarm","help_text":"CLEAN the strainer.","sort_order":90,"ref":"3.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":261,"active":true,"required":false,"type":"REMARK","label":"CHECK & VERIFY - Alarm signalling equipment (ASE) (Standalone)","help_text":"Where an ASE is standalone and is connected to a power supply unit and batteries:\n(a) CHECK the batteries for any condition likely to adversely affects its function and\n(b) Where the battery has not been replaced in the previous two years, VERIFY the battery condition by carrying out a battery discharge test in accordance with Appendix F.","sort_order":91,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1490,"active":true,"required":false,"type":"DATE","label":"RECORD - Date last replaced","help_text":"RECORD date last replaced","sort_order":92,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":262,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Tank quick fill (reduced capacity or break tank)","help_text":"CONDUCT a water supply test through a flowmeasuring device or other appropriate methods that the flow corresponds to the required quick fill-rate.","sort_order":93,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1528,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Flow","help_text":"RECORD flow (L/min)","sort_order":94,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1529,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pressure","help_text":"RECORD pressure (kPa)","sort_order":95,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":263,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Spray booths and ducts","help_text":"INSPECT accumulated spray residue on sprinklers and reapply protective medium (petroleum jelly/paper bags).\nNOTE: The required frequency of inspection depends upon the amount of spraying being done and could be accomplished at the same time as the cleaning of booth.","sort_order":96,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":264,"active":true,"required":false,"type":"REMARK","label":"INSPECT- Kitchen hoods and ducts","help_text":"INSPECT all sprinklers inside kitchen hoods and ducts and CLEAN if necessary to remove accumulated grease and any other foreign matter and verify that the sprinkler head is appropriate for this application.","sort_order":97,"ref":"3.14","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":265,"active":true,"required":false,"type":"REMARK","label":"DRAW - Foam water sprinkler systems - Foam concentrate","help_text":"DRAW a sample and verify condition in accordance with NFPA 11 (pH, specific gravity, sediment, expansion ratio, 25% drain time).","sort_order":98,"ref":"3.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":266,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foam concentrate strainer (where fitted)","help_text":"CHECK and clean foam concentrate strainer (fitted upstream of proportioning device).","sort_order":99,"ref":"3.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":267,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Pipes and hangers","help_text":"CHECK that exposed water distribution system, including pipework, pipe supports and valves, appear free from corrosion and damage, not subject to external loads and pipework is properly supported.","sort_order":100,"ref":"3.17","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":268,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler condition","help_text":"CHECK sprinklers for any condition, including physical damage, contamination, and paint on operating elements or cover plates, likely to adversely affect their function.\nNOTE: Sprinkler frames may be painted as part of the manufacturing process; however, the heat response elements should not be painted as this will delay or prevent operation and paint accumulated at the seat of the sprinkler may affect operation. Minor spatter on the fusible elements may be acceptable but operation should be checked if doubt exists.","sort_order":101,"ref":"3.18","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":269,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Escutcheons, cover plates or guards","help_text":"CHECK for poorly fitting or missing escutcheons or cover plates, damaged guards, and attachment of foreign material.","sort_order":102,"ref":"3.19","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":270,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler obstructions","help_text":"CHECK for obstructions likely to impede sprinkler discharge and for adequate clear space below sprinklers.","sort_order":103,"ref":"3.20","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":271,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Unprotected areas","help_text":"(a) CHECK for presence of unprotected areas such as mezzanines, platforms and building extensions.\n(b) CHECK for sprinkler spacing and location relative to wall, bulkhead and partition alterations and the introduction of fixtures and fittings shielding sprinkler discharge.\n(c) CHECK for the need to install sprinkler guards.","sort_order":104,"ref":"3.21","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":272,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler compatibility","help_text":"CHECK that sprinklers within a compartment are of similar operating characteristics (e.g. area coverage, RTI and temperature rating).","sort_order":105,"ref":"3.22","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":273,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler ambient conditions","help_text":"CHECK for localized changes in ambient temperatures, which may require different sprinkler temperature ratings (e.g. exposure to freezing or high temperature conditions).","sort_order":106,"ref":"3.23","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":274,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - External sprinklers","help_text":"CHECK for new building structures, yard storage or the like, exposing unprotected openings, non-fire resistant walls that may require the provision for external sprinklers.","sort_order":107,"ref":"3.24","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":275,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Occupancy","help_text":"CHECK that sprinkler design remains applicable for the occupancy hazard classification and the category of storage involved.","sort_order":108,"ref":"3.25","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":276,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Storage heights, encapsulation","help_text":"(a) CHECK that sprinkler design remains applicable for storage heights.\nIf height limits are exceeded, check for in-rack (intermediate) sprinklers.\n(b) CHECK for shrink wrapping (encapsulation) where not employed previously.","sort_order":109,"ref":"3.26","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":277,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Site documentation (where required)","help_text":"(a) CHECK that block plans and emergency instructions contain the required details.\n(b) CHECK that up-to-date sprinkler plans are available on site.","sort_order":110,"ref":"3.27","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":231,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.3.3 (Annual Inspection)","help_text":"AS1851-2012 Table 2.4.3.3 (Annual Dry Pipe Inspection)","sort_order":112,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":232,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and sixmonthly service","help_text":"COMPLETE all monthly and six-monthly service activities listed in Tables 2.4.3.1 and 2.4.3.2 and all Annual wet pipe service activities listed in Table 2.4.2.3 that are applicable to a dry pipe system.","sort_order":113,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":233,"active":true,"required":false,"type":"REMARK","label":"REPLACE - System air desiccators or dryer","help_text":"REPLACE the desiccators.","sort_order":114,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":234,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Pipes and hangers","help_text":"CHECK that the water distribution pipe work is correctly pitched to drain.","sort_order":115,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":235,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.3.4 (Five-yearly Inspection)","help_text":"AS1851-2012 Table 2.4.3.4 (Five-yearly Dry Pipe Inspection)","sort_order":116,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":236,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly, six-monthly and Annual service","help_text":"COMPLETE all monthly, six-monthly and Annual service activities, listed in Tables 2.4.3.1, 2.4.3.2 and 2.4.3.3.","sort_order":117,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":237,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Wet pipe systems five Annual service","help_text":"COMPLETE all five-Annual wet pipe service activities listed in Table 2.4.2.4 that are applicable to a dry pipe system.","sort_order":118,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":238,"active":true,"required":false,"type":"REMARK","label":"FIT - Valve overhaul","help_text":"FIT new dry pipe valve seats and seals. FIT new faceplate gasket (perishable items).","sort_order":119,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":239,"active":true,"required":false,"type":"REMARK","label":"FIT, CHECK & CLEAN - Accelerator/exhauster","help_text":"FIT new seals as appropriate. CHECK and CLEAN operating mechanism. FIT a new faceplate.","sort_order":120,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Dry Pipe","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Sprinkler System: Pre-Action","prompts":[{"id":392,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.1 (Monthly Inspection)","help_text":"AS1851-2012 Table 2.4.2.1 (Monthly Wet Pipe Inspection)","sort_order":1,"ref":"1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":393,"active":true,"required":false,"type":"REMARK","label":"CHECK - Control valve assembly","help_text":"CHECK that control valve assembly area is unobstructed and free of any condition that may adversely affect the operation or access.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":394,"active":true,"required":false,"type":"REMARK","label":"CHECK - Sprinkler spares, sprinklers and sprinkler spanner","help_text":"CHECK that there are spare sprinklers of appropriate quantity and type including a matching sprinkler spanner for each type of sprinkler fitted, available.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":395,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage","help_text":"CHECK for damage, legibility and appropriate location of required signage.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":396,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire brigade booster connection - Obstruction","help_text":"CHECK that the booster connection or enclosure is unobstructed and for any condition that may adversely affect the operation or access.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":397,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire brigade booster connection - Couplings","help_text":"CHECK that the booster connection coupling type is as per the local fire brigade requirements.","sort_order":6,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":398,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Main stop valves and alarm cocks","help_text":"INSPECT each main stop valve and alarm cock for each control assembly is secured in the open position and the main stop valve is correctly labelled.","sort_order":7,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":399,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump starting devices isolating valve","help_text":"CHECK that each isolating valve to each automatic pump start device is locked in the open position.","sort_order":8,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":400,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure switches","help_text":"CHECK each pressure switch and ensure that the cover is in place, correctly labelled, securely mounted and free from any condition likely to adversely affect its function.","sort_order":9,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":401,"active":true,"required":false,"type":"REMARK","label":"CHECK - Alarm signalling equipment (ASE) (stand-alone)","help_text":"CHECK the alarm signalling equipment to ensure that it is securely mounted, free from any condition likely to adversely affect its function and is not indicating alarm, fault, loss of connection, or isolated.","sort_order":10,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":402,"active":true,"required":false,"type":"REMARK","label":"CHECK - Sprinkler system interface to other systems","help_text":"CHECK the sprinkler system alarm interface with other systems is not isolated, inhibited or disabled.","sort_order":11,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":403,"active":true,"required":false,"type":"REMARK","label":"NOTE - Water supply stop valves","help_text":"1 - Where more than 12 water supply stop valves are distributed throughout a high-rise building, forming part of a combined sprinkler/hydrant system, the actions under actions (a) and (b) may be conducted on a rotating basis.\n2 - The period between testing of all water supply stop valves should not exceed 3 months.","sort_order":12,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":404,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Water supply stop valves","help_text":"(a) OPERATE (two full turns) all water supply stop valves (including backflow prevention stop valves but excluding underground keyoperated valves) and verify they are fully open, secure in the open position (relaxed Â¼ turn if appropriate) and are correctly labelled.","sort_order":13,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":405,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Water supply stop valves","help_text":"(b) VERIFY that the valve position indicators are securely mounted and indicate correctly.","sort_order":14,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":406,"active":true,"required":false,"type":"INTEGER","label":"RECORD - System pressure gauge readings before alarm function test, kPa.......","help_text":"(a) RECORD reading from each pressure gauge.","sort_order":15,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":407,"active":true,"required":false,"type":"REMARK","label":"VERIFY - System pressure gauge readings before alarm function test","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":16,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":408,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(a) OPERATE each alarm valve by opening each 15 mm test valve or 10 mm for residential sprinkler systems serving buildings up to 4 storeys in height. Where more than 12 control assemblies are distributed throughout a high-rise building forming part of a combined sprinkler/hydrant system, and initiate the fire brigade alarm, testing may be conducted on a rotating basis. The period between testing of all control assemblies shall not exceed 3 months.","sort_order":17,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":409,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(b) RECORD time(s) to operation of alarm gong(s) and verify that time does not exceed 180 s for general systems or 90 s for residential sprinkler systems.","sort_order":18,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":410,"active":true,"required":false,"type":"REMARK","label":"RESET - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(c) RESET the alarm test valve on completion of each test.","sort_order":19,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":411,"active":true,"required":false,"type":"REMARK","label":"TEST - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(d) Where multiple control valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.","sort_order":20,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":412,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Alarm signal","help_text":"VERIFY the correct operation of each alarm signal. Where the system is monitored ensure the alarm has activated the alarm signalling equipment.","sort_order":21,"ref":"1.13","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":413,"active":true,"required":false,"type":"REMARK","label":"INSPECT - DSEP/DBEP strobe indicator","help_text":"INSPECT for the correct operation of each DSEP/DBEP strobe indicator, where fitted.","sort_order":22,"ref":"1.14","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":414,"active":true,"required":false,"type":"INTEGER","label":"RECORD - System pressure gauge readings after alarm valve test","help_text":"(a) RECORD reading from each pressure gauge.","sort_order":23,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":415,"active":true,"required":false,"type":"REMARK","label":"VERIFY - System pressure gauge readings after alarm valve test","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":24,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":416,"active":true,"required":false,"type":"REMARK","label":"TEST - Pump starting devices function test - Compression ignition drivers (diesel) and electric motor drivers","help_text":"(a) TEST each automatic pump starting device and pump operation by reducing the applied water pressure to the starting device and run pump, in accordance with Section 3. Where more than one starting device is installed, including the manual starting device, the test may be carried out on a rotating basis. The period between the exercising of each starting device is not to exceed 3 months. Where this would require the pump to start more than 5 times in succession, the period may be extended to 6 months.","sort_order":25,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":417,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pump starting devices function test - CUT IN PRESSURE","help_text":"(b) RECORD the pump cut-in pressures and verify that they are within the ranges required.","sort_order":26,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":418,"active":true,"required":false,"type":"REMARK","label":"TEST - Manual pump start device, function test","help_text":"TEST each manual pump starting device and pump operation in accordance with Section 3.","sort_order":27,"ref":"1.17","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":419,"active":true,"required":false,"type":"REMARK","label":"PERFORM - Water supply tanks - Atmospheric or pressure","help_text":"Perform routine service in accordance with Section 5.","sort_order":28,"ref":"1.18","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":420,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foam water sprinkler systems - foam concentrate","help_text":"CHECK that the concentrate level is correct and level indicator reads correctly.","sort_order":29,"ref":"1.19","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":380,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.5.1 (Monthly Inspection)","help_text":"AS1851-2012 Table 2.4.5.1 (Monthly Pre-Action Inspection)","sort_order":30,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":381,"active":true,"required":false,"type":"REMARK","label":"CHECK - Monthly service activities","help_text":"COMPLETE all monthly wet pipe service activities listed in Table 2.4.2.1 that are applicable to a pre-action system.","sort_order":31,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":382,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure gauge readings","help_text":"CHECK that all pressure gauge readings are within the ranges required and RECORD readings from each pressure gauge.","sort_order":32,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":383,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air compressor oil level (where fitted)","help_text":"(a) CHECK oil level is correct and visually assess condition of oil.","sort_order":33,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":384,"active":true,"required":false,"type":"REMARK","label":"CHECK - Air compressor oil level (where fitted)","help_text":"(b) CHECK regulator is locked and set in the correct position.","sort_order":34,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":385,"active":true,"required":false,"type":"REMARK","label":"INSPECT and TEST - Electrical detection","help_text":"INSPECT and TEST in accordance with Section 6.","sort_order":35,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":386,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Air compressor (where fitted)","help_text":"VERIFY that air compressor operates at specified cut-in and cut-out pressures.","sort_order":36,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":387,"active":true,"required":false,"type":"REMARK","label":"CHECK - Nitrogen supply (where fitted)","help_text":"(a) CHECK cylinder contents per pressure gauge.\n(b) CHECK regulator is locked and set in correct position.","sort_order":37,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":388,"active":true,"required":false,"type":"REMARK","label":"TEST - Solenoid valve(s)","help_text":"TEST solenoid valves for correct operations.","sort_order":38,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":389,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Low air pressure alarms(s)","help_text":"(a) VERIFY: Low air pressure alarm operates at predetermined levels.\n(b) Low air pressure alarm(s) visual indicator and sounders are optional.","sort_order":39,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":390,"active":true,"required":false,"type":"REMARK","label":"GENERATE - Local alarm and fire brigade test simulation in lieu of Item 1.12 in Table 2.4.2.1","help_text":"(a) GENERATE a test of the alarm signalling equipment and local alarm in accordance with the manufacturer's operating manual.\n** NOTE: ** Where fitted, bypass valve may be used for this test.","sort_order":40,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":391,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Local alarm and fire brigade test simulation in lieu of Item 1.12 in Table 2.4.2.1","help_text":"(b) VERIFY correct operation of the fire brigade alarm from each pre-action valve or group of pre-action valves. Where the system is monitored, ensure the alarm has activated the alarm signalling equipment.\n** NOTE: ** Where multiple pre-action valve assemblies are separately identified at the FIP, only one transmission from the FIP to the monitoring station is required.","sort_order":41,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1491,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.2 (Six-monthly Inspection)","help_text":"AS1851-2012 Table 2.4.2.2 (Six-monthly Wet Pipe Inspection)","sort_order":42,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1492,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Floor/zone indication test (where fitted)","help_text":"COMPLETE all monthly service activities, as listed in Table 2.4.2.1.","sort_order":43,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1493,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Floor/zone indication test (where fitted)","help_text":"(a) OPERATE each flow switch test arrangement (automatic or manual).","sort_order":44,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1494,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Floor/zone indication test (where fitted)","help_text":"(b) VERIFY correct flow switch indication at the CIE.","sort_order":45,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1495,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Underground keyoperated and subsidiary valves","help_text":"(a) Except where owned by the water supply authority, OPERATE (two full turns) all underground key-operated valves and verify they are fully open, secure in the open position (relaxed Â¼ turn if appropriate) and are correctly labelled.\n** NOTE: ** Where underground key-operated valves are owned by the water supply authority, the owner should arrange for the water supply authority to test the valve(s) to confirm the valve(s) is operational and in the correct position.\n(b) OPERATE all subsidiary stop valves (floor isolation valves, tail-end valves).Ensure that they are fully open and, where applicable, secured in the open position and are correctly labelled.","sort_order":46,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1530,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Number valves checked","help_text":"RECORD number underground keyoperated and subsidiary valves checked.","sort_order":47,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1496,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Valve-monitoring device test","help_text":"Test each valve monitor by operating the valve and VERIFY the correct indication at the CIE.","sort_order":48,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1531,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Number monitors checked","help_text":"RECORD number valve monitors checked.","sort_order":49,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1532,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pressure gauge readings before main drain test","help_text":"RECORD reading from each pressure gauge.","sort_order":50,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1497,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Pressure gauge readings before main drain test","help_text":"VERIFY pressure gauge readings are within the ranges required.","sort_order":51,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1498,"active":true,"required":false,"type":"REMARK","label":"OPEN - Main drain valve water supply test - Town main supply only","help_text":"(a) OPEN the sprinkler control assembly main drain valve without pump(s) running. In the case of grouped valve sets, open one only.","sort_order":52,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1499,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Main drain valve water supply test - Town main supply only","help_text":"(b) VERIFY that residual water supply pressure, with drain valve open, is within 10% of the original value recorded.","sort_order":53,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1533,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Stabilize flow water supply pressure","help_text":"RECORD stabilize flow water supply pressure (kPa)","sort_order":54,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1500,"active":true,"required":false,"type":"REMARK","label":"CLOSE - Main drain valve water supply test - Town main supply only","help_text":"(c) CLOSE main drain valve and record time for pressure recovery.","sort_order":55,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1534,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Time for pressure recovery","help_text":"RECORD time for pressure recovery (sec)","sort_order":56,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1501,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Main drain valve water supply test - Town main supply only","help_text":"(d) VERIFY that the time for pressure recovery aligns with previously recorded value.\n** NOTE: ** Where the building exceeds four storeys in height, care should be taken to ensure that the static head of the installation does not excessively elevate the residual pressure reading.","sort_order":57,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1502,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water supply (river, lake, etc.) strainers/screens","help_text":"CHECK suction inlet strainer(s) or screen(s) for any condition likely to affect its function. Where blocked, CLEAN the suction inlet strainers or screens.","sort_order":58,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":421,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.5.2 (Six-monthly Inspection)","help_text":"AS1851-2012 Table 2.4.5.2 (Six-monthly Pre-Action Inspection)","sort_order":59,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":422,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service activities","help_text":"COMPLETE all monthly service activities listed in Table 2.4.5.1 and all six-monthly wet pipe service activities listed in Table 2.4.2.2 that are applicable to a pre-action system.","sort_order":60,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":423,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pre-action valve and auxiliaries, local alarm and fire brigade alarm test","help_text":"(a) Where fitted, CLOSE isolation valve located above pre-action valve (prevents entry of water into system piping).\n(b) OPERATE each pre-action valve by releasing the system via electrical detection subsystem.\n(c) CHECK for correct operation of alarm.\n(e) OBSERVE correct operation of the fire brigade alarms from each pre-action valve or group of pre-action assemblies. Where the system is monitored, ensure the alarm has activated the alarm signalling equipment.\n** NOTE: ** Where multiple pre-action valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.\n(f) Where an isolation valve has not been fitted above the alarm valve, the main stop valve should be closed, enabling a partial test of the alarm valve.\n** NOTE: **Consider full testing at the first opportunity (at which time the isolation test valve should be installed).","sort_order":61,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":424,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Pre-action valve and auxiliaries, local alarm and fire brigade alarm test","help_text":"(d) RECORD time(s) to operation of alarms and verify that these do not exceed 180 s.","sort_order":62,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":425,"active":true,"required":false,"type":"REMARK","label":"RESET - Installation supervisory air pressure","help_text":"RESET pre-action valve and restore supervisory air pressure.","sort_order":63,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":426,"active":true,"required":false,"type":"REMARK","label":"RESTORE - Electrical control unit (and FIP/ASE)","help_text":"RESTORE units to operational status.","sort_order":64,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":427,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Pressure gauge readings - Record kPa...","help_text":"(a) RECORD readings from each pressure gauge.","sort_order":65,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":428,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Pressure gauge readings - readings","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":66,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":429,"active":true,"required":false,"type":"REMARK","label":"SECURE - Valve and cocks","help_text":"SECURE all valves and alarm cocks in the open position or the closed position as labelled.","sort_order":67,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":430,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.2 (Six-monthly Inspection)","help_text":"AS1851-2012 Table 2.4.2.2 (Six-monthly Wet Pipe Inspection)","sort_order":68,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":431,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Floor/zone indication test (where fitted)","help_text":"COMPLETE all monthly service activities, as listed in Table 2.4.2.1.","sort_order":69,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":432,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Floor/zone indication test (where fitted)","help_text":"(a) OPERATE each flow switch test arrangement (automatic or manual).","sort_order":70,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":433,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Floor/zone indication test (where fitted)","help_text":"(b) VERIFY correct flow switch indication at the CIE.","sort_order":71,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":434,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Underground keyoperated and subsidiary valves","help_text":"(a) Except where owned by the water supply authority, OPERATE (two full turns) all underground key-operated valves and verify they are fully open, secure in the open position (relaxed Â¼ turn if appropriate) and are correctly labelled.\n** NOTE: ** Where underground key-operated valves are owned by the water supply authority, the owner should arrange for the water supply authority to test the valve(s) to confirm the valve(s) is operational and in the correct position.\n(b) OPERATE all subsidiary stop valves (floor isolation valves, tail-end valves).Ensure that they are fully open and, where applicable, secured in the open position and are correctly labelled.","sort_order":72,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1535,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Number valves checked","help_text":"RECORD number underground keyoperated and subsidiary valves checked.","sort_order":73,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":435,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Valve-monitoring device test","help_text":"Test each valve monitor by operating the valve and VERIFY the correct indication at the CIE.","sort_order":74,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1536,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Number monitors checked","help_text":"RECORD number valve monitors checked.","sort_order":75,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":436,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pressure gauge readings before main drain test","help_text":"RECORD reading from each pressure gauge.","sort_order":76,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":437,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Pressure gauge readings before main drain test","help_text":"VERIFY pressure gauge readings are within the ranges required.","sort_order":77,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":438,"active":true,"required":false,"type":"REMARK","label":"OPEN - Main drain valve water supply test - Town main supply only","help_text":"(a) OPEN the sprinkler control assembly main drain valve without pump(s) running. In the case of grouped valve sets, open one only.","sort_order":78,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":439,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Main drain valve water supply test - Town main supply only","help_text":"(b) VERIFY that residual water supply pressure, with drain valve open, is within 10% of the original value recorded.","sort_order":79,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1537,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Stabilize flow water supply pressure","help_text":"RECORD stabilize flow water supply pressure (kPa)","sort_order":80,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":440,"active":true,"required":false,"type":"REMARK","label":"CLOSE - Main drain valve water supply test - Town main supply only","help_text":"(c) CLOSE main drain valve and record time for pressure recovery.","sort_order":81,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1538,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Time for pressure recovery","help_text":"RECORD time for pressure recovery (sec)","sort_order":82,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":441,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Main drain valve water supply test - Town main supply only","help_text":"(d) VERIFY that the time for pressure recovery aligns with previously recorded value.\n** NOTE: ** Where the building exceeds four storeys in height, care should be taken to ensure that the static head of the installation does not excessively elevate the residual pressure reading.","sort_order":83,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":442,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water supply (river, lake, etc.) strainers/screens","help_text":"CHECK suction inlet strainer(s) or screen(s) for any condition likely to affect its function. Where blocked, CLEAN the suction inlet strainers or screens.","sort_order":84,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":443,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.5.3 (Annual Inspection)","help_text":"AS1851-2012 Table 2.4.5.3 (Annual Pre-Action Inspection)","sort_order":85,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":444,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and six-monthly service","help_text":"COMPLETE all monthly and six-monthly service activities, listed in Tables 2.4.5.1 and 2.4.5.2.","sort_order":86,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1503,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Yearly service","help_text":"COMPLETE all yearly wet pipe service activities listed in Table 2.4.2.3 that are applicable to a pre-action system.","sort_order":87,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1504,"active":true,"required":false,"type":"REMARK","label":"DRAIN - Air receiver condensate","help_text":"DRAIN condensate from:\n(a) Condensate trap.\n(b) Air compressor receiver.","sort_order":88,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1505,"active":true,"required":false,"type":"REMARK","label":"CHECH - Survey - Installation","help_text":"CHECK that sprinkler piping and detection installations are properly secured throughout the protection area.","sort_order":89,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1506,"active":true,"required":false,"type":"REMARK","label":"CHECH - Survey - Design","help_text":"CHECK that pre-action sprinkler protection covers full extend of special hazard area.","sort_order":90,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":445,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.3 (Annual Inspection)","help_text":"AS1851-2012 Table 2.4.2.3 (Annual Wet Pipe Inspection)","sort_order":91,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":446,"active":true,"required":false,"type":"REMARK","label":"OPERATE & VERIFY - Pressure reducing valve test","help_text":"(a) OPERATE all pressure-reducing valves and verify correct operation under flow conditions.\n(b) VERIFY that pressure readings on the low pressure side of the valves are within the range stated at the pressure-reducing valve station.","sort_order":92,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1539,"active":true,"required":false,"type":"INTEGER","label":"RECORD - High pressure gauge","help_text":"RECORD high pressure gauge (kPa)","sort_order":93,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1540,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Low pressure gauge","help_text":"RECORD low pressure gauge (kPa)","sort_order":94,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":447,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Pressure-relief valve test","help_text":"OPERATE pressure-relief valve and note operating pressure is within the range stated on the nameplate provided at the reducing valve station.\n**NOTES: **\n1 This test of the pressure-relief valve may be carried out using a portable test apparatus.\n2 Inappropriate settings for pressure-relief valves can result in very large quantities of water flowing to waste. Ensure settings are maintained to have pressures as identified and not higher than allowed by system component rated working pressures.","sort_order":95,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1541,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Operating pressure","help_text":"RECORD operating pressure (kPa)","sort_order":96,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":448,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water supply tanks - Atmospheric or pressure","help_text":"Perform routine service in accordance with Section 5.","sort_order":97,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":449,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Water supply proving test","help_text":"(a) CONDUCT a water supply test, subject to limitations imposed by the water agency controlling the supply source. The test may be a combination of physical testing and calculation as necessary.","sort_order":98,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":450,"active":true,"required":false,"type":"DECIMAL","label":"DISCHARGE - Water supply proving test - Favourable Flow Pressure kPa...","help_text":"(i) Discharge water through the flowmeasuring device at the flow corresponding to the hydraulically most favourable duty flow. Record the flowing pressure.","sort_order":99,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":451,"active":true,"required":false,"type":"DECIMAL","label":"REDUCE - Water supply proving test - Unfavourable Flow Pressure kPa...","help_text":"(ii) Reduce the water flow through the flow measuring device to that corresponding to the most unfavourable duty point. Record the flowing pressure.","sort_order":100,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":452,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Water supply proving test - Satic pressure kPa...","help_text":"(iii) Shut off water flow to flow-measuring device. Record static pressure.","sort_order":101,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":453,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water supply proving test","help_text":"(b) VERIFY that the system flow and pressure requirements are satisfied.\n(c) COMPLETE a water supply test report in accordance with AS 2118.1.\n** NOTE: ** This test should be conducted by substituting the installation and below stop valve pressure gauges with calibrated gauges of known accuracy.\nWhere pumpsets are fitted, the water supply flow test should be performed combined with the pumpset load test requirements in Section 3.","sort_order":102,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":454,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Alarm valve - Remote test valve","help_text":"(a) OPERATE the alarm valve by opening each remote test valve.","sort_order":103,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":455,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Alarm valve - Remote test valve - Gong time........s","help_text":"(b) RECORD time(s) to operation of alarm gong(s)","sort_order":104,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":456,"active":true,"required":false,"type":"HEADER","label":"VERIFY - Alarm valve - Remote test valve time","help_text":"(b) verify that time does not exceed 360 s for AS 2118.1 and 180 s for AS 2118.4 systems.","sort_order":105,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":457,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.1 system time does not exceed 360 s","help_text":"(b) verify that time does not exceed 360 s for AS 2118.1 systems","sort_order":106,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":458,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.1 system time exceed 360 s","help_text":"(b) verify that time does not exceed 360 s for AS 2118.1 systems","sort_order":107,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":459,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.4 system time does not exceed 180 s","help_text":"(b) verify that time does not exceed 180 s for AS 2118.4 systems.","sort_order":108,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":460,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.4 system time exceed 180 s","help_text":"(b) verify that time does not exceed 180 s for AS 2118.4 systems.","sort_order":109,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":461,"active":true,"required":false,"type":"REMARK","label":"CLOSE - Alarm valve - Remote test valve","help_text":"c) CLOSE remote test valve(s) and verify that alarm valve has reseated.","sort_order":110,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":462,"active":true,"required":false,"type":"REMARK","label":"CHECK - Anti-freeze solution test (where applicable)","help_text":"(a) DRAW a sample of anti-freeze solution.\n(b) VERIFY correct specific gravity and top up to correct solution level.","sort_order":111,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":463,"active":true,"required":false,"type":"REMARK","label":"CHECK - Sprinkler system interface control test (fire trips)","help_text":"(a) CONDUCT a functional system test via the pressure switch or flow switch with each interfaced system.\n(b) VERIFY that the interface functions as required.","sort_order":112,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":464,"active":true,"required":false,"type":"REMARK","label":"CLEAN - Water motor alarm gong","help_text":"CLEAN the strainer and lubricate the external gong mechanism.","sort_order":113,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":465,"active":true,"required":false,"type":"REMARK","label":"CLEAN- Water motor direct brigade alarm","help_text":"CLEAN the strainer.","sort_order":114,"ref":"3.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":466,"active":true,"required":false,"type":"REMARK","label":"CHECK & VERIFY - Alarm signalling equipment (ASE) (Standalone)","help_text":"Where an ASE is standalone and is connected to a power supply unit and batteries:\n(a) CHECK the batteries for any condition likely to adversely affects its function and\n(b) Where the battery has not been replaced in the previous two years, VERIFY the battery condition by carrying out a battery discharge test in accordance with Appendix F.","sort_order":115,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1507,"active":true,"required":false,"type":"DATE","label":"RECORD - Date last replaced","help_text":"RECORD date last replaced","sort_order":116,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":467,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Tank quick fill (reduced capacity or break tank)","help_text":"CONDUCT a water supply test through a flowmeasuring device or other appropriate methods that the flow corresponds to the required quick fill-rate.","sort_order":117,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1542,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Flow","help_text":"RECORD flow (L/min)","sort_order":118,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1543,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pressure","help_text":"RECORD pressure (kPa)","sort_order":119,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":468,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Spray booths and ducts","help_text":"INSPECT accumulated spray residue on sprinklers and reapply protective medium (petroleum jelly/paper bags).\nNOTE: The required frequency of inspection depends upon the amount of spraying being done and could be accomplished at the same time as the cleaning of booth.","sort_order":120,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":469,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Kitchen hoods and ducts","help_text":"INSPECT all sprinklers inside kitchen hoods and ducts and CLEAN if necessary to remove accumulated grease and any other foreign matter and verify that the sprinkler head is appropriate for this application.","sort_order":121,"ref":"3.14","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":470,"active":true,"required":false,"type":"REMARK","label":"DRAW - Foam water sprinkler systems - Foam concentrate","help_text":"DRAW a sample and verify condition in accordance with NFPA 11 (pH, specific gravity, sediment, expansion ratio, 25% drain time).","sort_order":122,"ref":"3.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":471,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foam concentrate strainer (where fitted)","help_text":"CHECK and clean foam concentrate strainer (fitted upstream of proportioning device).","sort_order":123,"ref":"3.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":472,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Pipes and hangers","help_text":"CHECK that exposed water distribution system, including pipework, pipe supports and valves, appear free from corrosion and damage, not subject to external loads and pipework is properly supported.","sort_order":124,"ref":"3.17","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":473,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler condition","help_text":"CHECK sprinklers for any condition, including physical damage, contamination, and paint on operating elements or cover plates, likely to adversely affect their function.\nNOTE: Sprinkler frames may be painted as part of the manufacturing process; however, the heat response elements should not be painted as this will delay or prevent operation and paint accumulated at the seat of the sprinkler may affect operation. Minor spatter on the fusible elements may be acceptable but operation should be checked if doubt exists.","sort_order":125,"ref":"3.18","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":474,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Escutcheons, cover plates or guards","help_text":"CHECK for poorly fitting or missing escutcheons or cover plates, damaged guards, and attachment of foreign material.","sort_order":126,"ref":"3.19","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":475,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler obstructions","help_text":"CHECK for obstructions likely to impede sprinkler discharge and for adequate clear space below sprinklers.","sort_order":127,"ref":"3.20","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":476,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Unprotected areas","help_text":"(a) CHECK for presence of unprotected areas such as mezzanines, platforms and building extensions.\n(b) CHECK for sprinkler spacing and location relative to wall, bulkhead and partition alterations and the introduction of fixtures and fittings shielding sprinkler discharge.\n(c) CHECK for the need to install sprinkler guards.","sort_order":128,"ref":"3.21","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":477,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler compatibility","help_text":"CHECK that sprinklers within a compartment are of similar operating characteristics (e.g. area coverage, RTI and temperature rating).","sort_order":129,"ref":"3.22","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":478,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler ambient conditions","help_text":"CHECK for localized changes in ambient temperatures, which may require different sprinkler temperature ratings (e.g. exposure to freezing or high temperature conditions).","sort_order":130,"ref":"3.23","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":479,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - External sprinklers","help_text":"CHECK for new building structures, yard storage or the like, exposing unprotected openings, non-fire resistant walls that may require the provision for external sprinklers.","sort_order":131,"ref":"3.24","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":480,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Occupancy","help_text":"CHECK that sprinkler design remains applicable for the occupancy hazard classification and the category of storage involved.","sort_order":132,"ref":"3.25","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":481,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Storage heights, encapsulation","help_text":"(a) CHECK that sprinkler design remains applicable for storage heights.\nIf height limits are exceeded, check for in-rack (intermediate) sprinklers.\n(b) CHECK for shrink wrapping (encapsulation) where not employed previously.","sort_order":133,"ref":"3.26","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":482,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Site documentation (where required)","help_text":"(a) CHECK that block plans and emergency instructions contain the required details.\n(b) CHECK that up-to-date sprinkler plans are available on site.","sort_order":134,"ref":"3.27","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":483,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Installation","help_text":"CHECK that sprinkler piping and detection installations are properly secured throughout the protection area.","sort_order":136,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":484,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Design","help_text":"CHECK that pre-action sprinkler protection covers full extend of special hazard area.","sort_order":137,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":485,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.5.4 (Five-yearly Inspection)","help_text":"AS1851-2012 Table 2.4.5.4 (Five-yearly Pre-Action Inspection)","sort_order":138,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":486,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly, six-monthly and Annual service","help_text":"COMPLETE all monthly, six-monthly and Annual service activities, listed in Tables 2.4.5.1, 2.4.5.2 and 2.4.5.3.","sort_order":139,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":487,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Five Annual service","help_text":"COMPLETE all five-Annual wet pipe service activities listed in Table 2.4.2.4 that are applicable to a pre-action system.","sort_order":140,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":488,"active":true,"required":false,"type":"REMARK","label":"FIT - Valve overhaul","help_text":"FIT new pre-action valve seats and seals.","sort_order":141,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":489,"active":true,"required":false,"type":"REMARK","label":"CHECK & CLEAN - Valve overhaul","help_text":"CHECK and CLEAN operating mechanism. FIT new cover plate gasket.","sort_order":142,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Pre-Action","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Fire Sprinkler System: Wet Pipe & Residential","prompts":[{"id":77,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.1 (Monthly Inspection)","help_text":"AS1851-2012 Table 2.4.2.1 (Monthly Wet Pipe Inspection)","sort_order":1,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":78,"active":true,"required":false,"type":"REMARK","label":"CHECK - Control valve assembly","help_text":"CHECK that control valve assembly area is unobstructed and free of any condition that may adversely affect the operation or access.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":79,"active":true,"required":false,"type":"REMARK","label":"CHECK - Sprinkler spares, sprinklers and sprinkler spanner","help_text":"CHECK that there are spare sprinklers of appropriate quantity and type including a matching sprinkler spanner for each type of sprinkler fitted, available.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":80,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signage","help_text":"CHECK for damage, legibility and appropriate location of required signage.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":81,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire brigade booster connection - Obstruction","help_text":"CHECK that the booster connection or enclosure is unobstructed and for any condition that may adversely affect the operation or access.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":82,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire brigade booster connection - Couplings","help_text":"CHECK that the booster connection coupling type is as per the local fire brigade requirements.","sort_order":6,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":83,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Main stop valves and alarm cocks","help_text":"INSPECT each main stop valve and alarm cock for each control assembly is secured in the open position and the main stop valve is correctly labelled.","sort_order":7,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":84,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pump starting devices isolating valve","help_text":"CHECK that each isolating valve to each automatic pump start device is locked in the open position.","sort_order":8,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":85,"active":true,"required":false,"type":"REMARK","label":"CHECK - Pressure switches","help_text":"CHECK each pressure switch and ensure that the cover is in place, correctly labelled, securely mounted and free from any condition likely to adversely affect its function.","sort_order":9,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":86,"active":true,"required":false,"type":"REMARK","label":"CHECK - Alarm signalling equipment (ASE) (stand-alone)","help_text":"CHECK the alarm signalling equipment to ensure that it is securely mounted, free from any condition likely to adversely affect its function and is not indicating alarm, fault, loss of connection, or isolated.","sort_order":10,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":87,"active":true,"required":false,"type":"REMARK","label":"CHECK - Sprinkler system interface to other systems","help_text":"CHECK the sprinkler system alarm interface with other systems is not isolated, inhibited or disabled.","sort_order":11,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":88,"active":true,"required":false,"type":"REMARK","label":"NOTE - Water supply stop valves","help_text":"1 - Where more than 12 water supply stop valves are distributed throughout a high-rise building, forming part of a combined sprinkler/hydrant system, the actions under actions (a) and (b) may be conducted on a rotating basis.\n2 - The period between testing of all water supply stop valves should not exceed 3 months.","sort_order":12,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":89,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Water supply stop valves","help_text":"(a) OPERATE (two full turns) all water supply stop valves (including backflow prevention stop valves but excluding underground keyoperated valves) and verify they are fully open, secure in the open position (relaxed Â¼ turn if appropriate) and are correctly labelled.","sort_order":13,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":90,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Water supply stop valves","help_text":"(b) VERIFY that the valve position indicators are securely mounted and indicate correctly.","sort_order":14,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":91,"active":true,"required":false,"type":"INTEGER","label":"RECORD - System pressure gauge readings before alarm function test, kPa.......","help_text":"(a) RECORD reading from each pressure gauge.","sort_order":15,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":92,"active":true,"required":false,"type":"REMARK","label":"VERIFY - System pressure gauge readings before alarm function test","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":16,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":93,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(a) OPERATE each alarm valve by opening each 15 mm test valve or 10 mm for residential sprinkler systems serving buildings up to 4 storeys in height. Where more than 12 control assemblies are distributed throughout a high-rise building forming part of a combined sprinkler/hydrant system, and initiate the fire brigade alarm, testing may be conducted on a rotating basis. The period between testing of all control assemblies shall not exceed 3 months.","sort_order":17,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":94,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(b) RECORD time(s) to operation of alarm gong(s) and verify that time does not exceed 180 s for general systems or 90 s for residential sprinkler systems.","sort_order":18,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":95,"active":true,"required":false,"type":"REMARK","label":"RESET - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(c) RESET the alarm test valve on completion of each test.","sort_order":19,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":96,"active":true,"required":false,"type":"REMARK","label":"TEST - Control assembly, alarm gong, alarm-initiating device, fire brigade alarm test and DSEP/DBEP strobes (Alarm function test)","help_text":"(d) Where multiple control valve assemblies are separately identified at an FIP, only one transmission from the FIP to the monitoring station is required.","sort_order":20,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":97,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Alarm signal","help_text":"VERIFY the correct operation of each alarm signal. Where the system is monitored ensure the alarm has activated the alarm signalling equipment.","sort_order":21,"ref":"1.13","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":98,"active":true,"required":false,"type":"REMARK","label":"INSPECT - DSEP/DBEP strobe indicator","help_text":"INSPECT for the correct operation of each DSEP/DBEP strobe indicator, where fitted.","sort_order":22,"ref":"1.14","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":99,"active":true,"required":false,"type":"INTEGER","label":"RECORD - System pressure gauge readings after alarm valve test","help_text":"(a) RECORD reading from each pressure gauge.","sort_order":23,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":100,"active":true,"required":false,"type":"REMARK","label":"VERIFY - System pressure gauge readings after alarm valve test","help_text":"(b) VERIFY pressure gauge readings are within the ranges required.","sort_order":24,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":101,"active":true,"required":false,"type":"REMARK","label":"TEST - Pump starting devices function test - Compression ignition drivers (diesel) and electric motor drivers","help_text":"(a) TEST each automatic pump starting device and pump operation by reducing the applied water pressure to the starting device and run pump, in accordance with Section 3. Where more than one starting device is installed, including the manual starting device, the test may be carried out on a rotating basis. The period between the exercising of each starting device is not to exceed 3 months. Where this would require the pump to start more than 5 times in succession, the period may be extended to 6 months.","sort_order":25,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":102,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pump starting devices function test - CUT IN PRESSURE","help_text":"(b) RECORD the pump cut-in pressures and verify that they are within the ranges required.","sort_order":26,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":103,"active":true,"required":false,"type":"REMARK","label":"TEST - Manual pump start device, function test","help_text":"TEST each manual pump starting device and pump operation in accordance with Section 3.","sort_order":27,"ref":"1.17","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":104,"active":true,"required":false,"type":"REMARK","label":"PERFORM - Water supply tanks - Atmospheric or pressure","help_text":"Perform routine service in accordance with Section 5.","sort_order":28,"ref":"1.18","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":105,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foam water sprinkler systems - foam concentrate","help_text":"CHECK that the concentrate level is correct and level indicator reads correctly.","sort_order":29,"ref":"1.19","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1508,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.2 (Six-monthly Inspection)","help_text":"AS1851-2012 Table 2.4.2.2 (Six-monthly Wet Pipe Inspection)","sort_order":30,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":107,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Floor/zone indication test (where fitted)","help_text":"COMPLETE all monthly service activities, as listed in Table 2.4.2.1.","sort_order":31,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":108,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Floor/zone indication test (where fitted)","help_text":"(a) OPERATE each flow switch test arrangement (automatic or manual).","sort_order":32,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":109,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Floor/zone indication test (where fitted)","help_text":"(b) VERIFY correct flow switch indication at the CIE.","sort_order":33,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":110,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Underground keyoperated and subsidiary valves","help_text":"(a) Except where owned by the water supply authority, OPERATE (two full turns) all underground key-operated valves and verify they are fully open, secure in the open position (relaxed Â¼ turn if appropriate) and are correctly labelled.\n** NOTE: ** Where underground key-operated valves are owned by the water supply authority, the owner should arrange for the water supply authority to test the valve(s) to confirm the valve(s) is operational and in the correct position.\n(b) OPERATE all subsidiary stop valves (floor isolation valves, tail-end valves).Ensure that they are fully open and, where applicable, secured in the open position and are correctly labelled.","sort_order":34,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1544,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Number valves checked","help_text":"RECORD number underground keyoperated and subsidiary valves checked.","sort_order":35,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":111,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Valve-monitoring device test","help_text":"Test each valve monitor by operating the valve and VERIFY the correct indication at the CIE.","sort_order":36,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1545,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Number monitors checked","help_text":"RECORD number valve monitors checked.","sort_order":37,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":112,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pressure gauge readings before main drain test","help_text":"RECORD reading from each pressure gauge.","sort_order":38,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":113,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Pressure gauge readings before main drain test","help_text":"VERIFY pressure gauge readings are within the ranges required.","sort_order":39,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":114,"active":true,"required":false,"type":"REMARK","label":"OPEN - Main drain valve water supply test - Town main supply only","help_text":"(a) OPEN the sprinkler control assembly main drain valve without pump(s) running. In the case of grouped valve sets, open one only.","sort_order":40,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":115,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Main drain valve water supply test - Town main supply only","help_text":"(b) VERIFY that residual water supply pressure, with drain valve open, is within 10% of the original value recorded.","sort_order":41,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1546,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Stabilize flow water supply pressure","help_text":"RECORD stabilize flow water supply pressure (kPa)","sort_order":42,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":116,"active":true,"required":false,"type":"REMARK","label":"CLOSE - Main drain valve water supply test - Town main supply only","help_text":"(c) CLOSE main drain valve and record time for pressure recovery.","sort_order":43,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1547,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Time for pressure recovery","help_text":"RECORD time for pressure recovery (sec)","sort_order":44,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":117,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Main drain valve water supply test - Town main supply only","help_text":"(d) VERIFY that the time for pressure recovery aligns with previously recorded value.\n** NOTE: ** Where the building exceeds four storeys in height, care should be taken to ensure that the static head of the installation does not excessively elevate the residual pressure reading.","sort_order":45,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":118,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water supply (river, lake, etc.) strainers/screens","help_text":"CHECK suction inlet strainer(s) or screen(s) for any condition likely to affect its function. Where blocked, CLEAN the suction inlet strainers or screens.","sort_order":46,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":119,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.3 (Annual Inspection)","help_text":"AS1851-2012 Table 2.4.2.3 (Annual Wet Pipe Inspection)","sort_order":47,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":120,"active":true,"required":false,"type":"REMARK","label":"OPRATE & VERIFY - Pressure reducing valve test","help_text":"(a) OPERATE all pressure-reducing valves and verify correct operation under flow conditions.\n(b) VERIFY that pressure readings on the low pressure side of the valves are within the range stated at the pressure-reducing valve station.","sort_order":48,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1548,"active":true,"required":false,"type":"INTEGER","label":"RECORD - High pressure gauge","help_text":"RECORD high pressure gauge (kPa)","sort_order":49,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1549,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Low pressure gauge","help_text":"RECORD low pressure gauge (kPa)","sort_order":50,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":121,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Pressure-relief valve test","help_text":"OPERATE pressure-relief valve and note operating pressure is within the range stated on the nameplate provided at the reducing valve station.\n**NOTES: **\n1 This test of the pressure-relief valve may be carried out using a portable test apparatus.\n2 Inappropriate settings for pressure-relief valves can result in very large quantities of water flowing to waste. Ensure settings are maintained to have pressures as identified and not higher than allowed by system component rated working pressures.","sort_order":51,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1550,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Operating pressure","help_text":"RECORD operating pressure (kPa)","sort_order":52,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":122,"active":true,"required":false,"type":"REMARK","label":"PERFORM - Water supply tanks - Atmospheric or pressure","help_text":"Perform routine service in accordance with Section 5.","sort_order":54,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":123,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Water supply proving test","help_text":"(a) CONDUCT a water supply test, subject to limitations imposed by the water agency controlling the supply source. The test may be a combination of physical testing and calculation as necessary.","sort_order":55,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":124,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Water supply proving test - Favourable Flow Pressure kPa...","help_text":"(i) Discharge water through the flowmeasuring device at the flow corresponding to the hydraulically most favourable duty flow. Record the flowing pressure.","sort_order":56,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":125,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Water supply proving test - Unfavourable Flow Pressure kPa...","help_text":"(ii) Reduce the water flow through the flow measuring device to that corresponding to the most unfavourable duty point. Record the flowing pressure.","sort_order":57,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":126,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Water supply proving test - Satic pressure kPa...","help_text":"(iii) Shut off water flow to flow-measuring device. Record static pressure.","sort_order":58,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":127,"active":true,"required":false,"type":"REMARK","label":"VERIFY & COMPLETE - Water supply proving test","help_text":"(b) VERIFY that the system flow and pressure requirements are satisfied.\n(c) COMPLETE a water supply test report in accordance with AS 2118.1.\n** NOTE: ** This test should be conducted by substituting the installation and below stop valve pressure gauges with calibrated gauges of known accuracy.\nWhere pumpsets are fitted, the water supply flow test should be performed combined with the pumpset load test requirements in Section 3.","sort_order":59,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":128,"active":true,"required":false,"type":"REMARK","label":"OPERATE - Alarm valve - Remote test valve","help_text":"(a) OPERATE the alarm valve by opening each remote test valve.","sort_order":60,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":129,"active":true,"required":false,"type":"DECIMAL","label":"RECORD - Alarm valve - Remote test valve - Gong time........s","help_text":"(b) RECORD time(s) to operation of alarm gong(s)","sort_order":61,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":130,"active":true,"required":false,"type":"HEADER","label":"VERIFY - Alarm valve - Remote test valve time","help_text":"(b) verify that time does not exceed 360 s for AS 2118.1 and 180 s for AS 2118.4 systems.","sort_order":62,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":131,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.1 system time does not exceed 360 s","help_text":"(b) verify that time does not exceed 360 s for AS 2118.1 systems","sort_order":63,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":132,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.1 system time exceed 360 s","help_text":"(b) verify that time does not exceed 360 s for AS 2118.1 systems","sort_order":64,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":133,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.4 system time does not exceed 180 s","help_text":"(b) verify that time does not exceed 180 s for AS 2118.4 systems.","sort_order":65,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":134,"active":true,"required":false,"type":"CHOICE","label":"VERIFY - AS 2118.4 system time exceed 180 s","help_text":"(b) verify that time does not exceed 180 s for AS 2118.4 systems.","sort_order":66,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":135,"active":true,"required":false,"type":"REMARK","label":"CLOSE - Alarm valve - Remote test valve","help_text":"c) CLOSE remote test valve(s) and verify that alarm valve has reseated.","sort_order":67,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":136,"active":true,"required":false,"type":"REMARK","label":"DRAW & VERIFY - Anti-freeze solution test (where applicable)","help_text":"(a) DRAW a sample of anti-freeze solution.\n(b) VERIFY correct specific gravity and top up to correct solution level.","sort_order":68,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":137,"active":true,"required":false,"type":"REMARK","label":"CONDUCT & VERIFY - Sprinkler system interface control test (fire trips)","help_text":"(a) CONDUCT a functional system test via the pressure switch or flow switch with each interfaced system.\n(b) VERIFY that the interface functions as required.","sort_order":69,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":138,"active":true,"required":false,"type":"REMARK","label":"CLEAN - Water motor alarm gong","help_text":"CLEAN the strainer and lubricate the external gong mechanism.","sort_order":70,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":139,"active":true,"required":false,"type":"REMARK","label":"CLEAN - Water motor direct brigade alarm","help_text":"CLEAN the strainer.","sort_order":71,"ref":"3.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":140,"active":true,"required":false,"type":"REMARK","label":"CHECK & VERIFY - Alarm signalling equipment (ASE) (Standalone)","help_text":"Where an ASE is standalone and is connected to a power supply unit and batteries:\n(a) CHECK the batteries for any condition likely to adversely affects its function and\n(b) Where the battery has not been replaced in the previous two years, VERIFY the battery condition by carrying out a battery discharge test in accordance with Appendix F.","sort_order":72,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1509,"active":true,"required":false,"type":"DATE","label":"RECORD - Date last replaced","help_text":"RECORD date last replaced","sort_order":73,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":141,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Tank quick fill (reduced capacity or break tank)","help_text":"CONDUCT a water supply test through a flowmeasuring device or other appropriate methods that the flow corresponds to the required quick fill-rate.","sort_order":74,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1551,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Flow","help_text":"RECORD flow (L/min)","sort_order":75,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1552,"active":true,"required":false,"type":"INTEGER","label":"RECORD - Pressure","help_text":"RECORD pressure (kPa)","sort_order":76,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":142,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Spray booths and ducts","help_text":"INSPECT accumulated spray residue on sprinklers and reapply protective medium (petroleum jelly/paper bags).\nNOTE: The required frequency of inspection depends upon the amount of spraying being done and could be accomplished at the same time as the cleaning of booth.","sort_order":77,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":143,"active":true,"required":false,"type":"REMARK","label":"INSPECT & CLEAN - Kitchen hoods and ducts","help_text":"INSPECT all sprinklers inside kitchen hoods and ducts and CLEAN if necessary to remove accumulated grease and any other foreign matter and verify that the sprinkler head is appropriate for this application.","sort_order":78,"ref":"3.14","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":144,"active":true,"required":false,"type":"REMARK","label":"DRAW - Foam water sprinkler systems - Foam concentrate","help_text":"DRAW a sample and verify condition in accordance with NFPA 11 (pH, specific gravity, sediment, expansion ratio, 25% drain time).","sort_order":79,"ref":"3.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":145,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foam concentrate strainer (where fitted)","help_text":"CHECK and clean foam concentrate strainer (fitted upstream of proportioning device).","sort_order":80,"ref":"3.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":146,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Pipes and hangers","help_text":"CHECK that exposed water distribution system, including pipework, pipe supports and valves, appear free from corrosion and damage, not subject to external loads and pipework is properly supported.","sort_order":81,"ref":"3.17","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":147,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler condition","help_text":"CHECK sprinklers for any condition, including physical damage, contamination, and paint on operating elements or cover plates, likely to adversely affect their function.\nNOTE: Sprinkler frames may be painted as part of the manufacturing process; however, the heat response elements should not be painted as this will delay or prevent operation and paint accumulated at the seat of the sprinkler may affect operation. Minor spatter on the fusible elements may be acceptable but operation should be checked if doubt exists.","sort_order":82,"ref":"3.18","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":148,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Escutcheons, cover plates or guards","help_text":"CHECK for poorly fitting or missing escutcheons or cover plates, damaged guards, and attachment of foreign material.","sort_order":83,"ref":"3.19","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":149,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler obstructions","help_text":"CHECK for obstructions likely to impede sprinkler discharge and for adequate clear space below sprinklers.","sort_order":84,"ref":"3.20","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":150,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Unprotected areas","help_text":"(a) CHECK for presence of unprotected areas such as mezzanines, platforms and building extensions.\n(b) CHECK for sprinkler spacing and location relative to wall, bulkhead and partition alterations and the introduction of fixtures and fittings shielding sprinkler discharge.\n(c) CHECK for the need to install sprinkler guards.","sort_order":85,"ref":"3.21","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":151,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler compatibility","help_text":"CHECK that sprinklers within a compartment are of similar operating characteristics (e.g. area coverage, RTI and temperature rating).","sort_order":86,"ref":"3.22","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":152,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Sprinkler ambient conditions","help_text":"CHECK for localized changes in ambient temperatures, which may require different sprinkler temperature ratings (e.g. exposure to freezing or high temperature conditions).","sort_order":87,"ref":"3.23","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":153,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - External sprinklers","help_text":"CHECK for new building structures, yard storage or the like, exposing unprotected openings, non-fire resistant walls that may require the provision for external sprinklers.","sort_order":88,"ref":"3.24","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":154,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Occupancy","help_text":"CHECK that sprinkler design remains applicable for the occupancy hazard classification and the category of storage involved.","sort_order":89,"ref":"3.25","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":155,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Storage heights, encapsulation","help_text":"(a) CHECK that sprinkler design remains applicable for storage heights.\nIf height limits are exceeded, check for in-rack (intermediate) sprinklers.\n(b) CHECK for shrink wrapping (encapsulation) where not employed previously.","sort_order":90,"ref":"3.26","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":156,"active":true,"required":false,"type":"REMARK","label":"CHECK - Survey - Site documentation (where required)","help_text":"(a) CHECK that block plans and emergency instructions contain the required details.\n(b) CHECK that up-to-date sprinkler plans are available on site.","sort_order":91,"ref":"3.27","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":157,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.4 (Five-yearly Inspection)","help_text":"AS1851-2012 Table 2.4.2.4 (Five-yearly Wet Pipe Inspection)","sort_order":92,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":158,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Alarm valve (wet)","help_text":"COMPLETE all monthly, six-monthly and Annual service activities, as listed in Tables 2.4.2.1, 2.4.2.2 and 2.4.2.3.","sort_order":93,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":159,"active":true,"required":false,"type":"REMARK","label":"FIT - Alarm valve (wet)","help_text":"FIT new alarm valve seating or port seating (perishable items), check and clean annular groove and outlet ports, polish and lubricate seating spindle/shaft, and check operation of compensator valve if fitted. Fit a new alarm valve faceplate gasket.","sort_order":97,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":161,"active":true,"required":false,"type":"REMARK","label":"EXAMINE - Main drain and test valve","help_text":"(a) For screw-down style valves, EXAMINE seating and fit new washers.","sort_order":101,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":162,"active":true,"required":false,"type":"REMARK","label":"FIT - Main drain and test valve","help_text":"(b) For packed gland variants, FIT new gland packing.","sort_order":103,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":163,"active":true,"required":false,"type":"REMARK","label":"CHECK - Main drain and test valve","help_text":"(c) For ball valves, CHECK for leakage and replace if leaking.","sort_order":105,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":164,"active":true,"required":false,"type":"REMARK","label":"REMOVE - Alarm cock plug type","help_text":"REMOVE alarm cock barrels, clean, lap in, grease and reinstall. For packed gland variants, fit new gland packing.","sort_order":110,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":165,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Jacking pump (where fitted)","help_text":"INSPECT hand pump seatings and FIT new pump washers and path cock washers. FIT new gland packing.\nFor electric jacking pumps, maintain as per manufacturer's instructions.","sort_order":114,"ref":"4.5","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":166,"active":true,"required":false,"type":"REMARK","label":"CLEAN - Retard chambers (where fitted)","help_text":"CLEAN orifice, check seals and overhaul, where indicated, by a functional test.","sort_order":119,"ref":"4.6","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":167,"active":true,"required":false,"type":"REMARK","label":"FIT - Stop valves","help_text":"(a) FIT new gland packing and lubricate spindle.","sort_order":123,"ref":"4.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":168,"active":true,"required":false,"type":"REMARK","label":"CHECK - Stop valves","help_text":"(b) For ball and butterfly valves, CHECK for leakage and replace if necessary.","sort_order":125,"ref":"4.7","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":169,"active":true,"required":false,"type":"REMARK","label":"RENEW - Water supply non-return valves","help_text":"RENEW water supply non-return valve seatings and gaskets.","sort_order":130,"ref":"4.8","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":170,"active":true,"required":false,"type":"REMARK","label":"CLEAN - Water motor alarm gong","help_text":"CLEAN strainer on inlet line, clear water jet, flush drain, renew gasket, check operation of main spindle and striker, remove excess grease and then lubricate.","sort_order":134,"ref":"4.9","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":171,"active":true,"required":false,"type":"REMARK","label":"CLEAN - Water motor direct brigade alarm (where fitted)","help_text":"CLEAN out well of direct brigade alarm, clear water jet, renew gasket, flush drain pipe, remove gear train, check operation of main spindle, remove excess grease and then lubricate.","sort_order":138,"ref":"4.10","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":172,"active":true,"required":false,"type":"REMARK","label":"CHECK - Gauges","help_text":"CHECK all pressure gauges against a master gauge of known accuracy. Verify that the reading of the gauge under test is within Â±30 kPa of the reading of the master gauge at the nominal pressure.","sort_order":142,"ref":"4.11","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":173,"active":true,"required":false,"type":"REMARK","label":"OVERHAUL - Special valves (other than alarm valves)","help_text":"OVERHAUL all pressure-reducing valves, pressurerelief valves, tail-end system valves, and any other special valves that are installed in accordance with suppliers' specifications.","sort_order":146,"ref":"4.12","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":174,"active":true,"required":false,"type":"REMARK","label":"DRAIN - Anti-freeze systems","help_text":"DRAIN tail-end anti-freeze systems, including individual sprinkler heads on droppers and refill with new solution.","sort_order":150,"ref":"4.13","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":175,"active":true,"required":false,"type":"REMARK","label":"PERFORM - Water supply tanks - Atmospheric","help_text":"Perform routine service in accordance with Section 5.","sort_order":154,"ref":"4.14","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":176,"active":true,"required":false,"type":"REMARK","label":"SERVICE - Air compressor (where fitted)","help_text":"SERVICE the air compressor assembly in accordance with the manufacturer's instructions. [Periodic hydrostatic testing of air receivers is not required (see AS/NZS 3788)].","sort_order":158,"ref":"4.15","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":178,"active":true,"required":false,"type":"REMARK","label":"GENERATE - Foam quality","help_text":"GENERATE foam through test foam maker or by other means. Check proportioning ratio\n(refractometer or conductivity test) and drainage rate. Top up foam concentrate tank.","sort_order":163,"ref":"4.16","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":179,"active":true,"required":false,"type":"REMARK","label":"PERFORM - Water supply tanks - Pressure","help_text":"Perform routine service in accordance with Section 5.","sort_order":169,"ref":"4.17","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":160,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 2.4.2.4 (Ten-yearly, Twenty-five-yearly, and Thirty-yearly Inspection)","help_text":"AS1851-2012 Table 2.4.2.4 (Ten-yearly, Twenty-five-yearly, and Thirty-yearly Inspection)","sort_order":173,"ref":null,"estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":180,"active":true,"required":false,"type":"REMARK","label":"TEST - Sprinklers","help_text":"Subject the sample sprinklers to the following tests conducted by a registered testing authority:\n(a) Release temperature.\n(b) Functional test.\n(c) Leak resistance test - Maximum system design pressure test.","sort_order":174,"ref":"4.18","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":181,"active":true,"required":false,"type":"REMARK","label":"REMOVE & TEST - Sprinklers","help_text":"REMOVE and TEST a representative sample of sprinklers at the following intervals:\n(i) Dry pendent sprinklers (representative sample), every 10 years.\n(ii) All other sprinklers (not less than 14 samples), at 25 years, then every 10 years.\n** NOTE: ** For all the above sprinklers, using ISO 6182-6, ISO 6182-7 and ISO 6182-12 component Standards, sample sprinklers should be selected from the range of site environmental conditions to which the system(s) is subjected\n(i.e. office, factory, boiler house environments, etc.).\nShould one or more sprinklers fail any of the above tests, further sampling and testing should be conducted until the results can be considered truly representative. The extent of sprinkler replacement, if any, will be dependent on the results of testing.","sort_order":175,"ref":"4.18","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":177,"active":true,"required":false,"type":"REMARK","label":"CHECK & REPLACE - Multiple jet controller (MJC)","help_text":"At 30 years and every 10 years thereafter:\n(a) Single MJC installed for alarm purposes only or to control a group of distributors, CHECK in situ for evidence of paint loading, corrosion, etc. Replace if necessary.\n(b) Multiple MJC installed for alarm purposes only or to control groups of distributors, REPLACE a representative sample. Subject the sample to the following tests conducted by a registered testing laboratory:\n(i) Leak resistance test.\n(iii) Functional test.\nUse ISO 6182-1.\nNOTE: Should the sample MJC fail any of the above tests, further sampling and testing should be conducted until the results can be considered truly representative.","sort_order":176,"ref":"4.19","estimated_duration":null,"prompt_set":"2012: Fire Sprinkler System: Wet Pipe & Residential","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Hinged and Pivoted Fire Rated Doorset","prompts":[{"id":1087,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.3.1 (SIX-MONTHLY SERVICE)","help_text":"AS1851-2012 Table 12.4.3.1 (SIX-MONTHLY SERVICE)","sort_order":0,"ref":null,"estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1088,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Location","help_text":"INSPECT to determine if the fire-resistant doorset has been modified since the previous routine service.","sort_order":1,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1089,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Marking - Tags and signage","help_text":"(a) INSPECT door leaves and door frames are tagged in accordance with AS 1905.1.\n\n(b) INSPECT to ensure relevant statutory signage has been applied and that the location of the signage is in accordance with regulatory requirements.","sort_order":2,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1090,"active":true,"required":false,"type":"REMARK","label":"CHECK - Clearances in the closed position","help_text":"(a) CHECK that gaps between the edge of the door leaf and the door frame are in accordance with AS 1905.1 or the relevant test report.\n\n(b) CHECK that the gap between the bottom edge of the door leaf and the finished floor level is in accordance with AS 1905.1 or the relevant test report.","sort_order":3,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1091,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Hardware general— Locksets and latches, closers and pivots, hinges and sequence selectors","help_text":"(a) INSPECT all hardware required for suspension, closing and latching is fitted and is a make and model that has been fire-tested for the specific fireresistant door.\n\n(b) INSPECT all hardware is located correctly, securely attached and operational with the correct fittings in accordance with the requirements of AS 1905.1 or the relevant test report.\n\n(c) INSPECT the door leaf and door frame are free from non-approved fittings, fixings or attachments and free from damage caused by relocation of hardware items.","sort_order":4,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1092,"active":true,"required":false,"type":"REMARK","label":"INSPECT & VERIFY - Frictional forces and self-closing and self-latching function","help_text":"(a) VERIFY the opening and closing forces are such that the doors can be easily opened and closed in normal conditions and in fire mode, taking into account any pressurization systems within the building.\n\n(b) INSPECT the doorset is self-closing and selflatching, if appropriate.\n\n(c) Where passage sets or knobs are incorporated, INSPECT that the minimum clearance of 35 mm to the door stop is present.","sort_order":5,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1093,"active":true,"required":false,"type":"REMARK","label":"CHECK & INSPECT - Door closers and pivots","help_text":"(a) CHECK closers are free from oil leakages.\n\n(b) INSPECT the door closer (body and arm) is free from obstruction by walls, fixtures and is operating freely throughout its swing.","sort_order":6,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1094,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Door seals","help_text":"INSPECT any installed door seals are approved for use on the proprietary door type, functioning as intended and are not damaged.","sort_order":7,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1095,"active":true,"required":false,"type":"REMARK","label":"CHECK Damage - Door leaves","help_text":"(a) CHECK doors for any visible delamination, buckling, warping, bowing, twisting or significant damage.\n\n(b) CHECK door edges are in good condition and free from any splitting or damage on all sides.","sort_order":8,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1096,"active":true,"required":false,"type":"REMARK","label":"CHECK - Door frames","help_text":"(a) CHECK door stop dimensions are approved for the proprietary door type and FRL.\n\n(b) CHECK steel door frames are back-filled as required for the proprietary door type and FRL.\n\n(c) CHECK door frame is free from excessive distortion at any point along frame sections.\n\n(d) CHECK to ensure doorframe incorporates a door striker plate.\n\n(e) CHECK condition of frame.\n\n** NOTE: ** See AS 1905.1.","sort_order":9,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1097,"active":true,"required":false,"type":"REMARK","label":"CHECK  - Vision panels (where fitted)","help_text":"(a) CHECK proprietary door type is approved for use of a vision panel.\n\n(b) CHECK to ensure glass is approved for the proprietary door type, in a sound condition and free from cracks.\n\n(c) CHECK to ensure perimeter trim and framing are secure and in sound condition, and all fixing screws are in place and consistent with the fire test approvals for the propriety door type.","sort_order":10,"ref":"1.10","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1098,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire-rated air transfer grilles or fire dampers (where fitted)","help_text":"CHECK proprietary door type is approved for use with the fire-resistant air transfer grille or fire damper and is installed as per manufacturer’s instructions.\n\n** NOTE: ** Where a damper is incorporated in a fire door it is considered to be a fire-rated air transfer grille.","sort_order":11,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1099,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Travel limiting device","help_text":"Where required, VERIFY travel limiting device is installed in accordance with AS 1905.1.","sort_order":12,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1100,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Other features","help_text":"(a) INSPECT the threshold for the door leaf is free from the addition of any combustible covering since installation or previous inspection.\n\n(b) INSPECT kickplates are securely fixed (where fitted).","sort_order":13,"ref":"1.13","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1101,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Meeting stiles for pairs of doors (where fitted)","help_text":"INSPECT to ensure that meeting stile astragals are correct for the proprietary door type, installed as per manufacturer’s instructions, are in good working order and incorporate seals where required.","sort_order":14,"ref":"1.14","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1102,"active":true,"required":false,"type":"REMARK","label":"TEST - Doors held in the open position","help_text":"TEST that doors held in the open position, which require activation of detection system to close, to ensure the door closes satisfactorily upon power failure or detector activation.","sort_order":15,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Fire Rated Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Hinged and Pivoted Smoke Doorset","prompts":[{"id":1103,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.4 (SIX-MONTHLY SERVICE)","help_text":"AS1851-2012 Table 12.4.4 (SIX-MONTHLY SERVICE)","sort_order":0,"ref":null,"estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1104,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Location","help_text":"INSPECT against drawings and all schedules (see Clause 12.2.5) that no smoke doors have been added, removed or modified.","sort_order":1,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1105,"active":true,"required":false,"type":"REMARK","label":"CHECK - Door type and signage","help_text":"(a) CHECK that the smoke door complies to appropriate door design specification, is at least 35 mm thick solid core door or in accordance with the requirement of the building approval .\n\n (b) CHECK that doors are self closing.\n\n (c) INSPECT to ensure relevant statutory signage has been applied and that the location of the signage is in accordance with regulatory requirements.","sort_order":2,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1106,"active":true,"required":false,"type":"REMARK","label":"CHECK - Clearance in the closed position","help_text":"(a) CHECK perimeter - gaps between the door leaf and the door frame are as per door assembly and seal manufacturers recommendations.\n\n (b) CHECK bottom - gaps between the door bottom and threshold are as per door assembly and seal manufacturers recommendations.","sort_order":3,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1107,"active":true,"required":false,"type":"REMARK","label":"CHECK - Smoke seals","help_text":"(a) CHECK smoke seals are suitable for use on the door/assembly type.\n\n (b) CHECK that any seal is in good condition and not damaged.\n\n (c) CHECK perimeter and bottom - perimeter and door bottom seals are correctly fitted in accordance with manufacturer s recommendations and that the sealing elements are in continuous contact with the door/frame/floor.","sort_order":4,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1108,"active":true,"required":false,"type":"REMARK","label":"CHECK - Meeting stiles for pairs of doors","help_text":"(a) CHECK to ensure meeting stile astragals or door meeting edges incorporate smoke seals.\n\n (b) CHECK seals are securely fixed.\n\n (c) CHECK smoke seals do not impede the correct operation of the door.","sort_order":5,"ref":"4.5","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1109,"active":true,"required":false,"type":"REMARK","label":"TEST - Doors held in the open position","help_text":"TEST smoke doors held in the open position, which require activation of detection system to close, to ensure that they close satisfactorily upon power failure or detector activation.","sort_order":6,"ref":"4.6","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1110,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hardware - General","help_text":"(a) CHECK all essential hardware required for suspension, closing and latching (as appropriate) is fitted.\n\n (b) CHECK all hardware is attached and is securely fixed.","sort_order":7,"ref":"4.7","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1111,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Frictional forces and self-closing and self-latching function","help_text":"VERIFY the opening and closing forces are such that the doors can be easily opened and closed in normal conditions and in fire mode, taking into account any pressurization systems within the building.","sort_order":8,"ref":"4.8","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1112,"active":true,"required":false,"type":"REMARK","label":"CHECK - Door closers and pivots","help_text":"(a) CHECK the door closer (body and arm) is free from obstructions by walls or fixtures and is operating freely throughout its swing.\n\n (b) CHECK any closer free from oil leakages.\n\n (c) CHECK screw fixing and mounting arrangements for door closer are secured to the door leaf and door frame.","sort_order":9,"ref":"4.9","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1113,"active":true,"required":false,"type":"REMARK","label":"CHECK - Hinges","help_text":"(a) CHECK hinges are free from any undue wear and tear and are correctly aligned and operating smoothly and freely.\n\n (b) CHECK hinges are securely fixed to the door leaf and frame.","sort_order":10,"ref":"4.10","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1114,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Door leaves","help_text":"(a) INSPECT that door is free from any visible delamination, buckling, warping, bowing, twisting or significant damage.\n\n (b) INSPECT that door edges are in good condition and free from any splitting or damage on all sides.","sort_order":11,"ref":"4.11","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1115,"active":true,"required":false,"type":"REMARK","label":"CHECK - Door frames","help_text":"(a) CHECK door frames are adequately anchored to the walling and restrained against rotational movement about their longitudinal axes.\n\n (b) CHECK door frame is free from excessive distortion at any point along frame sections.","sort_order":12,"ref":"4.12","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1116,"active":true,"required":false,"type":"REMARK","label":"CHECK - Glazing panels","help_text":"(a) CHECK glass to ensure it is in sound condition, and free from cracks.\n\n (b) CHECK perimeter trim and framing to ensure they are secure and in sound condition and that all fixings are in place.\n\n (c) CHECK to ensure clear glass panels are appropriately identified.","sort_order":13,"ref":"4.13","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1117,"active":true,"required":false,"type":"REMARK","label":"CHECK - Kickplates","help_text":"CHECK to ensure kickplates are securely fixed.","sort_order":14,"ref":"4.14","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1118,"active":true,"required":false,"type":"REMARK","label":"CHECK - Sequence selectors","help_text":"CHECK for doors that require correct sequencing to self close and ensure the sequencing device operates correctly.","sort_order":15,"ref":"4.15","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1119,"active":true,"required":false,"type":"REMARK","label":"CHECK - Meeting stiles for pairs of doors","help_text":"CHECK to ensure any essential meeting stile astragals are installed and in good working order and incorporate smoke seals where required.","sort_order":16,"ref":"4.16","estimated_duration":null,"prompt_set":"2012: Hinged and Pivoted Smoke Doorset","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","prompts":[{"id":769,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.4.1 (Annual service)","help_text":"AS1851-2012 Table 6.4.4.1 (Annual service)","sort_order":35,"ref":"1","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":770,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Emergency intercom equipment","help_text":"INSPECT the intercom panel to ensure that it is clearly visible, readily accessible and free from dust and contaminants. Where the panel is obscured by a door, check that the door is correctly labelled.","sort_order":36,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":771,"active":true,"required":false,"type":"REMARK","label":"TEST - Visual indicators","help_text":"TEST the operation of visual indicators and alphanumeric displays.","sort_order":37,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":772,"active":true,"required":false,"type":"REMARK","label":"TEST - Aural indicators","help_text":"TEST the operation of the aural indicators.","sort_order":38,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":773,"active":true,"required":false,"type":"REMARK","label":"TEST - Panel switches and keypads","help_text":"TEST the operation of each required control (e.g. secondary emergency control panels).","sort_order":39,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":774,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Fault","help_text":"SIMULATE a WIP circuit fault condition and confirm the fault condition is indicated at the intercom panel.","sort_order":40,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":775,"active":true,"required":false,"type":"REMARK","label":"TEST - Reset","help_text":"TEST the operation of the reset function.","sort_order":41,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":776,"active":true,"required":false,"type":"REMARK","label":"CHECK - Warden indicator and controls","help_text":"CHECK the operation of each warden indicator and controls.","sort_order":42,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":777,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Warden intercom points (WIPs)","help_text":"INSPECT all WIPs to ensure they are clearly visible and readily accessible. Where the WIP is obscured by a door, check that the door is correctly labelled.","sort_order":43,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":778,"active":true,"required":false,"type":"REMARK","label":"INSPECT - WIP","help_text":"INSPECT all WIPs to ensure there is no mechanical damage.","sort_order":44,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":779,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Stand-alone intercom system (battery enclosure)","help_text":"Where vented batteries are used, INSPECT the battery enclosure for evidence of corrosion.","sort_order":45,"ref":"1.11","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":780,"active":true,"required":false,"type":"REMARK","label":"INITIATE - Outgoing WIPs function test","help_text":"INITIATE a call from each WIP and confirm that each WIP is indicating correctly and that clear communication is possible with the intercom panel operator.","sort_order":46,"ref":"1.12","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":781,"active":true,"required":false,"type":"REMARK","label":"INITIATE - Incoming WIPs function test","help_text":"INITIATE a call to each WIP and phone and confirm that each WIP is indicating correctly and that clear communication is possible with the intercom panel operator.","sort_order":47,"ref":"1.13","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":782,"active":true,"required":false,"type":"REMARK","label":"CHECK - WIPs all call address","help_text":"Select the all-call address function and CHECK that the visual indicator for all WIP phones activate.\n\nCHECK that the address is heard at all WIP phones.\n\n** NOTE: ** This test may be carried out in conjunction with a practice evacuation or ECO training.","sort_order":48,"ref":"1.14","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":783,"active":true,"required":false,"type":"INTEGER","label":"MEASURE & CHECK - Stand-alone intercom system Battery capacity","help_text":"MEASURE system quiescent and alarm currents. Calculate the required battery capacity and\n\nCHECK the installed battery’s nominal capacity is no less than the required capacity. See\n\nAppendix F for calculating the required battery capacity.","sort_order":49,"ref":"1.15","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":784,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - System interface","help_text":"CONDUCT a functional test with any interfaced systems (see Appendix D).","sort_order":50,"ref":"1.16","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":785,"active":true,"required":false,"type":"REMARK","label":"TEST - Stand-alone intercom system (battery condition)","help_text":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","sort_order":51,"ref":"1.17","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":786,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Survey—Change of structure","help_text":"INSPECT building to ensure that no structural changes have occurred to change zones.","sort_order":52,"ref":"1.18","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":787,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Survey—Change of occupancy or use","help_text":"INSPECT the building to ensure that no changes to occupancy have affected the required audibility of the warden call signal at the WIP.","sort_order":53,"ref":"1.19","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":788,"active":true,"required":false,"type":"REMARK","label":"INSPECT - WIP locations","help_text":"INSPECT all evacuation zones to ensure at least one WIP is installed where required.","sort_order":54,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Intercom Systems for Emergency Purposes: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Lay Flat Fire Hose","prompts":[{"id":903,"active":false,"required":false,"type":"HEADER","label":"AS1851-2012 Table 8.4 (Annual service)","help_text":"AS1851-2012 Table 8.4 (Annual service)","sort_order":1,"ref":"1","estimated_duration":null,"prompt_set":"2012: Lay Flat Fire Hose","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":904,"active":false,"required":false,"type":"REMARK","label":"CHECK - Hose jacket","help_text":"CHECK hose when laid out, preferably straight and on a flat clean surface, for obvious defects such as cuts, abrasion, burns or contamination.\n\n** NOTE: ** The hose should be free of dirt, abrasives and contaminants prior to inspection.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Lay Flat Fire Hose","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":905,"active":false,"required":false,"type":"REMARK","label":"INSPECT - Couplings","help_text":"INSPECT hose couplings for damage or distortion to threads, lugs or gaskets.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Lay Flat Fire Hose","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":906,"active":false,"required":false,"type":"REMARK","label":"CHECK - Storage","help_text":"CHECK that the hose is stored as follows:\n\n(a) Its folds do not recur in the same position.\n\n(b) For normal industry use, on bollards or flaked.\n\n(c) Where personnel have the appropriate training, rolled on a bight, with both ends accessible, as an alternative to Action (b) above.\n\n(d) With the service tag visible and readily accessible.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Lay Flat Fire Hose","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":907,"active":false,"required":false,"type":"REMARK","label":"PRESSURE TEST - Periodic pressure test","help_text":"PRESSURE TEST the hose to a hydrostatic pressure test as follows:\n\n(a) LAY the hose out straight on a flat clean surface.\n\n(b) MARK the hose/coupling joints so that any movement between the two will be obvious.\n\n(c) FASTEN the hose ends to limit movement in the event of rupture.\n\n(d) CHARGE the hose with water to a nominal pressure of 500 kPa, taking care to vent all air.\n\n(e) INCREASE the pressure gradually, over a period of not less than 20 s and not more than 2 min, until the required maximum working pressure is reached:\n\n- For Class L hose—1000 kPa\n- For Class M hose—1400 kPa\n- For Class H hose—2100 kPa\n\n(f) SUSTAIN this working pressure for not less than 3 min while examining the hose for defects, leakage, and movement of the couplings.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Lay Flat Fire Hose","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":908,"active":false,"required":false,"type":"REMARK","label":"CLEAN - Cleaning","help_text":"CLEAN dirty hose to avoid dirt, abrasives and contaminants that can seriously damage hoses.\n\n** NOTE: ** Care should be taken not to damage the hose during cleaning. The manufacturer should be consulted in case of doubt.","sort_order":6,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Lay Flat Fire Hose","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":909,"active":false,"required":false,"type":"REMARK","label":"DRY - Drying","help_text":"DRY the wet hose prior to storage unless it is an extruded type.\n\n** NOTE: ** Where the hose is dried by heating:\n\n(a) The hose temperature should not exceed 40°C.\n\n(b) The heating should be accompanied by a natural or forced air draught through the hose.\n\n(c) The hose should not be exposed to the drying temperature for more than 12 h.","sort_order":7,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Lay Flat Fire Hose","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Service Penetrations and Control Joint","prompts":[{"id":1044,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.1.1,2,3 (Annual service)","help_text":"AS1851-2012 Table 12.4.1.1 (Annual service)","sort_order":1,"ref":"1","estimated_duration":null,"prompt_set":"2012: Service Penetrations and Control Joint","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1045,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Service penetration and control joint inspection","help_text":"(a) INSPECT against drawings and associated penetration schedules that no penetrations have been added, removed or modified.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Service Penetrations and Control Joint","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1046,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Service penetration and control joint inspection","help_text":"(b) CHECK that reference drawings and penetration schedules correctly represent the installed penetrations","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Service Penetrations and Control Joint","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1047,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Service penetration and control joint inspection","help_text":"(c) IDENTIFY any penetration and control joints work that is unprotected, damaged or incorrectly installed.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Service Penetrations and Control Joint","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","prompts":[{"id":735,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.3.1 (Monthly service)","help_text":"AS1851-2012 Table 6.4.3.1 (Monthly service)","sort_order":1,"ref":"1","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":736,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Zone Block plan","help_text":"INSPECT zone block plans to ensure that they are securely mounted and legible and supplementary zone drawings, if provided, are available and legible.","sort_order":2,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":737,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Control and indicating equipment","help_text":"INSPECT the warning system panel, and—\n\n(a) ensure that it is clearly visible, readily accessible and free from dust and contaminants;\n\n(b) where a panel is obscured by a door, CHECK that the door is correctly labelled; and\n\n(c) where manual call points use replaceable frangible elements, ENSURE that at least one replacement element and a tool is available for replacing the element where required.","sort_order":3,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":738,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Battery enclosure","help_text":"Where vented batteries are used, INSPECT the battery enclosure for evidence of corrosion.","sort_order":4,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":739,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Emergency warning system test","help_text":"SIMULATE an alarm condition and confirm that the required warning signal(s) operate.\n\nNOTE: It is recommended that the warden intercom system is used by the floor wardens to confirm the operation of the warning signals.","sort_order":5,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":740,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.3.2 (Annual service)","help_text":"AS1851-2012 Table 6.4.3.2 (Annual service)","sort_order":6,"ref":"2","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":741,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service","help_text":"COMPLETE all monthly service activities, as listed in Table 6.4.3.1.","sort_order":7,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":742,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Emergency call points","help_text":"INSPECT all emergency call points for any condition that is likely to adversely affect their operation.","sort_order":8,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":743,"active":true,"required":false,"type":"REMARK","label":"TEST - Emergency call points","help_text":"TEST the operation of each emergency call point.","sort_order":9,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":744,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Visual warning devices (VWDs)","help_text":"Where visual warning devices (VWDs) are used as the alarm-indicating devices, INSPECT all devices for any condition or damage that is likely to adversely affect their operation and ensure that they are clearly and correctly labelled where labelling is required.","sort_order":10,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":745,"active":true,"required":false,"type":"REMARK","label":"TEST - Visual warning devices (VWDs)","help_text":"TEST the operation of each visual warning device.","sort_order":11,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":746,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Other warning devices","help_text":"Where other warning devices are used as alarmindicating devices, INSPECT all devices to ensure that they are in place and ensure that they are clearly and correctly labelled where labelling is required.","sort_order":12,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":747,"active":true,"required":false,"type":"REMARK","label":"TEST - Other warning devices","help_text":"TEST for correct operation.","sort_order":13,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":748,"active":true,"required":false,"type":"REMARK","label":"INSPECT - As-installed drawings","help_text":"INSPECT the as-installed drawings to ensure the plan is legible and current.","sort_order":14,"ref":"2.8","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":749,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Warning system initiation","help_text":"SIMULATE an alarm condition via the fire system with the warning system in automatic mode.","sort_order":15,"ref":"2.9","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":750,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Fault","help_text":"SIMULATE a speaker circuit fault, emergency call point circuit fault and visual warning device circuit fault for each circuit and confirm the fault condition is indicated at the emergency warning panel (EWP), FIP and any corresponding SIP.","sort_order":16,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":751,"active":true,"required":false,"type":"REMARK","label":"TEST - Aural indicators","help_text":"TEST or confirm the operation of the aural indicators as required.","sort_order":17,"ref":"2.11","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":752,"active":true,"required":false,"type":"REMARK","label":"TEST - Panel switches and keypads","help_text":"TEST the operation of each control.","sort_order":18,"ref":"2.12","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":753,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Fault","help_text":"SIMULATE a fault between the fire system and the warning system and confirm the fault condition is indicated at the EWP and the FIP.","sort_order":19,"ref":"2.13","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":754,"active":true,"required":false,"type":"REMARK","label":"TEST - Visual indicators","help_text":"TEST the operation of each visual indicator and alphanumeric displays.","sort_order":20,"ref":"2.14","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":755,"active":true,"required":false,"type":"INTEGER","label":"MEASURE - Nominal battery capacity","help_text":"MEASURE system quiescent and alarm currents.","sort_order":21,"ref":"2.15","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":756,"active":true,"required":false,"type":"REMARK","label":"CALCULATE & CHECK - Nominal battery capacity","help_text":"Calculate the required battery capacity and\n\nCHECK the installed battery’s nominal capacity is no less than the required capacity. See Appendix F for calculating the required battery capacity.","sort_order":22,"ref":"2.15","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":757,"active":true,"required":false,"type":"REMARK","label":"TEST - Ancillary controls","help_text":"TEST the operation of ancillary control functions and ensure that each controlled device can be correctly initiated.","sort_order":23,"ref":"2.16","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":758,"active":true,"required":false,"type":"REMARK","label":"TEST - Audibility test","help_text":"TEST the Emergency warning system and check the signals are distinctly audible in all areas of the building.\n\n** NOTE: ** In order to reduce the disturbance to occupants an acceptable means of conducting this test is to provide an audio signal other than the warning signal at a reduced sound pressure level.","sort_order":24,"ref":"2.17","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":759,"active":true,"required":false,"type":"REMARK","label":"CONFIRM - Override test","help_text":"CONFIRM that the alarm signal overrides nonemergency audible signals.","sort_order":25,"ref":"2.18","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":760,"active":true,"required":false,"type":"REMARK","label":"CONDUCT - Interface and control test","help_text":"CONDUCT a functional system test with other interfaced fire systems (see Appendix D) and CHECK the interface functions as required.","sort_order":26,"ref":"2.19","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":761,"active":true,"required":false,"type":"REMARK","label":"VERIFY & TEST - Batteries","help_text":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","sort_order":27,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":762,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Survey—Change of structure","help_text":"INSPECT all areas of the building to ensure that no structural changes are likely to affect evacuation zones.","sort_order":28,"ref":"2.21","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":763,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Survey—Change of occupancy or use","help_text":"INSPECT all areas of the building to ensure that changes to the occupancy are not likely to affect the required performance of the system.","sort_order":29,"ref":"2.22","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":764,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.3.3 (Five Annual service)","help_text":"AS1851-2012 Table 6.4.3.3 (Five Annual service)","sort_order":30,"ref":"3","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":765,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and Annual Service","help_text":"Complete all monthly and Annual service activities, as listed in Tables 6.4.3.1 and 6.4.3.2.","sort_order":31,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":766,"active":true,"required":false,"type":"REMARK","label":"UNDERTAKE - Speech intelligibility","help_text":"UNDERTAKE tests to ensure intelligibility in all areas of the building where required.","sort_order":32,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":767,"active":true,"required":false,"type":"INTEGER","label":"MEASURE - Sound pressure level","help_text":"MEASURE and record the sound pressure level from at least one reference point for each amplifier used and ensure at each recorded point the measured value is consistent with the reference sound pressure level.","sort_order":33,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":768,"active":true,"required":false,"type":"INTEGER","label":"MEASURE - Emergency warning system speaker circuits","help_text":"MEASURE and record the impedance of each loud speaker circuit and check that it has not changed by more than 15% from the last test nor exceeded the rated output as required for the amplifier.","sort_order":34,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Sound System for Emergency Purposes: Control Panel: CIE Control Panel","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","prompts":[{"id":854,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.1.2 (Monthly service)","help_text":"AS1851-2012 Table 6.4.1.2 (Monthly service)","sort_order":1,"ref":"1","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":855,"active":true,"required":false,"type":"REMARK","label":"INSPECT - External alarm","help_text":"INSPECT the external alarm (bell or strobe light) to ensure it clearly indicates the designated building entry point.\n\nInspect to ensure the external alarm label is legible with the word ‘FIRE’ in characters not less than 25 mm in height.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":856,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Control and indicating equipment (CIE)","help_text":"INSPECT the following as applicable:\n\nFire indicator panel (FIP), sub-indicator panel (SIP), repeater panel, fire brigade panel (FBP), mimic panel, fire fan control panel (FFCP) and—\n\n(a) ensure that they are clearly visible, readily accessible and free from dust and contaminants;\n\n(b) where a panel is obscured by a door, check that the door is correctly labelled.\n\nWhere manual call points use replaceable frangible elements, ENSURE that at least one replacement element and tool are available","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":857,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Battery enclosure","help_text":"Where vented batteries are used, INSPECT the battery enclosure for evidence of corrosion.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":858,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Fire alarm","help_text":"SIMULATE an alarm condition and confirm that all required common or general visual and audible indications operate and the external alarm is activated. Where the system is monitored ensure the alarm has activated the alarm signalling equipment. Where CIE is a subindicator panel, confirm that the alarm condition is indicated at the FIP.","sort_order":5,"ref":"1.4","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":859,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Occupant warning system","help_text":"SIMULATE an alarm and confirm the alarm initiates the occupant warning system including any visual warning devices (VWD).","sort_order":6,"ref":"1.5","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":860,"active":true,"required":false,"type":"REMARK","label":"INITIATE - Isolate/Disable","help_text":"INITIATE an isolate/disable condition at the fire indicator panel and confirm that all required common or general visual and audible indications operate. Where the system is monitored, ensure the isolate is received by the monitoring service provider alarm signalling equipment. Where the panel is an SIP, confirm that the isolate/disable condition is indicated at the FIP as either a fault or isolate/disable.","sort_order":7,"ref":"1.6","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":861,"active":true,"required":false,"type":"REMARK","label":"TEST - Filament visual indicators","help_text":"TEST the operation of each filament type visual indicators.","sort_order":8,"ref":"1.7","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":862,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Zone block plan","help_text":"INSPECT zone block plans to ensure that they are securely mounted and legible and supplementary zone drawings, where required, are available and legible.","sort_order":9,"ref":"1.8","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":863,"active":true,"required":false,"type":"REMARK","label":"‘Text deleted’","help_text":"‘Text deleted’","sort_order":10,"ref":"1.9","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":864,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.1.3 (Six-monthly service)","help_text":"AS1851-2012 Table 6.4.1.3 (Six-monthly service)","sort_order":11,"ref":"2","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":865,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service","help_text":"Complete all monthly service activities, as listed in Table 6.4.1.2.","sort_order":12,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":866,"active":true,"required":false,"type":"REMARK","label":"CHECK - Local control station (LCS)","help_text":"(a) Ensure that they are clearly visible readily accessible and free from dust and contaminants.\n\n(b) Check that the door is correctly labelled.","sort_order":13,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":867,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Visual warning devices","help_text":"INSPECT all visual warning devices, including:\n\n• DO NOT ENTER\n• EVACUATE\n• FIRE ALARM\n• SYSTEM INOPERATIVE\n\nfor any condition or damage that is likely to adversely affect their function.","sort_order":14,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":868,"active":true,"required":false,"type":"REMARK","label":"TEST - Local control station (LCS) discharge inhibit switch","help_text":"TEST the operation of each inhibit or auto/manual switch and confirm that:\n\n(a) It prevents the automatic discharge of suppression system.\n\n(b) Stops and resets the normal system discharge sequence.\n\n(c) Causes the illumination of a visual indicator at the LCS and the system FIP.\n\n(d) Causes an audible indication.\n\n(e) Does not override the operation of the manual discharge switch.","sort_order":15,"ref":"2.4","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":869,"active":true,"required":false,"type":"REMARK","label":"TEST - Local control station (LCS) manual initiate switch","help_text":"TEST the operation of the manual initiate switch and confirm normal system discharge sequence, including fire and evacuation alarms, time delays equipment shutdowns, and that it overrides the LCS discharge inhibit switch.","sort_order":16,"ref":"2.5","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":870,"active":true,"required":false,"type":"REMARK","label":"CONFIRM - System inoperative visual warning device (VWD)","help_text":"CONFIRM the system inoperative VWD operates for:\n\n(a) Operation of a service switch (discharge initiating circuit electrical isolation).\n\n(b) Fault in the discharge actuator circuit.\n\n(c) Operation of a lock-off valve (where fitted).\n\n(d) Operation of a manual inhibit switch (where fitted).\n\n(e) Isolation or fault in any part of the fire detection or control system that prevents the automatic or electrical manual discharge of the suppression system.","sort_order":17,"ref":"2.6","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":871,"active":true,"required":false,"type":"REMARK","label":"TEST - System operation and logic","help_text":"TEST the system logic (e.g. dual detector operation or dependency on more than one alarm) and confirm the operation of—\n\n• VWDs\n• audible alarms\n• directional valve signal/output\n• equipment fire mode signal/output\n• HVAC fire mode signal/output\n• system discharge actuator\n• door and damper release and\n• ancillary controls\n\n** ‘Text deleted’ **","sort_order":18,"ref":"2.7","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":872,"active":true,"required":false,"type":"REMARK","label":"TEST - Actuator circuit faults","help_text":"TEST each supervised actuator circuit to ensure a fault is registered at the FIP.","sort_order":19,"ref":"2.8","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":873,"active":true,"required":false,"type":"REMARK","label":"TEST & CONFIRM - Actuator","help_text":"TEST the function of each actuator and ensure that each actuator operates correctly.\n\nEnsure that each actuator has been mechanically isolated or temporarily removed from the suppressant supply to prevent unintended discharge.\n\nFor non-resettable actuators (e.g. pyrotechnic types) substitute the actuator with a load of equivalent value and CONFIRM the operating current is as required.","sort_order":20,"ref":"2.9","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":874,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 6.4.1.4 (Annual service)","help_text":"AS1851-2012 Table 6.4.1.4 (Annual service)","sort_order":21,"ref":"3","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":875,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and sixmonthly service","help_text":"COMPLETE all monthly and six-monthly service activities, as listed in Table 6.4.1.2 and 6.4.1.3.","sort_order":22,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":876,"active":true,"required":false,"type":"REMARK","label":"CHECK - Manual call points","help_text":"CHECK all manual call points are free of conditions likely to adversely affect their function.","sort_order":23,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":877,"active":true,"required":false,"type":"REMARK","label":"TEST - Manual call points","help_text":"TEST the operation of each manual call point.","sort_order":24,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":878,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Other warning devices","help_text":"Where other warning devices are used as the alarm-indicating devices, INSPECT all devices to ensure that they are in place.","sort_order":25,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":879,"active":true,"required":false,"type":"REMARK","label":"TEST - Panel switches and keypads","help_text":"TEST the operation of each control.","sort_order":26,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":880,"active":true,"required":false,"type":"REMARK","label":"TEST - Visual indicators","help_text":"TEST the operation of each visual indicator and alphanumeric displays.","sort_order":27,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":881,"active":true,"required":false,"type":"REMARK","label":"MEASURE & CHECK - Battery","help_text":"MEASURE system quiescent and maximum alarm currents in accordance with Appendix F. Calculate the required battery capacity and CHECK the nominal capacity of the installed batteries is not less than the calculated capacity.\n\n** ‘Text deleted’ **","sort_order":28,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":882,"active":true,"required":false,"type":"REMARK","label":"TEST - Fire Detectors","help_text":"TEST detectors as specified in Appendix G and confirm correct alarm zone indication. Where the detectors are used as part of special hazards systems 100% of the detectors shall be functionally tested Annual.","sort_order":29,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":883,"active":true,"required":false,"type":"REMARK","label":"TEST - Audibility","help_text":"TEST the occupant warning system and check the signals are distinctly audible in all areas of the building.\n\n** NOTE: ** In order to reduce the disturbance to occupants an acceptable means of conducting this test is to provide an audio signal other than the warning signal at a reduced sound pressure level. Where the FIP is connected to a sound systems and intercom systems for emergency purposes (AS 1670.4) or EWIS (AS 2220.2) test in accordance with Table 6.4.3.2.","sort_order":30,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":884,"active":true,"required":false,"type":"REMARK","label":"MEASURE - Occupant warning system sound pressure level","help_text":"MEASURE and record the sound pressure level from at least one reference point for each amplifier used and ensure at each reference point the measured value is consistent with the required sound pressure level at each reference point.","sort_order":31,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":885,"active":true,"required":false,"type":"REMARK","label":"TEST - Alarm acknowledgement facility","help_text":"TEST not less than 20% of installed alarm acknowledgement facilities in such a manner that over a 5-year period, all facilities are tested. CHECK the alarm acknowledgement facility functions as required.","sort_order":32,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":886,"active":true,"required":false,"type":"REMARK","label":"TEST - Alarm investigation facility","help_text":"TEST the alarm investigation facility if enabled and check it functions as required.","sort_order":33,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":887,"active":true,"required":false,"type":"REMARK","label":"TEST - Batteries condition","help_text":"When the battery has not been replaced in the previous two years, verify the battery condition by carrying out a battery discharge test in accordance with Appendix F.","sort_order":34,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":888,"active":true,"required":false,"type":"REMARK","label":"Smoke alarms and heat alarms","help_text":"Refer to Clause 6.4.2.","sort_order":35,"ref":"3.14","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":889,"active":true,"required":false,"type":"REMARK","label":"INSPECT & REPORT - Service life","help_text":"Inspect detectors, equipment or other items having a defined service life and report where the service life is exceeded or will be exceeded before the next scheduled service.","sort_order":36,"ref":"3.15","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":890,"active":true,"required":false,"type":"REMARK","label":"SURVEY - Protected areas survey","help_text":"SURVEY all areas of the building from floor level and check—\n\n(a) that the fire detection and alarm system has not been altered, damaged or compromised;\n\n(b) detection device and remote indicators are appropriate for the current use;\n\n(c) for any condition that may cause a nuisance alarm or the unintentional operation of a suppression system;\n\n(d) all exposed cabling, conduits, junction boxes and the like for any condition that may impact on the performance of the system and are labelled correctly; and\n\n(e) all CIE to ensure all components are appropriately mounted and secure.","sort_order":37,"ref":"3.17","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":891,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Interfaced system initiation","help_text":"Simulate alarm(s) to verify that each interface transmission path initiates the corresponding interfaced system(s) as required.","sort_order":38,"ref":"3.18","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":892,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table6.4.1.5 (Five Annual service)","help_text":"AS1851-2012 Table6.4.1.5 (Five Annual service)","sort_order":39,"ref":"4","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":893,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly, sixmonthly and Annual service","help_text":"Complete all monthly, six-monthly and Annual service activities, as listed in Tables 6.4.1.2, 6.4.1.3 and 6.4.1.4.","sort_order":40,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":894,"active":true,"required":false,"type":"REMARK","label":"TEST - Supervised circuits","help_text":"TEST each input and output supervised circuit for any condition that prevents the transmission of the required signal and ensure a fault is registered at the FIP.","sort_order":41,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":895,"active":true,"required":false,"type":"REMARK","label":"SIMULATE - Fault","help_text":"SIMULATE a circuit fault condition at the FIP and confirm that all required common or general visual and audible indications operate. Where such faults are monitored, ensure the fault has activated the alarm signalling equipment. Where the panel is an SIP confirm that the fault condition is indicated at the FIP.","sort_order":42,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":896,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Addressable short circuit isolators","help_text":"Apply short circuits as required to verify that the short circuit isolation functions as required.","sort_order":43,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":897,"active":true,"required":false,"type":"REMARK","label":"REDUCE & CONFIRM - Power supply supervision","help_text":"Where the system is monitored, REDUCE the CIE operating voltage to trigger a power supply supervision fault and CONFIRM that it is received by the monitoring service provider. Where the panel is an SIP or a distributed power supply, confirm that the power supply supervision fault condition is indicated at least as a fault at the FIP.","sort_order":44,"ref":"4.5","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":898,"active":true,"required":false,"type":"REMARK","label":"REMOVE - Collective detection circuits","help_text":"For each collective fire detection circuit,\n\nREMOVE the last detector or device on the circuit and confirm that a fault signal is registered at the CIE.","sort_order":45,"ref":"4.6","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":899,"active":true,"required":false,"type":"REMARK","label":"CONDUCT & VERIFY - Interface and control test","help_text":"CONDUCT a functional test with each system’s interface and VERIFY that each interfaced system responds to the signal as required (see Appendix D).","sort_order":46,"ref":"4.7","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":900,"active":true,"required":false,"type":"INTEGER","label":"MEASURE & RECORD - Occupant warning system speaker circuits","help_text":"MEASURE and record the impedance of each loud speaker circuit and check that it has not changed by more than 15% from the last test nor exceeded the rated output as required for the amplifier.","sort_order":47,"ref":"4.8","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":901,"active":true,"required":false,"type":"REMARK","label":"TEST - Monitoring connection","help_text":"Where the system is monitored, TEST that the loss of each of the monitoring links is indicated at the monitored site.","sort_order":48,"ref":"4.9","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":902,"active":true,"required":false,"type":"REMARK","label":"TEST - Alarm verification facility","help_text":"TEST one detector of each type per circuit with alarm verification facility enabled to check that it functions as required.","sort_order":49,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Special Hazard: Local Control Station (SHCIE) (Control Panel)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Vertical and Horizontal Compartment: Barrier (Wall, Floors and Ceiling)","prompts":[{"id":1061,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.1 - Fire Walls (Annual )","help_text":"AS1851-2012 Table 12.4.1 - Fire Walls (Annual )","sort_order":1,"ref":null,"estimated_duration":null,"prompt_set":"2012: Vertical and Horizontal Compartment: Barrier (Wall, Floors and Ceiling)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1062,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Wall types, locations","help_text":"INSPECT against drawings (see Clause 12.2.5) that no fire and/or smoke walls have been added, removed or modified.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Vertical and Horizontal Compartment: Barrier (Wall, Floors and Ceiling)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1063,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Walls, where accessible","help_text":"(a) INSPECT that walls continue up to the next horizontal fire-resistant barrier or to the underside of the roof above.\n\n(b) INSPECT for any damage that will cause loss of fire resistance.","sort_order":3,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Vertical and Horizontal Compartment: Barrier (Wall, Floors and Ceiling)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1064,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.12 - Fire Floors (Annual )","help_text":"AS1851-2012 Table 12.4.12 - Fire Floors (Annual )","sort_order":4,"ref":null,"estimated_duration":null,"prompt_set":"2012: Vertical and Horizontal Compartment: Barrier (Wall, Floors and Ceiling)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1065,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Fire rated floors","help_text":"INSPECT against drawings (see Clause 12.2.5) that no fire-rated floors, including resistance to incipient spread of fire, have been added, removed or modified.","sort_order":5,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Vertical and Horizontal Compartment: Barrier (Wall, Floors and Ceiling)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1066,"active":true,"required":false,"type":"REMARK","label":"INSEPCT - Floors—General","help_text":"INSPECT for any damage that will cause loss of fire resistance.","sort_order":6,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Vertical and Horizontal Compartment: Barrier (Wall, Floors and Ceiling)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1067,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 12.4.3 - Fire Ceilings (Annual )","help_text":"AS1851-2012 Table 12.4.3 - Fire Ceilings (Annual )","sort_order":7,"ref":null,"estimated_duration":null,"prompt_set":"2012: Vertical and Horizontal Compartment: Barrier (Wall, Floors and Ceiling)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":1068,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Ceiling types, locations","help_text":"INSPECT against drawings (see Clause 12.2.5) that no fire-rated ceilings, including resistance to incipient spread of fire, have been added, removed or modified.","sort_order":8,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Vertical and Horizontal Compartment: Barrier (Wall, Floors and Ceiling)","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]},{"name":"2012: Water Storage Tank For Fire Protection","prompts":[{"id":679,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 5.4.1 (Monthly service)","help_text":"AS1851-2012 Table 5.4.1 (Monthly service)","sort_order":1,"ref":"1","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":680,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water level","help_text":"CHECK that the tank is full.","sort_order":2,"ref":"1.1","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":681,"active":true,"required":false,"type":"REMARK","label":"CHECK - Water level indicator","help_text":"CHECK for correct operation and reading of water level indicator.","sort_order":3,"ref":"1.2","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":682,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Water supply pressure tank (where fitted)","help_text":"VERIFY:\n\n(a) Gauge glass indicates the correct water level.\n\n(b) Tank pressure gauge reads within the range nominated.\n\n(c) Air pressure switch operates at specified compressor cut-in and cut-out pressures.\n\n(d) Low tank pressure alarm operates at specified pressure.\n\n(e) Air compressor or gas cylinder supply is operational.","sort_order":4,"ref":"1.3","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":683,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 5.4.2 (Six-monthly service)","help_text":"AS1851-2012 Table 5.4.2 (Six-monthly service)","sort_order":5,"ref":"2","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":684,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly service","help_text":"COMPLETE all monthly service activities, as listed in Table 5.4.1.","sort_order":6,"ref":"2.1","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":685,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Float valve","help_text":"VERIFY the operation of the float valve by exercising the valve.","sort_order":7,"ref":"2.2","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":686,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Level indicator","help_text":"VERIFY all water level indicators (mechanical and electronic) are operating properly by exercising the indicator or mechanism.","sort_order":8,"ref":"2.3","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":687,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 5.4.3 (Annual service)","help_text":"AS1851-2012 Table 5.4.3 (Annual service)","sort_order":9,"ref":"3","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":688,"active":true,"required":false,"type":"REMARK","label":"COMPLETE - Monthly and sixmonthly service","help_text":"COMPLETE all monthly and six-monthly service activities, as listed in Tables 5.4.1 and 5.4.2.","sort_order":10,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":689,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leakage","help_text":"CHECK for water leakage from all joints, flanges and fittings.","sort_order":11,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":690,"active":true,"required":false,"type":"REMARK","label":"CHECK - Loose components","help_text":"CHECK for loose bolts, anchors and fittings throughout the tank.","sort_order":12,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":691,"active":true,"required":false,"type":"REMARK","label":"CHECK - Damage","help_text":"CHECK for any physical damage caused by impact, including scratches and dents.","sort_order":13,"ref":"3.4","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":692,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foundation","help_text":"CHECK for earth subsidence and foundation cracks.","sort_order":14,"ref":"3.5","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":693,"active":true,"required":false,"type":"REMARK","label":"CHECK - Corrosion","help_text":"CHECK for corrosion of all external components and surfaces, and internal components as far as is safe to do so from the top inspection/access hatch.","sort_order":15,"ref":"3.6","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":694,"active":true,"required":false,"type":"REMARK","label":"CHECK - Access hatch","help_text":"CHECK to ensure the access hatch is secure and in satisfactory condition.","sort_order":16,"ref":"3.7","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":695,"active":true,"required":false,"type":"REMARK","label":"CHECK - Ladder","help_text":"CHECK the ladder system is secure and free from corrosion.","sort_order":17,"ref":"3.8","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":696,"active":true,"required":false,"type":"REMARK","label":"CHECK - Roof","help_text":"CHECK the roof structure for:\n\n(a) Stability and security roof sheets are secured.\n\n(b) Adequacy of sealing of penetrations.","sort_order":18,"ref":"3.9","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":697,"active":true,"required":false,"type":"REMARK","label":"CHECK - Vermin","help_text":"CHECK the condition of vermin proofing and adequacy of the positioning.","sort_order":19,"ref":"3.1","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":698,"active":true,"required":false,"type":"REMARK","label":"CHECK - Foreign objects","help_text":"CHECK for internal foreign objects visually through the top inspection/access hatch.","sort_order":20,"ref":"3.11","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":699,"active":true,"required":false,"type":"REMARK","label":"CHECK - Algae","help_text":"CHECK for internal accumulation of algae.","sort_order":21,"ref":"3.12","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":700,"active":true,"required":false,"type":"REMARK","label":"CHECK - Vents","help_text":"CHECK the condition and satisfactory operation of vents and rotary spinners.","sort_order":22,"ref":"3.13","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":701,"active":true,"required":false,"type":"REMARK","label":"CHECK - Accessibility","help_text":"CHECK for adequate means to access the tank.","sort_order":23,"ref":"3.14","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":702,"active":true,"required":false,"type":"REMARK","label":"CHECK - Signs","help_text":"CHECK for satisfactory condition of all signs.","sort_order":24,"ref":"3.15","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":703,"active":true,"required":false,"type":"REMARK","label":"CHECK - Gaskets and seals","help_text":"CHECK the condition of all gaskets and sealants.","sort_order":25,"ref":"3.16","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":704,"active":true,"required":false,"type":"REMARK","label":"CHECK - Vortex inhibitor","help_text":"CHECK the condition of the vortex inhibitor visually from the access hatch if practicable.","sort_order":26,"ref":"3.17","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":705,"active":true,"required":false,"type":"REMARK","label":"LUBRICATE - Level indicator","help_text":"LUBRICATE water level indicator, pulleys and cables.","sort_order":27,"ref":"3.18","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":706,"active":true,"required":false,"type":"REMARK","label":"CHECK - Fire authority hard suction fittings","help_text":"CHECK fittings are compatible with the local fire authority’s hard suction fittings.","sort_order":28,"ref":"3.19","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":707,"active":true,"required":false,"type":"REMARK","label":"DRAIN, CLEAN & REFILL - Only required after the first year of service and then every 10 years","help_text":"DRAIN and CLEAN the tank completely including:\n\n(a) Removing all sludge and debris.\n\n(b) Cleaning all internal surfaces, excluding the roof, with low pressure water spray.\n\n(c) Refilling the tank as soon as practicable.\n\n** NOTES: **\n\n1 A diver or other underwater inspection and cleaning technique may be used in lieu of draining the tank in consultation with the tank manufacturer to satisfy warranty requirements.\n\n2 For water conservation measures when tanks need to be drained, see AS 2304.","sort_order":29,"ref":"3.2","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":708,"active":true,"required":false,"type":"HEADER","label":"TANKS WITH LINERS—(A) ABOVE THE WATERLINE","help_text":"TANKS WITH LINERS—(A) ABOVE THE WATERLINE","sort_order":30,"ref":"3","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":709,"active":true,"required":false,"type":"REMARK","label":"CHECK - Eyelets and other liner fixing systems","help_text":"CHECK eyelets, attachment connectors and other mechanical fixings for wear, detachment or corrosion.","sort_order":31,"ref":"3.21","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":710,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discolouration","help_text":"CHECK to determine the extent of any discolouration to the tank liner and, if significant, contact the liner manufacturer.","sort_order":32,"ref":"3.22","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":711,"active":true,"required":false,"type":"REMARK","label":"CHECK - Shrinkage","help_text":"CHECK for signs of shrinkage and increased liner tension.","sort_order":33,"ref":"3.23","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":712,"active":true,"required":false,"type":"REMARK","label":"CHECK - Liner brittleness","help_text":"CHECK for signs of liner brittleness.","sort_order":34,"ref":"3.24","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":713,"active":true,"required":false,"type":"REMARK","label":"CHECK - Cuts and tears","help_text":"CHECK for signs of cuts and tear.","sort_order":35,"ref":"3.25","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":714,"active":true,"required":false,"type":"REMARK","label":"CHECK - Surface deterioration","help_text":"CHECK for signs of surface deterioration or chalking.","sort_order":36,"ref":"3.26","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":715,"active":true,"required":false,"type":"HEADER","label":"TANKS WITH LINERS—(B) BELOW THE WATERLINE","help_text":"TANKS WITH LINERS—(B) BELOW THE WATERLINE","sort_order":37,"ref":null,"estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":716,"active":true,"required":false,"type":"REMARK","label":"CHECK - Flexibility","help_text":"CHECK for signs of loss of flexibility.","sort_order":38,"ref":"3.27","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":717,"active":true,"required":false,"type":"REMARK","label":"CHECK - Discolouration","help_text":"CHECK to determine the extent of any discolouration to the tank liner.","sort_order":39,"ref":"3.28","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":718,"active":true,"required":false,"type":"REMARK","label":"CHECK - Elongation","help_text":"CHECK for signs of elongation of the liner.","sort_order":40,"ref":"3.29","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":719,"active":true,"required":false,"type":"REMARK","label":"CHECK - Bulging","help_text":"CHECK for signs of the liner bulging out from under the base girder (external).","sort_order":41,"ref":"3.3","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":720,"active":true,"required":false,"type":"REMARK","label":"CHECK - Leaks, cuts and tears","help_text":"CHECK for signs of leaks, cuts and tears of the liner.","sort_order":42,"ref":"3.31","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":721,"active":true,"required":false,"type":"REMARK","label":"DRAIN, CLEAN & REFILL - Only required after the first year of service and then every 10 years","help_text":"DRAIN and CLEAN the tank leaving a minimum of 50 mm of water to prevent liner movement, and—\n\n(a) remove all sludge and debris without using sharp tools or shovels to prevent tearing and puncturing of the liner;\n\n(b) clean all internal surfaces, excluding the roof, with low pressure water spray using appropriate footwear to avoid damage to the tank liner; and\n\n(c) refill the tank as soon as practicable.\n\n** NOTES: **\n\n1 For water conservation measures when tanks need to be drained, see AS 2304.\n\n2 Ensure the liner is in the correct position prior to refilling; this includes the positioning of the neoprene mat (where fitted) under the vortex inhibitor bottom support and strainer.\n\n3 A diver or other underwater inspection and cleaning technique may be used in lieu of draining the tank in consultation with the tank manufacturer to satisfy warranty requirements.","sort_order":43,"ref":"3.32","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":722,"active":true,"required":false,"type":"REMARK","label":"MEASURE - Sludge depth","help_text":"Complete a sludge depth measurement to determine the next period for draining and cleaning the tank.","sort_order":44,"ref":"3.33","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":723,"active":true,"required":false,"type":"REMARK","label":"STUDY - Tank base","help_text":"Undertake a study of the tank base and liner for weak spots due to undermining, noting that founding material needs to be felt solid at all areas. Minor hollow areas are to be underpinned and major hollowing requires a geotechnical investigation and reassessment of the sealing system.","sort_order":45,"ref":"3.34","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":724,"active":true,"required":false,"type":"HEADER","label":"RECTANGULAR PANEL TANKS","help_text":"RECTANGULAR PANEL TANKS","sort_order":46,"ref":null,"estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":725,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Stay support systems","help_text":"Complete a visual inspection of the internal stay support system comprising stay bars, bolts and brackets for the following:\n\n(a) Corrosion at connection points.\n\n(b) Tightness of bolts.\n\n(c) Elongation of bolt holes.\n\n(d) Distortion of panels and connection points.","sort_order":47,"ref":"3.35","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":726,"active":true,"required":false,"type":"HEADER","label":"PRESSURE TANKS","help_text":"PRESSURE TANKS","sort_order":48,"ref":null,"estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":727,"active":true,"required":false,"type":"REMARK","label":"INSPECT & VERIFY - Pressure tanks","help_text":"(a) INSPECT externally for structural integrity, freedom from corrosion, and acceptable condition in accordance with AS/NZS 3788.\n\n(b) VERIFY low water level alarm switch operates at predetermined level","sort_order":49,"ref":"3.36","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":728,"active":true,"required":false,"type":"HEADER","label":"AS1851-2012 Table 5.4.4 (Ten-Annual service)","help_text":"AS1851-2012 Table 5.4.4 (Ten-Annual service)","sort_order":50,"ref":"4","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":729,"active":true,"required":false,"type":"REMARK","label":"VERIFY - Monthly, sixmonthly, Annual service","help_text":"VERIFY completion of all monthly, six-monthly and Annual activities as listed in Tables 5.4.1, 5.4.2 and 5.4.3.","sort_order":51,"ref":"4.1","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":730,"active":true,"required":false,"type":"REMARK","label":"DRAIN, CLEAN & REFILL","help_text":"DRAIN and CLEAN the tank completely including—\n\n(a) REMOVE all sludge and debris.\n\n(b) CLEAN all internal surfaces, excluding the roof, with low pressure water spray.\n\n(c) REFILL the tank as soon as practicable.\n\n** NOTES: **\n\n1 A diver or other underwater inspection and cleaning technique may be used in lieu of draining the tank.\n\n2 For water conservation measures when tanks need to be drained see AS 2304.","sort_order":52,"ref":"4.2","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":731,"active":true,"required":false,"type":"HEADER","label":"TANKS WITH LINERS","help_text":"TANKS WITH LINERS","sort_order":53,"ref":null,"estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":732,"active":true,"required":false,"type":"REMARK","label":"DRAIN, CLEAN & REFILL","help_text":"DRAIN and CLEAN the tank leaving a minimum of 50 mm of water to prevent liner movement, and:\n\n(a) REMOVE all sludge and debris without using sharp tools or shovels to prevent tearing and puncturing of the liner.\n\n(b) CLEAN all internal surfaces, excluding the roof, with low pressure spray using appropriate footwear to avoid damage to the tank liner.\n\n(c) REFILL the tank as soon as practicable.\n\n** NOTES: **\n\n1 For water conservation measures when tanks need to be drained, see AS 2304.\n\n2 Ensure the liner is in the correct position prior to refilling; this includes the positioning of the neoprene mat (where fitted) under the vortex inhibitor bottom support and strainer.\n\n3 A diver or other underwater inspection technique may be used in lieu of draining the tank in consultation with the tank manufacturer (to satisfy warranty requirements).","sort_order":54,"ref":"4.3","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":733,"active":true,"required":false,"type":"HEADER","label":"PRESSURE TANKS","help_text":"PRESSURE TANKS","sort_order":55,"ref":null,"estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null},{"id":734,"active":true,"required":false,"type":"REMARK","label":"INSPECT - Water supply tanks—Pressure","help_text":"Conduct a six-Annual inspection by a qualified pressure vessel inspector.","sort_order":56,"ref":"4.4","estimated_duration":null,"prompt_set":"2012: Water Storage Tank For Fire Protection","remark_types":null,"limit_to_levels":null,"limit_to_variants":null,"config":{},"requirements_summary":null}]}],"counts":{"categories":13,"asset_types":62,"checklist_items":1348,"prompts":1476},"variants":[{"id":"rec03zZuZqCbkHfqL","name":"Concealed Heat Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec04EwpxxWJjqrwA","name":"Concealed Smoke Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0AKLwzRvE3ukz9","name":"Conventional: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0doZ8sgN7WpsTV","name":"Door Holder: Release","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0fAuZYrdyyxLXW","name":"Door Holder: Release Momentary Press","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0kvfPUo6XVzgRf","name":"Fire & Smoke Control System","asset_type_ids":["reclY0pYkUEuWixUW"],"description":null},{"id":"rec0MmgVqJe7WQ528","name":"Door handler: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0neFcsxevIvpfw","name":"Emergency Door Release","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0nWK0qyyiz98RS","name":"Duct probe Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0ojMa9jUkwJ5ee","name":"End of Line Resistor (EOLR)","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0Q4CUHpYDHH2HL","name":"Door Holder","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0QQDDp1tgf5vTl","name":"Door Holder: Electro Magnetic","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0sieNm791QfH05","name":"External Bell","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0u63SXhXa7GGqQ","name":"Fail Safe Device","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0u8JDHkRwwtiWb","name":"Fire Alarm Monitoring","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0uV7RV10KZLJQ9","name":"Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec0ycW2hhDVHCO2H","name":"Full Function Test","asset_type_ids":["reclY0pYkUEuWixUW"],"description":null},{"id":"rec101SzYjljz97Ly","name":"Flame Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec132S0Ouc1PZobY","name":"Air Control Damper","asset_type_ids":["recHD7M5vlcA8Wep9"],"description":null},{"id":"rec14fhqSvPtUWOKP","name":"Flame IR Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec18r6j84NtZDAZR","name":"Outdoor Air Control Damper","asset_type_ids":["recHD7M5vlcA8Wep9"],"description":null},{"id":"rec1bgkiDiKcY7GHP","name":"Heat Detector Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1C3wpGqJsEIq2L","name":"Flame Multiband spectrum Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1E1lDhjwuj8aAc","name":"Flame UV Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1F3KyEjgCy23qh","name":"Gas Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1h21dSCDvDG68A","name":"Heat Digital Linear Wire","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1HLdWNSd7Vp84K","name":"Gas Point Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1m9C2afn17xi89","name":"Heat Fibre Optic Linear Wire","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1MgQLwHyXiNvvG","name":"Recycle Air Control Damper","asset_type_ids":["recHD7M5vlcA8Wep9"],"description":null},{"id":"rec1PMcHEHoIFY5GB","name":"Relief Air Control Damper","asset_type_ids":["recHD7M5vlcA8Wep9"],"description":null},{"id":"rec1QfR9gu9GlfI5n","name":"Graphic User Interface","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1qZcAcoNfbEDfD","name":"Air Control Damper","asset_type_ids":["reckO73o3q9J2ScAK"],"description":null},{"id":"rec1sui1eRC5B4S0T","name":"Heat Point Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1tSJiT3RJs3pbo","name":"Horn","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1ulhz7eiQe7naj","name":"Exhaust Air Control Damper","asset_type_ids":["reckO73o3q9J2ScAK"],"description":null},{"id":"rec1VgT8IJPwx47uo","name":"Heat Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec1X1WNThvn1389Z","name":"Smoke Spill Air Control Damper","asset_type_ids":["recHD7M5vlcA8Wep9"],"description":null},{"id":"rec1xSkOw9AaJ0eJy","name":"Return Air Control Damper","asset_type_ids":["reckO73o3q9J2ScAK"],"description":null},{"id":"rec20h1NMLE0Qo7Nf","name":"Horn: Single","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec20idarawCjThGj","name":"Horn: Twin","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec26rXsljsDQh7G1","name":"Supply Air Control Damper","asset_type_ids":["reckO73o3q9J2ScAK"],"description":null},{"id":"rec284coI9Mw3qnYG","name":"Internal Bell","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2aaZX9HP0BUgob","name":"Fire Rated: Ceiling","asset_type_ids":["recaNgsM0omlzvLsJ"],"description":null},{"id":"rec2AoKfuBYlL8g15","name":"Automatic Heat Vent","asset_type_ids":["rechlq14W977UYLVb"],"description":null},{"id":"rec2bXeKrBBmhdKGO","name":"Mixed Zone: Addressable/Conventional Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2CcfPzYUSpCSI7","name":"Automatic Smoke Vent","asset_type_ids":["rechlq14W977UYLVb"],"description":null},{"id":"rec2CHQowbOXc27T1","name":"Isolator","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2dvsWIafnMcyqX","name":"Module","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2Ec9iVTbFjgUht","name":"Marine Addressable: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2Fjm7U7XR054wr","name":"Marine Conventional: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2h69CXN1v8pDrB","name":"Multisensor Carbon Monoxide & Smoke Point Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2Hl9gcnk2q6UpX","name":"MCP: Indoor","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2iKc5My8vgSvD1","name":"Multisensor Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2IYTREXlPc8rnD","name":"Ceiling Covering","asset_type_ids":["recaNgsM0omlzvLsJ"],"description":null},{"id":"rec2JCPKiZilFHqa3","name":"MCP: Intrinsically Safe","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2mpcclmMAnPeAr","name":"Smoke Ceiling","asset_type_ids":["recaNgsM0omlzvLsJ"],"description":null},{"id":"rec2PYkX7D9qsKGkn","name":"MCP: Red","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2rIFY0WNiWRll4","name":"ECO/EPC Training","asset_type_ids":["rec8OKcWFS01C7S7m"],"description":null},{"id":"rec2sJ1s2aTFuqs3z","name":"Multisensor Heat & Carbon Monoxide Point Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2Skkl1CLpfgIKn","name":"MCP: Weatherproof","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2Uwpv0UhQooLen","name":"MCP: White","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2vHiWKUggLTppT","name":"Emergency Evacuation Procedures","asset_type_ids":["rec8OKcWFS01C7S7m"],"description":null},{"id":"rec2WsLhVw7Wvm0bK","name":"Mimic: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec2zzQksVkucf8QA","name":"Multisensor Heat & Smoke Point Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec31hmojYOb11MZp","name":"Emergency Management Plan","asset_type_ids":["rec8OKcWFS01C7S7m"],"description":null},{"id":"rec35N2N8oKYqe5bu","name":"Networked: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec36vrbXT3vFjuca","name":"Optical Beam Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec3Af1i7kg5PEQkw","name":"Power Supply","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec3B0CWYIJq7tsue","name":"Pressure Switch","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec3D2dfs2lEpSimL","name":"Printer Port","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec3EuG9YGWOgG25u","name":"Radio Alarm","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec3EVA5397P8qqql","name":"Public Announcement Unit PA","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec3fKoKywZhFTeFM","name":"Remote Indicator","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec3gxhXvTxgoOxtU","name":"Fire Equipment Training","asset_type_ids":["rec8OKcWFS01C7S7m"],"description":null},{"id":"rec3iqJF06aSnvx9j","name":"Repeater: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec3PAhjZrPjNLEnl","name":"Emergency Plan","asset_type_ids":["rec8OKcWFS01C7S7m"],"description":null},{"id":"rec3V5q4tthOlmpsI","name":"Evacuation Diagram","asset_type_ids":["rec8OKcWFS01C7S7m"],"description":null},{"id":"rec3veEVRvopwDkZi","name":"Residential: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec3xrMBVf4nCcJ8P","name":"Smoke Concealed Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec3ZtoaeQp4FnCri","name":"Evacuation Exercise","asset_type_ids":["rec8OKcWFS01C7S7m"],"description":null},{"id":"rec41s9msH3ZdVCOX","name":"Smoke Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec44EcrNrh5d9JQs","name":"Smoke Duct Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec48piQgUOA7F3fQ","name":"Lay Flat Fire Hose","asset_type_ids":["recPXdkO0TUFaIxvl"],"description":null},{"id":"rec4aAKcaOr0IDuXc","name":"Speaker: Flush Mount c/w Strobe","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4bdSEgCQOR0uaJ","name":"Non-Percolating: 30 x 19mm","asset_type_ids":["recPXdkO0TUFaIxvl"],"description":null},{"id":"rec4CnGL0QmPQNrXZ","name":"Smoke Optical Linear","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4cPH4tqy4dck70","name":"Speaker: Sounder","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4gBUglX1gfsfyQ","name":"Speaker: Surface Mount","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4iO8SGRUc9vkZt","name":"Speaker: Surface Mount c/w Strobe","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4jPbi5z1SCgSZ9","name":"Non-Percolating: 30 x 38mm","asset_type_ids":["recPXdkO0TUFaIxvl"],"description":null},{"id":"rec4kkIRY5Zge2haa","name":"Sub: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4KMNYWlccK32D6","name":"Smoke Point Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4LYQnuIrmi8hWk","name":"Smoke: Wireless","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4NaMJSH7Z9ASS8","name":"Sounder Base","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4OxdYjoc02sQBq","name":"Speaker","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4qyAEOUoeCUM7C","name":"Switch","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4r2kfB8NxkfXEt","name":"VESDA-E: VEA-040-A00","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4SvQyzCa9cRsnB","name":"Speaker: Flush Mount","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4tGhFIm3Gjj3YU","name":"VESDA-E: VEA-040-A10","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4uf14BAl8SVjBL","name":"VESDA-E: VEP-A00-1P","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4woUemNNKHottW","name":"VESDA-E: VEP-A00-P","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec4ybzY9yxZ09ofm","name":"Non-Percolating: 30 x 65mm","asset_type_ids":["recPXdkO0TUFaIxvl"],"description":null},{"id":"rec50fFJLCTuC39R3","name":"VESDA-E: VES-A00-P","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec50IOLlKNCdl8W9","name":"Non-Percolating: Fire Hose","asset_type_ids":["recPXdkO0TUFaIxvl"],"description":null},{"id":"rec537lbMp2z9h5yK","name":"VESDA-E: VES-A10-P","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec53UZ05sYjicrwv","name":"VESDA-E: VEU-A00","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec567qeIeD78gCsa","name":"Percolating: 30 x 19mm","asset_type_ids":["recPXdkO0TUFaIxvl"],"description":null},{"id":"rec57kGl9lGxbAqCO","name":"VESDA-E: VEU-A10","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec58TwUr3vLpodJF","name":"VESDA: VEP-A10-P","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5BkZJgxZNSdxRr","name":"Percolating: 30 x 38mm","asset_type_ids":["recPXdkO0TUFaIxvl"],"description":null},{"id":"rec5dV4WrzWbGiYHq","name":"VESDA: VLS","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5FBGSQgTfO2RnF","name":"VESDA: VLC Marine","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5gNcrVrT2Cp7Xc","name":"Visual Alarm Device: Ceiling Mounted","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5iGzc0HcKVFNkO","name":"Percolating: Fire Hose:","asset_type_ids":["recPXdkO0TUFaIxvl"],"description":null},{"id":"rec5kwelifq1GKGJO","name":"Visual Alarm Device: Wall Mounted","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5l2yd5Va1oFh4C","name":"Visual Warning Device","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5li0RKRTpKaPtV","name":"Visual Warning Device: Stobe","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5lqAQUhn0Etyk1","name":"Window Closer","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5M5uIh3y3vzcRp","name":"VESDA: VLF-250","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5MMxqmpUTZostq","name":"VESDA: VLF-500","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5MZWJKAg1CHCvs","name":"Percolating: 30 x 65mm","asset_type_ids":["recPXdkO0TUFaIxvl"],"description":null},{"id":"rec5PRxKFnk8PaG6H","name":"VESDA: VLI-880","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5qkcYt7kkB5Q6R","name":"Heater","asset_type_ids":["reci5aqsQ2FmJSdcR"],"description":null},{"id":"rec5s1VpHIeEVIq5a","name":"Electric Heaters: Duct","asset_type_ids":["reci5aqsQ2FmJSdcR"],"description":null},{"id":"rec5skTE4w7yTRbjT","name":"Electric Heaters: Unit Monitored","asset_type_ids":["reci5aqsQ2FmJSdcR"],"description":null},{"id":"rec5t3TbIfaE7lTo3","name":"Xtralis XAS-1","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5U3BhZ3ap4TaYk","name":"VESDA: VLI-885","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5Uuh84nxtpnQCh","name":"VESDA: VLP","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec5vbTLh6k5NXRJW","name":"Xtralis XAS-2","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rec6cIpV1wfl9dWwj","name":"12V 1.3Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec6hteE5MyRUb0C7","name":"12V 150Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec6Oh8Xl7kh3iXHK","name":"12V 100Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec6oX44anC7FYl7X","name":"12V 15Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec6SptmDTdMuUSvj","name":"12V 120Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec6THuUJrYu8P82I","name":"12V 12Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec7bHI78Cw4HnKbt","name":"12V 2.3Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec7F5vBQb5CXWQ7K","name":"12V 18Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec7Fk5OMmggbRSGV","name":"12V 200Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec7l9dXy4i51v0qX","name":"12V 26Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec7VEkEQLUd8ceIY","name":"12V 22Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec7zyQyzC5huYfZh","name":"12V 2.9Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec8q8mFPVkGxLlVR","name":"12V 33Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec8RQjLFJgxdSFun","name":"12V 3.2Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec93huYr9GypclI4","name":"12V 40Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec9fINN7Y2EBIs8S","name":"12V 65Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec9K5OtL2oms3x9P","name":"12V 4Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec9MSPznEKqS4BrY","name":"12V 5.4Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec9oi9l8orrE1PPH","name":"12V 75Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"rec9SZor9YOy7UUPx","name":"12V 55Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"reca0kilujPzvLxQ4","name":"Portable: DCP B(E) 2.3kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"reca17chR00FYMDnN","name":"Portable: DCP B(E) 2.5kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recA2AY18XaGR47eq","name":"12V 7Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"reca5Jaj0utG2wKfR","name":"Portable: DCP B(E) 4.5kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"reca6NoGbXu3Qm7uc","name":"Portable: DCP B(E) 6.0kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recA860lkvqbGjU3s","name":"12V 85Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"reca9oRuzHLNWcZ25","name":"Portable: DCP B(E) 9.0kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recaA0Cj4dWfSTQtZ","name":"Portable: DCP (D) Metal","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recAB70HFr8LGNGQQ","name":"12V 90Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recAd6koio9I4Xe8M","name":"Fire Hose Reel: 100m x 19mm","asset_type_ids":["recQqdPE7BQOJOrqt"],"description":null},{"id":"recAfP6Y7iRk32cPv","name":"Fire Hose Reel: 100m x 25mm","asset_type_ids":["recQqdPE7BQOJOrqt"],"description":null},{"id":"recAGwAnjl3x6JLGt","name":"12V 9Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recaHAdgRm5PNJHrY","name":"Portable: (D) Sodium Chloride 13.5L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recajFLKyRFkAAOVo","name":"Portable: F-500 Encapsulator Agent (Lithium-ion Battery)","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recAjZw0aXrUCpe7W","name":"Fire Hose Reel: 36m x 19mm","asset_type_ids":["recQqdPE7BQOJOrqt"],"description":null},{"id":"recAkbfrjshg0rtiR","name":"6V 1.2Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recAnAUFZo1HpR92S","name":"6V 15Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recAnl7bC62JIO1f7","name":"Fire Hose Reel: 36m x 25mm","asset_type_ids":["recQqdPE7BQOJOrqt"],"description":null},{"id":"recaPV28P9IfABPHg","name":"Portable: (D) Sodium Chloride 18L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recar5kpEcRx36f9d","name":"Portable: Fire Extinguisher","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recat3R3SfZ4n4pXt","name":"Portable: Foam","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recaTNZCivMwZEDVP","name":"Portable: (D) Sodium Chloride 6L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recaU4W389QCoF4SY","name":"Portable: (D) Sodium Chloride 9kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recAxLfGOgUEraaRa","name":"Fire Hose Reel: 50m x 19mm","asset_type_ids":["recQqdPE7BQOJOrqt"],"description":null},{"id":"recb1gOPEYOynYO2X","name":"Portable: Foam (AFFF)","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recb2GxgVuAwMfmFc","name":"Portable: Foam (AFFF) 9.0L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recB2Prd7wh8EvYph","name":"Fire Hose Reel: 50m x 25mm","asset_type_ids":["recQqdPE7BQOJOrqt"],"description":null},{"id":"recb6363n6flTrmwr","name":"Portable: Foam (F3) Fluorine Free","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recB6cuRS2LyqSobQ","name":"6V 3.5Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recB6waJCDSACwt2K","name":"Fire Hose Reel: Fire Hose Reel","asset_type_ids":["recQqdPE7BQOJOrqt"],"description":null},{"id":"recb96GILwABoC4Pe","name":"Portable: Foam Fluorine Free (F3) 9L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recB9cJZvFKTf0RRO","name":"6V 5.4Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recB9hh75tm7M61zQ","name":"6V 7.2Ah Battery","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recBAiaSjZInNJlNW","name":"Fire Hose Reel: Flow Test Point","asset_type_ids":["recQqdPE7BQOJOrqt"],"description":null},{"id":"recBbAtrr7AulWKQq","name":"Amplifier: 200W","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recBC3VQMEqS52e0t","name":"Amplifier: 100W","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recbc7uj0fHpzB51o","name":"Portable: Wet Chemical 2L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recBDaCljf8g4lK3D","name":"Green Wash Down: 36m x 19mm","asset_type_ids":["recQqdPE7BQOJOrqt"],"description":null},{"id":"recBDdeWvuNJHD3J5","name":"20L Foam Pail","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recBer6HmXtfC4fon","name":"Booster: Hydrant","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recBGb89BtEq0qQGZ","name":"Above Ground Hydrant Valve","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recblyY7NpamKoMiS","name":"Portable: Wet Chemical 3L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recBOqTHnABmvUgGI","name":"Amplifier: 150W","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recBpeyL7FsTZxIOF","name":"Booster: Quad head","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recBpmrbhEKgWjVLY","name":"Booster: Single Head","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recbq9ygWcyln0T7C","name":"Portable: Wet Chemical 6L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recBRe6hwEc03Te64","name":"Annubar: Flow Test Point","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recBRjB3Cws9YSXiR","name":"Booster: Dual Head","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recBrZP9GhotUcPda","name":"Amplifier: 20W","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recbS7sVQkTXfaTO1","name":"Portable: Vaporising Liquid","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recbSEVlxOX7vouNt","name":"Portable: Wet Chemical","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recbsoqxc6Urapdbi","name":"Portable: Wet Chemical 7L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recBTnBxISEBTfh2a","name":"Booster: Hex Head","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recBVAqhScuBr0Vb3","name":"Amplifier: 15W","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recBwwwcoeSX8TEm6","name":"Amplifier: 250W","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recBXn4lMfA4jsCQS","name":"Co2 Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recbyhzo9kVRsyMX0","name":"Portable: Wet Chemical 9L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recbzNq6wNddiwutQ","name":"9 Litre Cold Fire Extinguisher","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recc0O6OR3k58dLak","name":"9 Litre Cold Fire Fire Extinguisher","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recC1KRtEK5IZgw1c","name":"Booster: Sprinkler","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recc3mHiWUtqxN9sY","name":"Portable: Air/Water","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recCaCF4UA0F3lJKP","name":"Foam Proportioner","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"reccArtse2CSNg94Q","name":"Portable: Air/Water 6.0L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recCBDe5xlWUiLUri","name":"Amplifier: 25W","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recCbFOhnVhC3ciXD","name":"Hydrant System: Block Plan","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recCdyMGxopqw4d2R","name":"Emergency Intercom System (EIS)","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"reccgqyQGm39Kl9vs","name":"Portable: CO2 (E)","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recchL0U7MyvWy5MC","name":"Portable: CO2 (E) 2.0kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recChs4SXVVucWEI9","name":"MCP: Indoor","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"reccIG4Y68X0WgCGa","name":"Portable: Air/Water 9.0L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"reccixyBrxWfggp8S","name":"Portable: CO2 (E) 2.5kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recCJDsw3VTmH23XB","name":"Booster: Suction Point","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recCk1wjTOpbR9AmI","name":"MCP: Intrinsically Safe","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recCkt6AH12Ouxn9M","name":"Hydrant System: Flow Test Point","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recCL2qO5DFCaqT2J","name":"Canon: Water","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recCMk4Z5FabdIEWq","name":"Foam Applicator","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recCnMuBDXXdzTB7q","name":"MCP: Weatherproof","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"reccq5rlRXyzczTXJ","name":"Portable: CO2 (E) 3.5kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recCtsm76HKw3g3rn","name":"Isolation: Ball Valve","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"reccU6V6uPUaB9Smy","name":"Portable: Air/Water 9.0L Additive","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recCWshCHJFXmcMw6","name":"Foam Cannon","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recCwV2p5Agniut3k","name":"Sounder: Bell","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recczw4smC3JSCYvr","name":"Portable: CO2 (E) 5.0kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recd3BZo8r3XIQkRH","name":"Portable: DCP AB(E)","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recd6iiQUSQFoqy92","name":"Portable: DCP AB(E) 1.0kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recdaP7cc3vSDWf23","name":"Portable: DCP AB(E) 4.5kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recDh1bcgahXMOld8","name":"Landing Valve: Below Ground","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recdHl4wo9yo9TUg6","name":"Portable: DCP AB(E) 1.5kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recdhZFhAZ0xlyXl4","name":"Portable: DCP AB(E) 6.0kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recDiM3AHBuz0MR6v","name":"Sounder: Horn","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recDMy6lppJEavF4i","name":"Isolation: Butterfly Valve","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recDP4dnLaaxQFQAq","name":"Isolation: Double Check Valve","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recdPaNl21qkMACuu","name":"Portable: DCP AB(E) 2.0kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recDPGwuZWqIeA8kg","name":"Isolation: Gate Valve","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recdpQ2W3x4Cs4HSp","name":"Portable: DCP AB(E) 9.0kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recdQcSx48GHZEA18","name":"Portable: DCP AB(E) 2.3kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recDqezYNjnJsvyL8","name":"Sounder: Speaker c/w Strobe","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recdqLuCDsz9IELgr","name":"Portable: DCP B(E)","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recDqUiFHCewZkYaP","name":"Sounder: Speaker","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recdTW4BNcWis5qZC","name":"Portable: DCP AB(E) 2.5kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recduylnWrSSljHVz","name":"Portable: DCP B(E) 1.0kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recDvmFPJHBn9Ioqu","name":"Sounder: Speaker Flush Mount","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recDwyoVKGOz1kI0a","name":"Landing Valve: External","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recdxW33SWsjLQirx","name":"Portable: DCP B(E) 1.5kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recDYd87KRWStmjDx","name":"Landing Valve: Above Ground","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recdzjcvGPtlO1uIH","name":"Portable: DCP B(E) 2.0kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"rece0zW4IdFMPCiew","name":"Portable: DCP B(E) 2.3kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"rece11DPj2Arb1qyG","name":"Portable: DCP B(E) 2.5kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recE14zehvicOOL63","name":"Sounder: Speaker Flush Mount c/w Strobe","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recE4OrG8KHTYidWy","name":"Landing Valve: In Ground","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"rece5aUoC85ocZ0fl","name":"Portable: DCP B(E) 4.5kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"rece61adpIA5gtBqQ","name":"Portable: DCP B(E) 6.0kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recE8ubeLCmPHfbry","name":"Landing Valve: Internal","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recE9RrIVIDhh1PfT","name":"Riser Main: Dry","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"rece9zXV3uQ5rVEUi","name":"Portable: DCP B(E) 9.0kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"receaGwSTmdBdCzDl","name":"Portable: (D) Sodium Chloride 6L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recEAQECcmSrTXLq5","name":"Riser Main: Wet","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recEBWhF77QXCLd3W","name":"Sprinkler System: Block Plan","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recEcsTGFWS15HISm","name":"Fire Hydrant System","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recECXbZCDaJd5LEP","name":"Sounder: Speaker Surface Mount","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"reced7J5tQ6JEvd7X","name":"Portable: (D) Sodium Chloride 9kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"receeyEjC3PgeFfgB","name":"Portable: F-500 Encapsulator Agent (Lithium-ion Battery)","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recEh5t0lnHqo6Sqn","name":"Calibrated Gauge","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recEHirzEdofamEo9","name":"Sprinkler System: Flow Test Point","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"receikliJqLjJzd3w","name":"Portable: Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recEiwyOmMhej228f","name":"Fire Hydrant Single","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"receJjhrm8z5EAAjP","name":"Portable: DCP (D) Metal","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recekO0nesTiZMUSm","name":"Portable: Foam","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recEl4oLiximWNrP1","name":"Fire Hydrant - Dual","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recEM8f5olEaGDzEX","name":"Standpipe: Dual Head","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recENBwQuc2SiCzXZ","name":"Standpipe: Single Head","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recenfoO2LtWztf4M","name":"Portable: Foam (AFFF)","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recEOVbbxeuj7lGqL","name":"Gate Valve","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recep1aQmr4WIJPf0","name":"Portable: Foam (AFFF) 9.0L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recEqLbpyYavzYR7p","name":"Stand-Alone Emergency Intercom System (EIS)","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"receR3pGkdrH8HFmc","name":"Portable: (D) Sodium Chloride 13.5L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recErce0A20w5I9lk","name":"Visual Warning: Device","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"reces0u4T9pfCsK5R","name":"Portable: Foam (F3) Fluorine Free","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recEsMXvmKpMzDCua","name":"Hydrant Flow Meter","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"receU5fhGBnKzVRnL","name":"Portable: (D) Sodium Chloride 18L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recevl8HkfHGaWxTI","name":"Portable: Foam Fluorine Free (F3) 9L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recEvmNEW5AGmAihN","name":"Visual Warning: Stobe","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recexFDUm83QPTo0w","name":"Portable: Vaporising Liquid","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recEXgfBMcTz40lNu","name":"Isolation Valve","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recEyf22dvmEneA3y","name":"Sluice Valve","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"receyflcrygC6VA5N","name":"Portable: Wet Chemical","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recEYonDGLAvSoHAs","name":"Sounder: Speaker Surface Mount c/w Strobe","asset_type_ids":["rec25eomX5uBrivZP"],"description":null},{"id":"recEYRY8fR5NaiB77","name":"Butterfly Valve","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recF3ySd2mxf5WXrs","name":"Calibrated Meter","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recF4CefMk0ZHvmgT","name":"Fire Hydrant - Storz (no cap/chain)","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recf5dBmZ31M16pp9","name":"Portable: Wet Chemical 2L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recF90CffzqeHbmOZ","name":"OS&Y Gate Valve","asset_type_ids":["recKv879KGEvHpA2l"],"description":null},{"id":"recfByD4PCI8Diw7F","name":"Portable: Wet Chemical 3L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recFCvIZy2zZqi7ej","name":"Fire Isolated Exit Pressurisation System","asset_type_ids":["recCNF62ZNJDZKWQE"],"description":null},{"id":"recfdaVzpry87CrVB","name":"Wheeled: AFFF Foam 50L Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recFgkQVqtLwkKPQx","name":"12V 100Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recfHmw8L7aCMCxow","name":"Portable: Wet Chemical 6L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recfijLS3SRKUHNHq","name":"Wheeled: AFFF Foam 70L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recfjTlp6CTo44O4c","name":"Wheeled: AFFF Foam 70L Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recFk8nV3r91EDHnJ","name":"12V 120Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recfKcGcBdXUTNvka","name":"Portable: Wet Chemical 7L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recFkVkKmDisg4cfM","name":"12V 150Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recFptVEFRkIFXVr2","name":"12V 200Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recFqX4ittLfG6w2S","name":"12V 22Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recFr0PgpkGq6e3ta","name":"12V 26Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recFrycqAmhxuJ6SX","name":"12V 33Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recfs2B0xz6uCRXKj","name":"Wheeled: AFFF Foam 90L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recfT8ARsoZMtraBe","name":"Portable: Wet Chemical 9L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recFtvL697HFw1DIT","name":"12V 40Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recFVejknMkh1mJa8","name":"Stair Pressurisation Fan","asset_type_ids":["recCNF62ZNJDZKWQE"],"description":null},{"id":"recfvIUwPrWmyv9Mq","name":"Exhaust Air Fan","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"recFvQMD3MA4ZPgRs","name":"12V 55Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recfWFxyq6mlmg1MP","name":"Car Park Exhaust Fan","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"recfX6lz0tZ7qVtro","name":"Wheeled: AFFF Foam 30L Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recfXrvk8kjjEcOTy","name":"Wheeled: AFFF Foam 50L","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recfyLTcmGqtTY8Vv","name":"Fan","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"recG3sGkWQbAP2M8Y","name":"12V 65Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recg4354gUnf8RC60","name":"Fire Fan Control Panel (FFCP)","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"recG4fduM2dKO359d","name":"12V 75Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recG5DRqk8PaJVyeX","name":"12V 85Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recg5V61XzoK6gSVG","name":"Wheeled: AFFF Foam 90L Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recg8LHF4hz3E4eXi","name":"Wheeled: Clean Agent","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recG9rFKg2rrYsu9O","name":"12V 90Ah Battery","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recgB6dvyI2l3V5tc","name":"Wheeled: Clean Agent Halon 1211","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recGDrG0ukUnYgk6m","name":"Control Panel","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recGE2FnTJBZlKC8k","name":"Control Panel: Dual Control","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recGeph1dqri5oP9g","name":"Diesel Pump: Combined System","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recgeUQRvShEQVjPR","name":"Wheeled: CO2 10kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recgfv3bjHtLRP5N3","name":"Wheeled: CO2 20kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recggyZl7T98xpFIr","name":"Kitchen Exhaust","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"recgHuQA41NIPXLvQ","name":"Wheeled: Clean Agent Halotron","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recGhwLjgBxK94tBv","name":"Diesel Pump: Hydrant System","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recGiwsi0R4kPa4q4","name":"Diesel Pump: Sprinkler System","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recGJi2UaOzPTFboK","name":"Control Panel: Monitored","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recGk7LqXHOH4lyBD","name":"Electric Pump","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recGKaPcHLlbP6FRB","name":"Control Panel: Networked","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recGKqLMEw1t7JPZ1","name":"Diesel Pump","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recGLnUEPpb0EhkZZ","name":"Diesel Pump","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recGlyFu81ioepxPA","name":"Electric Pump","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recgmRaNSksCsNmAH","name":"Wheeled: CO2 22kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recgom2JRsvieFju9","name":"Wheeled: CO2 30kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recgRUIq3scQrdNvU","name":"Wheeled: Clean Agent Novec 1230","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recGs917vrIC1TKte","name":"Electric Pump: Combined System","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recGtapgxFtcXWi6x","name":"Electric Pump: Hydrant System","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recgtUn6uBXAEopBA","name":"Kitchen Exhaust Fan","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"recgUHgE07sxPjBcc","name":"Wheeled: CO2","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recgvcIlqTE7FG5oL","name":"Wheeled: CO2 45kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recGvWksoqFMbsZzE","name":"Electric Pump: Sprinkler System","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recH1Pea9ip5NZkck","name":"Fuel Tank","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"rech5qP3iu8clWLRM","name":"Wheeled: CO2 50kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"rechAjdnamrUASw89","name":"Lobby Relief Fan","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"recHDYf0sgb315pns","name":"Fuel Tank: Above Ground","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"rechGmbR4TfWmf4m5","name":"Wheeled: DCP ABE","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recHhDXsBNPJuu68x","name":"Fire Rated: Sliding: Single Glaze","asset_type_ids":["rec21IZiCY2ATu9Xb"],"description":null},{"id":"recHhVT92d96ZLkI1","name":"Fire Rated: Sliding: Triple Glaze","asset_type_ids":["rec21IZiCY2ATu9Xb"],"description":null},{"id":"recHi4agsRWIDkh8T","name":"Booster: Deluge and Water Spray System","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"rechKD4Madr1jyutU","name":"Wheeled: DCP ABE 20kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recHkEmXBXz2hxNeb","name":"Deluge Sprinkler System: Manifold","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"rechKhwGUyHezEVA5","name":"Wheeled: DCP ABE 30kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recHLAcZz1nF4fHPT","name":"Fuel Tank: Below Ground","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"rechM2YLreQJKMgTz","name":"Wheeled: DCP ABE 50kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"rechmbwRCjSUpqhCa","name":"Wheeled: DCP BE","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recHN7stPOkHYgCwg","name":"Residential Sprinkler Pumpset","asset_type_ids":["recer7HJaBbq7yIqD"],"description":null},{"id":"recHnctpvMnIGTLtv","name":"Deluge Sprinkler System: Valve","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"rechNX6kSaMUKS4Zd","name":"Wheeled: DCP ABE 70kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recho8xyNuCLs1mOj","name":"Motor","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"rechoLXduAeoWeDNH","name":"Return Air Control","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"rechp7s4Pl3SW2BKN","name":"Wheeled: DCP BE 20kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recHPP1d0GHROnaGp","name":"Fire Rated: External Cladding","asset_type_ids":["rec21IZiCY2ATu9Xb"],"description":null},{"id":"recHPWhpcekRIi7ki","name":"Fire Rated: Horizontal Shutter","asset_type_ids":["rec21IZiCY2ATu9Xb"],"description":null},{"id":"recHR9Z0gz5FO0r9r","name":"Fire Rated: Internal Shutter","asset_type_ids":["rec21IZiCY2ATu9Xb"],"description":null},{"id":"recHrmY0pgxA5wM1l","name":"Deluge & Water Spray System: Valve","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recHSbOkOwR1Vj4FT","name":"Fire Rated: Lateral Shutter","asset_type_ids":["rec21IZiCY2ATu9Xb"],"description":null},{"id":"rechsOxMsLUefd6eM","name":"Wheeled: DCP BE 30kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"rechulJ6ViqUOuBGG","name":"Smoke Control","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"rechURiB0bzvcG1yA","name":"Wheeled: DCP ABE 90kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recHV6FfBrvNLRLqS","name":"Fire Rated: Mini Shutter","asset_type_ids":["rec21IZiCY2ATu9Xb"],"description":null},{"id":"recHvtHMihELmW5qj","name":"Drencher Wall Wetting System: Manifold","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recHYdXjEDPgQdNfi","name":"Fire Rated: Shutter","asset_type_ids":["rec21IZiCY2ATu9Xb"],"description":null},{"id":"recHYyLrGCXzQk5zI","name":"Fire Rated: Sliding: Double Glaze","asset_type_ids":["rec21IZiCY2ATu9Xb"],"description":null},{"id":"recI1nRUGwbqtJkwK","name":"Drencher Wall Wetting System: Valve","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recI5Z4TVBeuFk60C","name":"Drencher Window Wetter System: Manifold","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recI6Yl5wq2SJS4dI","name":"Drencher Window Wetter System: Valve","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"reci9hDyBebKk6ZAE","name":"Smoke Exhaust Fan","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"recI9OBtn6Zfw1otT","name":"FM Spray Nozzle: Open Cornice Nozzle","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"reciA8o9aA50gF7E3","name":"Smoke Exhaust System","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"reciaqYEvyH6aemVq","name":"Wheeled: F3 Foam 20L Fluorine Free","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recIbnSlKCepf5q8a","name":"Light Hazard System: Valve","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recicPCsGEzSMDLyl","name":"Wheeled: F3 Foam 20L (Fluorine Free) Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"reciCqWopqWt0qaSA","name":"Smoke Spill Fan","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"reciEN08fI2Ikou5n","name":"Wheeled: DCP BE 50kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recIeQ4bw0S8apGnA","name":"Model B Spray Nozzle: Open Window Nozzle","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"reciGliASbhIRdrZE","name":"Supply Air Fan","asset_type_ids":["recXsIA8l4pxQp2Bb"],"description":null},{"id":"recIhFbtgh7UtwqAs","name":"Model TNL280 Pendent Spray Nozzle","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"reciiqGY8riRCwcgM","name":"Wheeled: F3 Foam 30L Fluorine Free","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recijoZKekRC7D7PQ","name":"Wheeled: F3 Foam 30L (Fluorine Free) Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recIkl0JPgK0ybZw8","name":"MV Spray Nozzle: 110 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"reciKy7ewwzKlJAyf","name":"Wheeled: DCP BE 70kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recil7siYXCSopYGy","name":"Wheeled: F3 Foam 50L Fluorine Free","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recIM0jnm1hNFhs7e","name":"FM Spray Nozzles: Open Window Nozzle","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"reciMHUDbiOxgIWsX","name":"Wheeled: DCP BE 90kg","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recIo1n9ucTcHYHtY","name":"MV Spray Nozzle: 125 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recIPGKjroBjo1STS","name":"High Hazard System: Valve","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"reciPQoLbeeK98euq","name":"Wheeled: Dry Chemical powder (Copper)","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recirKh99q4WvQnlK","name":"Curtain","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"recirm7XPBlVowmOf","name":"Wheeled: F3 Foam 70L Fluorine Free","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recirURS8wAyUi9BK","name":"Wheeled: F3 Foam 50L (Fluorine Free) Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recisOFFaB1V0QxaE","name":"Wheeled: F3 Foam 70L (Fluorine Free) Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"reciT1Nz5jO770oQa","name":"Wheeled: Dry Chemical Powder (Purple K)","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recIuw4QZjXGbCsqx","name":"MV Spray Nozzle: 140 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"reciVNbaqZZmOCaM6","name":"Wheeled: Dry Chemical powder (Sodium Chloride)","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recIWhZTcpeFMhFOW","name":"HV Spray Nozzle: 115 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recIWi75YLeZCC2IK","name":"HV Spray Nozzle: 120 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recIwjGMuaz5D5bcD","name":"MV Spray Nozzle: 160 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recIWWLjyOIIVJHmZ","name":"HV Spray Nozzle","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recIX2rnAisav7X5E","name":"HV Spray Nozzle: 75 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recix3F159Uh38Ksn","name":"Wheeled: F3 Foam 90L Fluorine Free","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recIXNMyH8zKqw37S","name":"HV Spray Nozzle: 80 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recIy5SV2OoC5Pw20","name":"MV Spray Nozzle: 180 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"reciybx5zLnlBazZR","name":"Wheeled: F3 Foam 90L (Fluorine Free) Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recIZ1QBg58EQL0Au","name":"HV Spray Nozzle: 90 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recizlzkXrC0Wpdm6","name":"Wheeled: F3 Foam Fluorine Free","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recJ0fgXMWrhfDG5x","name":"MV Spray Nozzle: 65 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recJ19wDJPsAs0P7X","name":"MV Spray Nozzle: 80 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recj27cnS5SwtLEvc","name":"Wheeled: Wheeled Fire Extinguisher","asset_type_ids":["recNDWLONf131V1bp"],"description":null},{"id":"recJ2kVB8COzXxWYu","name":"MV Spray Nozzle: 95 deg","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recj3wslPEdmF0tdL","name":"Wheeled: AFFF Foam","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recj5B2gaR5ocNa5f","name":"Wheeled: AFFF Foam","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recj5gACZmnwP7Hee","name":"Wheeled: AFFF (Foam)","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recJ5sNLM7OIiRSII","name":"Open Sprinkler: F1-56 Pendent","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recJ9qvcwUqJsadIx","name":"Open Sprinkler: F1-56 Upright","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recJaQQ5BxZoadz0g","name":"Wall Wetter: Standard Response Ordinary Temperature","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recjaXfZQzQNgVvmV","name":"Wheeled: AFFF (Foam) 70L Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recJAXxi4cUzAOff9","name":"Open Sprinkler: GFR VELO ECOH Pendent","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recJBOA8gA8corUjU","name":"Open Sprinkler: GFR VELO ECOH Upright","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recjBXaYhhWcqLkn3","name":"Wheeled: AFFF (Foam)","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recJCcBVDmtC4oUFI","name":"Ordinary Hazard System: Valve","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recjDbjoKxBUKRzke","name":"Wheeled: AFFF Foam 20L","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recjEhyDCqUCD1llp","name":"Wheeled: AFFF Foam 20L","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recJfHwiAn0bFLt4v","name":"Water Spray System: Manifold","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recJGMUoLA8bXvhCx","name":"Sprinkler Head: Deluge and Water Spray","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recJHxVwCwJqtZNuP","name":"Sprinkler Head: Drencher (Wall Wetting)","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recjJ0m3ZTRHE4lJM","name":"Wheeled: AFFF (Foam) 20L Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recJJMM1LC4Neet1E","name":"Wall Wetter: Quick Response High Temperature","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recjJYBpKaWFSYkQE","name":"Wheeled: AFFF Foam 20L Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recJLtZbV8XhzO63G","name":"Wall Wetter: Quick Response Intermediate Temperature","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recJlX3JBqwC2t5KA","name":"Water Spray System: Valve","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recjMAgj2FICSQZmQ","name":"Wheeled: AFFF Foam 30L","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recjN0wp1iEsgP1OG","name":"Wheeled: AFFF Foam 30L","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recjntI5sl4tK9ccd","name":"Wheeled: AFFF Foam 90L","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recJNXI22M8UVUitR","name":"Wall Wetter: Quick Response Ordinary Temperature","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recjO9lAKpNcKIuzV","name":"Wheeled: AFFF (Foam) 30L Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recjOL88rpkTJtNH3","name":"Fire Curtain","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"recjQv98129mcs5xq","name":"Fire Horizontal","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"recJR4xyfZzvlMHpV","name":"Wall Wetter: Standard Response High Temperature","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recjT83BDHcQJqnnQ","name":"Wheeled: AFFF Foam 50L","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recjTEV40NMEy0OF4","name":"Wheeled: AFFF (Foam) 50L Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recJu2sk0zSunK7Ar","name":"Booster: Dry Pipe System","asset_type_ids":["recw9mfMuplsVem7l"],"description":null},{"id":"recjvgb79Lhn3Xe9U","name":"Fire Vertical","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"recjwCYimVNHWtrCd","name":"Wheeled: AFFF (Foam) 90L Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recJXmPzAK63PPzO8","name":"Wall Wetter: Standard Response Intermediate Temperature","asset_type_ids":["recH9hrBvqyEZ98HW"],"description":null},{"id":"recjYBVjZtDR0Mo8H","name":"Wheeled: AFFF Foam 70L","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recjyQaV5H4lDm074","name":"Wheeled: Clean Agent","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recJyt7RE57rbUmw8","name":"Dry-Pipe System: Valve","asset_type_ids":["recw9mfMuplsVem7l"],"description":null},{"id":"recJyYMN0qfAnJZlN","name":"Dry-Pipe System: Tail-End","asset_type_ids":["recw9mfMuplsVem7l"],"description":null},{"id":"reck4U7N0YooGJcUw","name":"Wheeled: Clean Agent Halon 1211","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recK95qdkOwbe9IGK","name":"High Hazard System: Valve","asset_type_ids":["recw9mfMuplsVem7l"],"description":null},{"id":"reckB2Ct07g83ZvmY","name":"Wheeled: Clean Agent Halotron","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recKbMn4sOge4QlxR","name":"In Rack System: Valve","asset_type_ids":["recvUb7ks9fiR4fCf"],"description":null},{"id":"recKE6fxwgp1mT0s1","name":"In Rack System: Valve","asset_type_ids":["recw9mfMuplsVem7l"],"description":null},{"id":"reckFa9YLK87t6DUR","name":"Wheeled: Clean Agent Novec 1230","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reckfEyY2Lh11vPRO","name":"Fire Attenuation Screen","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"reckFnsgDfGdHs3eR","name":"Smoke","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"reckhdO2B3lCy7ri1","name":"Wheeled: DCP ABE","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recKhlvlGmXBIgoZ2","name":"Light Hazard System: Valve","asset_type_ids":["recvUb7ks9fiR4fCf"],"description":null},{"id":"reckIoNy325iWELm3","name":"Wheeled: CO2","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reckjrlyksRX42pzN","name":"Louver Screen","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"reckkMLqWL9UbRsf8","name":"Opening Screen","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"reckkqvy3Z1UUGMxB","name":"Wheeled: DCP ABE 20kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reckKXyxt7xwW9FhW","name":"Wheeled: CO2 10kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recKm41eSgKXHzmtv","name":"Ordinary Hazard System: Valve","asset_type_ids":["recvUb7ks9fiR4fCf"],"description":null},{"id":"reckMidS4IGG2ZLa8","name":"Wheeled: CO2 20kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reckmJgXzVYSIMQI0","name":"Wheeled: DCP ABE 30kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reckN8f6rlbgN7IeX","name":"Smoke Curtain","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"reckOgG22zA3jEfoG","name":"Smoke Horizontal","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"recKOPOeQIqTXpl6g","name":"Light Hazard System: Valve","asset_type_ids":["recw9mfMuplsVem7l"],"description":null},{"id":"reckOWgnFH93077KQ","name":"Wheeled: CO2 22kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recKrflhozE1GTSak","name":"Pre-Action: Tail-End","asset_type_ids":["recvUb7ks9fiR4fCf"],"description":null},{"id":"reckRl6CEWGUCWNek","name":"Smoke Vertical","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"recKS1YCbQX4KUGC5","name":"Ordinary Hazard System: Valve","asset_type_ids":["recw9mfMuplsVem7l"],"description":null},{"id":"recKSgkDD4kv1XPfm","name":"Sprinkler Head: Dry Pipe","asset_type_ids":["recw9mfMuplsVem7l"],"description":null},{"id":"recKT94usv93A4yII","name":"Booster: Pre-Action System","asset_type_ids":["recvUb7ks9fiR4fCf"],"description":null},{"id":"recKTaYjoKZJJZ9Az","name":"High Hazard System: Valve","asset_type_ids":["recvUb7ks9fiR4fCf"],"description":null},{"id":"reckUExamodqA3mtG","name":"Wheeled: CO2 30kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reckUIVAtvLEjd7VI","name":"Bush Fire Retention","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"reckUKLyoFu1a79cJ","name":"Door Screen","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"reckVecliygBFztuj","name":"Wheeled: CO2 45kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reckY2mhyEBQWwZfb","name":"Wheeled: CO2 50kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reckYLOIxXUkLIf1K","name":"Fence","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"recKz6cTYNqAYiHaD","name":"Pre-Action: Valve","asset_type_ids":["recvUb7ks9fiR4fCf"],"description":null},{"id":"recL0efscPeR3BmVj","name":"Sprinkler Head: Pre-Action","asset_type_ids":["recvUb7ks9fiR4fCf"],"description":null},{"id":"recl0LuCmOFhcbttW","name":"Wheeled: DCP ABE 50kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recL31MPIcYFGcTiZ","name":"Balanced Pressure Bladder","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recL50pgasqZyjFqD","name":"Booster: Drencher (Wall Wetting)","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recl6CN7A0J66g8Ev","name":"Wheeled: DCP ABE 70kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recL6kCNoX8EBOHXl","name":"Booster: Fire Sprinkler","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recL7ltDj9nQ1zCkH","name":"Booster: General Wet Pipe System","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recL9nOhaq6IQlH8M","name":"Combined Sprinkler & Hydrant System: Block Plan","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"reclAtncRScEwNHeU","name":"Wheeled: DCP ABE 90kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recLB6ozS4HUpLEct","name":"Concealed: Quick Response High Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recLdhQLug5wbQ2L0","name":"Concealed: Standard Response Intermediate Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recLduNQVEiEbyF5s","name":"Concealed: Standard Response Ordinary Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"reclHe5RTxvkxsp6n","name":"Wheeled: DCP BE","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recLIm4CRwM6ejuNI","name":"Concealed: Quick Response Intermediate Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recLj4IwnkIlNNf5n","name":"Extended Coverage: Quick Response High Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"reclLAyfqWSR7nR8o","name":"Wheeled: DCP BE 20kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recLlc2AqIn0mY0Ly","name":"Extended Coverage: Quick Response Intermediate Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"reclm5M2xFd6AxFNF","name":"Wheeled: Dry Chemical powder (Copper)","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reclmXYkIFEey4Wct","name":"Ceiling Access Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"reclnB87f5sJVJWjx","name":"Ceiling Access Panel","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"reclOzAS2Jz85CeG3","name":"Window Screen","asset_type_ids":["recns6YC4Kb6ZBFcx"],"description":null},{"id":"reclpi49r4cCw4G3n","name":"Wheeled: Dry Chemical Powder (Purple K)","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recLq8i24GrbTKPvh","name":"Extended Coverage: Quick Response Ordinary Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"reclr3p7Se8kHXcM3","name":"Wheeled: Dry Chemical powder (Sodium Chloride)","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recLsc1YfAPN0tNQc","name":"Extended Coverage: Standard Response High Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"reclSmDg8IKBvmYax","name":"Access Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"reclT2954Yp7n6M8b","name":"Wheeled: DCP BE 30kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recltgZdIT7H2xHxz","name":"Floor Access Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recLus2AxNLwcYKhG","name":"Extended Coverage: Standard Response Intermediate Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"reclVLX2npOsQkSGI","name":"Wheeled: DCP BE 50kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recLvPF7LoKupTwjL","name":"Extended Coverage: Standard Response Ordinary Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recLWrrzJuRklZoc7","name":"Concealed: Quick Response Ordinary Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"reclX79USfjvlgZxT","name":"Wheeled: DCP BE 70kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reclXVeJU77b2XgXC","name":"Wheeled: DCP BE 90kg","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"reclZECOl5O1pkK3m","name":"Access Panel","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recLZUy2eD9PcIVhw","name":"Concealed: Standard Response High Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recM1oLyjSE9Vy5MN","name":"Foam Concentrate Tank","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recm6Acj1oK2B5mXs","name":"Floor Access Panel","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recm6JoQdmUZHUH8y","name":"Wheeled: F3 Foam 20L Fluorine Free","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recM6MnvOU95iCJto","name":"Foam Proportioner","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recM73sc1bhF9VvlI","name":"Foam System: Valve","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recmAVY9YDsnyYNCJ","name":"Garbage Shoot","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recmB1tEpbepqzwGJ","name":"Non-Rated: Aluminium Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recMeQwMSQ752IuQZ","name":"Residential: Quick Response High Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recMF65F0pbaUbYdh","name":"High Hazard System: Valve","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recmfKppHNchELtmg","name":"Wheeled: F3 (Foam) 30L (Fluorine Free) Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recmFzt4ioNhCJo3m","name":"Wheeled: F3 (Foam) 20L (Fluorine Free) Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recmivPXTjO6wmhzR","name":"Wheeled: F3 Foam 50L Fluorine Free","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recMjc5IPsoUQpnUc","name":"Residential: Quick Response Intermediate Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recmkv2XefwwadWup","name":"Wheeled: F3 (Foam) 50L (Fluorine Free) Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recMmRoZzLdbWvArv","name":"Residential: Quick Response Ordinary Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recMNO8RkCTAwC8L2","name":"In Rack System: Valve","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recMo2ltV1jwXb7F2","name":"Residential: Standard Response High Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recMS8tkArvwbGsGc","name":"Light Hazard System: Valve","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recMtKRt837Bak3zK","name":"Residential: Standard Response Intermediate Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recmVu1m9zebRHWmS","name":"Non-Rated: Carbon steel Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recMXXs1yDLV1ozuh","name":"Ordinary Hazard System: Valve","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recmyUqwLftEWqvKs","name":"Wheeled: F3 Foam 70L Fluorine Free","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recmZ98L5LkCdys86","name":"Wheeled: F3 Foam 30L Fluorine Free","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recmzs9xiQAFe54Fl","name":"Wheeled: F3 (Foam) 70L (Fluorine Free) Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recn2XowsWBPwQfCO","name":"Wheeled: F3 Foam 90L Fluorine Free","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recN6a2tF8jHCtFd4","name":"Sidewall: Quick Response Intermediate Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recN6EINX68Eq8rW7","name":"Residential: Standard Response Ordinary Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recN6WMEHVOfom8GW","name":"Sidewall: Quick Response High Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recnAafD4kYkumgf2","name":"Non-Rated: Ceiling Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recNbDIeOjjJMVp5O","name":"Upright: Quick Response Ordinary Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recNBFkCIwYPgv46b","name":"Sidewall: Quick Response Ordinary Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recnC36Be0Jfb6xdm","name":"Non-Rated: Floor Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recnDCNAeIKucfb2m","name":"Non-Rated: Garbage Shoot","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recNdfLJkUlFTWUQE","name":"Upright: Standard Response High Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recNEeIB2ujJXxUTw","name":"Sidewall: Standard Response High Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recnESMURWvIQgVkm","name":"Wheeled: F3 (Foam) 90L (Fluorine Free) Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recnGU9WdDRQXctXH","name":"Non-Rated: Manual trapdoors Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recnhb9YMT3fU0Irc","name":"Non-Rated: Self closing trapdoors Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recnKuEcIc7crlUm9","name":"Wheeled: Wheeled Fire Extinguisher","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recnKVJWbAFeEyo2S","name":"Wheeled: F3 Foam Fluorine Free","asset_type_ids":["recCtPsSMx1T8wKw9"],"description":null},{"id":"recnmEnA1jTUi9fzH","name":"Non-Rated: Stainless steel Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recNnD4pvbyXoWnu1","name":"Upright: Standard Response Intermediate Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recNqWO75MZKP2qpP","name":"Upright: Standard Response Ordinary Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recnR7V7d2iZFR9sO","name":"Non-Rated: Self closing safety Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recNrOlZqm76tI2rz","name":"Valve: Over 4 Stories","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recNUmXdHpdFFSB00","name":"Sidewall: Standard Response Intermediate Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recNUydkq5H6G9rNu","name":"Sidewall: Standard Response Ordinary Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recNWuq5csO8Vd5uJ","name":"Sprinkler Head: General Wet Pipe","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recNXNFCcUrOTXL2K","name":"Upright Pendent: Standard Response","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recNXpzxNVXPMCCzG","name":"Upright: Quick Response High Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recNYXnskMWkRzyqe","name":"Upright: Quick Response Intermediate Temperature","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recO3BGtizinPqzP5","name":"Valve: Under 4 Stories","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recO489E3ELUSRPlr","name":"Wet Pipe System: Manifold","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"reco5Ae3ypEMdlSOQ","name":"Non-Rated: Wall Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recO6Wy6DEASkVELh","name":"Wet Pipe System: Tail-End","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recObtdq5NFZ5hEsc","name":"Hydrant Pipe Protection Wrap","asset_type_ids":["recXj6wDu0oglV5PY"],"description":null},{"id":"recOBW3ZKhq2YS6zU","name":"Wet Pipe System: Valve","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recobzq0lVBXu9Vb8","name":"1.2m x 1.2m","asset_type_ids":["recSkqyhfPouyc79m"],"description":null},{"id":"recoeOQJMRxc5Svf5","name":"1.2m x 1.8m","asset_type_ids":["recSkqyhfPouyc79m"],"description":null},{"id":"recOFPAiZt07mcMTj","name":"Residential Domestic Sprinkler System","asset_type_ids":["recXnAJDdJ3cQuUpx"],"description":null},{"id":"recoHuq2lmRriZkuv","name":"Wall Access Hatch","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recOnHUjeN6NFc1vk","name":"Beam","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recooFRAj1OJW09mm","name":"1.8m x 1.8m","asset_type_ids":["recSkqyhfPouyc79m"],"description":null},{"id":"recos1VbURvueKok0","name":"1m x 1m","asset_type_ids":["recSkqyhfPouyc79m"],"description":null},{"id":"recOTszufZ0J5yRPn","name":"Air Duct","asset_type_ids":["recXj6wDu0oglV5PY"],"description":null},{"id":"recOvoVcyS2xpZCK1","name":"Column","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recOVoYxs4bGd0XE7","name":"Fire Stopping Around Damper","asset_type_ids":["recXj6wDu0oglV5PY"],"description":null},{"id":"recowBOdweING4MvM","name":"Fire Blanket","asset_type_ids":["recSkqyhfPouyc79m"],"description":null},{"id":"recOX2elDp3Xo6mpy","name":"Fire Wrap: Ductwork","asset_type_ids":["recXj6wDu0oglV5PY"],"description":null},{"id":"recoXn8MmbrY13rbZ","name":"Wall Access Panel","asset_type_ids":["rechOWZYAlVujBFIf"],"description":null},{"id":"recP0xeHsSoa5xF20","name":"Concrete Floor","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recPaLRrqi70xXWZZ","name":"Floor Covering","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recPeFT8EqCmpKS53","name":"Fyrcheck","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recpfwOy2T52Cu17l","name":"12V 100Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recPGYeyltimeF3xZ","name":"Concrete Pillar","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recPp6Qm9u9SvLi85","name":"Girder","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recPqLm22v2jJpjuG","name":"Lightweight Construction","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recpSvG2pWDR0zh7G","name":"Gel Blanket","asset_type_ids":["recSkqyhfPouyc79m"],"description":null},{"id":"recPTGTRz4RnvKYxj","name":"Concrete Wall","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recPUxPA6fbZGF7j2","name":"Fire Rated: Material","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recpVE4mAqrRRrgEC","name":"Welders Blanket","asset_type_ids":["recSkqyhfPouyc79m"],"description":null},{"id":"recPWhZZGMcds82rq","name":"Fire Rated: Wall Covering","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recQ0A6Q727s7YOQL","name":"Lightweight Construction: Boxing","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recQ50PE3fHB3RJkV","name":"Lightweight Construction: Calcium Silicate Board","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recq5NnkCFll6Ko9H","name":"12V 120Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recQ5xQDExRHH27a8","name":"Lightweight Construction: Fire Batt","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recQ8ojkqPaUtRJJp","name":"Steel","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recq8xpa5qbWL9CQi","name":"12V 12Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recQ9XfiHvuOhRDei","name":"Timber","asset_type_ids":["rec2oTGr7pr54Qhur"],"description":null},{"id":"recQbGgD7mfyY07pi","name":"Fire Rated: Double Hung Double Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recQFH0qUl2ndEGRo","name":"Fire Rated: Awning Double Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recQfJnmethu2jp5j","name":"Fire Rated: Double Hung Single Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recqGVgdzQelmAuwj","name":"12V 12Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recQIawkpcqThXLOx","name":"Fire Rated: Awning Single Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recQKNtkzVq6ewJDQ","name":"Fire Rated: Awning Triple Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recQmlhCxICeDJBI3","name":"Fire Rated: Double Hung Triple Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recQrMRTGkfvHgwIn","name":"Fire Rated: Fixed Double Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recQT0rgZ8SwsUNcT","name":"Fire Rated: Centre Pivot Double Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recQTfsiBuck0D1ML","name":"Fire Rated: Centre Pivot Single Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recQWW0KiFqIae208","name":"Fire Rated: Centre Pivot Triple Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recQx5jW8vduskNv2","name":"Fire Rated: Fixed Triple Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recqx8ldvcb8DYQOt","name":"Power Supplies: Main Switchboards Low Voltage","asset_type_ids":["recGdvqgim8FzHNua"],"description":null},{"id":"recQxAYunVlaFhCWG","name":"Fire Rated: Glass Door","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recqXD5ZbL5UCVVK1","name":"12V 1.3Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recqxIWPZ9wSTqQvb","name":"Mechanical Smoke Damper","asset_type_ids":["recnO36HiT7wmEPzD"],"description":null},{"id":"recQzdzwbmqhAQDPq","name":"Fire Rated: Glass Window","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recQZVagHqNlcJZFO","name":"Fire Rated: Double Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recR1iLLM3mNP13n5","name":"Fire Rated: Glazing","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recr2LTixPHWWJbLQ","name":"Smoke Damper","asset_type_ids":["recnO36HiT7wmEPzD"],"description":null},{"id":"recR3V6XTEFBArnIJ","name":"Fire Rated: Hopper Double Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recR6hmJuxJwstdg7","name":"Fire Rated: Hopper Triple Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recR6Krs4BFpPPO37","name":"Fire Rated: Hopper Single Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recr8gj2iPncH0HnN","name":"Smoke Exhaust System","asset_type_ids":["reczwjpBSwKxfPEyW"],"description":null},{"id":"recr8hroJSdmzQmqP","name":"12V 1.3Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recr8KF33UzbRHpVO","name":"Smoke Louvers","asset_type_ids":["recnO36HiT7wmEPzD"],"description":null},{"id":"recr9v2pdHFYNmjSf","name":"12V 150Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recrawp8dkkrdf9py","name":"CO Alarm: 10yr Lithium BT Interconnected","asset_type_ids":["rec5PYzWjYMKYLkYI"],"description":null},{"id":"recRBbfVvhfgvxXsZ","name":"Fire Rated: Single Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recrc2CYCfeV9Q9dN","name":"12V 18Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recrdBKOGXLaIPYyC","name":"CO Alarm: 9V Standalone","asset_type_ids":["rec5PYzWjYMKYLkYI"],"description":null},{"id":"recrEg84scUW4Qlba","name":"Smoke Reservoir","asset_type_ids":["recF02GvAeiRTzdlR"],"description":null},{"id":"recrEwCGfRUhYfOpm","name":"Alarm Control Panel","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recRFTxnABcjnwrCb","name":"Fire Rated: Single Hung Double Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recRHmwpLPhJSGCYc","name":"Fire Rated: Single Hung Single Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recRhYf5wjJFf3Nuu","name":"Fire Door: Double Equal Pair","asset_type_ids":["recnrMixWMp1DbCR6","recBIKJKuGI2NhUw7"],"description":null},{"id":"recrJdFzZzL85CfbP","name":"Carbon Monoxide 240/9V","asset_type_ids":["rec5PYzWjYMKYLkYI"],"description":null},{"id":"recrJwKVqpjXIi4dA","name":"Carbon Monoxide Alarm 240/9V","asset_type_ids":["rec5PYzWjYMKYLkYI"],"description":null},{"id":"recRLNXA2UDL869Hr","name":"Fire Rated: Single Hung Triple Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recRM6AhzJruz3FJR","name":"Fire Rated: Triple Glaze","asset_type_ids":["recbiBQelzVodmYCL"],"description":null},{"id":"recRP6pJTUPeHnkc3","name":"Collar Floor Waste","asset_type_ids":["recI7nTr2kH2VBSsV"],"description":null},{"id":"recRPlZGsRBzpoguv","name":"Fire Rated: Floor","asset_type_ids":["recI7nTr2kH2VBSsV"],"description":null},{"id":"recrpSxzcJ2Ejw4qO","name":"Combination: Smoke & Heat Alarm","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recRqkjSHKeVuGEyB","name":"Fire Door: Double Pivot Equal Pair","asset_type_ids":["recnrMixWMp1DbCR6","recBIKJKuGI2NhUw7"],"description":null},{"id":"recRRx9ON3deNW4OX","name":"Floor Waste Collar: In-Cast","asset_type_ids":["recI7nTr2kH2VBSsV"],"description":null},{"id":"recrsUn3pm2XAffTo","name":"Heat Alarm","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recRtwXp47nmy2u7b","name":"Fire Door: Double Pivot Unequal Pair","asset_type_ids":["recnrMixWMp1DbCR6","recBIKJKuGI2NhUw7"],"description":null},{"id":"recrU3kax6k9P36rM","name":"CO2 Alarm 240/9V","asset_type_ids":["rec5PYzWjYMKYLkYI"],"description":null},{"id":"recRUPolaHtImWSeT","name":"Smoke Floor","asset_type_ids":["recI7nTr2kH2VBSsV"],"description":null},{"id":"recrvR14kmDnlGej2","name":"Heat Alarm: 10yr Lithium (Wireless)","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recrVVR1rtrHaqP2w","name":"12V 15Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recrxHh2wQXG7M4Yy","name":"12V 18Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recrxhsL1EdmZGqtE","name":"Heat Alarm: 12V Wireless","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recrXrM8L44zsi9ba","name":"CO Alarm: 10yr Lithium","asset_type_ids":["rec5PYzWjYMKYLkYI"],"description":null},{"id":"recrxyZFFSJ9GLGhv","name":"Heat Alarm: 240/9V","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recrYhcQYJ3yrtXc7","name":"12V 15Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recRzAJOkrpWvVpdA","name":"Fire Door: Double Unequal Pair","asset_type_ids":["recnrMixWMp1DbCR6","recBIKJKuGI2NhUw7"],"description":null},{"id":"recrzAscpoX5fGNxy","name":"Heat Alarm: Standalone 9V","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recs1746GbxcePMju","name":"Smoke Alarm","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recs4k5juW31t73M5","name":"Smoke Alarm: 12V Wireless","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recs5k2tPZlCGBFap","name":"Smoke Alarm: Combination Ionisation/Photoelectric","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recS6juhDG2dW351e","name":"Fire Door: Single","asset_type_ids":["recnrMixWMp1DbCR6","recBIKJKuGI2NhUw7"],"description":null},{"id":"recs9IaJE50wGR9RQ","name":"Smoke Alarm: Ionisation 240/9V","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recs9pjoSJrpzhHTp","name":"Smoke Alarm: Ionisation 9V","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recsAlK312PBu0Ju3","name":"Smoke Alarm: Photoelectric 10yr Lithium (Wireless)","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recsdiFMLPeCv4UJ6","name":"Conventional: Agent Release Local Control Station","asset_type_ids":["recSANxXnNGt9CZfH"],"description":null},{"id":"recsdkPXvzzgo4SGO","name":"Detector","asset_type_ids":["recSANxXnNGt9CZfH"],"description":null},{"id":"recSdl94HWXbm7AXJ","name":"Solid Core Door: Double Pivot Unequal Pair","asset_type_ids":["recGMslnFtOuh6mkF","recG8NFpzAHWcvBng"],"description":null},{"id":"recsECsRQadpJNSqt","name":"Smoke Alarm: Photoelectric 240/9V","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recSF5mLD5TBRJu09","name":"Fire Door: Single Double Action","asset_type_ids":["recnrMixWMp1DbCR6","recBIKJKuGI2NhUw7"],"description":null},{"id":"recsFYyYSG1ZmoXXL","name":"Smoke Alarm: Photoelectric 9V","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recSGtNOJmVICNK17","name":"Fire Door: Single Pivot Action","asset_type_ids":["recnrMixWMp1DbCR6","recBIKJKuGI2NhUw7"],"description":null},{"id":"recSgtXtVIcan45Y2","name":"Solid Core Door: Double Unequal Pair","asset_type_ids":["recGMslnFtOuh6mkF","recG8NFpzAHWcvBng"],"description":null},{"id":"recsIF8jCdftCehL5","name":"Smoke Alarm: Standalone 9V","asset_type_ids":["rec5PYzWjYMKYLkYI","recqjdzxhag0yzqOi"],"description":null},{"id":"recsJmEKhJHUJGC8y","name":"12V 200Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recsjZkn5b2pVIvaP","name":"FirePro","asset_type_ids":["recSANxXnNGt9CZfH"],"description":null},{"id":"recSL8C5LQD0zWZ3x","name":"Solid Core Door: Double Equal Pair","asset_type_ids":["recGMslnFtOuh6mkF","recG8NFpzAHWcvBng"],"description":null},{"id":"recsPjuviRmjswUQ2","name":"12V 22Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recspsqBPbCDWUWcf","name":"Flame Detector","asset_type_ids":["recSANxXnNGt9CZfH"],"description":null},{"id":"recSrhkvnMlP3a237","name":"Solid Core Door: Single","asset_type_ids":["recGMslnFtOuh6mkF","recG8NFpzAHWcvBng"],"description":null},{"id":"recSSwqOV6SLlu8Xr","name":"Solid Core Door: Double Pivot Equal Pair","asset_type_ids":["recGMslnFtOuh6mkF","recG8NFpzAHWcvBng"],"description":null},{"id":"recst0g89t50OwCjn","name":"Generator","asset_type_ids":["recSANxXnNGt9CZfH"],"description":null},{"id":"recSuEiBuoILZn30V","name":"Solid Core Door: Single Pivot Action","asset_type_ids":["recGMslnFtOuh6mkF","recG8NFpzAHWcvBng"],"description":null},{"id":"recsUVzFC56TEwY9j","name":"Addressable: Agent Release Local Control Station","asset_type_ids":["recSANxXnNGt9CZfH"],"description":null},{"id":"recswrdmMzQamQK76","name":"Heat Detector","asset_type_ids":["recSANxXnNGt9CZfH"],"description":null},{"id":"recsyoTeqXu6OhJxh","name":"Linear Detection Wire","asset_type_ids":["recSANxXnNGt9CZfH"],"description":null},{"id":"recSzA8Pcu3nD4Ka9","name":"Smoke Door: Double Equal Pair","asset_type_ids":["recG8NFpzAHWcvBng","recGMslnFtOuh6mkF"],"description":null},{"id":"recsZCEmGdztJDCua","name":"Agent Release Local Control Station","asset_type_ids":["recSANxXnNGt9CZfH"],"description":null},{"id":"recT3M5WFVkQl2Z4Q","name":"Smoke Door: Double Pivot Equal Pair","asset_type_ids":["recG8NFpzAHWcvBng","recGMslnFtOuh6mkF"],"description":null},{"id":"rect7t7U7bkT4wTSB","name":"Linear Heat Detector","asset_type_ids":["recSANxXnNGt9CZfH"],"description":null},{"id":"rect9sT06Ox4QBe39","name":"12V 22Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rectBg2gwFEPSOYHU","name":"Agent Release Local Control Station","asset_type_ids":["recSBPZsb9soMtNVb"],"description":null},{"id":"rectBPjmz02pHMtZj","name":"Addressable: Agent Release Local Control Station","asset_type_ids":["recSBPZsb9soMtNVb"],"description":null},{"id":"rectbTVFZAxSbEoNQ","name":"12V 2.3Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rectd8MgQ5w8jO0Zh","name":"Nozzle","asset_type_ids":["recSBPZsb9soMtNVb"],"description":null},{"id":"rectECLXsBYGLuHjg","name":"Conventional: Agent Release Local Control Station","asset_type_ids":["recSBPZsb9soMtNVb"],"description":null},{"id":"recteF0Bg95pB6RHV","name":"Open: Non Automatic","asset_type_ids":["recSBPZsb9soMtNVb"],"description":null},{"id":"recTgIAzDD9eafTSq","name":"Smoke Door: Single Double Action","asset_type_ids":["recG8NFpzAHWcvBng","recGMslnFtOuh6mkF"],"description":null},{"id":"recTImRTPyYY6ayZC","name":"Smoke Door: Double Pivot Unequal Pair","asset_type_ids":["recG8NFpzAHWcvBng","recGMslnFtOuh6mkF"],"description":null},{"id":"rectipC5qLYZJhRrN","name":"Open Nozzle Water Mist","asset_type_ids":["recSBPZsb9soMtNVb"],"description":null},{"id":"rectkGrtxqfTO6Trf","name":"Addressable: Agent Release Local Control Station","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recTlwesT5AACHeyb","name":"Fire Rated: Sliding Door","asset_type_ids":["receY5fSkLOPKGxSx"],"description":null},{"id":"rectLZVrcBuYHWAar","name":"12V 2.3Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rectM5cnuB4aDPmlA","name":"Cylinder","asset_type_ids":["recSBPZsb9soMtNVb"],"description":null},{"id":"rectMR6SCE2V3oGS1","name":"Gas Container","asset_type_ids":["recSBPZsb9soMtNVb"],"description":null},{"id":"rectnd04vL54AJ9B2","name":"12V 26Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"rectpbNuzNrpjIeR6","name":"12V 26Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recTqLcwY87B2fRkq","name":"Fire Rated: Sliding Door: Above 2.4m","asset_type_ids":["receY5fSkLOPKGxSx"],"description":null},{"id":"recTSkTGKCLUl2szO","name":"Smoke Door: Double Unequal Pair","asset_type_ids":["recG8NFpzAHWcvBng","recGMslnFtOuh6mkF"],"description":null},{"id":"recTsZQWgvdENFdEk","name":"Fire Rated: Sliding Door: Glass","asset_type_ids":["receY5fSkLOPKGxSx"],"description":null},{"id":"recTWKoqN4uHTTFbt","name":"Smoke Door: Single","asset_type_ids":["recG8NFpzAHWcvBng","recGMslnFtOuh6mkF"],"description":null},{"id":"rectZoxtKpDctDC9Q","name":"Hybrid","asset_type_ids":["recSBPZsb9soMtNVb"],"description":null},{"id":"recu0HdRkvhwA2f8g","name":"Agent Release Local Control Station","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recu2bVV2OonVoniR","name":"12V 2.9Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recu4St0FCU5UPnpk","name":"Argonite IG-55","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recu5WabAppimXOVZ","name":"Co2","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recU5YEdV8cjRUvL7","name":"Fire Rated: Sliding Door: Steel","asset_type_ids":["receY5fSkLOPKGxSx"],"description":null},{"id":"recUaVxBoNQIBiZ1N","name":"Jacking Pump: Hose Reel System","asset_type_ids":["recrf1xCIxeQtYrX2"],"description":null},{"id":"recuClzGywKqH5LjT","name":"12V 2.9Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recuD5AZ7LqWW5yQF","name":"Conventional: Agent Release Local Control Station","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recuDCQZeJ35fP2pQ","name":"12V 3.2Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recUhj1iAKkzhQVbi","name":"Jacking Pump: Manual, Twin Stage","asset_type_ids":["recrf1xCIxeQtYrX2"],"description":null},{"id":"recUhXa1AdK8p9WWs","name":"Jacking Pump: Hydrant System","asset_type_ids":["recrf1xCIxeQtYrX2"],"description":null},{"id":"recuHZtTmRmHJ8f2Y","name":"Detector, Heat","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recuiEsaIHsTunBdR","name":"Gaseous Cylinder","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recUIppQ5LwxT0E7e","name":"Fire Rated: Sliding Door: Timber","asset_type_ids":["receY5fSkLOPKGxSx"],"description":null},{"id":"recuIpYH4lEKNLBLA","name":"12V 3.2Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recukH1ExUYWQOu1p","name":"Halon 1301","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recUlufS1EGIs7GVQ","name":"Jacking Pump: Pressure Maintenance","asset_type_ids":["recrf1xCIxeQtYrX2"],"description":null},{"id":"recumC8I1nCH5U3rO","name":"Haylon","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recuMWIoWrnDuAUzU","name":"12V 33Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recup779kOhSgrHeS","name":"12V 40Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recuQq4A3nJjGf3qu","name":"Detector, Smoke","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recusoYVLq4QNIXQG","name":"IG-01","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recusPdHbCyPpkbiE","name":"HFC-227ea","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recUSUT32dcaj8Ye0","name":"Fire Rated: Sliding Door: Under 2.4m","asset_type_ids":["receY5fSkLOPKGxSx"],"description":null},{"id":"recuTsalnlvC7NLZh","name":"ECARO-25","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recUuC70aptKO0ghn","name":"Jacking Pump: Sprinkler System","asset_type_ids":["recrf1xCIxeQtYrX2"],"description":null},{"id":"recUVTqqERE7Hacsd","name":"Jacking Pump: Combined System","asset_type_ids":["recrf1xCIxeQtYrX2"],"description":null},{"id":"recuWh4Ljct0WWN0U","name":"FM200","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recUxZ5V8GoRfv7Ov","name":"Twin Submersible Sump Pump","asset_type_ids":["recrf1xCIxeQtYrX2"],"description":null},{"id":"recuyF2lWorgxUgXp","name":"IG-100","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recuZPRoAUQh89ZzT","name":"12V 33Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recV0Eu4VnaQiVHwm","name":"Conventional: Agent Release Local Control Station","asset_type_ids":["recXTAXJ6j6LIBS3z"],"description":null},{"id":"recV0p8Pl4r1swEnI","name":"Kitchen Exhaust System","asset_type_ids":["recXTAXJ6j6LIBS3z"],"description":null},{"id":"recv6OcyJbQeZiMds","name":"IG-541","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvCegRII4MmDeZR","name":"12V 40Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recvCm6H2bcx3EXr8","name":"Inergen","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvdBc5dJBeU4I15","name":"Nitrogen","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvec5ZDnPV12EDH","name":"Nozzle, Extinguishing Agent Nozzle","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvEv7t7JjcDKJ9w","name":"Inert Gas IG100","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvex3oaa7YctmTa","name":"SAG: Muster Fire","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvheKvNjp1tCTiG","name":"Sealed: Automatic","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvhsjg2laLo04BF","name":"Smoke Detector","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvIrC0Ja8xj975u","name":"MH227","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvIX56U14xzt0Mk","name":"Inert Gas IG-541","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvjXzEjOCY9hFTS","name":"12V 5.4Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recvLEgu7rrr58IEn","name":"NAF P-IV","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvMWd8BjBGTjqSo","name":"12V 4Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recvnNFnyjqwLAbGz","name":"Stand Alone: Agent Release Local Control Panel","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvOAjQu0u4K0ioM","name":"12V 4Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recvWtn9o0W679uB8","name":"NAF S 125","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvX7OVVklvGZbFd","name":"NAF S 227","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recvZbmOKCtUmsN04","name":"NAF S-III","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recw13XABqt492bjP","name":"Stat-X","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recw4B8TMo5hBnkZr","name":"Triiodide","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recw4KdMwy7VieBrR","name":"Valve, Extinguishing Agent Check Valve","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recw6p7cuFD5ALosX","name":"Valve, Selector Valve","asset_type_ids":["recoMHFXU1KocjaUB"],"description":null},{"id":"recw81UjwP1maatkV","name":"System Shutdown","asset_type_ids":["recZ1U9gFhSsdvLVo"],"description":null},{"id":"recw9D7w9Ywc9KEkI","name":"12V 5.4Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recwG1PP2D84c03jy","name":"12V 55Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recWgpbSaOUYTGfdO","name":"Curtain Damper","asset_type_ids":["reczmXK0WrIpxuI0s"],"description":null},{"id":"recwHyLuygD3wkUuJ","name":"12V 55Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recWk0rJftCjGlqb7","name":"Electrical Fire Damper","asset_type_ids":["reczmXK0WrIpxuI0s"],"description":null},{"id":"recWqjL7yMHI5RFEb","name":"Electrical Smoke Damper","asset_type_ids":["reczmXK0WrIpxuI0s"],"description":null},{"id":"recwri6fiEvOH0puY","name":"12V 7Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recwSiy0bH0wadQS2","name":"12V 65Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recwX7Big6rA8APLn","name":"12V 75Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recwZUDuAXdmjg1KE","name":"12V 7Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recX60MKp9OQGSRQy","name":"Fire Damper","asset_type_ids":["reczmXK0WrIpxuI0s"],"description":null},{"id":"recx6osWHDmiGia9Y","name":"12V 85Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recX6tGLiASsBVAcH","name":"Fire Louvers","asset_type_ids":["reczmXK0WrIpxuI0s"],"description":null},{"id":"recX88qHSNdP8YBsk","name":"Intumescent","asset_type_ids":["reczmXK0WrIpxuI0s"],"description":null},{"id":"recxAQ3BzAQ0T5sh0","name":"12V 90Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recXCCHu6q8pRHIB0","name":"Mechanical Fire Damper","asset_type_ids":["reczmXK0WrIpxuI0s"],"description":null},{"id":"recXDYhhpXDfqJU61","name":"Motor Control Centre","asset_type_ids":["recPfp5rPgBuqKZrD"],"description":null},{"id":"recXE9HTGTE4eJThd","name":"Motorized Relief Opening: Shutter","asset_type_ids":["recBWgH7naCbYbxsO"],"description":null},{"id":"recxeAiAHbjv7EZN1","name":"Bulkhead System: Fireboard","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recXf997x3oTBIvNU","name":"Outdoor Intake","asset_type_ids":["recMHbxO45GpJiWRQ"],"description":null},{"id":"recxHbROm2w2MRSvJ","name":"12V 9Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recxhvMFDPkr9x5PO","name":"6V 1.2Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recxiG8kSGUdVtuoY","name":"Collar Cast In","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recxjgBhvC95Tbxmi","name":"6V 15Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recxkBbTLpGuBXYSB","name":"Collar Retrofit","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recxkmxwkPsWNiF9l","name":"Control Joint","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recxkWJ0s6wuxLaKR","name":"Conduit Fire Collar","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recxmeM7OJx9oDzsC","name":"Fibre Stuffing","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recXni6ypXePh6FSb","name":"Pneumatic Compressor/Receiver Station","asset_type_ids":["recTU27tupBDXTwn8"],"description":null},{"id":"recxPcBQveAjfesKJ","name":"12V 9Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recxrGuW906a6bRjS","name":"Fire Box: In-Cast","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recxTNT2WQdCjr8vp","name":"Variable Frequency Inverters VFIs","asset_type_ids":["recSWgdGeR0vfIQso"],"description":null},{"id":"recxTnusE75yOGGRd","name":"Barrier Plug","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recXTzs6TAswMIUqY","name":"Motorized Relief Opening: Window","asset_type_ids":["recBWgH7naCbYbxsO"],"description":null},{"id":"recxubp4maY6MTvK7","name":"Fire Rated: Compartment","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recxW6YuePZcYj55y","name":"Bulkhead","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recXxFPG52hjKedCB","name":"Portable: Air/Water","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recy0jN8lvEG0aRz5","name":"Fire Rated Downlight Covers","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recY0p9nMkFlCVXax","name":"Portable: Air/Water 6.0L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recy1nEdqg7RtFGPA","name":"Fire Rated Pillows","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recY1SuRk5yOPPJ1s","name":"Portable: Air/Water 9.0L","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recy2LG54AJ6OWy59","name":"Fire Rated: Wall","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recY6I4gqauOjyAC7","name":"ADT","asset_type_ids":["recy1ku5NAMITWtry"],"description":null},{"id":"recY8kL43CdtTps6d","name":"Alarm Signalling Equipment","asset_type_ids":["recy1ku5NAMITWtry"],"description":null},{"id":"recY9lbpgHW9tW3h4","name":"Portable: Air/Water 9.0L Additive","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recYeeblI95Dbg6F5","name":"Portable: CO2 (E) 5.0kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recYEKPpv5icf7tg0","name":"Portable: CO2 (E)","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recYgsRIpjoDXbI6R","name":"Portable: DCP AB(E)","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recygUJQhSnXu8tD0","name":"Intumescent Pillow","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recYJelC8SNctq5dH","name":"Portable: CO2 (E) 2.0kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recyl1xo1Ei6EThPD","name":"Putty Bandage","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recym6kk3PhFC3o6q","name":"Seal","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recym8n3H5ADcc74E","name":"6V 3.5Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recyn5Hn5RAwZr07O","name":"6V 5.4Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recYnMWx78MdIWyUw","name":"Portable: DCP AB(E) 1.0kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recYoOltoCL7If2ET","name":"Code Red","asset_type_ids":["recy1ku5NAMITWtry"],"description":null},{"id":"recyoph59xaafNodC","name":"6V 7.2Ah Battery","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recyOs4raaJAbFLye","name":"Hinged Retrofit Collar","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recYq8ADLZmRHT1AK","name":"Portable: DCP AB(E) 1.5kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recYR5rv2Far4agVo","name":"Portable: CO2 (E) 2.5kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recyrj7hJ0KfuZW2n","name":"Addressable: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recyRRaetSod25nuU","name":"Intumescent Fire Box Maxi: Through Cast","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recyV26jBJ3DLDywo","name":"Intumescent Fire box Mini: Through Cast","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recYV7ZYwOMsugAWO","name":"ASE Alarm Monitoring","asset_type_ids":["recy1ku5NAMITWtry"],"description":null},{"id":"recYXRCmHguOyh6OY","name":"Brooks","asset_type_ids":["recy1ku5NAMITWtry"],"description":null},{"id":"recyYDHkckeb8lmKa","name":"Intumescent Fire Box: Slab Mount","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recYYWwpFyy88pZrP","name":"Portable: CO2 (E) 3.5kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recZ01OU2NPoaMriX","name":"Portable: DCP AB(E) 2.0kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recz1JVV8prb5bszT","name":"Service Penetration","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recZ4kEvn7gYs9nE2","name":"Combination Fire/Security Monitoring","asset_type_ids":["recy1ku5NAMITWtry"],"description":null},{"id":"recz56EJ47xrkdPqu","name":"Sleeve","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recZ645bJkvHpWJ77","name":"Emergency Warning System (EWS)","asset_type_ids":["recy1ku5NAMITWtry"],"description":null},{"id":"recz7HW8BjJBxkkpN","name":"Smoke Lobby","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recz84TWbvgxBCrE3","name":"Smoke Wall","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recz9T0ib7vxU9C6H","name":"Stack High Collar: In-Cast","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"reczAAAQ14ho8paCE","name":"Stack Low Collar: In-Cast","asset_type_ids":["recyJ4V4XnfrB4BTn"],"description":null},{"id":"recZBkWGYaKTu5107","name":"Portable: DCP AB(E) 2.3kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"reczfeU425PUUSx4o","name":"Beam Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"reczFvVJ55MwSIjMb","name":"Analogue: Fire Indicator Panel","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recZGylr46zd7x724","name":"Romteck","asset_type_ids":["recy1ku5NAMITWtry"],"description":null},{"id":"recZH4MyeVyL1Dc3S","name":"Portable: DCP AB(E) 2.5kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"reczHNfCIJw1LwvcV","name":"Water Storage Tank","asset_type_ids":["recYcid2mLApcEh2Z"],"description":null},{"id":"reczIb1rBlszplPf8","name":"Aspirating Smoke Detection ASD","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recZIF8t7dMLGwSD3","name":"Security Alarm Monitoring","asset_type_ids":["recy1ku5NAMITWtry"],"description":null},{"id":"recZLDdZVGAdmhgI1","name":"Stand-Alone Emergency Warning System (EWS)","asset_type_ids":["recy1ku5NAMITWtry"],"description":null},{"id":"reczolHi8xeVDDOyx","name":"Block Plan","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"reczPgnwbpeNJcojX","name":"Water Storage Tank: Below Ground","asset_type_ids":["recYcid2mLApcEh2Z"],"description":null},{"id":"recZpIw9xhaVOaa8V","name":"Portable: DCP AB(E) 6.0kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"reczPS1fy233SA8G6","name":"Water Storage Tank: Above Ground","asset_type_ids":["recYcid2mLApcEh2Z"],"description":null},{"id":"reczrpej7lk9DNRoH","name":"Water Storage Tank: Liner A Above The Waterline","asset_type_ids":["recPVmEAYvGKqZVfK"],"description":null},{"id":"recZTYcLmoB9fudPJ","name":"Portable: DCP AB(E) 4.5kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"reczUXAzMrm3FwZsD","name":"Water Storage Tank: Combined Fire & Potable","asset_type_ids":["recYcid2mLApcEh2Z"],"description":null},{"id":"recZuXShEq4oyh5PE","name":"Portable: DCP AB(E) 9.0kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recZv0KsfC9jVfzn2","name":"Portable: DCP B(E)","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"recZvQjiwMiBGHufq","name":"Portable: DCP B(E) 1.0kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"reczw61jJNQpvwP6G","name":"Water Storage Tank: Liner B Below The Waterline","asset_type_ids":["receJzXoQISUPKcqA"],"description":null},{"id":"recZwTXSCiAFxnZ1v","name":"Portable: DCP B(E) 1.5kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"reczx7qIz5GP3qVPH","name":"Carbon Monoxide Detector","asset_type_ids":["recAhOjivmmUeMZhW"],"description":null},{"id":"recZybkKuNhdivlJ0","name":"Portable: DCP B(E) 2.0kg","asset_type_ids":["recAtQLGgbEbGMXi8"],"description":null},{"id":"reczZOiuLhpJHvkbl","name":"Water Storage Tank: Rectangular","asset_type_ids":["recAn91z5MfnsPweZ"],"description":null}],"uncategorised_asset_types":[],"prompt_association":{"method":"prompt_set_year_prefix","prefix":"2012:","note":"Imported prompts have no direct standard link; prompt sets are matched by the year in the standard name."}}}